Electrical Pressure Measurement

Duct humidity temperature sensor Type A2G-70, air2guide T+H


WIKADatasheetA2G-70

Applications
Formeasuringrelativehumidityandtemperatureof gaseousmediainheating,coolingandair-conditioning systems DesignedforPLCsandothercontrolanddisplaypanels

Special features
Easyinstallation Directassemblyintotheprocess Compactandrobustdesign Comesstandardwithmountingflange

Duct humidity temperature sensor air2guide T+H, Type A2G-70

Description
Design standards CE-conformity: 2004/108/EGElectromagnetic compatibility ProductSafety: 2001/95/EGProductSafety EMC: EN607301:2002 ProductSafety: EN607301:2002 Supply voltage DC15...24V/AC24V10% Scale range / measuring range Humidity: 0100%rH Temperature: -4+176F Power consumption 0.5W/1.7VA Transmitter outputs Humidity: DC010V,load:min.5kOhm Temperature: DC010V,load:min.5kOhm Ingress protection NEMA4(IP65perEN60529/IEC592(connectinghead)) Accuracy Humidity: Temperature: 3%between2080%rH 1.0%between+41+113F

WIKADatasheetA2G-7004/2011

Page1of3
R

Electrical connection ScrewconnectionM16x1.5forwirewithmax.dia=0.31 Theinstrumentisdesignedtooperatewithsafetyextralowvoltage(SELV).Thetransmittermustbeoperatedata constantoperatingvoltage(0.2V).Current/Voltagespikes fromswitchingthepowersupplyonoroffmustbeprevented bythecustomer. Insertion length L (standard) 5.51 Otherlengthsonrequest Operating Temperature Ambient:-4+158F Sensortip:max.+140F

Probe tube PVC,black Filter element Stainlesssteel,meshsize80m Connection head PA6,white Mounting instructions Max.airspeed10m/s

Mounting flange MF19-PA


0.75
40212351.01

0.79

Wiring diagram for output 0 ... 10 V (standard)

0.16

2.17 0.83
Out Temp 0-10V Out RH0-10V UB15-24V=/24V~ Gnd Temp. sensor (option)

Load

Load

DRW_TH0.04a

Option
Transmitteroutput4...20mA -Humidity: 4...20mA,load<500OhmatDC24V -Temperature: 4...20mA,load<500OhmatDC24V Wiring diagram for output 4 ... 20 mA (optional)
DRW_TH0.05

UB15-24V= GND / Temp Out 4-20mA Temp. Offset UB 15-24V= GND / rF/rH Out 4-20mA

Note Ifonlythehumidityoutputisused,"UB15-24V=(Temp.)"has tobebridgedto"UB15-24V=(rF/rH)",andthetemperature output"GND/Temp.Out4-20mA"hastobebridgedto "GND"ofthepowersupply..


Page2of3 WIKADatasheetA2G-7004/2011

0.19

rF/rH Offset

Dimensions in inches

2.56

1.79

1.67

0.75 2.56 1.54

1.97

1.5

0.59

Thespecificationsgiveninthisdocumentrepresentthestateofengineeringatthetimeofpublishing. Wereservetherighttomakemodificationstothespecificationsandmaterials.

Page3of3

0.75

WIKADatasheetA2G-7004/2011
R

WIKA Instrument Corporation 1000WiegandBoulevard Lawrenceville,GA30043 Tel(770)513-8200Toll-free1-888-WIKA-USA Fax(770)338-5118 E-Mail info@wika.com www.wika.com