SF6 insulated test transformers are especially designed for testing metal-clad switchgear (GIS) in the factory and on-site, and for testing on-site substation equipment. The conventional transformers can be flanged directly to the GIS. This makes testing of such GIS installations possible without feeding them through an air-SF6 bushing. Therefore, the merits of the encapsulation remains effective also during the testing which is of importance for Partial Discharge tests. These systems are particularly suited for on-site tests of GIS after assembly. In the factory, they allow to test sub-assemblies and components directly in the manufacturing line, thus avoiding transportation to a central test facility, and extra handling.
8VHU EHQHILWV
Small and compact dimensions resulting in minimum space requirements Light-weight components Rugged construction to withstand transportation stresses Direct flanging to the test object High safety for operating personnel because of encapsulation of all HV carrying parts Large range of application in conjunction with test bushing for testing of open equipment Built-in HV measuring capacitor
4XDOLW\
Haefely quality assurance complies with ISO 9001. The electronic measurement and control devices are designed and manufactured in-house. Our many years of experience in dealing with EMC is therefore an important asset. The design of the test system complies with the VDE 0104 standard for optimal protection of the operating personnel. The test system is shut-down in case of over-voltage, over-current and fast voltage transients. Damage at the fault is minimised.
%ORFNGLDJUDP IRU WHVWLQJ HQFDSVXODWHG WHVW REMHFWV LQ WKH IDFWRU\ V\VWHP 766
Insulating transformer
Regulating transformer
Compensating reactor
HV test transformer
Coupling capacitor
kV
Control unit
C 9 D @AB F8
C 9 D @AB 8
C E AB @ 98
Encapsulated components
Test object
3 way-flange
HV test transformer
Coupling capacitor
Standard capacitor
Control unit Control cables Power connections Measuring cables Partial discharge detector Capacitance and tan delta bridge
6\VWHP FRPSRQHQWV
The test system includes following main components: Regulating transformer type STL (only with factory test system TSS) Power line filter type NLFA Compensating reactor type KDL (only with factory test system TSS) Low voltage protection unit (included in systems rated 510 kV or higher) type NSP Test transformer type TES Control system type OT 247 for factory tests (TSS) or Regulating cubicle with control panel, type TKMT, for on-site tests (TSSV)
$YDLODEOH 2SWLRQV Encapsulated coupling capacitor type KKS SF6-air bushing type DFS and various connection or adaptation flanges between test transformer & bushing & coupling capacitor & test object. Specific base frames or containers for on-site testing. Encapsulated standard capacitor type NKS Control system type OT 257 instead of the OT 247 HV and grounding connections if bushing is used. The connection to test object is usually not included. Partial Discharge detectors Capacitance and power loss factor measuring bridges Other devices upon request.
