TECHNICAL DATA & SERVICE MANUAL

FILE NO.

SPW-XR253GH56 SPW-XR253GH56 SPW-XR253GH56 SPW-XR253GH56 SPW-XR363GH56 SPW-XR363GH56 SPW-XR483GH56 SPW-XR483GH56

SPW-CR253EHL5 SPW-CR253EL5 SPW-CR253EHL8 SPW-CR253EL8 SPW-CR363EHL8 SPW-CR363EL8 SPW-CR483EHL8 SPW-CR483EL8 SPW-CR253EHL5 SPW-CR253EL5 SPW-CR253EHL8 SPW-CR253EL8 SPW-CR363EHL8 SPW-CR363EL8 SPW-CR483EHL8 SPW-CR483EL8

SPW-TR253GH56 SPW-TR253GH56 SPW-TR253GH56 SPW-TR253GH56 SPW-TR363GH56 SPW-TR363GH56 SPW-TR483GH56 SPW-TR483GH56 SPW-DR253GH56 SPW-DR253GH56 SPW-DR253GH56 SPW-DR253GH56 SPW-DR363GH56 SPW-DR363GH56 SPW-DR483GH56 SPW-DR483GH56

SPW-CR253EHL5 SPW-CR253EL5 SPW-CR253EHL8 SPW-CR253EL8 SPW-CR363EHL8 SPW-CR363EL8 SPW-CR483EHL8 SPW-CR483EL8 SPW-CR253EHL5 SPW-CR253EL5 SPW-CR253EHL8 SPW-CR253EL8 SPW-CR363EHL8 SPW-CR363EL8 SPW-CR483EHL8 SPW-CR483EL8

SPW-UR253GHN56 SPW-UR253GHN56 SPW-UR253GHN56 SPW-UR253GHN56 SPW-UR363GHN56 SPW-UR363GHN56 SPW-UR483GHN56 SPW-UR483GHN56

SPLIT SYSTEM AIR CONDITIONER


INDOOR MODEL No. SPW-XR253GH56 SPW-XR363GH56 SPW-XR483GH56 SPW-TR253GH56 SPW-TR363GH56 SPW-TR483GH56 SPW-UR253GHN56 SPW-UR363GHN56 SPW-UR483GHN56 SPW-DR253GH56 SPW-DR363GH56 SPW-DR483GH56 PRODUCT CODE No. 854 014 17 854 014 18 854 014 19 854 014 31 854 014 32 854 014 33 854 015 85 854 015 86 854 015 87 854 014 34 854 014 35 854 014 36 OUTDOOR MODEL No. SPW-CR253EHL5 SPW-CR253EL5 SPW-CR253EHL8 SPW-CR253EL8 SPW-CR363EHL8 SPW-CR363EL8 SPW-CR483EHL8 SPW-CR483EL8 PRODUCT CODE No. 854 015 40 854 015 57 854 015 41 854 015 46 854 015 42 854 015 47 854 015 43 854 015 48

Section

Indoor Unit

Outdoor Unit

3
SPW-TR253GH56 SPW-TR363GH56 SPW-TR483GH56

SPW-XR253GH56

SPW-XR363GH56 SPW-XR483GH56

SPW-CR253EHL5, SPW-CR253EHL8 SPW-CR253EL5 , SPW-CR253EL8

SPW-UR253GHN56

SPW-UR363GHN56 SPW-UR483GHN56

SPW-DR253GH56 SPW-DR363GH56 SPW-DR483GH56

5
SPW-CR363EHL8, SPW-CR483EHL8 SPW-CR363EL8 , SPW-CR483EL8

0.8180.219.2

11/02

Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must : Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

When Installing
In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.

In an area with High Winds


Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

In a Snowy Area (for Heat Pump-type Systems)


Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing


Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas. Keep all tubing runs as short as possible. Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run.

CAUTION

If Necessary, Get Help


These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation


The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either narrow or wide rather than as liquid or gas.

SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

When Servicing

Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.

CAUTION
Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas. Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.

When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

SM830080

WHO SHOULD USE THIS MANUAL


This service manual is made to assist the service technician apply his knowledge and training to this model air conditioner. This manual is written both for experienced service persons and those who are new to air conditioning service. To help those with less experience or who are new to this kind of unit we have included more explanations of basic procedures in simple language than is usual in some service manuals. The experienced technician will of course find he knows many of these things already and can go directly to the procedures and information he needs; the less experienced technician will better understand what to do even before he arrives on the job, and therefore be better able to work by himself as well as assist the more experienced technician.

TABLE OF CONTENTS
1. SPECIFICATIONS ............................................................................................ I - 1 1-1 Unit Specifications .....................................................................................I - 2 1-2 Major Component Specifications ...............................................................I - 34 (A) Indoor Units..........................................................................................I - 34 (B) Outdoor Units .......................................................................................I - 46 1-3 Other Component Specifications ...............................................................I - 52 1-4 Dimensional Data ......................................................................................I - 60 (A) Indoor Units..........................................................................................I - 60 (B) Outdoor Units .......................................................................................I - 67 1-5 Refrigerant Flow Diagram ..........................................................................I - 69 1-6 Operating Range .......................................................................................I - 72 1-7 Cooling Capacity........................................................................................I - 73 1-8 Noise Criterion Curves...............................................................................I - 90 1-9 Indoor Fan Performance ............................................................................I - 95 1-10 Air throw Distance Chart ............................................................................I - 97 1-11 Installation Instructions ..............................................................................I - 99 2. PROCESSES AND FUNCTIONS ......................................................................II 2-1 Room Temperature Control ......................................................................II (A) Cooling ................................................................................................II (B) Heating ................................................................................................II 2-2 Cold Draft Prevention (Heating Cycle) ......................................................II 2-3 Automatic Fan Speed (Indoor Unit) ..........................................................II (A) Cooling ................................................................................................II (B) Heating ................................................................................................II 2-4 Outdoor Fan Speed Control ......................................................................II (A) Cooling ................................................................................................II (B) Heating ................................................................................................II 2-5 Freeze Prevention (Cooling) .....................................................................II 2-6 Condensing Temperature Control (Cooling) .............................................II ii

1 2 2 3 4 5 5 5 6 6 6 7 8

SM830080

2-7 2-8 2-9 2-10 2-11

2-12 2-13 2-14

2-15 2-16 2-17 2-18 2-19

Overload Protection (Heating) ..................................................................II - 9 Discharge Temperature Control (Cooling and Heating) ........................... II - 10 Auto. Mode for Automatic Heating/Cooling Switching ..............................II - 11 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) ....................II - 12 4-Way Valve, Solenoid Control .................................................................II - 13 (A) Normal Control Mode ..........................................................................II - 13 (B) AUTO Control Mode ...........................................................................II - 14 Automatic Restart after Power Interruption ...............................................II - 14 Electronic Expansion Control Valve ..........................................................II - 15 Compressor Discharge Gas Temperature ................................................II - 15 (A) Cooling ................................................................................................II - 15 (B) Heating (Except During Defrosting) .................................................... II - 15 Compressor Current Detection Circuit ......................................................II - 16 Dehumidifying Operation ..........................................................................II - 17 Auto-flap Control .......................................................................................II - 18 Controlled by Electronic Expansion Valve ................................................II - 19 Voltage Detection Control .........................................................................II - 20

3. ELECTRICAL DATA ........................................................................................III - 1 3-1 Indoor Unit (Electric Wiring Diagram, Schematic Diagram) ..................... III - 2 3-2 Outdoor Unit (Electric Wiring Diagram, Schematic Diagram) .................. III - 14 4. SERVICE PROCEDURES ............................................................................... IV - 1 4-1 Troubleshooting ...................................................................................... IV - 2 4-2 Checking the Electrical Components ...................................................... IV - 36 5. APPENDIX ....................................................................................................... V - 1 5-1 P.C.B. ...................................................................................................... V - 2

iii

SM830080

Introduction: Read Me First!


This manual will help you understand and service the air conditioner. To help you find the information you need, we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explanations to help you find and repair problems. u Section 1: Specifications, tells you about the physical and electrical make up of the unit, as well as its heating and cooling capacities. Look in this section to find the correct values for components and functions. Section 2: Processes and Functions, explains each different part of the cooling and heating cycle, and how each control function reacts to changing conditions to keep the room at the set temperature range. Section 3: Electrical Data, which has fold-out schematic and wiring diagrams so you can find the parts you need to check when something is wrong, and see how they should be connected. Section 4: Service Procedures, has two main parts, a diagnostic chapter to help you find the specific component to replace or adjust, and a chapter with specific procedures and values to guide you in checking the electrical components in the unit.

WHAT IS IN THIS MANUAL

HOW TO USE THIS MANUAL


You can use this manual both as a reference to find specific information about the capacity, functions and construction of this unit, and as a source of information to help you set up and maintain the unit. When this unit is not working properly, and the cause is not known, you can use the procedures in Section 3: Servicing Procedures to find the problem, fix it, and restore the unit to its proper functioning. This air conditioner has many helpful self diagnostic features to help you identify problem areas quickly. So you will be ready when a problem happens, we suggest you look this manual over and become familiar with it by following these steps: 1. 2. Look at the TABLE OF CONTENTS to get an idea of what is in this manual and where to find it. Look at the chapter about TROUBLE SHOOTING, so you are familiar with the way the flow charts work. They are designed to guide you quickly through the possible causes for each kind of problem that is likely to happen to the Unit. Particularly read the introduction to this section, and the parts about the self-diagnosis and error codes which show on the display. Look at the chapter about CHECKING ELECTRICAL COMPONENTS. You already know about most of these procedures. This chapter gives you the specific values and methods for these components. If you dont know some of these procedures, you can easily learn them here. Read the Instruction Manual! The Instruction Manual is included here because it helps you help the user to set the temperature controls properly and know how to take care of any simple problems that may happen, as well as know when to call for service. The Instruction Manual also has illustrations, care, and installation information not found in the rest of the service manual. It is short, and if you read it carefully, you will be able to answer the customers questions easily, and also know the most efficient ways for setting times and temperatures.

3.

4.

Please use this manual to make your work easier, keep the air conditioner functioning well, and keep your customers satisfied.

iv

SM830080

1. Specifications

1. SPECIFICATIONS
1-1 Unit Specifications ................................................................................. I - 2 4-Way Air Discharge Semi-concealed Type ........................................... I - 2 Ceiling Mounted Type .............................................................................. I - 10 Concealed Duct Type .............................................................................. I - 18 Concealed Duct High Static Pressure Type ............................................ I - 26 1-2 Major Component Specifications ............................................................. I - 34 (A) Indoor Units ........................................................................................ I - 34 (B) Outdoor Units ..................................................................................... I - 46 1-3 Other Component Specifications ............................................................. I - 52 4-Way Air Discharge Semi-concealed Type ........................................... I - 52 Ceiling Mounted Type .............................................................................. I - 53 Concealed Duct High Static Pressure Type ............................................ I - 54 Concealed Duct Type .............................................................................. I - 55 Outdoor Units ........................................................................................... I - 56 1-4 Dimensional Data .................................................................................... I - 60 (A) Indoor Units ........................................................................................ I - 60 4-Way Air Discharge Semi-concealed Type ....................................... I - 60 Ceiling Mounted Type ........................................................................ I - 62 Concealed Duct Type ......................................................................... I - 63 Concealed Duct High Static Pressure Type ....................................... I - 66 (B) Outdoor Units ..................................................................................... I - 67 1-5 Refrigerant Flow Operating Range .......................................................... I - 69 1-6 Operating Range ..................................................................................... I - 72 1-7 Cooling Capacity ...................................................................................... I - 73 1-8 Noise Criterion Curves ............................................................................. I - 90 1-9 Indoor Fan Performance .......................................................................... I - 95 1-10 Air throw Distance Chart .......................................................................... I - 97 1-11 Installation Instructions ............................................................................ I - 99 Tubing Length .......................................................................................... I - 99 Selecting the Installation Site................................................................... I - 100 Electrical Wiring ....................................................................................... I - 104 Electrical Characteristics ......................................................................... I - 107

5
I - 1
SM830080

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft) Indoor Unit Outdoor Unit SPW-XR253GH56 SPW-CR253EL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling 7.3 25,000 1,140 / 1,020 / 840 3.6 220 13.32 14.66 2.81 2.6 69 230 198 264 13.46 14.72 2.93 2.49 72 240 13.58 14.76 3 2.43 75

kW BTU / h m3/h Liters/h V V A A kW W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Rotary (Sanyo) 37 / 35 / 31 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

2 1

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 6.35 (1 / 4) mm (in.) 15.88 (5 / 8) kg R407C - 3.2 Indoor unit (Include panel) Outdoor unit mm (in.) 328 ( 12 - 29 / 32) 735 (28 - 30 / 32) mm (in.) 860 ( 33 - 27 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-X253GH56 Panel : PNR-X253GHA Outdoor unit 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 ) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 30 (66) 69 ( 152) 27 ( 60 ) 8 ( 18 ) 75 ( 165 ) 0.195 ( 6.9 ) 0.1 ( 3.5 ) 0.349 (12.3)

m (ft.) m (ft.) m (ft.)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 2

SM830080

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft) Indoor Unit Outdoor Unit SPW-XR253GH56 SPW-CR253EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 7.3 25,000 1,140 / 1,020 / 840 3.6 380 4.82 5.67 2.76 2.64 27 400 342 456 4.78 5.68 2.79 2.62 29 415 4.73 5.69 2.82 2.59 30

kW BTU / h m3/h Liters/h V V A A kW W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Rotary (Sanyo) 37 / 35 / 31 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 6.35 (1 / 4) mm (in.) 15.88 (5 / 8) kg R407C - 3.2 Indoor unit (Include panel) Outdoor unit mm (in.) 328 ( 12 - 29 / 32) 735 (28 - 30 / 32) mm (in.) 860 ( 33 - 27 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unit 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 ) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 30 (66) 69 ( 152) 27 ( 60 ) 8 ( 18 ) 75 ( 165) 0.195 ( 6.9 ) 0.1 ( 3.5 ) 0.349 (12.3)

m (ft.) m (ft.) m (ft.)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 3

SM830080

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft) Indoor Unit Outdoor Unit SPW-XR363GH56 SPW-CR363EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 10.6 36,000 1,920 / 1,680 / 1,320 4.6 380 7.01 7.86 3.92 2.7 47 400 342 456 7.02 7.87 3.97 2.67 49 415 7.05 7.9 4.02 2.64 50

kW BTU / h m3/h Liters/h V V A A kW W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Scroll (Sanyo) 43 / 40 / 36 53 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

2 1

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 9.52 (3 / 8) mm (in.) 19.05 (3 / 4) kg R407C - 4.0 Indoor unit (Include panel) Outdoor unit mm (in.) 358 ( 14 - 3 / 32) 1,235 (48 - 20 / 32) mm (in.) 1,150 ( 45 - 9 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR363GH56 Panel : PNR-X483GHA Outdoor unit 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32) 1,114 (43 - 27 / 32) 1,257 (49 - 16 / 32) 1,016 (40 ) 860 (33 - 27 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 38 (84) 104 ( 229) 32 ( 71 ) 10 ( 22 ) 111 ( 245 ) 0.303 (10.7) 0.131 ( 4.6 ) 0.56 (19.8)

m (ft.) m (ft.) m (ft.)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 4

SM830080

1. Specifications

1-1

Unit Specifications
4-Way Air Discharge Semi-concealed Type

MODEL No. POWER SOURCE PERFORMANCE Capacity

Indoor Unit Outdoor Unit

Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft)

kW BTU / h m3/h Liters/h V V A A kW W/W A 380 8.35 9.47 4.6 2.74 53

SPW-XR483GH56 SPW-CR483EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 12.6 43,000 1,920 / 1,680 / 1,320 6.3 400 342 456 8.35 9.47 4.64 2.72 56 415 8.37 9.49 4.67 2.70 58

