Sunteți pe pagina 1din 47

ONSHORE ENGINEERING DEPARTMENT

CONTRACT NO.: GC07102200

PROJECT NO.: 2456

PHASE-I OF THE EXPANSION OF EXISTING DOMESTIC WASTEWATER TREATMENT PLANT & CONSTRUCTION OF 3NOS WASTEWATER PUMPING STATION RISING MAINS & TRUNK SEWERS IN MESAIEED COMMUNITY AREA
DOCUMENT TITLE:

DATA SHEETS
SCADA PLC WORKS FOR DWTP

MAIN CONTRACTOR

VENDOR

NEW ERA CONTROLS W.L.L DOHA-QATAR

A 1 0
REV.

21.07.11 05.07.11 07.06.11


DATE

Approved For Construction Incorporated comments Issued for comments


DESCRIPTION

RK RK RK

MKV MKV MKV

KV KV KV

PREPARED

CHECKED

APPROVED

QP

DWG. / DOC NO.:

5 6

5 5

SHEET

OF

47

REV.

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 2 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

TABLE OF CONTENTS 1. 1.1 1.2 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. INTRODUCTION ................................................................................................... 3 DEFINITION ....................................................................................................... 3 CODES AND STANDARDS .............................................................................. 3 REFERENCE DOCUMENTS ................................................................................ 4 UNIVERSAL BLACKLANE.................................................................................... 5 POWER SUPPLY 24VDC ..................................................................................... 6 CPU ....................................................................................................................... 7 ETHERNET MODULE .......................................................................................... 9 GENIUS BUS CONTROLLER ............................................................................ 10 DIGITAL OUTPUT RELAY TYPE ....................................................................... 11 DIGITAL INPUT MODULE 24VDC ..................................................................... 12 ANALOG INPUT MODULE.............................................................................. 13 ANALOG OUTPUT MODULE.......................................................................... 15 I/O CARRIER BOX STYLE .............................................................................. 16 GENIUS NETWORK INTERFACE UNIT......................................................... 17 24VDC POWER SUPPLY FOR IO .................................................................. 18 BOOSTER POWER SUPPLY CARRIER ........................................................ 19 15TFT OUICKPANEL VIEW........................................................................... 20 HIGH CAPACITY BATTERY ........................................................................... 21 REFLECTIVE MEMORY EXCHANGE ............................................................ 22 LOGIC DEVELOPER PLC............................................................................... 23 MODBUS COMMUNICATION MODULE ........................................................ 24 8 PORT ETHERNET SWITCH ........................................................................ 25 QP VIEW GENIUS LAN INTERFACE MODULE ............................................ 26 BUS SWITCHING MODULE ........................................................................... 27 IFIX PROFSNL SCADA PAK UNLMTD SRVR ............................................... 28 IFIX PROFSNL SCADA PAK UNLMTD DEV .................................................. 29 IFIX ICLIENT RUNTIME .................................................................................. 30 IFIX HISTORIAN ENTERPRISE SERVER 1000 POINTS (M4 KEY) ............. 31 APPLICATION SERVER ................................................................................. 33 ARCHIVE SERVER ......................................................................................... 36 ENGINEERING WORKSTATION .................................................................... 39 OPERATOR WORKSTATION ......................................................................... 40 22 INCH LCD DISPLAY ................................................................................... 41 PRINTER ......................................................................................................... 42 GPS TIME SYNCHRONIZATION SYSTEM ................................................. 44 24 PORT 10/100 DESTOP/RACK MOUNATABLE ETHERNET SWITCH ..... 45 RACK CABINET FOR SERVERS & WORKSTATIONS ................................. 46 CONTROL CONSOLE DESK .......................................................................... 47

Rev .A

Page 2 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 3 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

1.

INTRODUCTION Mesaieed Industrial City (MIC) is upgrading its Domestic Wastewater Treatment Plant (DWTP), sewerage network and Treated Sewage Effluent (TSE) discharge system. This project involves Phase 1 expansion of the DWTP together with construction of 3 numbers of wastewater pumping stations, rising mains, trunk sewers, fibre optic network and a new TSE pipeline. A SCADA system will be installed under Phase 1 Extension to monitor and control all mechanical and electrical equipment on the DWTP works referred to as On-Site system and the external pumping station referred to as Off-site system. The SCADA system will comprise of off-site PLC/RTUs connected via fibre optic cables to a central control point station which will perform monitoring and supervisory control from the Control Room in the new Administration Building at Mesaieed DWTP. The SCADA system will be provided with facilities to receive/transfer process and control equipment data from the existing DWTP to the new DWTP Control room. 1.1 DEFINITION This document contains datasheet of the equipment required for new PLC/SCADA system to be provided for Waste water pumping station control system by the control system vendor. This presents an outline of specifications of the equipment & elements both of hardware and software of control system for the project Programmable Logic Controller Based SCADA Control System for Phase-I of the Expansion of Existing Domestic Wastewater Treatment Plant & Construction Of 3nos Wastewater Pumping Station Rising Mains & Trunk Sewers in Mesaieed Community Area, based on user requirement and specifications. 1.2 CODES AND STANDARDS The system will meet, but not limited to, following specific standards wherever applicable: ISA S5.1 ISA S5.2 ISA S5.3 ISA S5.4 ISA S5.5 IEC 144 BS-5420 (1977) IEC 801-2/3/5 IEC 68/2 IEC 61131-3 ISO 9001 NEMA ICS 1 NEMA ICS 2
Rev .A

: Instrumentation symbols and identification : Binary Logic Diagrams for process Operation : Graphic symbols of distributed control/shared display instruments, Logic and computer systems : Instrument Loop Diagrams. : Graphic symbols for process displays. : Ingress protection for dust and water jets. : EMI and RFI immunity : Basic environment testing procedure for electronic components and equipment. : Advanced programming languages. : Quality Systems-Model for quality assurance in design, development, production, installation and service. : General Standards for industrial control systems. : Industrial Control devices, controllers and assemblies.
Page 3 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 4 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

2.

REFERENCE DOCUMENTS This document is generated based on the following Project reference documents. 2456-5001 2456-5501 2456-000 to 2456-0033 2456-5504 Appendix A, 2456-5529 2456-5531 2456-5534 2456-5532 : Rev A Mesaieed-EPIC Phase-I DWTP (Overall Communication Schematic). : Operating & Control Philosophy : Rev E P&ID : DWTP Instrument IO Schedule : Attachment 9 : System Architecture : PLC-SCADA IA/GA Drawings : PLC-SCADA Wiring & Termination Drawings : PLC-SCADA Bill of Quantities

Rev .A

Page 4 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 5 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

3.

UNIVERSAL BLACKLANE Make: GE Model: IC695CHS012 I S.No 1. 2.

No of Slots Dimensions

Description 12 428 x 141.5 mm

Rev .A

Page 5 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 6 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

4.