Ey
Test object
Ey
Ey
Ey
Ey
TSS 230-45 TSS 325-30 TSS 510-90 TSS 750-250 TSS 1000-375
TES 230-45 TES 325-30 TES 510-90 TES 750-250 TES 1000-375
KDL 180 KDL 120 KDL 360 KDL 900 KDL 1800
7HFKQLFDO GDWD RI WKH 67/ UHJXODWLQJ WUDQVIRUPHU VHULHV RQO\ VRPH UDWLQJV VKRZQ
t pPPc3D35m qVp c r Rs qV Pqct r z m r m p q c5 V ccVq5 k m '~ c}wk5 3 o | qV3tEqVq %d# l k m g s V 55
25 50 150 200
1.2 x 0.5 x 1.8 1.6 x 0.6 x 2.0 1.0 x 1.8 x 1.5 1.2 x 2.0 x 1.7
14 kHz...10 MHz
7HFKQLFDO GDWD RI WKH .'/ FRPSHQVDWLQJ UHDFWRU VHULHV RQO\ VRPH UDWLQJV VKRZQ
t pPPc3D35m r qVp c Rs m r m qV Pqct r z q cp5 Vtk5 3 o '~ c}|w5 3 o k qV3tEqVqq g%# l k m d x s z y55
KDL 120 KDL 180 KDL 360 KDL 900 KDL 1800
1.0 x 0.8 x 1.0 1.1 x 1.2 x 1.0 1.2 x 1.2 x 1.0 1.6 x 1.3 x 1.4 2.5 x 1.3 x 1.5
A secondary part for voltage measurement with a Haefely control unit or measuring instrument is fixed on the transformer housing. A platin-foil thermometer is built in the low voltage winding. The temperature is checked and switches the system off should it be over-loaded. 7HFKQLFDO GDWD RI WKH 7(6 WUDQVIRUPHU VHULHV DW +]
q 2 3c53 q cpc5 Vk p r q c rE c ~ p q c5 V ct E ~ r p%~ 3 m k 3cc55v r Pp V V r l r m r k q 3c 55c3R5c 5t }{ | ' qiV3Xc} ~ t }{ 2 c5 V d p q n V 55
TES 230-45 TES 325-30 TES 510-90 TES 750-250 TES 1000-375
45 30 90 250 375
12 8 25 70 105
25 17 17 17 19
10 10
Other voltage ratings are possible! Please contact us. The given power rating is valid at the output of the test transformer. If other components like a coupling capacitor, bushing or connecting flange are added, their internal capacitance reduce the available power available for the test object.
u d
q P
# P
#F
q P
3 #
g %d# 5 #F
d#
5 5 5
'LPHQVLRQV
nV 55
TES 230-45 TES 325-30 TES 510-90 TES 750-250 TES 1000-375 3' PHDVXUHPHQWV
The indicated PD level is inherent to the test system itself, without considering possible external radiated interference or interference from the power supply. The PD level will be checked during the system test in our works. The above specified PD level presumes that the test system will be equipped with adequate filtering (low voltage filter) and earthing (< 2 ). The mains must fulfil the following requirements (according to IEC): Disturbances of supply voltage, peaks phase to ground Harmonics of supply: Ratio of peak to RMS value 7\SLFDO DFRXVWLF QRLVH OHYHO measured based on IEC 60551 max. 4 V 2 5 % < 75 dBA
The actual noise level on site depends to a large extent on the on-site conditions, such as type of walls and the geometrical configuration. :RUN WHVWV High voltage withstand test at 1.2 Un PD measurement Short circuit impedance measurement Measurement of the voltage ratio JDV FRQQHFWLRQ
7UDQVSRUWDWLRQ
Usually, the test transformers are shipped assembled and are therefore ready for immediate use. For transportation, the SF6 gas pressure should be reduced to 1.2 bar. The standard filling valve is compatible with DILO treatment equipment. Other valves are available under request. The SF6 gas treatment equipment is not included in our scope of supply.