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Scroll (Sanyo) 43 / 40 / 36 55 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 9.52 (3 / 8) mm (in.) 19.05 (3 / 4) kg R407C - 4.5 Indoor unit (Include panel) Outdoor unit mm (in.) 358 ( 14 - 3 / 32) 1,235 (48 - 20 / 32) mm (in.) 1,150 ( 45 - 9 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR483GH56 Panel : PNR-X483GHA Outdoor unit 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32) 1,114 (43 - 27 / 32) 1,257 (49 - 16 / 32) 1,016 (40 ) 860 (33 - 27 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 38 (84) 106 ( 234) 32 ( 71 ) 10 ( 22 ) 113 ( 249 ) 0.303 (10.7) 0.131 ( 4.6 ) 0.56 (19.8)

m (ft.) m (ft.) m (ft.)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 5

SM830080

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft)
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW W/W A 220

SPW-XR253GH56 SPW-CR253EHL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,140 / 1,020 / 840 3.6 230 240 198 264 13.32 13.46 13.58 14.66 14.72 14.76 2.81 2.93 3 2.6 2.49 2.43 69 72 75 230 240 198 264 14.69 14.64 14.57 16.59 16.94 16.27 3.07 3.14 3.21 2.8 2.74 2.68 69 72 75 220

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Rotary (Sanyo) 37 / 35 / 31 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

2 1

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 6.35 (1 / 4) mm (in.) 15.88 (5 / 8) kg R407C - 3.2 Indoor unit (Include panel) Outdoor unit mm (in.) 328 ( 12 - 29 / 32) 735 (28 - 30 / 32) mm (in.) 860 ( 33 - 27 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unit 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 ) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 30 (66) 71 ( 157) 27 ( 60 ) 8 ( 18 ) 77 ( 170 ) 0.195 ( 6.9 ) 0.1 ( 3.5 ) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

I - 6

SM830080

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft)
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW W/W A 380 4.82 5.67 2.76 2.64 27

SPW-XR253GH56 SPW-CR253EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,140 / 1,020 / 840 3.6 400 342 456 4.78 5.68 2.79 2.62 29 415 4.73 5.69 2.82 2.59 30 380 5.31 5.41 3 2.87 27 400 342 456 5.21 5.32 3.03 2.84 29 415 5.12 5.22 3.06 2.81 30

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Rotary (Sanyo) 37 / 35 / 31 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 6.35 (1 / 4) mm (in.) 15.88 (5 / 8) kg R407C - 3.2 Indoor unit (Include panel) Outdoor unit mm (in.) 328 ( 12 - 29 / 32) 735 (28 - 30 / 32) mm (in.) 860 ( 33 - 27 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR253GH56 Panel : PNR-X253GHA Outdoor unit 284 (11 - 6 / 32) 104 ( 4 - 3 / 32) 826 (32 - 17 / 32) 824 (32 - 14 / 32) 967 (38 - 2 / 32) 1,016 (40 ) 833 (32 - 25 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 30 (66) 71 ( 157) 27 ( 60 ) 8 ( 18 ) 77 ( 170 ) 0.195 ( 6.9 ) 0.1 ( 3.5 ) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

5
SM830080

I - 7

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft)
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW W/W A 380 7.01 7.86 3.92 2.7 47

SPW-XR363GH56 SPW-CR363EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 10.6 12.5 36,000 42,700 1,920 / 1,680 / 1,320 4.6 400 342 456 7.02 7.87 3.97 2.67 49 415 7.05 7.9 4.02 2.64 50 380 7.58 7.98 4.26 2.93 47 400 342 456 7.6 8 4.3 2.91 49 415 7.64 8.04 4.33 2.89 50

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Scroll (Sanyo) 43 / 40 / 36 53 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

2 1

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 9.52 (3 / 8) mm (in.) 19.05 (3 / 4) kg R407C - 4.0 Indoor unit (Include panel) Outdoor unit mm (in.) 358 ( 14 - 3 / 32) 1,235 (48 - 20 / 32) mm (in.) 1,150 ( 45 - 9 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR363GH56 Panel : PNR-X483GHA Outdoor unit 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32) 1,114 (43 - 27 / 32) 1,257 (49 - 16 / 32) 1,016 (40 ) 860 (33 - 27 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 38 (84) 106 ( 234) 32 ( 71 ) 10 ( 22 ) 113 ( 249 ) 0.303 (10.7) 0.131 ( 4.6 ) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

I - 8

SM830080

1. Specifications

1-1 Unit Specifications


4-Way Air Discharge Semi-concealed Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net weight kg (lb.) Shipping weight kg (lb.) Shipping volume m3 (cu. ft)
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW W/W A 380 8.35 9.47 4.6 2.74 53

SPW-XR483GH56 SPW-CR483EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 12.6 15.3 43,000 52,200 1,920 / 1,680 / 1,320 6.3 400 342 456 8.35 9.47 4.64 2.72 56 415 8.37 9.49 4.67 2.7 58 380 9.48 9.99 5.46 2.8 53 400 415 342 456 9.49 9.52 10 10.02 5.5 5.53 2.78 2.77 56 58

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve Max. head 25 cm above drain connection (25A, OD32 mm) Scroll (Sanyo) 43 / 40 / 36 55 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL

50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) mm (in.) 9.52 (3 / 8) mm (in.) 19.05 (3 / 4) kg R407C - 4.5 Indoor unit (Include panel) Outdoor unit mm (in.) 358 ( 14 - 3 / 32) 1,235 (48 - 20 / 32) mm (in.) 1,150 ( 45 - 9 / 32) 940 (37 ) mm (in.) 860 ( 33 - 27 / 32) 340 (13 - 12 / 32) Body : SPW-XR483GH56 Panel : PNR-X483GHA Outdoor unit 316 (12 - 14 / 32) 104 ( 4 - 3 / 32) 1,326 (52 - 7 / 32) 1,114 (43 - 27 / 32) 1,257 (49 - 16 / 32) 1,016 (40 ) 860 (33 - 27 / 32) 999 (39 - 11 / 32) 416 (16 - 12 / 32) 38 (84) 108 ( 238) 32 ( 71 ) 10 ( 22 ) 115 ( 254 ) 0.303 (10.7) 0.131 ( 4.6 ) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

5
SM830080

I - 9

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-TR253GH56 SPW-CR253EL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling 7.3 25,000 1,080 / 960 / 840 3.5 220 13.15 14.49 2.77 95.7 2.64 69 230 198 264 13.27 14.53 2.89 94.7 2.53 72 240 13.38 14.56 2.95 91.9 2.47 75

kW BTU / h m3/h Liters/h V V A A kW % W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve No (20A, OD26 mm) Rotary (Sanyo) 39 / 37 / 34 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 190 ( 7 - 15 / 32) 735 (28 - 30 / 32) 1,300 ( 51 - 6 / 32) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 266 ( 10 - 15 / 32) 826 (32 - 17 / 32) 1,403 ( 55 - 8 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 26 ( 57 ) 69 ( 152 ) 32 ( 71 ) 75 ( 165 ) 0.294 (10.4) 0.349 (12.3)

2 1

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

5
I - 10
SM830080

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-TR253GH56 SPW-CR253EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 7.3 25,000 1,080 / 960 / 840 3.5 380 4.77 5.62 2.72 86.6 2.68 27 400 342 456 4.72 5.63 2.75 84.1 2.65 29 415 4.67 5.64 2.77 82.5 2.64 30

kW BTU / h m3/h Liters/h V V A A kW % W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve No (20A, OD26 mm) Rotary (Sanyo) 39 / 37 / 34 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 190 ( 7 - 15 / 32) 735 (28 - 30 / 32) 1,300 ( 51 - 6 / 32) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 266 ( 10 - 15 / 32) 826 (32 - 17 / 32) 1,403 ( 55 - 8 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 26 ( 57 ) 69 ( 152 ) 32 ( 71 ) 75 ( 165 ) 0.294 (10.4) 0.349 (12.3)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

5
I - 11
SM830080

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-TR363GH56 SPW-CR363EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 10.6 36,000 1,800 / 1,560 / 1,200 4.7 380 7.01 7.86 3.92 85 2.7 47 400 342 456 7.02 7.88 3.97 81.6 2.67 49 415 7.06 7.91 4.02 79.2 2.64 50

kW BTU / h m3/h Liters/h V V A A kW % W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve No (20A, OD26 mm) Scroll (Sanyo) 42 / 40 / 35 53 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.0 Indoor unit Outdoor unit 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32) 1,575 ( 62 ) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 317 ( 12 - 15 / 32) 1,326 (52 - 7 / 32) 1,678 ( 66 - 2 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 38 ( 84 ) 104 ( 229 ) 44 ( 97 ) 111 ( 245 ) 0.42 (14.8) 0.56 (19.8)

2 1

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

5
I - 12
SM830080

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-TR483GH56 SPW-CR483EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 12.6 43,000 1,920 / 1,680 / 1,320 5.9 380 8.35 9.47 4.6 83.7 2.74 53 400 342 456 8.35 9.48 4.64 80.2 2.72 56 415 8.38 9.5 4.67 80.4 2.7 58

kW BTU / h m3/h Liters/h V V A A kW % W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-5PS3EWL Electronic expansion valve No (20A, OD26 mm) Scroll (Sanyo) 44 / 41 / 37 55 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.5 Indoor unit Outdoor unit 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32) 1,575 ( 62 ) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 317 ( 12 - 15 / 32) 1,326 (52 - 7 / 32) 1,678 ( 66 - 2 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 38 ( 84 ) 106 ( 234 ) 44 ( 97 ) 113 ( 249 ) 0.42 (14.8) 0.56 (19.8)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

5
I - 13
SM830080

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW % W/W A 220

SPW-TR253GH56 SPW-CR253EHL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,080 / 960 / 840 3.5 230 240 198 264 13.15 13.27 13.38 14.49 14.53 14.56 2.77 2.89 2.95 95.7 94.7 91.9 2.64 2.53 2.47 69 72 75 230 240 198 264 14.65 14.58 14.49 16.55 16.38 16.19 3.06 3.13 3.19 94.9 93.3 91.7 2.81 2.75 2.7 69 72 75 220

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve No (20A, OD26 mm) Rotary (Sanyo) 39 / 37 / 34 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 190 ( 7 - 15 / 32) 735 (28 - 30 / 32) 1,300 ( 51 - 6 / 32) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 266 ( 10 - 15 / 32) 826 (32 - 17 / 32) 1,403 ( 55 - 8 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 26 ( 57 ) 71 ( 157 ) 32 ( 71 ) 77 ( 170 ) 0.294 (10.4) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

2 1

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

I - 14

SM830080

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW % W/W A 380 4.77 5.62 2.72 86.6 2.68 27

SPW-TR253GH56 SPW-CR253EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,080 / 960 / 840 3.5 400 342 456 4.72 5.63 2.75 84.1 2.65 29 415 4.67 5.64 2.77 82.5 2.64 30 380 4.9 5.7 2.81 87.1 3.06 27 400 342 456 4.8 5.5 2.82 84.8 3.05 29 415 4.7 5.3 2.85 84.4 3.02 30

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve No (20A, OD26 mm) Rotary (Sanyo) 39 / 37 / 34 52 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 190 ( 7 - 15 / 32) 735 (28 - 30 / 32) 1,300 ( 51 - 6 / 32) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 266 ( 10 - 15 / 32) 826 (32 - 17 / 32) 1,403 ( 55 - 8 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 26 ( 57 ) 71 ( 157 ) 32 ( 71 ) 77 ( 170 ) 0.294 (10.4) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

5
SM830080

I - 15

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW % W/W A 380 7.01 7.86 3.92 85 2.7 47

SPW-TR363GH56 SPW-CR363EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 10.6 12.5 36,000 42,700 1,800 / 1,560 / 1,200 4.7 400 342 456 7.02 7.88 3.97 81.6 2.67 49 415 7.06 7.91 4.02 79.2 2.64 50 400 342 456 7.64 7.65 8.04 8.05 4.3 4.34 85.5 81.9 2.91 2.88 47 49 380 415 7.68 8.09 4.37 79.2 2.86 50

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve No (20A, OD26 mm) Scroll (Sanyo) 42 / 40 / 35 53 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.0 Indoor unit Outdoor unit 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32) 1,575 ( 62 ) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 317 ( 12 - 15 / 32) 1,326 (52 - 7 / 32) 1,678 ( 66 - 2 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 38 ( 84 ) 106 ( 234 ) 44 ( 97 ) 113 ( 249 ) 0.42 (14.8) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

2 1

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

I - 16

SM830080

1. Specifications

1-1 Unit Specifications


Ceiling Mounted Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h V V A A kW % W/W A 380 8.35 9.47 4.6 83.7 2.74 53

SPW-TR483GH56 SPW-CR483EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 12.6 15.3 43,000 52,200 1,920 / 1,680 / 1,320 5.9 400 342 456 8.35 9.48 4.64 80.2 2.72 56 415 8.38 9.5 4.67 77.5 2.7 58 400 415 342 456 9.54 9.54 9.56 10.05 10.05 10.07 5.5 5.54 5.57 87.6 83.8 81.1 2.78 2.76 2.75 53 56 58 380

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours ON/OFF 24-hours & Program 3 and Automatic control / 3 (Auto) Automatic (Remote control) Washable, easy access, long life (2,500 hr) Wired : RCS-SH80TG Wireless : RCS-SH80TGWL Electronic expansion valve No (20A, OD26 mm) Scroll (Sanyo) 44 / 41 / 37 55 Munsell 10Y9.3 / 0.4, RAL 9010-GL Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.5 Indoor unit Outdoor unit 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32) 1,575 ( 62 ) 940 (37 ) 670 ( 26 - 12 / 32) 340 (13 - 12 / 32) 317 ( 12 - 15 / 32) 1,326 (52 - 7 / 32) 1,678 ( 66 - 2 / 32) 1,016 (40 ) 789 ( 31 - 2 / 32) 416 (16 - 12 / 32) 38 ( 84 ) 108 ( 238 ) 44 ( 97 ) 115 ( 254 ) 0.42 (14.8) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB

5
SM830080

I - 17

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-DR253GH56 SPW-CR253EL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling 7.3 25,000 1,380 / 1,320 / 1,260 3.1 19 (186) : at shipment 220 15.01 16.35 3.16 95.7 2.31 71 230 198 264 15.14 16.4 3.3 94.8 2.21 74 240 15.26 16.44 3.38 92.3 2.16 77

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

2 1

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Rotary (Sanyo) 44 / 43 / 42 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 420 ( 16 - 17 / 32) 735 (28 - 30 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 826 (32 - 17 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 69 ( 152 ) 61 ( 134 ) 75 ( 165 ) 0.42 (14.8) 0.349 (12.3)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 18

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-DR253GH56 SPW-CR253EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 7.3 25,000 1,380 / 1,320 / 1,260 3.1 19 (186) : at shipment 380 5.3 6.15 3.11 89.2 2.35 29 400 342 456 5.24 6.14 3.16 87 2.31 31 415 5.19 6.14 3.2 85.8 2.28 32

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Rotary (Sanyo) 44 / 43 / 42 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 420 ( 16 - 17 / 32) 735 (28 - 30 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 826 (32 - 17 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 69 ( 152 ) 61 ( 134 ) 75 ( 165 ) 0.42 (14.8) 0.349 (12.3)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 19

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-DR363GH56 SPW-CR363EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 10.6 36,000 1,800 / 1,680 / 1,500 4.4 18 (176) : at shipment 380 7.43 8.29 4.24 86.7 2.5 49 400 342 456 7.43 8.28 4.31 83.7 2.46 51 415 7.45 8.31 4.37 81.6 2.43 52

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

2 1

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Scroll (Sanyo) 45 / 44 / 42 53 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.0 Indoor unit Outdoor unit 420 ( 16 - 17 / 32) 1,235 (48 - 20 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 1,326 (52 - 7 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 50 ( 110 ) 104 ( 229 ) 64 ( 141 ) 111 ( 245 ) 0.42 (14.8) 0.56 (19.8)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 20

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-DR483GH56 SPW-CR483EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 12.6 43,000 2,160 / 2,100 / 1,980 5.4 17 (167) : at shipment 380 8.87 10.02 5 85.6 2.52 55 400 342 456 8.89 10.03 5.09 82.6 2.48 58 415 8.92 10.06 5.16 80.5 2.44 60