POWER SUPPLY 24VDC Make: GE Model: IC695PSD040 S.No Nominal Rated Voltage Input Voltage Range Start Run Input Power Inrush Current Description 24 VDC 18 to 30 VDC 12 to 30 VDC 60 Watts maximum at full load 4 Amps, 100 milliseconds maximum * 5.1 VDC: 5.0 VDC to 5.2 VDC (5.1 VDC nominal) 3.3 VDC: 3.1 VDC to 3.5 VDC (3.3 VDC nominal) 5.1 VDC: 0 to 6 Amps 3.3 VDC: 0 to 9 Amps NONE 50 mV 50 mV 10 ms This is the length of time the Power Supply maintains valid outputs if the power source is Interrupted. If this Power Supply is used with IC694 and IC693 modules that have relay outputs, note that dropouts longer than 10ms will cause dropouts on the Modules. Each terminal accepts one 14 AWG to 18 AWG wire. 6 Amps Up to 2

1. 2.

3. 4. 5. 6. 7.

Output Power Output Current Isolation Ripple (all outputs) Noise (all outputs)

8. 9. 10. 11.

Ride-through time Wiring Terminals Terminal Current Number of Daisy-Chained PSD040 Supplies

* The Inrush Current specification is given as a guide for sizing the external power source for the IC695PSD040. Peak inrush current may be higher for shorter durations.

Rev .A

Page 6 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 7 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

5.

CPU Make: Model: S.No

GE IC695CRU320 Description Estimated 30 days using an IC693ACC302 Auxiliary Battery Module at 20C. Up to 64 Mbytes of battery-backed RAM 64 Mbytes of non-volatile flash user memory +3.3 VDC: 1.0 Amps nominal +5 VDC: 1.2 Amps nominal Operating Temperature 0 to 60C (32F to 140F) Yes 0.047 ms per 1000 Boolean instructions Maximum drift of 2 seconds per day 0.01% maximum RS-232, RS-485 Modbus RTU Slave, SNP Slave, Serial I/O Dual backplane bus support: RX3i PCI and 90-30-style serial System designed to be electrically compliant with PCI 2.2 standard Up to 512 program blocks. Maximum size for a block is 128KB. 1.25A 100,000 write/erase cycles minimum Single bit correcting and multiple bit checking. Maximum 1 logic scan, minimum 3.133 msec. 3.66 msec: 1K Discrete I/O, 125 Analog I/O and 1K Registers 3.87 msec: 2K Discrete I/O, 250 Analog I/O and 2K Registers 4.30 msec: 4K Discrete I/O, 500 Analog I/O and 4K Registers 5.16 msec: 8K Discrete I/O, 1K Analog I/O and 8K Registers Up to 2 Mbytes
Page 7 of 47

1. Battery: Memory retention 2. Program storage 3. Power requirements 4. Operating Temperature 5. Floating point 6. Boolean execution speed, typical 7. Time of Day Clock accuracy 8. Elapsed Time Clock (internal timing) accuracy 9. Embedded communications 10 Serial Protocols supported 11 Backplane 12 PCI compatibility 13 Program blocks 14 Memory 15 Flash memory endurance rating 16 Memory error checking and correction (ECC) 17 Switchover Time* 18

Typical Base Sweep Time (Reference Data Transfer List Impact)** 19 Maximum amount of
Rev .A

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 8 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

data in transfer list 20 Number of redundancy links supported

Up to two IC695RMX128 synchronization links are supported

Rev .A

Page 8 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 9 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

6.

ETHERNET MODULE Make: GE Model: IC695ETM001 S.No 1. Ethernet Processor speed 2. Connectors 3. LAN 4. Number of IP addresses 5. Number of Ethernet Port Connectors 6. Embedded Ethernet Switch 7. Serial Port Description 200 Mhz - Station Manager (RS-232) Port: 9-pin female Dconnector - Two 10BaseT / 100BaseTX Ports: 8-pin female shielded RJ-45 IEEE 802.2 Logical Link Control Class I IEEE 802.3 CSMA/CD Medium Access Control 10/100 Mbps One Two, both are 10BaseT / 100BaseTX with auto-sensing RJ-45 connection. Yes Allows daisy chaining of Ethernet nodes. Station Manager Port: RS-232 DCE, 1200 - 115200 bps.

Rev .A

Page 9 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 10 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

7.

GENIUS BUS CONTROLLER Make: GE Model: IC694BEM331

S.No 1. 2. 3. 4. Diagnostics Communications Data Length Data Rates Genius Bus Specifications 5.

Description Advanced diagnostics capabilities Global Data and Datagrams 128 bytes per message Configurable: 153.5Kbaud standard/extended, 76.8Kbaud, or 38.4Kbaud Daisy-chained bus cable; single twisted-pair plus shield or Twin ax. Fiber optical cable and modems can also be used. 75, 100, 120, or 150 Ohm resistor at both ends of electrical bus cable. 7800 feet at 38.4Kbaud, 4500 feet at 76.8Kbaud, 3500 feet at 153.6Kbaud extended, 2000 feet at 153.6Kbaud standard. Maximum length at each baud rate also depends on cable type, 32 devices at all baud rates except 38.4Kbaud. 16 devices at 38.4Kbaud. 2000 volts Hi-Pot, 1500 volts transient common mode rejection.

Bus Type 6. Bus Termination 7.

8. 9.

Maximum Bus Length Maximum Number of Devices Isolation

Rev .A

Page 10 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 11 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

8. DIGITAL OUTPUT RELAY TYPE Make: GE Model: IC200MDL940

S.No 1. 2. 3. Points Module ID Isolation: User input to logic (optical) or frame ground Group to group Point to point LED indicators Backplane current consumption External power supply Thermal derating Output Characteristics Output voltage Output voltage drop

Description 16 individually isolated Form A relay outputs 80408040 250VAC continuous; 1500VAC for 1 minute 250VAC continuous; 1500VAC for 1 minute 250VAC continuous; 1500VAC for 1 minute One LED per point shows individual point ON/OFF state OK LED indicates backplane power is present 5V output: 490mA maximum 0 to 125VDC, 5/24/125VDC nominal 0 to 265VAC (47 to 63Hz), 120/240VAC nominal None 0 to 125VDC, 5/24/125VDC nominal 0 to 265VAC (47 to 63Hz), 120/240VAC nominal 0.3V maximum 10mA per point minimum 2.0A for 5 to 265VAC maximum (resistive) 2.0A for 5 to 30 VDC maximum (resistive) 0.2A for 31 to 125 VDC maximum (resistive) Not applicable (open contact) 10ms maximum 10ms maximum No internal fuses or snubbers 20 cycles per minute (inductive load) Fixed coil, moving armature Silver alloy See appendix D

4. 5.. 6. 7.

8. 9.

10. 11. 12. 13. 14. 15. 16. 17.

Load current Output leakage current On response time Off response time Protection Switching frequency Relay type Contact type Contact life

Rev .A

Page 11 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 12 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

9.

DIGITAL INPUT MODULE 24VDC Make: GE Model: IC200MDL650

S.No 1. 2. 3. Points Module ID Isolation: User input to logic (optical) or frame ground Group to group Point to point

Description 32 (4 groups of 8) 80408040 250VAC continuous; 1500VAC for 1 minute 250VAC continuous; 1500VAC for 1 minute 250VAC continuous; 1500VAC for 1 minute One LED per point shows individual point ON/OFF state OK LED indicates backplane power is present 5V output: 50mA maximum None Input response times 0 to +30VDC,+24VDC nominal +15 to +30VDC 0 to +5VDC 2.0 to 5.5mA 0 to 0.5mA 0.5ms maximum 0 ms, 1.0ms (default), or 7.0ms 10kOhms maximum

4. 5. 6. 7. LED indicators Backplane current consumption External power supply Configuration parameters Input Characteristics Input voltage On state voltage Off state voltage On state current Off state current On response time Off response time Configurable filter time Input impedance

8. 9. 10. 11. 12. 13. 14.