d#
At any time and in addition to the output high voltage a selection of four of the following information can be displayed: Status of the protection system Status of the safety circuit and the emergency trip Output voltage and current of the regulating transformer Timer
+LJK 9ROWDJH PHDVXUHPHQW The measuring signal is derived from the built-in HV divider of the TES transformer. The value of the high voltage is permanently displayed, either as peak value/2 or as RMS value. In case of flashover at the test object the control unit automatically stores the last voltage measurement as well as the polarity of the high voltage during the discharge. Measuring error of the electronic Measuring error of the complete measuring system (divider/coupling quadripole, electronic system) at 50/60 Hz. 0.5 % of the measured value between 10 % and 100 % of the system output voltage 1 % of the measured value between 10 % and 100 % of the output voltage
Warning lamps (one green, one red) are mounted on the TKMT cabinet. Plugs are provided for a safety circuit (Interlock). 'HVFULSWLRQ RI WKH UHJXODWLQJ WUDQVIRUPHU SDUW With this air insulated regulating transformer the input voltage of the test transformer can be varied smoothly & continuously. The unit is for indoor operation, air-cooled. The primary winding is galvanically separated from the secondary winding. The zero start interlock forces the operator to start always from zero. 7HFKQLFDO GDWD RI WKH 7.07 FRQWUROV VHULHV
t pPPcX35m qVp c r t pPPc Rs m r m qV Pqct r z q cp5 V cckVq5 m '~ c}|w5 3 o k qVq5h%Vp %d# l k j i g { x 55
30 45 90 250
1.3 x 0.8 x 2.2 1.3 x 0.8 x 2.2 1.3 x 0.8 x 2.2 1.3 x 0.8 x 2.2
10
The DMI 551 has 3 separate analogue measuring channels and is available in all combinations. E.g. as a pure impulse measuring device up to a multi purpose AC, DC, IMP measuring device. Due to its modular system a later upgrade can be performed easily on-site without sending the device back to the Haefely works. +DUG DQG 6RIWZDUH Are based on Haefely in house developments especially adapted to the demanding high voltage test environment. 3 individual measuring channels allow for better performance and higher reliability. Microprocessor control is based on PC 104 industrial standard and built with high quality industrial strength components. The illuminated LCD CFL screen has a size of 120 x 64 mm and offer a resolution of 240 x 128 dots. Software is stored on an EPROM and can be updated if required. 7HFKQLFDO GDWD Technical data are listed for a DMI equipped with only the AC measuring channel. $& 9ROWDJH 0HDVXULQJ &KDQQHO Measured values Display Accuracy Input voltage Measuring range Range setting Input impedance Frequency of the measured voltage 16 2/3...40 Hz, Flash detection Peak / 2 (capacitor), RMS (fast A/D conversion) kV, 4 Digits 0,5 %, 3 Counts max 150 V RMS 5...100 % automatic 1 M, 60 pF 40...400 Hz, +/- 0.5 % Accuracy +/- 1 % Accuracy polarity and last Peak / 2
P X
Used in conjunction with the TKMT controls for on-site tests, the DMI 551 is a multi purpose measuring instrument for all kind of voltages present in high voltage test laboratories. The instrument has a high EMC compatibility and does not need additional screening. It is built into a 19" standard housing, 3 units in height.
12
Pm
d#
&RQQHFWLRQ IODQJHV
'HVFULSWLRQ A multitude of connection flanges can be realised to connect: coupling capacitors SF6-air bushings test object test transformer
These flanges can be equipped with a switch for separating a coupling capacitor from the test transformer for example. This helps to increase the capacitive load range of the test system. Earthing or PD calibration studs can be integrated too.
Special base frames for the test transformer, coupling capacitor, SF6-air bushing can be realised.
d #
13
7HVW DFURVV RSHQ VZLWFK ZLWK ERWK 7(6 RXWSXWV SKDVH VKLIWHG E\ GHJUHHV Output TES 1 Effective test voltage across test object is the sum of the outputs of the TES 1 and the TES 2.
Output TES 2
14
&RQWDLQHUV
'HVFULSWLRQ For storage and transportation of the AC test system test system including the high voltage transformer TES. If possible, the container is subdivided by a partition in a "control room" and a "storage room". If not enough space is available, a separate container serves as control room. The regulating transformer TKMT with controls is installed inside the control room. The feeding voltage is transferred via special cables to the HV transformer. A desk with drawers can also be installed in the control room, which is lighted. Provision for a safety circuit connection is given. The container is usually equipped with a power distribution panel, including protection system and main circuit breaker. An opening is provided for the power and control cables which can be closed with a hinged door. All pieces of equipment are earthed at a central point, accessible from the outside of the container. The test transformer, eventual bushing with HV electrode as well as base frames are arranged inside the storage room / container. These elements are secured by adapted fastenings during transportation. Haefely uses the following standard steel container which are specially customised for the test equipment arrangement. A special double component paint, standard light grey RAL 9002, is used and the centre of gravity is clearly indicated. They can be transported by ship, train and lorry.