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Scroll (Sanyo) 47 / 46 / 44 55 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.5 Indoor unit Outdoor unit 450 ( 17 - 23 / 32) 1,235 (48 - 20 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 1,326 (52 - 7 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 54 ( 119 ) 106 ( 234 ) 69 ( 152 ) 113 ( 249 ) 0.42 (14.8) 0.56 (19.8)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 21

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A 220

SPW-DR253GH56 SPW-CR253EHL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,380 / 1,320 / 1,260 3.1 19 (186) : at shipment 230 240 198 264 15.01 15.14 15.26 16.35 16.4 16.44 3.16 3.3 3.38 95.7 94.8 92.3 2.31 2.21 2.16 71 74 77 230 240 198 264 16.61 16.54 16.46 18.51 18.34 18.16 3.47 3.56 3.64 95 93.6 92.1 2.48 2.42 2.36 71 74 77 220

dB - A dB - A

2 1

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Rotary (Sanyo) 44 / 43 / 42 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 420 ( 16 - 17 / 32) 735 (28 - 30 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 826 (32 - 17 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 71 ( 157 ) 61 ( 134 ) 77 ( 170 ) 0.42 (14.8) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 22

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A 380 5.3 6.15 3.11 89.2 2.35 29

SPW-DR253GH56 SPW-CR253EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,380 / 1,320 / 1,260 3.1 19 (186) : at shipment 400 342 456 5.24 6.14 3.16 87 2.31 31 415 5.19 6.14 3.2 85.8 2.28 32 380 5.6 6.4 3.22 87.4 2.67 29 400 342 456 5.4 6.1 3.25 86.9 2.65 31 415 5.4 5.9 3.3 85 2.61 32

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Rotary (Sanyo) 44 / 43 / 42 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 420 ( 16 - 17 / 32) 735 (28 - 30 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 826 (32 - 17 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 71 ( 157 ) 61 ( 134 ) 77 ( 170 ) 0.42 (14.8) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 23

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A 380 7.43 8.29 4.24 86.7 2.5 49

SPW-DR363GH56 SPW-CR363EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 10.6 12.5 36,000 42,700 1,800 / 1,680 / 1,500 4.4 18 (176) : at shipment 400 342 456 7.43 8.28 4.31 83.7 2.46 51 415 7.45 8.31 4.37 81.6 2.43 52 380 8.09 8.49 4.64 87.1 2.69 49 400 342 456 8.08 8.48 4.7 84 2.66 51 415 8.1 8.51 4.74 81.4 2.64 52

dB - A dB - A

2 1

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Scroll (Sanyo) 45 / 44 / 42 53 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.0 Indoor unit Outdoor unit 420 ( 16 - 17 / 32) 1,235 (48 - 20 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 1,326 (52 - 7 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 50 ( 110 ) 106 ( 234 ) 64 ( 141 ) 113 ( 249 ) 0.42 (14.8) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 24

1. Specifications

1-1 Unit Specifications


Concealed Duct High Static Pressure Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating:A Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A 380

SPW-DR483GH56 SPW-CR483EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 12.6 15.3 43,000 52,200 2,160 / 2,100 / 1,980 5.4 17 (167) : at shipment 400 415 342 456 8.87 8.89 8.92 10.02 10.03 10.06 5 5.09 5.16 85.6 82.6 80.5 2.52 2.48 2.44 55 58 60 400 415 342 456 10.11 10.12 10.15 10.62 10.63 10.66 5.92 6.01 6.08 89 85.7 83.3 2.58 2.55 2.52 55 58 60 380

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve No (25A, OD32 mm) Scroll (Sanyo) 47 / 46 / 44 55 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.5 Indoor unit Outdoor unit 450 ( 17 - 23 / 32) 1,235 (48 - 20 / 32) 1,065 ( 41 - 30 / 32) 940 (37 ) 620 ( 24 - 13 / 32) 340 (13 - 12 / 32) 513 ( 20 - 6 / 32) 1,326 (52 - 7 / 32) 1,148 ( 45 - 6 / 32) 1,016 (40 ) 713 ( 28 - 2 / 32) 416 (16 - 12 / 32) 54 ( 119 ) 108 ( 238 ) 69 ( 152 ) 115 ( 254 ) 0.42 (14.8) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 25

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-UR253GHN56 SPW-CR253EL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling 7.3 25,000 1,080 / 900 / 780 3.5 5.1 (50) : at shipment, 9.4 (92) : using the booster cable 220 14.65 15.65 3.01 93.4 2.43 69 230 198 264 14.6 15.5 3.14 93.5 2.32 72 240 14.54 15.44 3.21 92 2.27 75

kW BTU / h m3/h Liters/h mmAq(Pa) VAC VAC A A kW % W/W A

dB - A dB - A

2 1

Microprocessor ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Rotary (Sanyo) 34 / 30 / 27, (38 / 34 / 30 : using the booster cable) 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 735 (28 - 30 / 32) 1,000 ( 39 - 12 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 826 (32 - 17 / 32) 1,191 ( 46 - 28 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 32 ( 71 ) 69 ( 152 ) 37 ( 82 ) 75 ( 165 ) 0.334 (11.8) 0.349 (12.3)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 26

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-UR253GHN56 SPW-CR253EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 7.3 25,000 1,080 / 900 / 780 3.5 5.1 (50) : at shipment, 9.4 (92) : using the booster cable 380 5.14 5.74 2.96 87.5 2.47 27 400 342 456 5.05 5.75 3.00 85.7 2.43 29 415 5.00 5.76 3.03 84.3 2.41 30

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

Microprocessor ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Rotary (Sanyo) 34 / 30 / 27, (38 / 34 / 30 : using the booster cable) 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 735 (28 - 30 / 32) 1,000 ( 39 - 12 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 826 (32 - 17 / 32) 1,191 ( 46 - 28 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 32 ( 71 ) 69 ( 152 ) 37 ( 82 ) 75 ( 165 ) 0.334 (11.8) 0.349 (12.3)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 27

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-UR363GHN56 SPW-CR363EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 10.6 36,000 1,800 / 1,560 / 1,260 4.2 8.1 (79) : at shipment, 12.4 (122) : using the booster cable 380 7.15 8.01 4.03 85.6 2.63 47 400 342 456 7.16 8.02 4.09 82.5 2.59 49 415 7.19 8.04 4.14 80.1 2.56 50

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

2 1

Microprocessor ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Scroll (Sanyo) 38 / 33 / 31, (42 / 38 / 33 : using the booster cable) 53 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.0 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 1,235 (48 - 20 / 32) 1,480 ( 58 - 9 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 1,326 (52 - 7 / 32) 1,671 ( 65 - 25 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 104 ( 229 ) 52 ( 115 ) 111 ( 245 ) 0.468 (16.5) 0.56 (19.8)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 28

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Indoor Unit Outdoor Unit SPW-UR483GHN56 SPW-CR483EL8 380 - 400 - 415 V / 3N / 50 Hz Cooling 12.6 43,000 1,980 / 1,800 / 1,500 5.4 8.0 (78) : at shipment, 11.5 (113) : using the booster cable 380 8.49 9.62 4.71 84.3 2.68 53 400 342 456 8.49 9.62 4.76 80.9 2.65 56 415 8.51 9.63 4.79 78.3 2.63 58

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

dB - A dB - A

Microprocessor ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Scroll (Sanyo) 40 / 37 / 33, (44 / 40 / 37 : using the booster cable) 55 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.5 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 1,235 (48 - 20 / 32) 1,480 ( 58 - 9 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 1,326 (52 - 7 / 32) 1,671 ( 65 - 25 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 106 ( 234 ) 52 ( 115 ) 113 ( 249 ) 0.468 (16.5) 0.56 (19.8)

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

DATA SUBJECT TO CHANGE WITHOUT NOTICE. Cooling: Rating conditions (*): Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Full load conditions (**): Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB

I - 29

SM830080

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

SPW-UR253GHN56 SPW-CR253EHL5 220 - 230 - 240 V / 1 phase / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,080 / 900 / 780 3.5 5.1 (50) : at shipment, 9.4 (92) : using the booster cable 230 240 198 264 14.65 14.6 14.54 15.65 15.5 15.44 3.01 3.14 3.21 93.4 93.5 92 2.43 2.32 2.27 69 72 75 220 220 15.6 17.4 3.25 94.7 2.65 69 230 240 198 264 15.45 15.39 17.15 16.99 3.32 3.4 93.4 92.1 2.59 2.53 72 75

dB - A dB - A

2 1

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Rotary (Sanyo) 34 / 30 / 27, (38 / 34 / 30 : using the booster cable) 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 735 (28 - 30 / 32) 1,000 ( 39 - 12 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 826 (32 - 17 / 32) 1,191 ( 46 - 28 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 32 ( 71 ) 71 ( 157 ) 37 ( 82 ) 77 ( 170 ) 0.334 (11.8) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 30

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

SPW-UR253GHN56 SPW-CR253EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 7.3 8.6 25,000 29,300 1,080 / 900 / 780 3.5 5.1 (50) : at shipment, 9.4 (92) : using the booster cable 380 5.14 5.74 2.96 87.5 2.47 27 400 342 456 5.05 5.75 3.00 85.7 2.43 29 415 5 5.76 3.03 84.3 2.41 30 380 5.42 5.53 3.09 86.6 2.78 27 400 342 456 5.33 5.43 3.12 84.5 2.76 29 415 5.24 5.34 3.16 83.9 2.72 30

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Rotary (Sanyo) 34 / 30 / 27, (38 / 34 / 30 : using the booster cable) 52 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 6.35 (1 / 4) 15.88 (5 / 8) R407C - 3.2 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 735 (28 - 30 / 32) 1,000 ( 39 - 12 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 826 (32 - 17 / 32) 1,191 ( 46 - 28 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 32 ( 71 ) 71 ( 157 ) 37 ( 82 ) 77 ( 170 ) 0.334 (11.8) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 31

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

SPW-UR363GHN56 SPW-CR363EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 10.6 12.5 36,000 42,700 1,800 / 1,560 / 1,260 4.2 8.1 (79) : at shipment, 12.4 (122) : using the booster cable 380 7.15 8.01 4.03 85.6 2.63 47 400 342 456 7.16 8.02 4.09 82.5 2.59 49 415 7.19 8.04 4.14 80.1 2.56 50 380 7.79 8.19 4.42 86.2 2.83 47 400 342 456 7.8 8.20 4.47 82.7 2.8 49 415 7.83 8.23 4.50 80 2.78 50

dB - A dB - A

2 1

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Scroll (Sanyo) 38 / 33 / 31, (42 / 38 / 33 : using the booster cable) 53 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.0 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 1,235 (48 - 20 / 32) 1,480 ( 58 - 9 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 1,326 (52 - 7 / 32) 1,671 ( 65 - 25 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 47 (104) 106 ( 234 ) 52 ( 115 ) 113 ( 249 ) 0.468 (16.5) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 32

1. Specifications

1-1 Unit Specifications


Concealed Duct Type
MODEL No. POWER SOURCE PERFORMANCE Capacity Air circulation (Hi / Me / Lo) Moisture removal (High) External static pressure (High) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes* Max. running amperes** Power input Power factor C.O.P Max. starting amperes FEATURES Controls / Thermostat control Timer Fan speeds Indoor / Outdoor Airflow direction (Indoor) Air filter Remote controller (Option) Refrigerant control Drain pump (Drain connection) Compressor Operation sound Indoor - Hi/Me/Lo Outdoor - Hi Color (Approximate value) Indoor Outdoor REFRIGERANT TUBING Limit of tubing length Limit of tubing length at shipment Limit of elevation difference between the two units Refrigerant tube Narrow tube outer diameter Wide tube Refrigerant amount at shipment DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume
Cooling: Rating conditions (*): Full load conditions (**): Heating: Rating conditions (*): Full load conditions (**):

Indoor Unit Outdoor Unit

kW BTU / h m3/h Liters/h mmAq(Pa) V V A A kW % W/W A

SPW-UR483GHN56 SPW-CR483EHL8 380 - 400 - 415 V / 3N / 50 Hz Cooling Heating 12.6 15.3 43,000 52,200 1,980 / 1,800 / 1,500 5.4 8.0 (78) : at shipment, 11.5 (113) : using the booster cable 380 8.49 9.62 4.71 84.3 2.68 53 400 342 456 8.49 9.62 4.76 80.9 2.65 56 415 8.51 9.63 4.79 78.3 2.63 58 400 415 342 456 9.69 9.69 9.71 10.20 10.20 10.21 5.62 5.66 5.70 88.1 84.3 81.7 2.72 2.7 2.68 53 56 58 380

dB - A dB - A

Microprocessor / I.C. thermostat ON / OFF 72-hours 3 and Automatic control / 3 (Auto) Field supply Wired : RCS-SH80TG Electronic expansion valve Max. head 75 cm above unit bottom (25A, OD32 mm) Scroll (Sanyo) 40 / 37 / 33, (44 / 40 / 37 : using the booster cable) 55 Munsell 5Y8.4 / 0.5, RAL 9002-GL 50 (164 ) 30 ( 98 ) Outdoor unit is higher than indoor unit : 50 (164) Outdoor unit is lower than indoor unit : 30 (98) 9.52 (3 / 8) 19.05 (3 / 4) R407C - 4.5 Indoor unit Outdoor unit 310 ( 12 - 7 / 32) 1,235 (48 - 20 / 32) 1,480 ( 58 - 9 / 32) 940 (37 ) 630 ( 24 - 26 / 32) 340 (13 - 12 / 32) 358 ( 14 - 3 / 32) 1,326 (52 - 7 / 32) 1,671 ( 65 - 25 / 32) 1,016 (40 ) 783 ( 30 - 26 / 32) 416 (16 - 12 / 32) 47 ( 104 ) 108 ( 238 ) 52 ( 115 ) 115 ( 254 ) 0.468 (16.5) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

m (ft.) m (ft.) m (ft.) mm (in.) mm (in.) kg mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lb.) kg (lb.) m3 (cu. ft)

Indoor air temperature 27 C DB / 19 C WB, Outdoor air temperature 35 C DB Indoor air temperature 32 C DB / 23 C WB, Outdoor air temperature 43 C DB Indoor air temperature 20 C DB, Outdoor air temperature 7 C DB / 6 C WB Indoor air temperature 24 C DB, Outdoor air temperature 24 C DB / 15.5 C WB SM830080

I - 33

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open C Close C Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) DKV-MOZS582E0 ORG GRY : 46, RED GRY : 46, YEL GRY : 46 BLK GRY : 46 VAC, F 130 8 ( 79 15 ) 440 V , 4 F rpm. W SFG6X-41A5P 40 W 220 - 230 - 240 V / 1 phase / 50 Hz 6 470 BRN WHT : 114.0 WHT VLT : 23.9 VLT ORG : 12.4 ORG YEL WHT PNK YEL BLK : : : 66.4 77.4 82.1 mm SPW-XR253GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Turbo (1 490)

Valve body Heat exchanger Coil Rowsfin pitch Face area mm m


2

IKV-24D12

Aluminum plate fin / Copper tube 2 1.5 0.295

2 1

Panel Model No. Dew proof heater Auto louver motor Auto louver motorRated V, W, rpm. Coil resistance (at 25 C) Drain Pump Rated Total head & capacity VAC, W PNR-X253GHA 240 V, 26 W M2LB24ZA12 240 VAC, 3W, 2.5 rpm 15.620 15 % WP20SL - 21 AC230 V, 50 Hz, 14.7 W 400 mm, 600 cc/min

5
I - 34
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open C Close C Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) Valve body Heat exchanger Coil Rowsfin pitch Face area Panel Model No. Dew proof heater Auto louver motor Auto louver motorRated Coil resistance (at 25 C) Drain Pump Rated Total head & capacity VAC, W V, W, rpm. PNR-X483GHA 240 V, 31 W M2LB24ZA12 240 VAC, 3W, 2.5 rpm 15.620 15 % WP20SL - 21 AC230 V, 50 Hz, 14.7 W 400 mm, 600 cc/min mm m
2

SPW-XR363GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) mm Turbo (1 490)