Rev .A

Page 12 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 13 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

10.

ANALOG INPUT MODULE Make: GE Model: IC200ALG240

S.No 1. 2. 3. Channels Module ID Isolation: User input to log ic ( optic al) and to frame ground, Group to Group Channel to channel

Description 8 inputs FFFF9802 250 VAC continuous; 1500VAC f or 1 minute

4. 5. 6. 7. 8. LED indicator s Backplane current consumption External power supply : Rang e Current consumption Thermal derating

Not applicable 250VAC continuous; 1500VAC f or 1 minute. FLD PWR LED indicates the presence of both logic Power and user power. OK LED indicates module status. 5V output: 15mA maximum. 3.3V output: 120mA maximum + 19.5 to + 30VDC including ripple 100mA maximum plus load currents None High/Low Limit, Over /Under rang e, Open Wire, Loss of Field Power Supply , Non- volatile memory fault Current mode: + 1 to 20mA Voltage mode: + /- 10VDC + /- 0.1% maximum of f ull sc ale Current mode: 45ppm/C typical, 90 ppm/C maximum Voltage mode: 30ppm/C typical, 60 ppm/C maximum Current mode: 381 nA nominal Voltage mode: 381 UV nominal Approximately 20 ms max. @ 50 Hz filter frequency Approximately 16.7 ms max. @ 60 Hz filter frequency 70dB minimum 0 ( default) Hold Last State ( configurable) Current mode: 150 Ohms Voltage mode: 760 K Ohms Ty pe: Dig ital w /programmable notches at 50 or 60 Hz 3 dB Corner Frequency : 10Hz _ 25%
Page 13 of 47

Diagnostics INPUT Characteristics 9. 10. 11. 12. 13. 14. 15. Input default 16. Field input DC resistance 17. Field input filter
Rev .A

Input operating rang e Accuracy at 25 degrees C Temperature coefficient Analog Resolution ( 1 LSB) Channel data Update r ate per module Channel- to- channel cross talk rejection

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 14 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

18. 19 20.

Nor mal mode Field Input Rang es Maximum field input ( without damage)

35 dB minimum Current mode: Approximately 0 ma to + 25 ma Voltage mode: Approximately. 12.5 V to + 12.5 V Current mode: _ 35 ma continuous Voltage mode: _ 17.5 V continuous

Rev .A

Page 14 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 15 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

11.

ANALOG OUTPUT MODULE Make: GE Model: IC200AL331 S.No 1. 2. 3. Channels Module ID Isolation: User input to log ic ( optic al) and to frame ground, Group to Group Channel to channel Description 4 outputs FFFF9805 250VAC c continuous; 1500VAC for 1 minute

4. 5. 6. 7. 8.

9. 10. 11. 12. 13. 14. 15.

LED indicator s Backplane current consumption External power supply : Rang e + 19.5 to + 30VDC including ripple Current consumption 100mA maximum plus load currents Thermal derating None High/Low Limit, Over / Under range, Open Wire, Loss of Diagnostics Field Power Supply , Non- volatile memory fault OUTPUT Characteristics Current mode: + 4 to 20mA Input operating rang e Voltage mode: + /- 10VDC Accuracy at 25 degrees C + /- 0.1% maximum of full sc ale Temperature Current mode: 45ppm/C typical, 90 ppm/C maximum coefficient Voltage mode: 30ppm/C typical, 60 ppm/C maximum Analog Resolution ( 1 Current mode: 381 nA nominal LSB) Voltage mode: 381 UV nominal Channel data Update Approximately 7 ms max. rate per module Channel- to- channel cross talk rejection 70dB minimum 0 ( default) Input default Hold Last State ( configurable)

Not applicable 250VAC c continuous; 1500VAC for 1 minute. FLD PWR LED indicates the presence of both logic Power and user power. OK LED indicates module status. 5V output: 15mA maximum. 3.3V output: 115mA maximum

Rev .A

Page 15 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 16 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

12.

I/O CARRIER BOX STYLE Make: GE Model: IC200CHS022

S.No 1. 2. 3. 4. No of Slots Dimensions Depth without Modules Weight

Description 1 66.8 x 163.5 mm 49.682 2 lbs

Rev .A

Page 16 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 17 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

13.

GENIUS NETWORK INTERFACE UNIT Make: GE Model: IC200GBI001

S.No 1. 2. 3. 4. 5. Number of Modules Network inputs per bus scan Network outputs per bus scan Discrete Input Memory Discrete Output Memory

Description 8 per rack, 64 per NIU/station 128 bytes 128 bytes 1024 points

1024 points

6.

Analog Input Memory 128 bytes

7. 8. 9. 10. Analog Output Memory Power Consumption Serial Bus Address Network data rate

128 bytes +5V@ 250mA, +3.3V@ 10mA 0 to 31 153.6 Kbaud extended, 153.6 Kbaud standard, 76.8 Kbaud, or 38.4 Kbaud.

Rev .A

Page 17 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 18 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

14.

24VDC POWER SUPPLY FOR IO Make: GE Model: IC200PWR002

S.No 1. 2. 3. 4. 5. 6. 7. Input Voltage Input Power Holdup Time Inrush Current Output Voltage Protection Output Current Total 3.3VDC Output 5VDC Output

Description 18 to 30 VDC, 24VDC nominal 11W 10ms 20A at 24VDC 25A at 30 VDC 5VDC, 3.3VDC Short circuit, overload, reverse polarity 1.5A maximum* 1.0A maximum (1.5A - I3.3V ) maximum

*The total output current should not exceed 1.5A. For example, if 3.3V @ 1.0A is required, 0.5A is available on the 5V output.

Rev .A

Page 18 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 19 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

15.

BOOSTER POWER SUPPLY CARRIER Make: GE Model: IC200PWB001

S.No 1. 2. Din Rail Mounting

Description 7.5mm X 35mm PWR: indicates that the attached booster power supply is functioning properly OK : indicates that the CPU or NIU and attached booster power supply are functioning properly.

LED

Rev .A

Page 19 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 20 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

16.

15TFT OUICKPANEL VIEW Make: GE Model: IC754VGF15CTD

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. Type Resolution Size MEMORY Flash Dram Expandable Communication Serial Com #1 Serial Com #2 Ethernet Lan #1 Ethernet Lan #2 Comm expansion(view) USB Compact Flash Environmental Operating temperature Agencies Environmental

Description 15" Color-TFT 1024 x 768 pixels 15.1" (Diagonal) 64 MB 64 MB To 96 MB or 128 MB RS232/RS485 RS232 10/100 Mbps 10/100 Mbps GE Genius, Data Highway Plus, DeviceNet Slave, and PROFIBUS Slave V1.1 Compatible One, Type 2 0 to 50 Deg C (32 to 122 Deg F) NEMA 4/4x 12 VDC @ +/- 20% or 24 VDC @ +/- 20% 48 Watts S = Standard overlay, B = Blank overlay, G = GE overlay, K = Kit 14.93" x 12.03" x 2.78" 379 mm x 305 mm x 71 mm

18.

