Documente Academic
Documente Profesional
Documente Cultură
TOPIC OUTLINE
Lateral Restraint Shear & Moment Capacity Local Buckling & Bearing Deflection Design Procedures
General Not Full Restrained Unrestrained
LEARNING OUTCOME
Student would be able:
To identify the degree of lateral restraint To identify the shear & moment capacity of beam structure To calculate shear & moment capacity of beam structure To identify the local buckling, bearing and deflection of beam To calculate buckling resistance, bearing capacity & buckling moment resistance To identify the degree of lateral restraint To design of beam subjected to Lateral-Torsional Buckling
DEFINITION
In building construction, a beam is a horizontal member spanning an opening and carrying a load that may be a brick or stone wall above the opening A beam is a structural member which is subject to transverse loads MUST be designed to withstand shear & moment
BEAMS
Purlin carries the roof load to the trusses Rafter a slopping beam carrying the roof load to the
purlins
Figure 2: Fascia
TYPES of BEAM
Simple beam
supported w/out restrained
Overhanging beam
freely supported BUT extended beyond one or both of its supports
Continuous beam
freely supported BUT extended over three or more supports
Fixed-end beam
having its ends fixed against rotation
Restrained beam
partially fixed at one or both ends
Cantilever beam
BEAM LOADS
Types of beams load
1) Concentrated loads from secondary beams & columns 2) Distributed loads from selfweight & floor slab
Classified load
1) Dead loads from self weight, slabs, finishes etc 2) Imposed loads from people, fittings, snow on roof 3) Wind loads mainly on purlins and sheeting rails
LATERAL RESTRAINT
Degree of lateral restraint
Partial Restraint
Without Restraint
-Lateral torsional stability is assumed adequate -Maybe provided by the concrete floor which sufficiently connected to the beam/bracing member
-D compression by loading make the flange is susceptible to fail by buckling sideway -Overall moment capacity will not be reached
SHEAR CAPACITY
REMEMBER
MOMENT CAPACITY
REMEMBER
The Moment due to design load M SHOULD NOT be greater than the moment capacity Mc
Figure 14: Cases where The checking of Local Buckling & Bearing Could Be Avoided & Could Not Be Avoided
- D stiff bearing length, b1 should be taken as the length of support that cannot deform appreciably in bending - Assume that the load disperses at 450 through d section elements which are firmly fixed together.
BUCKLING CAPACITY
If the flange through which the load or reaction is applied is effectively restrained against both
a) rotational relative to the web b) lateral movement relative to the web
Then, provided that d distance ae from d load or reaction to the nearer end of the member is at least 0.7d
EXAMPLE
Equivalent Slenderness LT
- Generally, for I & H section (cl. 4.3.6.7)
mLT
- For normal loading, the equivalent uniform moment factor for lateral-torsional buckling mLT should be obtained from Table 18 for the pattern of major axis moments over the segment length LLT. - Purpose- to indicate one of the major parameter in determining elastic critical moment Mcr
2 EH 1 M cr = EI y GJ 1 + 2 mL L GJ
m L EIy G J E H is mLT is either LE or LLT is flexural rigidity about y-axis is shear constant is torsional constant is modulus of elastic is warping section constant (H=Iyh2/4)
-The criterion of the beam to pass the lateral-torsional buckling checking is:
M x M b / mLT &
Mcx Mx
M x M cx
is the major axis moment capacity of the cross section is the maximum major axis moment in the segment
EXAMPLE
HAPPY ENDING