SFG6X-61A3P60 W 220 - 230 - 240 V / 1 phase / 50 Hz

rpm. BRN WHT : WHT VLT : VLT ORG :

6 530 71.1 8.7 13.3 130 ORG YEL VLT PNK YEL BLK : 22.7 : 43.2 : 126.7

( 79 15 ) 440 V , 6 F

VAC, F

EKV-MOZS584E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46

HKV-30D16

Aluminum plate fin / Copper tube 21.5 0.479

5
I - 35
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open C Close C Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) EKV-MOZS584E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 VAC, F 130 8 ( 79 15 ) 440 V , 6 F rpm. BRN WHT : WHT VLT : VLT ORG : W SFG6X-61A3P60 W 220 - 230 - 240 V / 1 phase / 50 Hz 6 530 71.1 8.7 13.3 ORG YEL VLT PNK YEL BLK : 22.7 : 43.2 : 126.7 mm SPW-XR483GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Turbo (1 490)

Valve body Heat exchanger Coil Rowsfin pitch Face area mm m


2

HKV-30D16

Aluminum plate fin / Copper tube 21.5 0.479

2 1

Panel Model No. Dew proof heater Auto louver motor Auto louver motorRated V, W, rpm. Coil resistance (at 25 C) Drain Pump Rated Total head & capacity VAC, W PNR-X483GHA 240 V, 31 W M2LB24ZA12 240 VAC, 3W, 2.5 rpm 15.620 15 % WP20SL - 21 230 V, 50 Hz, 14.7 W 400 mm, 600 cc/min

5
I - 36
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Ceiling Mounted Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20 C) Safety device Operating temperature Open C Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20 C) Valve body Heat exchanger Coil Rowsfin pitch Face area Auto louver motor Auto louver motorRated Coil resistance (at 25 C) VAC, Hz, W, rpm. mm m2 Aluminum plate fin / Copper tube 3 1.7 0.168 MT8 - 3C 220 240 V, 50 Hz, 3 W, 3.3 rpm. 16.430 8 % DKV - MOZS582E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 C VAC, F 130 8 ( 79 15 ) 440 V, 1.5 F rpm. W SR4X-51A6P 50 W 220 - 230 - 240 V / 1 phase / 50 Hz 4 1,172 BRN WHT : 111.0 WHT VLT : 35.4 VLT ORG : 13.4 ORG YEL YEL BLK BLK PNK : 16.7 : 136.6 : 23.9 mm SPW-TR253GH56 220 - 230 - 240 V / 1 phase / 50 Hz CR-X253GH (Microprocessor) Centrifugal (4 130)

IKV-24D12

5
I - 37
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Ceiling Mounted Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20 C) Safety device Operating temperature Open C Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20 C) EKV - MOZS584E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 C VAC, F 130 8 ( 79 15 ) 440 V, 4.0 F rpm. W KFG4X-101C6P100 W 220 - 230 - 240 V / 1 phase / 50 Hz 41,015 BRN WHT : 61.05 WHT VLT : 9.955 VLT ORG : 9.576 ORG YEL YEL BLK BLK PNK : 13.23 : 19.25 : 10.81 mm SPW-TR363GH56 220 - 230 - 240 V / 1 phase / 50 Hz CR-X253GH (Microprocessor) Centrifugal (4 150)

Valve body Heat exchanger Coil Rowsfin pitch Face area mm m


2

HKV - 30D16

Aluminum plate fin / Copper tube 3 1.7 0.326 MT8 - 3C VAC, Hz, W, rpm. 220 240 V, 50 Hz, 3 W, 3.3 rpm. 16.430 8 %

2 1

Auto louver motor Auto louver motorRated Coil resistance (at 25 C)

5
I - 38
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Ceiling Mounted Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) Valve body Heat exchanger Coil Rowsfin pitch Face area Auto louver motor Auto louver motorRated Coil resistance (at 25C) VAC, Hz, W, rpm. mm m2 Aluminum plate fin / Copper tube 31.7 0.326 MT8 - 3C 220 240 V, 50Hz, 3 W, 3.3 rpm. 16.430 8 % EKV - MOZS584E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 C C 130 8 ( 79 15 ) 440 V, 5.0 F rpm. W KFG4X-101C6P100 W 220 - 230 - 240 V / 1 phase / 50 Hz 41,070 BRN WHT : 61.05 WHT VLT : 9.955 VLT ORG : 9.576 ORG YEL YEL BLK BLK PNK : 13.23 : 19.25 : 10.81 mm SPW-TR483GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Centrifugal (4150)

VAC, F

HKV - 30D16

5
I - 39
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Concealed Duct High Static Pressure Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open C Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) DKV-MOZS550E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 C VAC, F 130 ( 115 5 5 ) rpm. W KFC4X-201B5P 200 W 220 - 230 - 240 V / 1 phase / 50 Hz 4 1,004 BRN WHT : 13.75 WHT VLT : 4.47 VLT ORG : 1.20 ORG YEL YEL BLK BLK PNK : 2.21 : 10.33 : 12.90 mm SPW-DR253GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Centrifugal (1 220)

440 V, 5.0 F

Valve body Heat exchanger Coil Rowsfin pitch Face area mm m2

IKV-24D12

Aluminum plate fin / Copper tube 3 2.0 0.233

2 1

5
I - 40
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Concealed Duct High Static Pressure Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open C Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) Valve body Heat exchanger Coil Rowsfin pitch Face area mm m
2

SPW-DR363GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) mm Centrifugal (1 220)

KFC4X-201B5P 200 W 220 - 230 - 240 V / 1 phase / 50 Hz

rpm.

4 1,134 BRN WHT : 13.75 WHT VLT : 4.47 VLT ORG : 1.20 130 ORG YEL YEL BLK BLK PNK : 2.21 : 10.33 : 12.90

( 79 15 ) 440 V, 7.0 F

VAC, F

EKV-MOZS559E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46

HKV-30D16

Aluminum plate fin / Copper tube 4 2.0 0.273

5
I - 41
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Concealed Duct High Static Pressure Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open C Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) EKV-MOZS559E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 C VAC, F 130 5 ( 79 15 ) 440 V, 7 F x 2 rpm. W KFC4Q-401A5P 400 W 220 - 230 - 240 V / 1 phase / 50 Hz 4 1,077 BRN WHT : 11.05 WHT VLT : 1.80 VLT ORG : 1.00 ORG YEL YEL PNK : : 4.57 7.70 mm SPW-DR483GH56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Centrifugal (1 250)

Valve body Heat exchanger Coil Rowsfin pitch Face area mm m


2

HKV-30D16

Aluminum plate fin / Copper tube 4 2.0 0.273

2 1

5
I - 42
SM830080

1. Specifications

1-2

Major Component Specifications


(A) Indoor Units : Concealed Duct Type

MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) Valve body Heat exchanger Coil Rowsfin pitch Face area Drain pump Rated Total head & capacity VAC, W mm m
2

SPW-UR253GHN56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) mm Centrifugal (2 190)

KFC4X-71B5P 70 W 220 - 230 - 240 V / 1 phase / 50 Hz

rpm.

4 1,063 BRN WHT : 74.72 WHT VLT : 19.14 VLT ORG : 10.52 130 ( 115 ORG YEL YEL BLK BLK PNK : 9.588 : 10.52 : 21.72

C C

5 5 )

VAC, F

440 VAC, 5 F

DKV-MOZS697E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46

IKV-24D12

Aluminum plate fin / Copper tube 3 1.7 0.189 PJV-1,422 AC 230 V, 50 Hz, 12 W 500 mm, 400 cc/min

5
I - 43
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Concealed Duct Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) rpm. W KFC4X-141A5P160 W 220 - 230 - 240 V / 1 phase / 50 Hz 4 1,207 BRN WHT VLT ORG YEL PNK WHT VLT ORG YEL BLK VLT : : : : : : 25.79 5.086 8.626 5.792 6.746 6.361 mm SPW-UR363GHN56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Centrifugal (3 190)

Safety device Operating temperature Open Close Run capacitor Electronic expansion valve C C 130 ( 115 5 5 )

VAC, F

440 VAC, 8 F

Coil Coil resistance (at 20C) Valve body Heat exchanger Coil

EKV-MOZS698E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46

HKV-30D16

Aluminum plate fin / Copper tube mm m


2

2 1

Rowsfin pitch Face area Drain pump Rated Total head & capacity

3 2.0 0.308 PJV-1,422

VAC, W

AC 230 V, 50 Hz, 12 W 500 mm, 400 cc/min

5
I - 44
SM830080

1. Specifications

1-2 Major Component Specifications


(A) Indoor Units : Concealed Duct Type
MODEL No. Source Controller P.C.B. Assy Fan (Numberdiameter) Fan motor ModelNominal output Source No. of poler.p.m. (230 V, High) Coil resistance (Ambient temperature 20C) rpm. W KFC4X-141A5P160 W 220 - 230 - 240 V / 1 phase / 50 Hz 4 1,207 BRN WHT VLT ORG YEL ORG WHT VLT ORG YEL BLK VLT : : : : : : 25.79 5.086 8.626 5.792 6.746 6.361 mm SPW-UR483GHN56 220 - 230 - 240 V / 1 phase / 50Hz CR-X253GH (Microprocessor) Centrifugal (3 190)

Safety device Operating temperature Open C Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) Valve body Heat exchanger Coil Rowsfin pitch Face area Drain pump Rated Total head & capacity VAC, W mm m2 Aluminum plate fin / Copper tube 3 2.0 0.308 PJV-1,422 AC 230 V, 50 Hz, 12 W 500 mm, 400 cc/min EKV-MOZS698E0 ORG GRY : 46 , RED GRY : 46 , YEL GRY : 46 BLK GRY : 46 C VAC, F 130 ( 115 5 5 )

440 VAC, 8 F

HKV-30D16

5
I - 45
SM830080

1. Specifications

1-2 Major Component Specifications


(B) Outdoor Unit
MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model ..... number Source Nominal output Compressor oil Coil resistance (Ambient temperature 25 C) Safety devices Overload relay models Operating temperature Open Close Crank case heater Refrigerant amount at shipment High pressure switch Set pressure OFF ON kg/cm2 kg/cm2 kg C C Internal type 160 5 87 11 240V, 25 W R407C - 3.2 ACB - 1TB07
0 32 + 1.5 0 (3.2 + 0.15 MPa)

SPW-CR253EL5 220 - 230 - 240 V / 1 phase / 50 Hz CR - CR253GHL5 (Microprocessor) 250 V, 3.15 A Rotary (Hermetic) C - RN220H5B 220 - 240 V / 1 phase / 50 Hz W cc 2200 1500 C R : 0.76 C S : 2.76 , R S : 3.52

24 2.0 (2.4 0.2 MPa) Propeller

Fan Number...diameter Air circulation (Hi) Fan speeds Fan motor Model mm m3/h

1 ..... 460 2800 3 (AUTO)

KFC6T - 91C5P 220 - 230 - 240 V / 1 phase / 50 Hz 6...772 / 376 / 252 W WHT BRN WHT VLT : 127.3 : 56.7 70 , , VLT YEL YEL PNK : : 15.0 7.2

2 1

Source No. of pole ..... rpm (230V, High / Med. / Low) Nominal output Coil resistance (Ambient temperature 20C) Safety device

Internal type Open Close C C F 130 8 79 15 440 V, 6 F

Operating temperature

Run capacitor Heat exchange Coil Rows ..... fin pitch

VAC,

Aluminium plate fin / Copper tube mm m


2

2 ..... 1.8 0.616

Face area

5
I - 46
SM830080

1. Specifications

1-2 Major Component Specifications


(B) Outdoor Unit
MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model ..... number Source Nominal output Compressor oil Coil resistance (Ambient temperature 25 C) Safety devices Overload relay models Operating temperature Open Close Crank case heater Refrigerant amount at shipment High pressure switch Set pressure OFF ON Fan Number...diameter Air circulation (Hi) Fan speeds Fan motor Model Source No. of pole ..... rpm (230V, High / Med. / Low) Nominal output Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open Close Run capacitor Heat exchange Coil Rows ..... fin pitch Face area mm m
2

SPW-CR253EHL5 220 - 230 - 240 V / 1 phase / 50 Hz CR - CR253GHL5 (Microprocessor) 250 V, 3.15 A Rotary (Hermetic) C - RN220H5B 220 - 240 V / 1 phase / 50 Hz W cc 2200 1500 C R : 0.76 C S : 2.76 , R S : 3.52

Internal type C C 160 5 87 11 240V, 25 W kg R407C - 3.2 ACB - 1TB07 kg/cm2 kg/cm2
0 32 + 1.5 0 (3.2 + 0.15 MPa)

24 2.0 (2.4 0.2 MPa) Propeller

mm m3/h

1 ..... 460 2800 3 (AUTO)

KFC6T - 91C5P 220 - 230 - 240 V / 1 phase / 50 Hz 6...772 / 376 / 252 W WHT BRN WHT VLT : 127.3 : 56.7 70 , , VLT YEL YEL PNK : : 15.0 7.2

Internal type C C F 130 8 79 15 440 V, 6 F

VAC,

Aluminium plate fin / Copper tube 2 ..... 1.8 0.616

5
I - 47
SM830080

1. Specifications

1-2 Major Component Specifications


(B) Outdoor Unit
MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model ..... number Source Nominal output Compressor oil Coil resistance (Ambient temperature 25 C) Safety devices Overload relay models Operating temperature Open Close Crank case heater Refrigerant amount at shipment High pressure switch Set pressure OFF ON kg/cm2 kg/cm2 kg C C Internal type 120 5 98 11 240V, 25 W R407C - 3.2 ACB - 1TB07
0 32 + 1.5 0 (3.2 + 0.15 MPa)

SPW-CR253EL8 380 - 400 - 415 V / 3 phase / 50 Hz CR - CR483GHL8 (Microprocessor) 250 V, 3.15 A Rotary (Hermetic) C - RN223H8D 380 - 400 - 415 V / 3 phase / 50 Hz W cc 2400 1350 T R : 5.77 S T : 5.38 , R S : 5.66

24 2.0 (2.4 0.2 MPa) Propeller

Fan Number...diameter Air circulation (Hi) Fan speeds Fan motor Model mm m3/h

1 ..... 460 2800 3 (AUTO)

KFC6T - 91C5P 220 - 230 - 240 V / 1 phase / 50 Hz 6...772 / 376 / 252 W WHT BRN WHT VLT : 127.3 : 56.7 70 , , VLT YEL YEL PNK : : 15.0 7.2

2 1

Source No. of pole ..... rpm (230V, High / Med. / Low) Nominal output Coil resistance (Ambient temperature 20C) Safety device

Internal type Open Close C C F 130 8 79 15 440 V, 6 F

Operating temperature

Run capacitor Heat exchange Coil Rows ..... fin pitch

VAC,

Aluminium plate fin / Copper tube mm m


2

2 ..... 1.8 0.616

Face area

5
I - 48
SM830080

1. Specifications

1-2 Major Component Specifications


(B) Outdoor Unit
MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model ..... number Source Nominal output Compressor oil Coil resistance (Ambient temperature 25 C) Safety devices Overload relay models Operating temperature Open Close Crank case heater Refrigerant amount at shipment High pressure switch Set pressure OFF ON Fan Number...diameter Air circulation (Hi) Fan speeds Fan motor Model Source No. of pole ..... rpm (230V, High / Med. / Low) Nominal output Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open Close Run capacitor Heat exchange Coil Rows ..... fin pitch Face area mm m
2

SPW-CR253EHL8 380 - 400 - 415 V / 3 phase / 50 Hz CR - CR483GHL8 (Microprocessor) 250 V, 3.15 A Rotary (Hermetic) C - RN223H8D 380 - 400 - 415 V / 3 phase / 50 Hz W cc 2400 1350 T R : 5.77 S T : 5.38 , R S : 5.66

Internal type C C 120 5 98 11 240V, 25 W kg R407C - 3.2 ACB - 1TB07 kg/cm2 kg/cm2
0 32 + 1.5 0 (3.2 + 0.15 MPa)

24 2.0 (2.4 0.2 MPa) Propeller

mm m3/h

1 ..... 460 2800 3 (AUTO)