Power Requirement Panel Cut-Out (W x H x D)

Rev .A

Page 20 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 21 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

17.

HIGH CAPACITY BATTERY Make: GE Model: IC693ACC302

S.No 1. 2. 3. 4. 5. 6. 7. Compatibility Operating temperature range Shelf life Battery capacity Physical dimensions Case material

Description 15.0 Amp-hours 5.713 long x 2.559 wide x 1.571 high (145.1 x 65.0 x 39.9 mm) Black, flame-retardant ABS plastic 2.0 (0.6 meter) twisted red/black 24 AWG lead with female 2-pin connector Compatible with all battery connectors on IC693 power supplies and IC697 CPUs 0 to +60C 7 years

Connection

Rev .A

Page 21 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 22 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

18.

REFLECTIVE MEMORY EXCHANGE Make: GE Model: IC695RMX128

S.No 1. 2. 3. 4. Packet size User memory Input power (from RX3i power supply)

Description Dynamic, automatically controlled by RMX128 module 128MB SDRAM 580 mA @ +3.3 VDC 220 mA @ +5 VDC Fiber optic LC type, conforms to IEC 61754-20 Zirconium ceramic ferrule Insertion loss: 0.35 dB (maximum) Return loss: -30dB

Connectors

Rev .A

Page 22 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 23 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

19.

LOGIC DEVELOPER PLC SOFTWARE Make: GE Model: IC646MPP001, VERSION-6.0

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20.

Description One Development Tool for All Controls, All Applications, All Users. With Proficy Machine Edition, you get the ultimate integration between HMI, motion and Multi-target control. Faster time to solution through increased efficiency Improved productivity to configure, develop, commission, and maintain applications Decreased development and maintenance costs Seamless migration path to the latest technologies Reduced training time with one software package for all controllers, operator interface, and motion Object Oriented Programming (Tool chest) User Defined Function Blocks Symbolic Names and Automated Address Management Cross Reference Tab Single Tag Database User Defined Data Types Web client/server Optimized view for systems with up to 2500 I/O points Expansive networking features Multi-language support Advanced scriptinguses standard VBScript with over 70 script functions to manipulate and format data Web publishingprovides remote monitoring and diagnostics and remote client-based reporting from a wide variety of web clients Wide range of PLC/device drivers and OPC client/server support, remote connectivity and thin client support for diagnostic and data monitoring
Page 23 of 47

Rev .A

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 24 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

20.

MODBUS COMMUNICATION MODULE Make: GE Model: IC200CMM020

S.No 1. Number of Serial Communications Modules

Description

Up to 2 per Genius NIU I/O Station 2. Number of RTU slaves per Serial Communications Module COMMREQ command memory (%AQ) required in the GENERIC_COMM module hardware configuration COMMREQ response memory (%AI) required COMMREQ response memory (%AI) required RTU Master Commands

1 to 247

3.

4. 5. 6.

Depends on individual COMMREQ content. Minimum: 22 words Maximum: 64 words Minimum: 2 words Maximum: 64 words for Genius NIU Minimum: 2 words Maximum: 64 words for Genius NIU As described in Modbus RTU Communications Manual, GFK-2220. Minor differences as described below. 65520, Initialize RTU Master Port 8000, Clear RTU Master Diag. Status8001, Read RTU Master Diag. Status8002, Send RTU Read/Force/Preset Query8003, Send RTU Diagnostic Query

Rev .A

Page 24 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 25 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

21.

8 PORT ETHERNET SWITCH Make: MOXA Model: EDS-208

S.No 1. 2. Ports Technology Standards:

Description 8 IEEE 802.3 for 10BaseTIEEE 802.3u for 100BaseT(X) and 100BaseFXIEEE 802.3x for Flow Control Processing Type: Store and Forward Flow Control: IEEE 802.3x flow control, back pressure flow control MAC Table Size: 1 K Packet Buffer Size: 512 Kbit Fiber Ports: 100BaseFX ports (SC/ST connector, multi-mode) RJ45 Ports: 10/100BaseT(X) auto negotiation speed, Full/Half duplex mode, and auto MDI/MDI-X connection LED Indicators: Power, 10/100M (TP port), 100M (fiber port) 12 to 45 VDC, 18 to 30 VAC (47 to 63 Hz) Housing: Plastic, IP30 protection Dimensions:40 x 100 x 86.5 mm (1.57 x 3.94 x 3.41 in) Weight: EDS-208: 170 g Installation: DIN-Rail mounting Operating Temperature: -10 to 60C (14 to 140F) Storage Temperature: -40 to 85C (-40 to 185F) Ambient Relative Humidity: 5 to 95% (noncondensing)

3. 4.

Switch Properties Interface

5.

Power Requirements Physical Characteristics

Environmental Limits

Rev .A

Page 25 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 26 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

22.

QP VIEW GENIUS LAN INTERFACE MODULE Make: GE Model: IC754GEN001

S.No 1. Environmental: Operating: Operating temperature on board Humidity Vibration Shock 2. No operating: Ambient temperature at board Humidity Vibration Shock 3. Bus type 4. Bus Termination 5. Baud rate 6. Max Num Of devices 7. 8. Environmental: Operating: Operating temperature on board Humidity Vibration Shock 9. No operating: Ambient temperature at board Humidity Vibration Shock

Description 0C to +60C,32F to +140F 5% to 95% non conditioning .012peak-peak displacement 10 to 57 Hz 1.0G acceleration 57-500 Hz per IEC68-2-6, Jisc 0911. 15G,11 ms sinusoidal duration per IEC68-27,6Jisc 0912 -40C to +85C,- 400F to +185F 5% to 95% non conditioning .2 inch displacement 5 to 10 Hz 1.0G acceleration 10 to200 Hz\ Board packed \in shipping Container 15G,10 ms duration per Mil STD 810C Method 516.2 Daisy Chained bus cable: Single twisted pair plus shield or Twin ax On board DIP switch selectable: None 75,100,120 or150 ohms. Configurable 153.6 Kbaud rate standard ,153.6KBraud Extended 32 Devices at 153.6 Kbaud standard 0C to +60C,32F to +140F 5% to 95% non conditioning .012peak-peak displacement 10 to 57 Hz 1.0G acceleration 57-500 Hz per IEC68-2-6, Jisc 0911. 15G,11 ms sinusoidal duration per IEC68-27,6Jisc 0912 -40C to +85C,- 400F to +185F 5% to 95% non conditioning .2 inch displacement 5 to 10 Hz 1.0G acceleration 10 to200 Hz\ Board packed \in shipping Container 15G,10 ms duration per Mil STD 810C Method 516.2

Rev .A

Page 26 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 27 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

23.