15
400 V
OSI generator
Test transformer
Test object
,QFOXGHV WKH IROORZLQJ PDLQ FRPSRQHQWV Impulse capacitors with connection circuit DC Charging and measuring circuits Polarity change circuit Integrated command panel Digital measuring instrument DMI 551 IMP
26, UDFN
Max. output OSI voltage with test transformer TES 600 kV Max. output OSI voltage with test transformer TES 750 kV The value depends of the test object load.
16
7HFKQLFDO VHUYLFHV
'HVFULSWLRQ Haefely Test AG has a dedicated Technical Services dept. with an experienced team of engineers doing the internal tests as well as the commissioning on-site and final testing of the test installations. Our Technical Services dept. does also preventive maintenance, repairs and calibrations if required. This responsive team allows to minimise eventual down-times and assures the shortest possible reaction time should any question arise. The full coverage of the warranty is granted only if Haefely Test AG has carried out the Technical Services. The charges for the delegation of our personnel are based on the terms and conditions of the Swiss Association of Machinery Manufacturers. ,QVWDOODWLRQ Big installations require our experienced team of mechanical erectors for supervising the assembly the test systems. 6\VWHP DQG $FFHSWDQFH 7HVWV RQ 6LWH Once the system is erected, we delegate our engineers for doing the systems tests at the customers. The system test shall proof that the system works according to the specification at customers site and gives a first training to the operating staff. These tests can also be done with a real test object. 7UDLQLQJ RI 2SHUDWLQJ 3HUVRQQHO The training is carried out by the Haefely senior engineer immediately after the systems tests. Detailed explanations about the use of the system, controls and measuring instruments are given, in addition to the operating manuals. 3UHYHQWLYH 0DLQWHQDQFH 6HUYLFH YLVLWV
Haefely Test AG can offer a regular service & maintenance visit on-site for checking the system condition & proposing necessary works. This is particularly appreciated for production line equipment. This visit can also be combined with the system re-calibration.
17
18
2UGHU WH[W
7\SH 766 IRU IDFWRU\ WHVWLQJ 7\SH 7669 IRU RQVLWH WHVWLQJ
'HVFULSWLRQ - Complete basic system - SF6 - insulated HV transformer with a built-in HV measuring capacitor - Switching and regulating cubicle - Compensating reactor - Control unit with set of control and measuring cables, 20 m - Voltage measurement - Power line filter - Low voltage protection device (only included for systems 510 kV and above) - One set of operating instructions and test reports in English or German) 2SWLRQV - Computerised control unit with set of control and measuring cables, 20 m - Encapsulated coupling capacitor - SF6 - air bushing - Connection flanges - Container for storage, transportation & test room - OSI generation rack - Technical services - Partial Discharge detectors & - C & tan measuring bridges
&RGH
&RGH
TSS ... kV, ... kVA TES ... kV, ... kVA STL ... kVA KDL ... kVA OT 247 in desk top housing incl. in OT 247 NLFA NSP
TSSV ... kV, ... kVA TES ... kV, ... kVA TKMT ... kVA incl. in TKMT incl. in TKMT DMI 551 incl. in TKMT as option as option
OT 257 with desk and mini-rack KKS ... kV, ... nF DFS ... kV ZF... --TES OSI ... kV DEL several models available, please see the Tettex General Catalogue please contact us
--KKS ... kV, ... nF DFS ... kV ZF... CONT AC TES OSI ... kV DEL several models available, please see the Tettex General Catalogue please contact us
- Other possibilities
19
/LVW RI OHDIOHWV
Modular AC test systems up to 300 kV, 0.25 A AC voltage test systems up to 1800 kV, 40 A Instrumentation for Partial Discharge, C and tan , accuracy and resistance Haefely Test AG offers also a complete range of impulse test systems for both impulse voltage and impulse current applications. E 151.30 E 152.51 Tettex General Catalogue