KFC6T - 91C5P 220 - 230 - 240 V / 1 phase / 50 Hz 6...772 / 376 / 252 W WHT BRN WHT VLT : 127.3 : 56.7 70 , , VLT YEL YEL PNK : : 15.0 7.2

Internal type C C F 130 8 79 15 440 V, 6 F

VAC,

Aluminium plate fin / Copper tube 2 ..... 1.8 0.616

5
I - 49
SM830080

1. Specifications

1-2 Major Component Specifications


(B) Outdoor Unit
MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model ..... number Source Nominal output Compressor oil Coil resistance (Ambient temperature 25 C) Crank case heater Safety devices Overload relay models Operating temperature Open Close Refrigerant amount at shipment High pressure switch Set pressure OFF kg/cm2 ON kg/cm
2

SPW-CR363EL8

SPW-CR483EL8

380 - 400 - 415 V / 3 phase / 50 Hz CR - CR483GHL8 (Microprocessor) 250 V, 3.15 A Scroll (Hermetic) C - SBN303H8A C - SBN373H8A

380 - 400 - 415 V / 3 phase / 50 Hz W cc 2,400 1,700 3,700 1,700

T R : 3.177 , R S : 3.177 T R : 2.806 , R S : 2.806 S T : 2.966 S T : 2.651 240 V, 32 W 240 V, 32 W

Internal type C C kg 155 5 61 9 R407C - 4.0 ACB - 1TB07


0 32 + 1.5

145 5 61 9 R407C - 4.5


+0 0.15

(3.2

Mpa)

24 2.0 (2.4 0.2 Mpa) LCB - JA89 0.5 0.3 (0.05 0.03 Mpa) 1.5 0.3 (0.15 0.03 Mpa) Propeller

Low pressure switch Set pressure OFF kg/cm2 ON Fan Number...diameter Air circulation mm m /h
3

kg/cm

2 ..... 460 5040 3 (AUTO) KFC6T - 91C5P 2 220 - 230 - 240 V / 1 phase / 50 Hz 6...772 / 376 / 252 70 W 2 BRN WHT WHT VLT : 127.3 : 56.7 , , VLT YEL YEL PNK : : 15.0 7.2

2 1

Fan speeds Fan motor Model Source No. of pole ..... rpm (230V, High / Med. / Low) Nominal output W

Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open Close Run capacitor VAC,

Internal type C C F 130 8 79 15 440 V, 6 F 2

Heat exchange Coil Rows ..... fin pitch Face area mm m


2

Aluminium plate fin / Copper tube 2 ..... 2.0 1.08 2 ..... 1.8

5
I - 50
SM830080

1. Specifications

1-2 Major Component Specifications


(B) Outdoor Unit
MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model ..... number Source Nominal output Compressor oil Coil resistance (Ambient temperature 25 C) Crank case heater Safety devices Overload relay models Operating temperature Open Close Refrigerant amount at shipment High pressure switch Set pressure OFF kg/cm2 ON Low pressure switch Set pressure OFF kg/cm2 ON Fan Number...diameter Air circulation Fan speeds Fan motor Model Source No. of pole ..... rpm (230V, High / Med. / Low) Nominal output Coil resistance (Ambient temperature 20C) Safety device Operating temperature Open Close Run capacitor Heat exchange Coil Rows ..... fin pitch Face area mm m
2

SPW-CR363EHL8

SPW-CR483EHL8

380 - 400 - 415 V / 3 phase / 50 Hz CR - CR483GHL8 (Microprocessor) 250 V, 3.15 A Scroll (Hermetic) C - SBN303H8A C - SBN373H8A

380 - 400 - 415 V / 3 phase / 50 Hz W cc 2,400 1,700 3,700 1,700

T R : 3.177 , R S : 3.177 T R : 2.806 , R S : 2.806 S T : 2.966 S T : 2.651 240 V, 32 W 240 V, 32 W

Internal type C C kg 155 5 61 9 R407C - 4.0 ACB - 1TB07


0 32 + 1.5

145 5 61 9 R407C - 4.5


+0 0.15

(3.2

Mpa)

kg/cm

24 2.0 (2.4 0.2 Mpa) LCB - JA89 0.5 0.3 (0.05 0.03 Mpa) 1.5 0.3 (0.15 0.03 Mpa) Propeller

kg/cm2

mm m /h
3

2 ..... 460 5040 3 (AUTO) KFC6T - 91C5P 2 220 - 230 - 240 V / 1 phase / 50 Hz 6...772 / 376 / 252 70 W 2 BRN WHT WHT VLT : 127.3 : 56.7 , , VLT YEL YEL PNK : : 15.0 7.2

Internal type C C F 130 8 79 15 440 V, 6 F 2

VAC,

Aluminium plate fin / Copper tube 2 ..... 2.0 1.08 2 ..... 1.8

5
I - 51
SM830080

1. Specifications

1-3 Other Component Specifications


4-Way Air Discharge Semi-concealed Type
MODEL NO. Power Transformer Rated Primary Secondary VAC, Hz 230 V, 50 Hz 10.2 V 1.4 A 14 V 0.5 A Coil resistance WHT WHT : 84 RED RED : 2.7 Thermal cut off temperature Thermistor (Coil sensor) : TH2, 3, 4 Resistance K C 145 PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S26 , PBC-41E-S36 -10 -5 0 5 10 C C C C C : : : : : 23.7 18.8 15.0 12.1 9.7 5 5 5 5 5 % % % % % , , , , 20 30 40 45 C C C C : : : : 6.5 4.4 3.1 2.6 5 5 5 5 % % % % , BRN BRN : 0.7 Indoor Unit SPW-XR253 ~ 483GH56 ATR-II215TA

Thermistor (Room sensor) : TH1 Resistance K 0 5 10 20 30 C C C C C :16.5 :12.8 :10.0 : 6.3 : 4.0

KTEC-35-S6 5% 5% 5% 5% 5% , , , , 40 45 50 55 C C C C : 2.7 : 2.2 : 1.8 : 1.5 5% 5% 5% 5%

1
Electronic expansion valve Valve body

IKV-24D12 (SPW-XR253GH56) HKV-30D16 (SPW-XR363 483GH56) DKV-MOZS582E0 (SPW-XR253GH56) EKV-MOZS584E0 (SPW-XR363 483GH56) WP20SL-21 230 V, 14.7 W FS-0218-102 (SPW-XR253GH56) FS-0218-103 (SPW-XR363 483GH56) DC 12 V, 25 W

2 1

Coil Drain pump Rated Float switch

3
Rated (Contact rated)

5
I - 52
SM830080

1. Specifications

1-3 Other Component Specifications


Ceiling Mounted Type
MODEL NO. Power Transformer Rated Primary Secondary VAC, Hz 230 V, 50 Hz 10.2 V 1.4 A 14 V 0.5 A Coil resistance WHT WHT : 110 RED RED : 2.3 Thermal cut off temperature Thermistor (Coil sensor) : TH2, 3, 4 Resistance K C 145 PB3M-41E-S6 , PBC-41E-S14 , PBC-41E-S25 -10 -5 0 5 10 C C C C C : : : : : 23.7 18.8 15.0 12.1 9.7 5 5 5 5 5 % % % % % , , , , 20 30 40 45 C C C C : : : : 6.5 4.4 3.1 2.6 5 5 5 5 % % % % , BRN BRN : 0.5 Indoor Unit SPW-TR253 ~ 483GH56 ATR-II215TB

Thermistor (Room sensor) : TH1 Resistance K 0 5 10 20 30 C C C C C :16.5 :12.8 :10.0 : 6.3 : 4.0

KTEC-35-S6 5% 5% 5% 5% 5% , , , , 40 45 50 55 C C C C : 2.7 : 2.2 : 1.8 : 1.5 5% 5% 5% 5%

Electronic expansion valve Valve body Coil IKV-24D12 (SPW-TR253GH56) HKV-30D16 (SPW-TR363 483GH56) DKV-MOZS582E0 (SPW-TR253GH56) EKV-MOZS584E0 (SPW-TR363 483GH56)

5
I - 53
SM830080

1. Specifications

1-3 Other Component Specifications


Concealed Duct High Static Pressure Type
MODEL NO. Power Transformer Rated Primary Secondary VAC, Hz 230 V, 50 Hz 10.2 V 1.4 A 14 V 0.5 A Coil resistance WHT WHT : 110 RED RED : 2.3 Thermal cut off temperature Thermistor (Coil sensor) : TH2, 3, 4 Resistance K -10 -5 0 5 10 C C C C C : : : : : C 145 PBC-41E-S36 , PBC-41E-S25 23.7 18.8 15.0 12.1 9.7 5 5 5 5 5 % % % % % , , , , 20 30 40 45 C C C C : : : : 6.5 4.4 3.1 2.6 5 5 5 5 % % % % , BRN BRN : 0.5 Indoor Unit SPW-DR253 ~ 483GH56 ATR-II215TB

Thermistor (Room sensor) : TH1, 5 Resistance K 0 5 10 20 30 C C C C C :16.5 :12.8 :10.0 : 6.3 : 4.0

KTEC-35-S85 5% 5% 5% 5% 5% , , , , 40 45 50 55 C C C C : 2.7 : 2.2 : 1.8 : 1.5 5% 5% 5% 5%

1
Electronic expansion valve Valve body

IKV-24D12 (SPW-DR253GH56) HKV-30D16 (SPW-DR363 483GH56) DKV-MOZS550E0 (SPW-DR253GH56) EKV-MOZS559E0 (SPW-DR363 483GH56) FS-0218-103 DC 12 V, 25 W

2 1

Coil Float switch Rated (Contact rated)

5
I - 54
SM830080

1. Specifications

1-3 Other Component Specifications


Concealed Duct Type
MODEL NO. Power Transformer Rated Primary Secondary VAC, Hz 230 V, 50 Hz 10.2 V 1.4 A 14 V 0.5 A Coil resistance WHT WHT : 110 RED RED : 2.3 Thermal cut off temperature Thermistor (Coil sensor) : TH2, 3, 4 Resistance K -10 -5 0 5 10 C C C C C : : : : : C 145 PBC-41E-S36 , PBC-41E-S25 23.7 18.8 15.0 12.1 9.7 5 5 5 5 5 % % % % % , , , , 20 30 40 45 C C C C : : : : 6.5 4.4 3.1 2.6 5 5 5 5 % % % % , BRN BRN : 0.5 Indoor Unit SPW-UR253 ~ 483GHN56 ATR-II215TB

Thermistor (Room sensor) : TH1, 5 Resistance K 0 5 10 20 30 C C C C C

KTEC-35-S6, KTEC-35-S85 :16.5 :12.8 :10.0 : 6.3 : 4.0 5% 5% 5% 5% 5% , , , , 40 45 50 55 C C C C : 2.7 : 2.2 : 1.8 : 1.5 5% 5% 5% 5%

Electronic expansion valve Valve body Coil Drain pump Rated Float switch Rated (Contact rated) IKV-24D12 (SPW-UR253GHN56) HKV-30D16 (SPW-UR363 483GHN56) DKV-MOZS697E0 (SPW-UR253GHN56) EKV-MOZS698E0 (SPW-UR363 483GHN56) PTV-1422 AC 230 V, 12 W FS-0218-103 DC 12 V, 25 W

5
I - 55
SM830080

1. Specifications

1-3 Other Component Specifications


Outdoor Unit
MODEL NO. Power Transformer Rated Primary Secondary Coil resistance Thermal cut off temperature Thermistor (Coil sensor) : TH7 Coil resistance k 10 C 5 C 0 C 5 C : : : : 23.7 18.8 15.0 12.1 C WHT WHT : 300 VAC, Hz 230 V, 50 Hz 14 V, 0.4 A , 145 PBC - 41E - S4 , , , , PTC - 51H - S1 60 C 70 C 75 C 80 C 85 C : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , FC - 1SZ607 VAC VAC, A 220 - 240 V 440 V, 13 A 90 C 100 C 110 C 120 C 130 C : : : : : 5.1 3.8 2.8 2.2 1.7 10 C 20 C 30 C 40 C 45 C : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.2 Outdoor Unit SPW-CR253EL5, SPW-CR253EL8 ATR - I65B

Thermistor (Discharge gas sensor) : TH8 Coil resistance k

Relay (Comp. Magnetic Contactor) Coil rated Contact rating Coil resistance (at 25 C) Solenoid coil or 4 way valve 4 way valve Solenoid coil

2 1

5
I - 56
SM830080

1. Specifications

1-3 Other Component Specifications


Outdoor Unit
MODEL NO. Power Transformer Rated Primary Secondary Coil resistance Thermal cut off temperature Thermistor (Coil sensor) : TH6, 7 Coil resistance k C PBC - 41E - S26 10 C 5 C 0 C 5 C : : : : 23.7 18.8 15.0 12.1 WHT WHT : 300 VAC, Hz 230 V, 50 Hz 14 V, 0.4 A , 145 , , , , , PTC - 51H - S1 60 C 70 C 75 C 80 C 85 C : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , FC - 1SZ607 VAC VAC, A 220 - 240 V 440 V, 13 A 90 C 100 C 110 C 120 C 130 C : : : : : 5.1 3.8 2.8 2.2 1.7 PBC - 41E - S4 10 C 20 C 30 C 40 C 45 C : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.2 Outdoor Unit SPW-CR253EHL5, SPW-CR253EHL8 ATR - I65B

Thermistor (Discharge gas sensor) : TH8 Coil resistance k

Relay (Comp. Magnetic Contactor) Coil rated Contact rating Coil resistance (at 25 C) Solenoid coil or 4 way valve 4 way valve Solenoid coil

CHV - 0201 CHV - 01AJ504D1

5
I - 57
SM830080

1. Specifications

1-3 Other Component Specifications


Outdoor Unit
MODEL NO. Power Transformer Rated Primary Secondary Coil resistance Thermal cut off temperature Thermistor (Coil sensor) : TH7 Coil resistance k 10 C 5 C 0 C 5 C : : : : 23.7 18.8 15.0 12.1 C WHT WHT : 300 VAC, Hz 230 V, 50 Hz 14 V, 0.4 A , 145 PBC - 41E - S4 , , , , PTC - 51H - S1 60 C 70 C 75 C 80 C 85 C : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , FC - 1SZ607 VAC VAC, A 220 - 240 V 440 V, 13 A 90 C 100 C 110 C 120 C 130 C : : : : : 5.1 3.8 2.8 2.2 1.7 10 C 20 C 30 C 40 C 45 C : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.2 Outdoor Unit SPW-CR363EL8, SPW-CR483EL8 ATR - I65B

Thermistor (Discharge gas sensor) : TH8 Coil resistance k

Relay (Comp. Magnetic Contactor) Coil rated Contact rating Coil resistance (at 25 C) Solenoid coil or 4 way valve 4 way valve Solenoid coil

2 1

5
I - 58
SM830080

1. Specifications

1-3 Other Component Specifications


Outdoor Unit
MODEL NO. Power Transformer Rated Primary Secondary Coil resistance Thermal cut off temperature Thermistor (Coil sensor) : TH6, 7 Coil resistance k C PBC - 41E - S36 10 C 5 C 0 C 5 C : : : : 23.7 18.8 15.0 12.1 WHT WHT : 300 VAC, Hz 230 V, 50 Hz 14 V, 0.4 A , 145 , , , , , PTC - 51H - S1 60 C 70 C 75 C 80 C 85 C : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , FC - 1SZ607 VAC VAC, A 220 - 240 V 440 V, 13 A 90 C 100 C 110 C 120 C 130 C : : : : : 5.1 3.8 2.8 2.2 1.7 PBC - 41E - S4 10 C 20 C 30 C 40 C 45 C : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.2 Outdoor Unit SPW-CR363EHL8 ATR - I65B SPW-CR483EHL8

Thermistor (Discharge gas sensor) : TH8 Coil resistance k

Relay (Comp. Magnetic Contactor) Coil rated Contact rating Coil resistance (at 25 C) Solenoid coil or 4 way valve 4 way valve Solenoid coil CHV - 0301