BUS SWITCHING MODULE Make: GE Model: IC660BSM021

S.No 10 11 12 13 14 Operating temperature Storage temperature Humidity Size (HxWxD) 24/48 VDC Block Input voltage Bus B selected: Bus A selected: Current draw at 24 VDC: at 48 VDC: 15 Reliability 16 Switch activation time 17 Switch release time 18 Input voltage Bus B selected: Bus A selected: Current draw at 24 VDC: at 48 VDC:

Description 0C to 60C (32F to 140F) -40C to +7OC (-4OF to 158F) 5% to 95% (non-condensing) 3.50 x 2.25 x 2.5 (8.9cm x 5.72cm x 6.35cm) 18 VDC to 56 VDC (not polarized) Less than 4 VDC (not polarized 17mA maximum, 1OmA minimum 60mA maximum, 30mA minimum 500,000 operations, minimum Less than 20mS (including switch bounce) Less than 70mS (including switch bounce) 90 VAC minimum to 130 VAC maximum, or 95 VDC minimum to 150 VDC maximum Less than 35 volts AC or DC 40mA minimum, 60mA maximum 5mA minimum, 12mA maximum

Rev .A

Page 27 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 28 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

24. IFIX PROFSNL SCADA PAK UNLMTD SRVR SOFTWARE Make: GE Model: IC647IFPRSRUNLMTM, VERSION-5.1

S.No 1. Powerful Distributed, Client/Server Architecture

Description Proficy HMI/SCADA iFIX SCADAs collect, process and distribute real-time data to Clients Clients, including both Thick and Thin offerings Client/server architecture delivers unparalleled scalability The iFIX Workspace is an intuitive integrated development environment Develop and deploy applications quickly using powerful Wizards Leverage Office applications like Excel and Word for mass editing and documentation Develop and improve applications online, without shutting down operations or recompiling applications Windows 2000/XP/2003/Vista based SQL/ODBC interfaces for easy integration with relational databases Advanced visualization (HMI) Math, Logic and Supervisory control (SCADA) User and role based node or domain linked security Real-time and historical trending Manual data collection and data management Proficy HMI/SCADA iFIX SCADAs collect, process and distribute real-time data to Clients Clients, including both Thick and Thin offerings Client/server architecture delivers unparalleled scalability

2.

Faster System Development and Deployment

3. Extensive Functionality

4. Powerful Distributed, Client/Server Architecture

Rev .A

Page 28 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 29 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

25. IFIX PROFSNL SCADA PAK UNLMTD DEV SOFTWARE Make: GE Model: IC647IFPRDVUNLMTM, VERSION-5.1 A

S.No 1. Faster System Development and Deployment

Description The iFIX Workspace is an intuitive integrated development environment Develop and deploy applications quickly using powerful Wizards Leverage Office applications like Excel and Word for mass editing and documentation Develop and improve applications online, without shutting down operations or recompiling applications iFIX delivers an industry leading ActiveX container for hosting third party objects Drop in ActiveX controls and bring them to life using the Animation Expert Windows 2000/XP/2003/Vista based SQL/ODBC interfaces for easy integration with relational databases Advanced visualization (HMI) Math, Logic and Supervisory control (SCADA) User and role based node or domain linked security Real-time and historical trending Manual data collection and data management Certified OPC client and server support Object-oriented graphics Workspace and an integrated development environment Fully Integrated Change Management Capabilities Electronic Signatures and Audit Trails (designed for 21 CFR Part 11) Biometric Password Support Application Integrity Validation Advanced Communications, Database and Network Diagnostics Redundancy and Validation on High Availability Computing Platforms Environment Protection Database Block Toolkit for Developers Integration Toolkit for Developers Installation Scripting and Customization Microsoft SMS Capable Alarm Emailing through Alarm and Event

2. Application Integration 3.

Extensive Functionality

4.

More Features

Rev .A

Page 29 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 30 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

26. IFIX ICLIENT RUNTIME SOFTWARE Make: GE A Model: IC647IFCLNTCRNM, VERSION-5.1

S.No 1. Lower Total Cost of Ownership

Description - Simple, intuitive configuration - True thin-client administration - Support for virtualization - 64-bit architecture - Sub-second sampling - Full 32-bit compatibility - Wide range of collectors, including OPC Alarms and Events - Embedded applications support via Windows XP - Highly compatible with third-party solutions - Fault tolerant architecture - Support for Microsoft Cluster Server - Redundant data collectors - Enhanced data security - Powerful data management and system optimization tools - Designed to help customers comply with FDAs 21 CFR Part 11 - Calculation & server-to-server collection - Open access for ERP and MES applications - Application integration via OLE DB, User API, SDK, and OPC HDA - Third-party historian collectors

2. Enterprise Performance 3. Open & Layered Compatibility 4. Highly Reliable System Architecture 5. Advanced Data Management 6. Standard Interfaces for Data Access

Rev .A

Page 30 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 31 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

27. IFIX HISTORIAN ENTERPRISE SERVER 1000 POINTS SOFTWARE (M4 KEY) Make: GE A Model: IC647HSTES1KM, VERSION-4.0

S.No 1.

Description An Intel Core or Xeon 3GHz (or 2GHz Core Duo) or equal AMD CPU with minimum 4 GB RAM A DVD-ROM drive 100 MBit TCP/IP-compatible network interface adapter A monitor that supports resolution of at least 1024 X 768 or better 80 GB free hard drive space, for the data archives, message files, buffer files, and log files used by the system A Pentium 4-based 2.0 GHz or better computer with 1 GB RAM 40 GB of free hard drive space to store buffered data A DVD-ROM drive TCP/IP-compatible network interface adapter for network communication and certain I/O drivers An Intel Core or Xeon 3GHz (or 2GHz Core Duo) or equal AMD CPU with minimum 4 GB RAM 80 GB of local free hard drive space 40 GB shared SCSI hard drive (RAID preferred) Two 100 Mbit TCP/IP-compatible network interface adapters for network communication and certain I/O drivers (one for public network, another for private network) One of the following operating systems, with latest service packs or revisions: - Windows 7 Professional (32 or 64 Bit) - Windows Vista Professional (32 or 64 Bit) - Windows Server 2003 (32 or 64 Bit) - Windows Server 2003 R2 (32 or 64 Bit) - Windows Server 2008 (32 or 64 Bit) - Windows Server 2008 R2 (64 Bit) - Windows XP Professional SP3 (32 or 64 Bit) - Windows XP Embedded (32 Bit) Internet Explorer v6.0, 7.0, or 8.0 For systems with Historian Web Administrators, Microsoft IIS (Internet Information Server) 6.0 or 7.0 is required. IIS is not required for Historian Non-Web Administrators Network interface software for network communication. The TCP/IP network protocol required One of the following 32 bit or 64 bit SQL Server systems to configure alarm and event archiving:
Page 31 of 47

Historian Servers

2. Data Collector nodes

3.

Microsoft Cluster service

4.

Software Requirements

Rev .A

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 32 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

- Microsoft SQL Server 2008 Standard, Professional, or Enterprise Edition - Microsoft SQL Server 2005 Standard SP2, Professional SP2, or Enterprise Edition SP2 - Microsoft SQL Server Express One of the following 32 bit versions of SQL Server to use Historian as a linked server: - Microsoft SQL Server 2008 Standard, Professional, or Enterprise Edition - Microsoft SQL Server 2005 Standard SP2, Professional SP2, or Enterprise Edition SP2 - Microsoft SQL Server Express IMPORTANT: Historian 4.0 does not support 64 bit linked SQL Server. The Historian Excel Add-In requires installation of Microsoft Office XP, Microsoft Office 2003, or Microsoft Office 2007. The Historian Web Administrator requires the Java Runtime Environment version 1.6 update 5.

Note: Item Numbers 19, 24, 25, 26 & 27 are offered softwares which will be the latest versions from GE-IP (General Electric Intelligent Platforms- the System Manufacturer). Licenses will be supplied in the form of hard keys. And there is no expiration of licenses. The guarantee/Warranty term is not applicable for softwares, since the system integrator/vendor will provide the running softwares with full compliance of GE software standards during handover.

Rev .A

Page 32 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 33 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

28. APPLICATION SERVER Make: DELL Model: POWER EDGE R -710

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. Form Factor Processors Processor Sockets Interconnect L2/L3 Cache Chipset Memory I/O Slots Drive Controller

Description 2U rack height Latest quad-core or six-Core Intel Xeon 5500 and 5600 series processors 2 Intel QuickPath Interconnect (QPI) 4MB and 8MB Intel 5520 Up to 144GB (18 DIMM slots*): 1GB/2GB/4GB/8GB DDR3, 800MHz, 1066MHz or 1333MHz 2 PCIe x8 + 2 PCIe x4 G2 Or 1 x16 + 2 x4 G2 PERC6/i or SAS6/iR, PERC 5/E and PERC 6/E External: Internal: PERC H800 (6Gb/s) with PERC H200 (6Gb/s) 512MB Non-Volatile cache PERC H700 (6Gb/s) with PERC H800 (6Gb/s) with 512MB Non-Volatile 512MB of battery backed cache cache PERC H700 (6Gb/s) with PERC 6/E with 256MB or 512MB battery backed 512MB of battery backed cache cache SAS 6/iR External HBAs (non-RAID): PERC 6/i with 256MB 6Gbps SAS HBA battery-backed cache SAS 5/E HBA PERC S100 (software LSI2032 based) PERC S300 (software based) 8 x 2.5 Hard Drive Option or 6 x 3.5 Hard Drive Option; Optional flex bay expansion to support half-height TBU Up to four 3.5" drives with optional flex bay OR Up to eight 2.5 SAS or SATA drives with optional flex bay 6TB SATA or Near Line SAS 2.5" SAS (10K RPM): 36GB, 3.5" SATA (7.2K): 80 GB,160GB, 73GB, 146GB, 250GB, 500GB, 750GB, 147GB, 300GB 2.5" SAS (15K RPM) 36GB, 1TB 3.5" SAS (10K): 400GB 73GB 3.5" SAS (15K): 73GB, 2.5" SATA II (5.4K RPM):
Page 33 of 47

10.

RAID Controller

11.

Drive Bays

12.

Max. Internal Storage

13.

Hard Drives1

Rev .A

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 34 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

80GB, 160GB, 250GB 2.5"SATA II (7.2K RPM): 80GB, 120GB, 160GB, 250GB 2.5 500GB SATA

146GB, 300GB, 450GB 3.5" Near-Line SAS (7.2K): 500GB, 750GB, 1TB 3.5 2.0TB SATA

14.

Network Interface Cards

15.

Power Supply

16.

Uninterruptible Power Supplies

17.

Availability

18. 19. 20. 21. 22. 23. 24.


Rev .A

Video Remote Management Systems Management Rack Support Fans Acoustics Operating Systems

Four embedded Broadcom NetXtreme II 5709c Gigabit Ethernet NIC with failover and load balancing; TOE (TCPIP Offload Engine) supported on Microsoft Windows Server 2003 SP1 or higher with Scalable Networking Pack; Optional 1GBe and 10GBe add-in NICs Broadcom NetXtreme II 57711 Dual Port Direct Attach 10Gb Ethernet PCI-Express Network Interface Card with TOE and iSCSI Offload Intel Gigabit ET Dual Port Server Adapter and Intel Gigabit ET Quad Port Server Adapter Dual Port 10GB Enhanced Intel Ethernet Server Adapter X520-DA2 (FcoE Ready for Future Enablement) Energy Smart Two hot-plug high-efficient 570W PSU OR High Output Two hot-plug 870W PSUs 1000W-5600W 2700W-5600W High Efficiency Online Extended Battery Module (EBM) Network Management Card DDR3; hot-plug hard drives; optional hot-plug redundant power supplies; dual embedded NICs with failover and load balancing support; PERC 6/i; optional PERC5/i integrated daughtercard controller with battery-backed cache; hot-plug redundant cooling; tool-less chassis; fibre and SAS cluster support; validated for Dell/EMC SAN Matrox G200 with 8MB of cache iDRAC6 Dell OpenManage 4-post (Dell rack), 3rd party Versa rails, sliding rails and Cable Management Arm Standard redundant cooling Typically configured** 2.5" chassis in 23 +/- 2 C ambient Idle: LwA-UL*** = 5.5 bels, LpAm**** = 39 dBA Microsoft Windows Small Business Server 2008 Microsoft Windows Essential Business Server 2008
Page 34 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 35 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

Microsoft Windows Server 2008 SP2, x86/x64 (x64 includes Hyper-V) Microsoft Windows Server 2008 R2, x64 (includes Hyper-V v2) Microsoft Windows HPC Server 2008 Novell SUSE Linux Enterprise Server Red Hat Enterprise Linux Sun Solaris For more information on the specific versions and additions, visit www.dell.com/OSsupport.

Rev .A

Page 35 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 36 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

29. ARCHIVE SERVER Make: DELL Model: POWER EDGE R -710

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. Form Factor Processors Processor Sockets Interconnect L2/L3 Cache Chipset Memory I/O Slots Drive Controller

Description 2U rack height Latest quad-core or six-Core Intel Xeon 5500 and 5600 series processors 2 Intel QuickPath Interconnect (QPI) 4MB and 8MB Intel 5520 Up to 144GB (18 DIMM slots*): 1GB/2GB/4GB/8GB DDR3, 800MHz, 1066MHz or 1333MHz 2 PCIe x8 + 2 PCIe x4 G2 Or 1 x16 + 2 x4 G2 PERC6/i or SAS6/iR, PERC 5/E and PERC 6/E External: Internal: PERC H800 (6Gb/s) with PERC H200 (6Gb/s) 512MB Non-Volatile PERC H700 (6Gb/s) with cache 512MB Non-Volatile PERC H800 (6Gb/s) with cache 512MB of battery backed PERC H700 (6Gb/s) with cache 512MB battery backed PERC 6/E with 256MB or cache 512MB of battery backed SAS 6/iR cache PERC 6/i with 256MB External HBAs (non-RAID): battery-backed cache 6Gbps SAS HBA PERC S100 (software SAS 5/E HBA based) LSI2032 PERC S300 (software based) 8 x 2.5 Hard Drive Option or 6 x 3.5 Hard Drive Option; Optional flex bay expansion to support half-height TBU Up to four 3.5" drives with optional flex bay OR Up to eight 2.5 SAS or SATA drives with optional flex bay 6TB SATA or Near Line SAS 2.5" SAS (10K RPM): 36GB, 3.5" SATA (7.2K): 80 GB,160GB, 73GB, 146GB, 250GB, 500GB, 750GB, 147GB, 300GB 2.5" SAS (15K RPM) 36GB, 1TB 3.5" SAS (10K): 400GB 73GB 3.5" SAS (15K): 73GB, 2.5" SATA II (5.4K RPM):
Page 36 of 47

10.