1
CHV - 0401

CHV - 01AJ504D1

5
I - 59
SM830080

1. Specifications

1-4 Dimensional Data


(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type 25 Type
207 205 61

61

X-view

760 100

50

150 255 30

820 (Ceiling opening) 590 (Suspention bolt pitch) 342 15


35

298 205 165

860 500

1
345 730 (Suspention bolt pitch) 820 (Ceiling opening) 760 100 Panel center

12

2 1

48 125

207

12

Air intake grille Air outlet Refrigerant liquid line [ 9.52 (In case of 25 type, use the tube connector.)] Refrigerant gas line 12.7: 12 type, 15.88: 18, 25 type Drain connection Power supply entry For discharge duct Humidifier (option) mounting hole 9 Suspension bolt mounting
1488_X_I

5
I - 60
SM830080

860 500

1. Specifications

1-4 Dimensional Data


(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type 36, 48 Type
218

210 60

X-view

61

35

760 145

70 165 285

820 (Ceiling opening) 590 (Suspention bolt pitch) 342 15

328 218 125

30

860 500

40

490

12

1020 (Suspention bolt pitch) 1110 (Ceiling opening)

Panel center

1050

1150 790

48 210

12

4
Air intake grille Air outlet Refrigerant liquid line (9.52) Refrigerant gas line (19.05) Drain connection Power supply entry For discharge duct Humidifier (option) mounting hole 9 Suspension bolt mounting
100 100

5
0183_X_I

I - 61

SM830080

1. Specifications

1-4 Dimensional Data


(A) Indoor Units : Ceiling Mounted Type 25, 36, 48 Type

280 D E F K 141 Hole for wall-through piping (View from front) 280 670 L

G 146 280 Holes in the rear unit (View from front) I J 53 (Suspension bolt hole pitch) 132 C (Suspension bolt hole pitch) B 160 71 35 28

86

1
500 or more 251 Air intake 250 Air outlet or more (Service space) A Front 250 or more (Service space) 81 214 170

320

160

2 1

89 147 183

103

Dimension : mm Drain connection Drain connection for left side Refrigerant liquid line (9.52) Refrigerant gas line (18, 25 type: 15.88 / 36, 48 type: 19.05) Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (100 hole) Hole for upper side refrigerant tubing (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply cord (Knockout hole 40) Hole for remote controller wiring
1394_X_S

4
A 25 type B C D E F G H I J K L M N 1,300 1,280 1,230 147 101 64 134 147 116 83 120 95 147 190

36, 48 type 1,575 1,555 1,505 197 151 114 184 197 121 80 170 140 197 240

5
I - 62

SM830080

1. Specifications

1-4 Dimensional Data


(A) Indoor Units : Concealed Duct Type 25 Type

10
190

25 175

35 130

310

210

25

160 10 25 30 630 70

25 85

Inspection access (450 450) (Field supply)

70

285

115

(150)

11

19

31

40

260 (Air outlet duct flange)

24

16-3.3 (Hole)

75 65

1
180 1080 (Suspension bolt pitch) 290 272 1000

962 (Air outlet duct flange)

900

2
290

3
580 (Suspension bolt pitch) 25

31

90

185

9 10 11

Refrigerant liquid line 9.52 (narrow tube) (Use the tube connector) Refrigerant gas line 15.88 (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 26 mm) Suspension lug Power supply outlet (2-30) Fresh air intake port (150) Flange for the flexible air outlet duct (200) Tube cover Electrical component box Flange for the air intake duct (Option or field supply)
1731_U_I

I - 63

SM830080

1. Specifications

1-4 Dimensional Data


(A) Indoor Units : Concealed Duct Type 36, 48 Type

10
190
25 175 35 130 310 210 25

160 10 25 30 630 70

25 85

Inspection access (450 450) (Field supply)

70

285

115

(150)

11

19

31

40

260 (Air outlet duct flange)

24

18-3.3 (Hole)

230

230 P 6 = 1380

2 1

1560 (Suspension bolt pitch)

1442 (Air outlet duct flange)

1480

3
31

580 (Suspension bolt pitch)

25

4
90

185

5
I - 64

10 11

335

335

335

310

75 65

Refrigerant liquid line 9.52 (narrow tube) Refrigerant gas line 19.05 (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 26 mm) Suspension lug Power supply outlet (2-30) Fresh air intake port (150) Flange for the flexible air outlet duct (200) Tube cover Electrical component box Flange for the air intake duct (Option or field supply)
1732_U_I

SM830080

1. Specifications

1-4 Dimensional Data


7 Flange for the air intake duct (Field supply) : For Concealed Duct Type
2-3.3 (Hole)

210

25

305 25 260 (O.D.)


I-6 (Hole)

23

10

31

C-3.3 (Hole)

18

10

25

1
B (O.D.)

3
F

4
8 45 200 45
1766_U_I

(mm) A 9, 12, 18 type 698 25 type 36, 48 type 998 B 662 962 C 4 6 7 D E 600 900 F 170 120 120 G 245 (245 1) 490 (245 2) H 340 250 240 I 12 16 20 200 3 200P = 180 5 180P =

5
SM830080

1,478 1,442

230 6 230P = 1,380

I - 65

1. Specifications

1-4 Dimensional Data


(A) Indoor Units : Concealed Duct High Static Pressure Type 25, 36, 48 Type
A 310 55 100 100 25 55

A 25, 36 type 48 type


500 620

B 395 425

C 68 98

420 450

Refrigerant liquid line [ 9.52 (In case of


25 type, use the tube connector.)]

100

100 300 B

10

50 55 80 290 130

70

Refrigerant gas line ( 19.05) Power supply entry Drain connection (20 A / VP20) Duct connection for suction Duct connection for discharge

35

1
980 (Suspension bolt pitch) 22 - 3.2 55 (Hole for full circumference) (Hole for full circumference) 46 4 100 = 400 7 100 = 700

1010

940

15

(Suspension bolt pitch)

500

793

16 - 3.2

48

2 1

3
35 Electric box
81 100

40

15

60

5
0184_D_I

Drain pan

23

55

(274)

4-20 Hole for suspension bolt)

90

20

I - 66

SM830080

940

1. Specifications

1-4 Dimensional Data


(B) Outdoor Units : SPW-CR253EHL5 , SPW-CR253EL5 SPW-CR253EHL8 , SPW-CR253EL8

170 50

660 50

110 30 10 380 400

340

940

735

1
280 307

Dimension : mm Hole for anchor bolt (4-13) Refrigerant tube joint (narrow tube) Flare connection 1/4 in (6.35 mm) Refrigerant tube joint (wide tube) Flare connection 5/8 in (15.88 mm) Refrigerant tubing inlet Power supply inlet
0411_C_S

5
I - 67
SM830080

1. Specifications

1-4 Dimensional Data


(B) Outdoor Units : SPW-CR363EHL8 , SPW-CR363EL8 SPW-CR483EHL8 , SPW-CR483EL8

170 50

660 50

110 30 10 380
580 607

340

940

2 1
Dimension : mm Hole for anchor bolt (4-13) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
1553_C_S

5
I - 68
SM830080

1235

400

1. Specifications

1-5 Refrigerant Flow Diagram


Outdoor Units : SPW-CR253EL5 SPW-CR253EL8
Compressor Accumulator Accumulator High pressure switch HP Gas line service valve

Indoor Unit : 25 Type

O.D. 15.88mm (5/8")

Gas line nipple

EC Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 6.35mm (1/4") Distributor Strainer Electronic ref.control valve M Liquid line nipple P

Strainer

1
1549_C_S

Cooling Cycle

5
I - 69
SM830080

1. Specifications

1-5 Refrigerant Flow Diagram


Outdoor Units : SPW-CR363EL8 SPW-CR483EL8
Compressor LP High pressure switch HP Gas line service valve Low pressure switch Accumulator

Indoor Units : 36, 48 Type

O.D. 19.05mm (3/4")

Gas line nipple

EC Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 9.52mm (3/8") Distributor Strainer Electronic ref.control valve M Liquid line nipple P

1
Cooling Cycle

Strainer

1550_C_S

2 1

5
I - 70
SM830080

1. Specifications

1-5 Refrigerant Flow Diagram


Outdoor Units : SPW-CR253EHL5 SPW-CR253EHL8
Compressor Accumulator Accumulator Gas line service valve

Indoor Unit : 25 Type

O.D. 15.88mm (5/8")

Gas line nipple

High pressure switch

HP Muffler 4-way valve EC Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 6.35mm (1/4") Distributor Strainer Electronic ref.control valve M Liquid line nipple P

Sub-heat exchanger Cooling Cycle Heating Cycle

Strainer

1
1551_C_S

5
I - 71
SM830080

1. Specifications

1-5 Refrigerant Flow Diagram


Outdoor Units : SPW-CR363EHL8 SPW-CR483EHL8
Compressor LP High pressure switch HP Muffler 4-way valve Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 9.52mm (3/8") Distributor Strainer Electronic ref.control valve M Liquid line nipple P EC Gas line service valve Gas line nipple Low pressure switch Accumulator

Indoor Units : 36, 48 Type

O.D. 19.05mm (3/4")

Sub-heat exchanger Cooling Cycle Heating Cycle

Strainer

1552_C_S

2 1

1-6 Operating Range


Temperature Maximum Cooling Indoor air intake temp. 35C DB / 23C WB 18C DB / 14C WB 27C DB / WB 15C DB / WB Outdoor air intake temp. 43 C DB -15 C DB 21 C DB / 15.5C WB -15 C DB / WB

4
Heating

Minimum Maximum Minimum

5
I - 72
SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-XR253GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.37 2.55 4.47 4.28 5.03 4.83 5.58 5.39 6.14 5.95 6.7 6.51 7.03 6.67 7.31 6.96 2.44 2.62 3.78 3.6 4.34 4.16 4.89 4.72 5.45 5.28 6.01 5.83 6.56 6.39 7.6 # 7.3 2.52 2.7 3.08 2.94 3.63 3.49 4.19 4.05 4.75 4.61 5.31 5.17 5.86 5.72 7.85 7.56 2.59 2.78 2.91 2.78 3.47 3.34 4.03 3.9 4.58 4.46 5.14 5.01 8.17 7.88 2.65 2.85 2.76 2.65 3.32 3.21 3.88 3.77 4.44 4.32 8.45 8.2 2.74 2.91 2.6 2.51 3.15 3.06 3.71 3.62 1140 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

25 7.37 2.22 4.66 5.21 5.77 6.33 6.88 7.37 7.61 2.28 3.93 4.49 5.05 5.6 6.16 6.72 7.88 2.35 3.21 3.76 4.32 4.88 5.44 5.99 8.14 2.41 3.03 3.59 4.15 4.7 5.26 8.42 2.48 2.86 3.42 3.97 4.53 8.76 2.56 2.71 3.27 3.82

40 6.26 2.49 4.06 4.61 5.17 5.73 6.26 6.26 6.59 2.57 3.42 3.98 4.54 5.09 5.65 6.21 6.94 2.66 2.77 3.33 3.89 4.45 5 5.56 7.21 2.74 2.64 3.2 3.75 4.31 4.87 7.59 2.82 2.54 3.1 3.65 4.21 7.91 2.9 2.41 2.97 3.52

45 5.81 2.45 3.83 4.39 4.94 5.5 5.81 5.81 6.18 2.52 3.23 3.78 4.34 4.9 5.46 6.01 6.54 2.62 2.6 3.16 3.71 4.27 4.83 5.39 6.86 2.7 2.5 3.05 3.61 4.17 4.73 7.24 2.78 2.41 2.97 3.52 4.08 7.61 2.88 2.3 2.86 3.42

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 73

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-XR253GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.22 2.38 4.47 4.28 5.03 4.83 5.58 5.39 6.14 5.95 6.7 6.51 7.03 6.67 7.31 6.96 2.28 2.44 3.78 3.6 4.34 4.16 4.89 4.72 5.45 5.28 6.01 5.83 6.56 6.39 7.6 # 7.3 2.35 2.52 3.08 2.94 3.63 3.49 4.19 4.05 4.75 4.61 5.31 5.17 5.86 5.72 7.85 7.56 2.41 2.59 2.91 2.78 3.47 3.34 4.03 3.9 4.58 4.46 5.14 5.01 8.17 7.88 2.48 2.66 2.76 2.65 3.32 3.21 3.88 3.77 4.44 4.32 8.45 8.2 2.56 2.71 2.6 2.51 3.15 3.06 3.71 3.62 1140 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

25 7.37 2.07 4.66 5.21 5.77 6.33 6.88 7.37 7.61 2.13 3.93 4.49 5.05 5.6 6.16 6.72 7.88 2.19 3.21 3.76 4.32 4.88 5.44 5.99 8.14 2.25 3.03 3.59 4.15 4.7 5.26 8.42 2.31 2.86 3.42 3.97 4.53 8.76 2.39 2.71 3.27 3.82

40 6.26 2.49 4.06 4.61 5.17 5.73 6.26 6.26 6.59 2.57 3.42 3.98 4.54 5.09 5.65 6.21 6.94 2.65 2.77 3.33 3.89 4.45 5 5.56 7.21 2.72 2.64 3.2 3.75 4.31 4.87 7.59 2.79 2.54 3.1 3.65 4.21 7.91 2.87 2.41 2.97 3.52

45 5.81 2.62 3.83 4.39 4.94 5.5 5.81 5.81 6.18 2.69 3.23 3.78 4.34 4.9 5.46 6.01 6.54 2.77 2.6 3.16 3.71 4.27 4.83 5.39 6.86 2.85 2.5 3.05 3.61 4.17 4.73 7.24 2.93 2.41 2.97 3.52 4.08 7.61 3.02 2.3 2.86 3.42

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 74

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-XR363GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 10.6 kW

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 10.21 9.69 3.09 3.31 6.69 6.43 7.62 7.36 8.56 8.3 9.49 9.23 10.21 9.69 10.21 9.69 10.61 10.11 3.17 3.4 5.57 5.33 6.5 6.27 7.43 7.2 8.37 8.13 9.3 9.06 10.23 9.99 11.03 # 10.6 3.27 3.51 4.43 4.24 5.36 5.17 6.29 6.11 7.23 7.04 8.16 7.97 9.09 8.9 11.41 10.97 3.36 3.61 4.2 4.02 5.13 4.96 6.06 5.89 6.99 6.82 7.93 7.75 11.86 11.45 3.45 3.7 3.99 3.84 4.92 4.77 5.85 5.7 6.79 6.63 12.27 11.9 3.56 3.78 3.75 3.63 4.69 4.56 5.62 5.49 1920 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 10.7 2.89 6.95 7.88 8.81 9.74 10.67 10.7 11.06 2.96 5.78 6.71 7.65 8.58 9.51 10.44 11.45 3.05 4.61 5.55 6.48 7.41 8.34 9.28 11.82 3.14 4.37 5.3 6.23 7.16 8.09 12.22 3.22 4.12 5.06 5.99 6.92 12.72 3.33 3.9 4.84 5.77

40 9.08 3.38 6.13 7.06 7.99 8.93 9.08 9.08 9.57 3.48 5.09 6.02 6.95 7.88 8.81 9.57 10.07 3.59 4.01 4.94 5.88 6.81 7.74 8.67 10.47 3.7 3.83 4.76 5.69 6.62 7.56 11.02 3.8 3.68 4.61 5.55 6.48 11.49 3.9 3.5 4.43 5.36

45 8.44 3.46 5.81 6.74 7.68 8.44 8.44 8.44 8.98 3.56 4.81 5.74 6.67 7.61 8.54 8.98 9.5 3.68 3.77 4.7 5.64 6.57 7.5 8.43 9.96 3.79 3.63 4.56 5.49 6.42 7.36 10.52 3.89 3.5 4.43 5.37 6.3 11.05 4.02 3.35 4.28 5.21

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 75

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-XR483GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 12.6 kW

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 12.13 11.52 3.66 3.93 7.72 7.38 8.65 8.31 9.58 9.25 10.51 10.18 11.45 11.11 12.13 11.52 12.61 12.02 3.76 4.04 6.55 6.25 7.49 7.19 8.42 8.12 9.35 9.05 10.28 9.98 11.21 10.92 13.12 # 12.6 3.88 4.16 5.37 5.14 6.31 6.07 7.24 7 8.17 7.93 9.1 8.87 10.04 9.8 13.56 13.04 3.99 4.28 5.09 4.87 6.02 5.81 6.96 6.74 7.89 7.67 8.82 8.6 14.1 13.61 4.09 4.39 4.84 4.65 5.77 5.58 6.71 6.51 7.64 7.45 14.59 14.15 4.22 4.48 4.56 4.4 5.49 5.33 6.42 6.26 1920 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 12.71 3.42 8.04 8.97 9.9 10.84 11.77 12.7 13.14 3.51 6.83 7.76 8.69 9.62 10.56 11.49 13.61 3.62 5.61 6.54 7.48 8.41 9.34 10.27 14.05 3.72 5.31 6.24 7.17 8.1 9.04 14.53 3.82 5.01 5.94 6.88 7.81 15.12 3.94 4.75 5.68 6.61

40 10.8 4.14 7 7.93 8.86 9.8 10.73 10.8 11.38 4.26 5.94 6.87 7.8 8.74 9.67 10.6 11.97 4.4 4.85 5.78 6.71 7.65 8.58 9.51 12.45 4.52 4.62 5.56 6.49 7.42 8.35 13.1 4.64 4.45 5.39 6.32 7.25 13.66 4.76 4.23 5.16 6.09

45 10.03 4.38 6.6 7.54 8.47 9.4 10.03 10.03 10.67 4.49 5.6 6.53 7.46 8.39 9.33 10.26 11.29 4.63 4.54 5.47 6.41 7.34 8.27 9.2 11.84 4.76 4.37 5.31 6.24 7.17 8.1 12.5 4.89 4.22 5.16 6.09 7.02 13.13 5.04 4.05 4.98 5.91

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 76

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-TR253GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.37 2.55 4.56 4.37 5.12 4.93 5.69 5.5 6.25 6.06 6.82 6.63 7.03 6.67 7.31 6.96 2.44 2.62 3.87 3.7 4.43 4.26 5 4.83 5.56 5.39 6.13 5.95 6.69 6.52 7.6 # 7.3 2.52 2.7 3.16 3.03 3.73 3.59 4.29 4.16 4.86 4.72 5.42 5.29 5.99 5.85 7.85 7.56 2.59 2.78 3.01 2.88 3.57 3.44 4.14 4.01 4.7 4.57 5.27 5.14 8.17 7.88 2.65 2.85 2.87 2.75 3.43 3.32 3.99 3.88 4.56 4.45 8.45 8.2 2.74 2.91 2.7 2.62 3.27 3.18 3.83 3.74 1080 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

25 7.37 2.22 4.74 5.31 5.87 6.44 7 7.37 7.61 2.28 4.02 4.58 5.15 5.71 6.28 6.84 7.88 2.35 3.29 3.86 4.42 4.99 5.55 6.12 8.14 2.41 3.12 3.69 4.25 4.82 5.38 8.42 2.48 2.96 3.52 4.09 4.65 8.76 2.56 2.81 3.38 3.94

40 6.26 2.49 4.15 4.72 5.28 5.85 6.26 6.26 6.59 2.57 3.52 4.08 4.65 5.21 5.78 6.34 6.94 2.66 2.87 3.43 4 4.56 5.13 5.69 7.21 2.74 2.74 3.3 3.87 4.43 5 7.59 2.82 2.64 3.21 3.77 4.34 7.91 2.9 2.52 3.08 3.65

45 5.81 2.45 3.93 4.49 5.06 5.62 5.81 5.81 6.18 2.52 3.32 3.89 4.45 5.02 5.58 6.15 6.54 2.62 2.69 3.26 3.82 4.39 4.95 5.52 6.86 2.7 2.6 3.16 3.73 4.29 4.86 7.24 2.78 2.52 3.08 3.65 4.21 7.61 2.88 2.41 2.98 3.54

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 77

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-TR253GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.37 2.55 4.56 4.37 5.12 4.93 5.69 5.5 6.25 6.06 6.82 6.63 7.03 6.67 7.31 6.96 2.44 2.62 3.87 3.7 4.43 4.26 5 4.83 5.56 5.39 6.13 5.95 6.69 6.52 7.6 # 7.3 2.52 2.7 3.16 3.03 3.73 3.59 4.29 4.16 4.86 4.72 5.42 5.29 5.99 5.85 7.85 7.56 2.59 2.78 3.01 2.88 3.57 3.44 4.14 4.01 4.7 4.57 5.27 5.14 8.17 7.88 2.65 2.85 2.87 2.75 3.43 3.32 3.99 3.88 4.56 4.45 8.45 8.2 2.74 2.91 2.7 2.62 3.27 3.18 3.83 3.74 1080 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

25 7.37 2.22 4.74 5.31 5.87 6.44 7 7.37 7.61 2.28 4.02 4.58 5.15 5.71 6.28 6.84 7.88 2.35 3.29 3.86 4.42 4.99 5.55 6.12 8.14 2.41 3.12 3.69 4.25 4.82 5.38 8.42 2.48 2.96 3.52 4.09 4.65 8.76 2.56 2.81 3.38 3.94

40 6.26 2.49 4.15 4.72 5.28 5.85 6.26 6.26 6.59 2.57 3.52 4.08 4.65 5.21 5.78 6.34 6.94 2.66 2.87 3.43 4 4.56 5.13 5.69 7.21 2.74 2.74 3.3 3.87 4.43 5 7.59 2.82 2.64 3.21 3.77 4.34 7.91 2.9 2.52 3.08 3.65

45 5.81 2.45 3.93 4.49 5.06 5.62 5.81 5.81 6.18 2.52 3.32 3.89 4.45 5.02 5.58 6.15 6.54 2.62 2.69 3.26 3.82 4.39 4.95 5.52 6.86 2.7 2.6 3.16 3.73 4.29 4.86 7.24 2.78 2.52 3.08 3.65 4.21 7.61 2.88 2.41 2.98 3.54

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 78

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-TR363GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 10.6 kW

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 10.21 9.69 3.09 3.31 6.75 6.49 7.72 7.46 8.69 8.43 9.66 9.4 10.21 9.69 10.21 9.69 10.61 10.11 3.17 3.4 5.59 5.36 6.56 6.33 7.53 7.3 8.5 8.26 9.47 9.23 10.43 10.11 11.03 # 10.6 3.27 3.51 4.42 4.23 5.39 5.2 6.35 6.17 7.32 7.14 8.29 8.11 9.26 9.07 11.41 10.97 3.36 3.61 4.18 4.01 5.15 4.98 6.12 5.95 7.09 6.92 8.06 7.89 11.86 11.45 3.45 3.7 3.98 3.83 4.95 4.8 5.92 5.76 6.88 6.73 12.27 11.9 3.56 3.78 3.74 3.62 4.71 4.59 5.68 5.56 1800 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 10.7 2.89 7 7.97 8.94 9.91 10.7 10.7 11.06 2.96 5.8 6.77 7.74 8.71 9.67 10.64 11.45 3.05 4.6 5.57 6.54 7.5 8.47 9.44 11.82 3.14 4.35 5.32 6.29 7.26 8.22 12.22 3.22 4.11 5.08 6.05 7.02 12.72 3.33 3.89 4.86 5.83

40 9.08 3.38 6.2 7.16 8.13 9.08 9.08 9.08 9.57 3.48 5.12 6.08 7.05 8.02 8.99 9.57 10.07 3.59 4.01 4.97 5.94 6.91 7.88 8.85 10.47 3.7 3.82 4.79 5.76 6.72 7.69 11.02 3.8 3.67 4.64 5.61 6.58 11.49 3.9 3.49 4.46 5.42

45 8.44 3.46 5.88 6.85 7.82 8.44 8.44 8.44 8.98 3.56 4.84 5.81 6.78 7.75 8.72 8.98 9.5 3.68 3.77 4.74 5.7 6.67 7.64 8.61 9.96 3.79 3.62 4.59 5.56 6.53 7.5 10.52 3.89 3.5 4.47 5.43 6.4 11.05 4.02 3.34 4.31 5.28

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 79

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-TR483GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 12.6 kW

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 12.13 11.52 3.66 3.93 7.86 7.53 8.88 8.55 9.9 9.58 10.92 10.6 11.94 11.52 12.13 11.52 12.61 12.02 3.76 4.04 6.61 6.32 7.63 7.34 8.65 8.36 9.67 9.38 10.69 10.4 11.71 11.42 13.12 # 12.6 3.88 4.16 5.34 5.11 6.36 6.13 7.38 7.15 8.4 8.18 9.43 9.2 10.45 10.22 13.56 13.04 3.99 4.28 5.06 4.85 6.08 5.87 7.11 6.9 8.13 7.92 9.15 8.94 14.1 13.61 4.09 4.39 4.82 4.63 5.84 5.65 6.86 6.68 7.88 7.7 14.59 14.15 4.22 4.48 4.54 4.39 5.56 5.41 6.58 6.43 1920 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 12.71 3.42 8.17 9.19 10.21 11.23 12.25 12.71 13.14 3.51 6.87 7.89 8.91 9.93 10.95 11.97 13.61 3.62 5.57 6.59 7.61 8.63 9.65 10.67 14.05 3.72 5.27 6.29 7.31 8.34 9.36 14.53 3.82 4.98 6 7.02 8.04 15.12 3.94 4.72 5.74 6.77

40 10.8 4.14 7.16 8.19 9.21 10.23 10.8 10.8 11.38 4.26 6.01 7.03 8.06 9.08 10.1 11.12 11.97 4.4 4.84 5.86 6.88 7.9 8.92 9.94 12.45 4.52 4.61 5.63 6.66 7.68 8.7 13.1 4.64 4.44 5.46 6.49 7.51 13.66 4.76 4.22 5.24 6.26

45 10.03 4.38 6.78 7.8 8.82 9.84 10.03 10.03 10.67 4.49 5.68 6.7 7.73 8.75 9.77 10.67 11.29 4.63 4.54 5.56 6.58 7.6 8.62 9.64 11.84 4.76 4.37 5.39 6.41 7.44 8.46 12.5 4.89 4.22 5.24 6.26 7.29 13.13 5.04 4.05 5.07 6.09

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 80

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-UR253GHN56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.51 2.69 4.68 4.5 5.26 5.07 5.84 5.65 6.41 6.23 6.99 6.67 7.03 6.67 7.31 6.96 2.58 2.76 3.99 3.82 4.56 4.4 5.14 4.97 5.72 5.55 6.3 6.13 6.87 6.71 7.6 # 7.3 2.66 2.85 3.28 3.15 3.86 3.72 4.44 4.3 5.01 4.88 5.59 5.46 6.17 6.03 7.85 7.56 2.73 2.93 3.13 3.01 3.71 3.59 4.29 4.16 4.86 4.74 5.44 5.32 8.17 7.88 2.8 3.01 3 2.89 3.58 3.47 4.15 4.04 4.73 4.62 8.45 8.2 2.89 3.07 2.85 2.76 3.42 3.34 4 3.91 1080 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

25 7.37 2.35 4.86 5.44 6.02 6.59 7.17 7.37 7.61 2.41 4.13 4.71 5.29 5.87 6.44 7.02 7.88 2.48 3.41 3.98 4.56 5.14 5.72 6.29 8.14 2.55 3.25 3.82 4.4 4.98 5.56 8.42 2.62 3.09 3.67 4.25 4.82 8.76 2.7 2.95 3.53 4.11

40 6.26 2.63 4.28 4.86 5.44 6.02 6.26 6.26 6.59 2.71 3.64 4.22 4.8 5.38 5.95 6.53 6.94 2.8 2.99 3.57 4.14 4.72 5.3 5.88 7.21 2.89 2.87 3.45 4.02 4.6 5.18 7.59 2.97 2.78 3.36 3.94 4.51 7.91 3.05 2.67 3.24 3.82

45 5.81 2.58 4.06 4.64 5.22 5.8 5.81 5.81 6.18 2.65 3.46 4.03 4.61 5.19 5.76 6.18 6.54 2.75 2.82 3.4 3.97 4.55 5.13 5.71 6.86 2.84 2.73 3.31 3.88 4.46 5.04 7.24 2.93 2.66 3.23 3.81 4.39 7.61 3.03 2.56 3.14 3.72

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 81

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-UR253GHN56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.35 2.52 4.68 4.5 5.26 5.07 5.84 5.65 6.41 6.23 6.99 6.67 7.03 6.67 7.31 6.96 2.41 2.59 3.99 3.82 4.56 4.4 5.14 4.97 5.72 5.55 6.3 6.13 6.87 6.71 7.6 # 7.3 2.49 2.67 3.28 3.15 3.86 3.72 4.44 4.3 5.01 4.88 5.59 5.46 6.17 6.03 7.85 7.56 2.56 2.74 3.13 3.01 3.71 3.59 4.29 4.16 4.86 4.74 5.44 5.32 8.17 7.88 2.62 2.82 3 2.89 3.58 3.47 4.15 4.04 4.73 4.62 8.45 8.2 2.71 2.87 2.85 2.76 3.42 3.34 4 3.91 1080 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

25 7.37 2.2 4.86 5.44 6.02 6.59 7.17 7.37 7.61 2.25 4.13 4.71 5.29 5.87 6.44 7.02 7.88 2.32 3.41 3.98 4.56 5.14 5.72 6.29 8.14 2.39 3.25 3.82 4.4 4.98 5.56 8.42 2.45 3.09 3.67 4.25 4.82 8.76 2.53 2.95 3.53 4.11

40 6.26 2.55 4.28 4.86 5.44 6.02 6.26 6.26 6.59 2.63 3.64 4.22 4.8 5.38 5.95 6.53 6.94 2.71 2.99 3.57 4.14 4.72 5.3 5.88 7.21 2.79 2.87 3.45 4.02 4.6 5.18 7.59 2.87 2.78 3.36 3.94 4.51 7.91 2.95 2.67 3.24 3.82

45 5.81 2.6 4.06 4.64 5.22 5.8 5.81 5.81 6.18 2.67 3.46 4.03 4.61 5.19 5.76 6.18 6.54 2.76 2.82 3.4 3.97 4.55 5.13 5.71 6.86 2.84 2.73 3.31 3.88 4.46 5.04 7.24 2.92 2.66 3.23 3.81 4.39 7.61 3.02 2.56 3.14 3.72

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 82

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-UR363GHN56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 10.6 kW

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 10.21 9.69 3.09 3.31 7.24 6.99 8.29 8.04 9.34 9.1 10.21 9.69 10.21 9.69 10.21 9.69 10.61 10.11 3.17 3.4 6.02 5.8 7.07 6.85 8.12 7.9 9.17 8.95 10.23 10 10.61 10.11 11.03 # 10.6 3.27 3.51 4.79 4.61 5.84 5.66 6.89 6.71 7.94 7.76 8.99 8.81 10.04 9.86 11.41 10.97 3.36 3.61 4.58 4.41 5.63 5.47 6.68 6.52 7.73 7.57 8.78 8.62 11.86 11.45 3.45 3.7 4.39 4.25 5.45 5.3 6.5 6.35 7.55 7.4 12.27 11.9 3.56 3.78 4.18 4.06 5.23 5.12 6.28 6.17 1800 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 10.7 2.89 7.48 8.53 9.58 10.63 10.7 10.7 11.06 2.96 6.22 7.27 8.32 9.37 10.42 11.06 11.45 3.05 4.96 6.01 7.06 8.11 9.17 10.22 11.82 3.14 4.74 5.79 6.84 7.89 8.94 12.22 3.22 4.52 5.57 6.62 7.67 12.72 3.33 4.32 5.37 6.43

40 9.08 3.38 6.71 7.76 8.81 9.08 9.08 9.08 9.57 3.48 5.56 6.61 7.67 8.72 9.57 9.57 10.07 3.59 4.39 5.44 6.49 7.55 8.6 9.65 10.47 3.7 4.23 5.28 6.33 7.38 8.43 11.02 3.8 4.1 5.15 6.2 7.26 11.49 3.9 3.94 4.99 6.04