RAID Controller

11.

Drive Bays

12.

Max. Internal Storage

13.

Hard Drives1

Rev .A

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 37 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

80GB, 160GB, 250GB 2.5"SATA II (7.2K RPM): 80GB, 120GB, 160GB, 250GB 2.5 500GB SATA

146GB, 300GB, 450GB 3.5" Near-Line SAS (7.2K): 500GB, 750GB, 1TB 3.5 2.0TB SATA

14.

Network Interface Cards

15.

Power Supply

16.

Uninterruptible Power Supplies

17.

Availability

18. 19. 20. 21. 22. 23. 24.


Rev .A

Video Remote Management Systems Management Rack Support Fans Acoustics Operating Systems

Four embedded Broadcom NetXtreme II 5709c Gigabit Ethernet NIC with failover and load balancing; TOE (TCPIP Offload Engine) supported on Microsoft Windows Server 2003 SP1 or higher with Scalable Networking Pack; Optional 1GBe and 10GBe add-in NICs Broadcom NetXtreme II 57711 Dual Port Direct Attach 10Gb Ethernet PCI-Express Network Interface Card with TOE and iSCSI Offload Intel Gigabit ET Dual Port Server Adapter and Intel Gigabit ET Quad Port Server Adapter Dual Port 10GB Enhanced Intel Ethernet Server Adapter X520-DA2 (FcoE Ready for Future Enablement) Energy Smart Two hot-plug high-efficient 570W PSU OR High Output Two hot-plug 870W PSUs 1000W-5600W 2700W-5600W High Efficiency Online Extended Battery Module (EBM) Network Management Card DDR3; hot-plug hard drives; optional hot-plug redundant power supplies; dual embedded NICs with failover and load balancing support; PERC 6/i; optional PERC5/i integrated daughter card controller with battery-backed cache; hot-plug redundant cooling; tool-less chassis; fibre and SAS cluster support; validated for Dell/EMC SAN Matrox G200 with 8MB of cache iDRAC6 Dell Open Manage 4-post (Dell rack), 3rd party Versa rails, sliding rails and Cable Management Arm Standard redundant cooling Typically configured** 2.5" chassis in 23 +/- 2 C ambient Idle: LwA-UL*** = 5.5 bels, LpAm**** = 39 dBA Microsoft Windows Small Business Server 2008 Microsoft Windows Essential Business Server 2008
Page 37 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 38 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

Microsoft Windows Server 2008 SP2, x86/x64 (x64 includes Hyper-V) Microsoft Windows Server 2008 R2, x64 (includes Hyper-V v2) Microsoft Windows HPC Server 2008 Novell SUSE Linux Enterprise Server Red Hat Enterprise Linux Sun Solaris For more information on the specific versions and additions, visit www.dell.com/OSsupport.

Rev .A

Page 38 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 39 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

30. ENGINEERING WORKSTATION Make: DELL Model: PRECISION R5400

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Base Microsoft Operating System Memory Keyboard Video Card Hard Drive Mouse Optical Devices Raid Controller Rack Mounting Rails Windows Live Dell System Media Kit Riser Card

Description One Intel Xeon E5450 (3.00GHz,1333MHz,2x6MB Cache, Quad Core) English Genuine Windows 7 Professional (32Bit OS) with recovery DVD 4GB DDR2 667MHz Quad Channel FBD Memory (4x1GB) UK/Irish (QWERTY) Dell Standard Quiet key USB Keyboard Black 256 MB NVIDIA Quadro NVS 295 - 2 DP (2 DP-DVI adapters) Graphics Card 250GB (7,200 rpm) SATA 3.0Gb/s Hard Drive with NCQ and 16MB Data Burst Cache Dell Optical (Not Wireless), Scroll USB (3 buttons scroll) Black Mouse 8X DVD +/ - RW with Software included All SATA Hard Drives ,Non- RAID for 1 Hard Racks : Rapid/Versa Rails Windows Live For window 7 Resource DVD : Rack Workstation R5400 Diagnostics and Drivers Riser Card with 2 Slots PCIe x16 Wired as x8 (1)PCI-X (1)

Rev .A

Page 39 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 40 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

31. OPERATOR WORKSTATION Make: DELL Model: PRECISION R5400

S.No 1. Base

Description One Intel Xeon E5450 (3.00GHz,1333MHz,2x6MB Cache, Quad Core) English Genuine Windows 7 Professional (32Bit OS) with recovery DVD 4GB DDR2 667MHz Quad Channel FBD Memory (4x1GB) UK/Irish (QWERTY) Dell Standard Quiet key USB Keyboard Black 256 MB NVIDIA Quadro NVS 295 - 2 DP (2 DP-DVI adapters) Graphics Card 250GB (7,200 rpm) SATA 3.0Gb/s Hard Drive with NCQ and 16MB Data Burst Cache Dell Optical (Not Wireless), Scroll USB (3 buttons scroll) Black Mouse 8X DVD +/ - RW with Software included All SATA Hard Drives ,Non- RAID for 1 Hard Racks : Rapid/Versa Rails Windows Live For window 7 Resource DVD : Rack Workstation R5400 Diagnostics and Drivers Riser Card with 2 Slots PCIe x16 Wired as x8 (1)PCI-X (1)

2. Microsoft Operating System 3. Memory 4. 5. 6. 7. 8. 9. 10 11 12 13 Keyboard Video Card Hard Drive Mouse Optical Devices Raid Controller Rack Mounting Rails Windows Live Dell System Media Kit Riser Card

Rev .A

Page 40 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 41 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

32. 22 INCH LCD DISPLAY Make: DELL Model: 22 S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. 10 11 12 13 14 15 16 17 18 19 20 Display Type TFT Technology Width Depth Height Diagonal Size Viewable Size Dot Pitch / Pixel Pitch Max Resolution Color Support Response Time Signal Input Display Positions Adjustments Image Aspect Ratio Image Brightness Image Contrast Ratio Image Max H-View Angle Image Max V-View Interfaces Compatible with Windows 7 Description LCD display / TFT active matrix TN 20.3 in 6.3 in 15 in 21.5" - widescreen 21.5" 0.248 mm 1920 x 1080 24-bit (16.7 million colors) 5 ms DVI-D, VGA Tilt 16:9 250 cd/m2 1000:1 170 160 1 x DVI-D - 24 pin digital DVI 1 x VGA - 15 pin HD D-Sub (HD-15) Compatible with Windows 7" software and devices carry Microsofts assurance that .0 these products have passed tests for compatibility and reliability with 32-bit and 64-bit Windows 7. AC 120/230 V ( 50/60 Hz ) 27 Watt Yes 32 F 104 F 10 - 80%
Page 41 of 47

21 Power Voltage Required 22 Power Consumption Operational 23 ENERGY STAR Qualified 24 Min Operating Temperature 25 Max Operating Temperature 26 Humidity Range Operating
Rev .A

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 42 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

33. PRINTER Make: Model:

HP LASERJET 5200 Q7545A

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Print speed First page out6 Resolution Processor Memory Memory, maximum Compact Flash slots Duty cycle Input Output Two-sided printing

Description Up to 35 ppm, letter; up to 18.5 ppm, tabloid Less than 10 seconds letter FastRes 1200 and ProRes 1200 (1200 by 1200 dpi) 460 MHz Memory 48 MB RAM, one open DIMM slot 64 MB RAM, one open DIMM Up to 512 MB RAM via a single industry-standard 100-pin DDR DIMM slot Two open industry-standard Compact Flash slots Up to 65,000 pages per month 100-sheet multipurpose tray 1 - 250-sheet input tray 2 500-sheet input tray 3 250-sheet output bin Optional automatic two-sided printing unit Multipurpose tray 1: 76.2 by 127 mm to 312 by 470 mm (3 by 5 in to 12.28 by 18.5 in); letter, letter rotated, legal, executive, statement, 8.5 by 13, 11 by 17, 12 by 18, envelopes (Monarch, #10), custom 250-sheet tray 2, 500-sheet tray 3: 148 by 210 mm to 297 by 431.8 mm (5.83 by 8.27 in to 11.69 by 17 in); letter, letter rotated, legal, executive, statement, 8.5 by 13, 11 by 17, custom Automatic two-sided printing unit: letter, letter rotated, legal, executive, 8.5 by 13, 11 by 17, custom Multipurpose tray: 60 to 199 g/m2 (16 to 53 lb); 250-sheet tray 2, 500-sheet tray 3, automatic two-sided printing unit: 60 to 120 g/m2 (16 to 32 lb) Paper (plain, preprinted, letterhead, prepunched, bond, recycled, color, rough, light, vellum, tough), transparencies, labels, envelopes, cardstock Hi-Speed USB 2.0 port, IEEE 1284 parallel port, one open EIO slot, HP Jet direct Fast Ethernet embedded print server HP PCL6, HP PCL 5e, HP postscript level 3 emulation, 103 built-in scalable PCL fonts, 93 internal PostScript fonts Microsoft Windows 2000, XP, Server 2003; Certified for Windows Vista; Mac OS X-10.2.8, 10.3 and 10.4 and higher Via embedded print server: Microsoft Windows 2000, XP,
Page 42 of 47

12.

Sizes

13.

Weights

14. 15. 16. 17. 18.


Rev .A

Types

Interfaces

Languages and fonts Client operating systems Network operating

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 43 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

systems 19. 20. Dimensions (WXDX H) Weight Whats in the box

21.

Server 2003; NetWare; UNIX; AppleTalk; Linux; HPUX; Local Talk 490 by 600 by 405 mm (19.3 by 23.6 by 15.9 in) 30.2 kg (66.5 lb) 5200tn printer, HP LaserJet Q7516A Black Print Cartridge with Smart Printing Technology, documentation (Getting Started Guide, Network Install Guide), software and documentation CD, power cord, control panel overlay, 100-sheet multipurpose tray 1, 250-sheet input tray 2, 500-sheet input tray 3

Rev .A

Page 43 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 44 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

34. GPS TIME SYNCHRONIZATION SYSTEM Make: BODNET Model: SIGMA RACK MOUNTED

S.No

Description

1. Power: 110/230V or TBT 24V 2. Time base accuracy: 0,1 sec/day 3. 3 x relays for D1D2 impulses, alarms or circuit programming 4. 1 x dry contact input 5. Integrated protection of the output against short circuits and overload 6. Fast adjustment of clock after power cut 7. Wireless (DHF) and wired time distribution 8. NTP (Network Time Protocol) server 9. Circuit programming in various modes: weekly, bank day, holidays, and special days, astronomic or periodic

Rev .A

Page 44 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 45 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

35. 24 PORT 10/100 DESTOP/RACK MOUNATABLE ETHERNET SWITCH Make: D - LINK Model: DES 1024D

S.No
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.

Description
Mac Address Table Switch Fabric Transmission Method Diagnostic LEDs RAM Buffer Diagnostic LEDs QoS Network Protocols & Standard IEEE
Electrical & Emissions Certifications

8K
4.8Gbps Forwarding Capacity Store-and-Forward Per Unit: Power
Per Unit :Power Per Port :Activity/link Speed 500,000 operations, minimum

12. Power 13. Power Consumption 14. Heat Dissipation 15. Environmental 16. Safety 17. Temperature 18. Humidity 19. Dimensions (W xDx H) 20. Weight

10BASE-T 100BASE-T 802.3 Ethernet, 802.3u Fast Ethernet, 802.3x Flow Control, 802.1p Priority Queuing FCC Class A CE Mark Class A C-Tick VCCI-A ICES-003 Class A 100-240VAC, 50/60Hz Internal Universal Power 6.8 Watts 3.2BTU/hr RoHS compliant CSA NRTL/C Operating: 32 to 104F Storage: 14 to 131F Operating: 5% ~ 95% RH (Non-condensing) 11in x 7in x 1.8in 3.5 lbs (1.6 kg)

Rev .A

Page 45 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 46 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

36. RACK CABINET FOR SERVERS & WORKSTATIONS Make: CHEVAL Model: ARION: 19 RACK

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9.

Description

Overall width = 600mm (23.6) Overall Height = 1,985mm (78)


Overall Depth = 1,090mm (43) Internal Height = 42 u Nominal Static Load =1,000 Kg Enhanced Static Load =1,200 Kg Caster Dynamic Load = 295 Kg Door Opening Radius = 120 degree Font Door Total Open Area =1,008 sq.inches

10. Split rear Door Total Open area = 1,030 sq.nches 11. Performance pattern of 71 % 12. 13. 14. 15. 16.

17. 18. Premium grade Hot and Cold rolled steel sheet 19. Designed and manufacture under ISO 9001:2008 20. All material RoHS complaint

Packing :Knock down bulk pack/Quantity per standard 40 foot Container = 128 sets Assembled quantity = 32 sets Estimated assembly time : 25 minutes Standards And Material Dimensions conform to EIA -310E,IEC- 60297-2 Five range iron-phosphate pre-treatment with textured powder coat finish, tested to 500 hours salt spray under ASTM-D610-01 and ASTM B117 Available in low gloss textured black of platinum

Rev .A

Page 46 of 47

QATAR PETROLEUM ONSHORE ENGINEERING DEPARTMENT DOC NO. CONTRACT NO: GC 07/102200 SHEET 47 of 47 REV. DATE A 21/07/11

2456-5533

CONTROL SYSTEM FOR DWTP

DATA SHEET SCADA-PLC WORKS FOR DWTP

37. CONTROL CONSOLE DESK Make: PYROTECH Model: EVOLVE

S.No 1. 2. 3. 4. 5. 6. 7. 8. 9.

Description Table top made of 25 mm MDF Structure is made of extruded aluminum profile Open Structure giving ample leg room Paint Shade :RAIL 5012 (Blue) Total Aluminum Extrusion power coated in aluminum grey Proper horizontal and vertical cable tray to hide wires Fire Retardant High load carrying capacity Easily expandable

Rev .A

Page 47 of 47

S-ar putea să vă placă și