45 8.44 3.46 6.41 7.46 8.44 8.44 8.44 8.44 8.98 3.56 5.3 6.35 7.4 8.46 8.98 8.98 9.5 3.68 4.16 5.21 6.27 7.32 8.37 9.42 9.96 3.79 4.04 5.09 6.14 7.19 8.24 10.52 3.89 3.93 4.98 6.03 7.09 11.05 4.02 3.8 4.85 5.9

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 83

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-UR483GHN56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 12.6 kW

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 12.13 11.52 3.66 3.93 8.39 8.09 9.53 9.23 10.68 10.37 11.82 11.51 12.13 11.52 12.13 11.52 12.61 12.02 3.76 4.04 7.05 6.78 8.19 7.92 9.33 9.06 10.47 10.2 11.62 11.34 12.61 12.02 13.12 # 12.6 3.88 4.16 5.69 5.47 6.83 6.62 7.97 7.76 9.12 8.9 10.26 10.04 11.4 11.18 13.56 13.04 3.99 4.28 5.44 5.24 6.58 6.38 7.72 7.53 8.87 8.67 10.01 9.81 14.1 13.61 4.09 4.39 5.22 5.05 6.36 6.19 7.5 7.33 8.65 8.47 14.59 14.15 4.22 4.48 4.97 4.82 6.11 5.96 7.25 7.11 1980 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 12.71 3.42 8.68 9.83 10.97 12.11 12.71 12.71 13.14 3.51 7.3 8.44 9.58 10.72 11.86 13.01 13.61 3.62 5.9 7.05 8.19 9.33 10.47 11.61 14.05 3.72 5.64 6.78 7.92 9.06 10.2 14.53 3.82 5.37 6.52 7.66 8.8 15.12 3.94 5.14 6.28 7.43

40 10.8 4.14 7.74 8.88 10.02 10.8 10.8 10.8 11.38 4.26 6.49 7.63 8.77 9.92 11.06 11.38 11.97 4.4 5.21 6.35 7.5 8.64 9.78 10.92 12.45 4.52 5.01 6.16 7.3 8.44 9.58 13.1 4.64 4.87 6.01 7.15 8.29 13.66 4.76 4.67 5.81 6.95

45 10.03 4.38 7.38 8.52 9.66 10.03 10.03 10.03 10.67 4.49 6.18 7.32 8.46 9.6 10.67 10.67 11.29 4.63 4.93 6.07 7.21 8.36 9.5 10.64 11.84 4.76 4.79 5.93 7.07 8.21 9.35 12.5 4.89 4.66 5.8 6.94 8.08 13.13 5.04 4.5 5.64 6.78

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 84

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-DR253GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.37 2.55 4.01 3.82 4.75 4.56 5.48 5.29 6.21 6.02 6.94 6.67 7.03 6.67 7.31 6.96 2.44 2.62 3.09 2.92 3.82 3.65 4.55 4.38 5.29 5.12 6.02 5.85 6.75 6.58 7.6 # 7.3 2.52 2.7 2.15 2.02 2.89 2.75 3.62 3.49 4.35 4.22 5.09 4.95 5.82 5.68 7.85 7.56 2.59 2.78 1.94 1.81 2.67 2.55 3.4 3.28 4.14 4.01 4.87 4.75 8.17 7.88 2.65 2.85 1.74 1.63 2.47 2.36 3.21 3.1 3.94 3.83 8.45 8.2 2.74 2.91 1.53 1.44 2.26 2.17 2.99 2.91 1380 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

25 7.37 2.22 4.19 4.92 5.66 6.39 7.12 7.37 7.61 2.28 3.23 3.97 4.7 5.43 6.17 6.9 7.88 2.35 2.28 3.01 3.75 4.48 5.21 5.94 8.14 2.41 2.05 2.78 3.52 4.25 4.98 8.42 2.48 1.83 2.56 3.3 4.03 8.76 2.56 1.63 2.37 3.1

40 6.26 2.49 3.61 4.34 5.07 5.81 6.26 6.26 6.59 2.57 2.74 3.47 4.21 4.94 5.67 6.41 6.94 2.66 1.86 2.59 3.33 4.06 4.79 5.53 7.21 2.74 1.67 2.41 3.14 3.87 4.61 7.59 2.82 1.52 2.26 2.99 3.72 7.91 2.9 1.35 2.08 2.81

45 5.81 2.45 3.39 4.12 4.85 5.58 5.81 5.81 6.18 2.52 2.55 3.28 4.02 4.75 5.48 6.18 6.54 2.62 1.69 2.42 3.16 3.89 4.62 5.35 6.86 2.7 1.53 2.27 3 3.73 4.47 7.24 2.78 1.4 2.13 2.86 3.6 7.61 2.88 1.24 1.98 2.71

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 85

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-DR253GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC 7.3 kW

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 7.03 6.67 2.22 2.38 4.01 3.82 4.75 4.56 5.48 5.29 6.21 6.02 6.94 6.67 7.03 6.67 7.31 6.96 2.28 2.44 3.09 2.92 3.82 3.65 4.55 4.38 5.29 5.12 6.02 5.85 6.75 6.58 7.6 # 7.3 2.35 2.52 2.15 2.02 2.89 2.75 3.62 3.49 4.35 4.22 5.09 4.95 5.82 5.68 7.85 7.56 2.41 2.59 1.94 1.81 2.67 2.55 3.4 3.28 4.14 4.01 4.87 4.75 8.17 7.88 2.48 2.66 1.74 1.63 2.47 2.36 3.21 3.1 3.94 3.83 8.45 8.2 2.56 2.71 1.53 1.44 2.26 2.17 2.99 2.91 1380 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

25 7.37 2.07 4.19 4.92 5.66 6.39 7.12 7.37 7.61 2.13 3.23 3.97 4.7 5.43 6.17 6.9 7.88 2.19 2.28 3.01 3.75 4.48 5.21 5.94 8.14 2.25 2.05 2.78 3.52 4.25 4.98 8.42 2.31 1.83 2.56 3.3 4.03 8.76 2.39 1.63 2.37 3.1

40 6.26 2.49 3.61 4.34 5.07 5.81 6.26 6.26 6.59 2.57 2.74 3.47 4.21 4.94 5.67 6.41 6.94 2.65 1.86 2.59 3.33 4.06 4.79 5.53 7.21 2.72 1.67 2.41 3.14 3.87 4.61 7.59 2.79 1.52 2.26 2.99 3.72 7.91 2.87 1.35 2.08 2.81

45 5.81 2.62 3.39 4.12 4.85 5.58 5.81 5.81 6.18 2.69 2.55 3.28 4.02 4.75 5.48 6.18 6.54 2.77 1.69 2.42 3.16 3.89 4.62 5.35 6.86 2.85 1.53 2.27 3 3.73 4.47 7.24 2.93 1.4 2.13 2.86 3.6 7.61 3.02 1.24 1.98 2.71

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 86

SM830080

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-DR363GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 10.6 kW

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 10.21 9.69 3.09 3.31 6.17 5.91 7.2 6.94 8.24 7.97 9.27 9.01 10.21 9.69 10.21 9.69 10.61 10.11 3.17 3.4 4.89 4.65 5.92 5.69 6.96 6.72 7.99 7.75 9.03 8.79 10.06 9.82 11.03 # 10.6 3.27 3.51 3.59 3.4 4.63 4.44 5.66 5.47 6.7 6.51 7.73 7.54 8.77 8.58 11.41 10.97 3.36 3.61 3.31 3.14 4.34 4.17 5.38 5.21 6.41 6.24 7.45 7.27 11.86 11.45 3.45 3.7 3.06 2.9 4.09 3.94 5.12 4.97 6.16 6.01 12.27 11.9 3.56 3.78 2.77 2.65 3.81 3.68 4.84 4.72 1800 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

21

23 25 27 29 31

23

25 27 29 31

25

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 10.7 2.89 6.42 7.46 8.49 9.53 10.56 10.7 11.06 2.96 5.1 6.14 7.17 8.21 9.24 10.27 11.45 3.05 3.78 4.81 5.85 6.88 7.92 8.95 11.82 3.14 3.48 4.51 5.55 6.58 7.62 12.22 3.22 3.19 4.22 5.26 6.29 12.72 3.33 2.92 3.96 4.99

40 9.08 3.38 5.6 6.63 7.67 8.7 9.08 9.08 9.57 3.48 4.4 5.43 6.47 7.5 8.54 9.57 10.07 3.59 3.17 4.21 5.24 6.28 7.31 8.35 10.47 3.7 2.94 3.97 5.01 6.04 7.08 11.02 3.8 2.75 3.78 4.81 5.85 11.49 3.9 2.51 3.55 4.58

45 8.44 3.46 5.28 6.31 7.35 8.38 8.44 8.44 8.98 3.56 4.12 5.16 6.19 7.22 8.26 8.98 9.5 3.68 2.93 3.96 5 6.03 7.07 8.1 9.96 3.79 2.74 3.77 4.81 5.84 6.87 10.52 3.89 2.57 3.6 4.63 5.67 11.05 4.02 2.37 3.4 4.43

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

5
SM830080

I - 87

1. Specifications

1-7 Cooling Capacity


Indoor Unit : SPW-DR483GH56
RATING CAPACITY : EVAPORATOR ENT. TEMP. C WB DB 12.6 kW

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8


AIR FLOW RATE : CONDENSER AMBIENT TEMP C 30 35 12.13 11.52 3.66 3.93 7.35 7.03 8.55 8.24 9.76 9.44 10.97 10.65 12.13 11.52 12.13 11.52 12.61 12.02 3.76 4.04 5.85 5.57 7.06 6.77 8.26 7.98 9.47 9.19 10.68 10.39 11.88 11.6 13.12 # 12.6 3.88 4.16 4.34 4.11 5.54 5.32 6.75 6.53 7.96 7.73 9.16 8.94 10.37 10.15 13.56 13.04 3.99 4.28 4 3.8 5.21 5 6.42 6.21 7.62 7.42 8.83 8.62 14.1 13.61 4.09 4.39 3.7 3.52 4.91 4.73 6.12 5.94 7.32 7.14 14.59 14.15 4.22 4.48 3.37 3.22 4.58 4.43 5.79 5.64 2160 CMH

15

21 23 25 27 29 31

17

21 23 25 27 29 31

19

21 23 25 27 29 31

2 1

21

23 25 27 29 31

23

3
25

25 27 29 31

27 29 31

TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC TC CI SHC SHC SHC

25 12.71 3.42 7.65 8.86 10.07 11.27 12.48 12.71 13.14 3.51 6.11 7.32 8.52 9.73 10.94 12.14 13.61 3.62 4.56 5.77 6.97 8.18 9.39 10.59 14.05 3.72 4.21 5.41 6.62 7.83 9.03 14.53 3.82 3.86 5.07 6.28 7.48 15.12 3.94 3.55 4.76 5.97

40 10.8 4.14 6.66 7.87 9.08 10.28 10.8 10.8 11.38 4.26 5.27 6.47 7.68 8.88 10.09 11.3 11.97 4.4 3.84 5.05 6.25 7.46 8.67 9.87 12.45 4.52 3.56 4.77 5.97 7.18 8.39 13.1 4.64 3.34 4.54 5.75 6.95 13.66 4.76 3.06 4.27 5.47

45 10.03 4.38 6.28 7.49 8.69 9.9 10.03 10.03 10.67 4.49 4.94 6.14 7.35 8.56 9.76 10.67 11.29 4.63 3.55 4.75 5.96 7.17 8.37 9.58 11.84 4.76 3.32 4.53 5.74 6.94 8.15 12.5 4.89 3.12 4.32 5.53 6.74 13.13 5.04 2.89 4.1 5.3

TC : Total Cooling Capacity SHC : Sensible Heat Capacity CI : Compressor Input

(kW) (kW) (kW)

Rating conditions are : Outdoor Ambient Temp. 35 C DB : Indoor Unit Entering Air Temp. 27 C DB / 19 C WB

I - 88

SM830080

1. Specifications

q Heating Capacity

140

120 % 100

Heating capacity ratio

Ind

em or t

per

ture

CD

15C 20C 25C

80

60

140

Comp. motor power input ratio

1
120 % 100
Indoo eratu r temp re C D B

25C 20C 15C

80

60 15 10 5 0 5 10 15
0413_M_S

Outdoor temperature C WB
NOTE Above characteristics are based on: 1) Tubing length is 7 meters. 2) Air flow speed is high speed. 2. Minimum outdoor ambient temperature: 15C WB 3. Above characteristics indicate instantaneous capacity. Integrated capacity is instantaneous capacity less the effect of frost on the outdoor coil and the drop of performance during defrost cycle. 1.

5
I - 89
SM830080

1. Specifications

1-8 Noise Criterion Curves


4-Way Air Discharge Semi-concealed Type
MODEL : SPW-XR253GH56 37 dB(A), NC 30 LOW CONDITION SOURCE
60

MODEL

: SPW-XR363GH56 , XR483GH56 43 dB(A), NC 36 36 dB(A), NC 24 Under the unit 1.5 m 1 Phase, 50 Hz LOW

SOUND LEVEL : HIGH : Center,

SOUND LEVEL : HIGH CONDITION 50 Hz SOURCE


60

31 dB(A), NC 22 Under the unit 1.5 m

: Center,

: 220 - 230 - 240 V, 1 Phase,

: 220 - 230 - 240 V,

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

NC-50

50

NC-50

40

NC-40

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

NC-20

1000 2000 4000 8000


0274_X_I

1000 2000 4000 8000


0275_X_I

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

2 1

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an anechoic room. NOTE To evaluate Noise level the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select the maximum value (vertical axis) among them.

5
I - 90
SM830080

1. Specifications

1-8 Noise Criterion Curves


Ceiling Mounted Type
MODEL : SPW-TR253GH56 39 dB(A), NC 34 MODEL : SPW-TR363GH56 SOUND LEVEL : HIGH LOW CONDITION SOURCE
60

SOUND LEVEL : HIGH 42 dB(A), NC 36 LOW CONDITION SOURCE


60

34 dB(A), NC 26

35 dB(A),

NC 28

: Distance 1 m, Under the unit 1 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

: Distance 1 m, Under the unit 1 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

NC-50

50

NC-50

40

NC-40

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

NC-20

1000 2000 4000 8000


1221_X_I

1000 2000 4000 8000


1222_X_I

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

MODEL

: SPW-TR483GH56 NC 38 NC 31

SOUND LEVEL : HIGH 44 dB(A), LOW CONDITION SOURCE


60

37 dB(A),

: Distance 1 m, Under the unit 1 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

NC-50

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

1000 2000 4000 8000


1223_X_I

5
I - 91
SM830080

BAND CENTER FREQUENCIES, Hz

1. Specifications

1-8 Noise Criterion Curves


Concealed Duct Type
MODEL : SPW-UR253GHN56 MODEL : SPW-UR363GHN56 SOUND LEVEL : HIGH 34 dB(A), NC 22 / LOW 27 dB(A), NC 18 CONDITION SOURCE : Under the unit 1.5 m : 220 - 230 - 240 V, 1 Phase, 50 Hz SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21 CONDITION SOURCE : Under the unit 1.5 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

60

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

60

50

NC-50

50

NC-50

40

NC-40

40

NC-40

30

NC-30

30

NC-30

20

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

20

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
1761_U_I

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
1762_U_I

MODEL

: SPW-UR483GHN56

SOUND LEVEL : HIGH 40 dB(A), NC 33 / LOW 33 dB(A), NC 25 CONDITION SOURCE : Under the unit 1.5 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

2 1

60

50

NC-50

40

NC-40

30

NC-30

20

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
1763_U_I

4
REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an anechoic room.

NOTE To evaluate Noise level the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select the maximum value (vertical axis) among them.

I - 92

SM830080

1. Specifications

1-8 Noise Criterion Curves


Concealed Duct High Static Pressure Type
MODEL SOUND LEVEL CONDITION SOURCE
90

: SPW-DR253GH56 : HIGH 44 dB(A), NC 38 : Under the unit 1.5 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

MODEL SOUND LEVEL CONDITION SOURCE


90

: SPW-DR363GH56 : HIGH 45 dB(A), NC 39 : Under the unit 1.5 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

80

70

NC-70

70

NC-70

60

NC-60

60

NC-60

50

NC-50

50

NC-50

40

NC-40

40

NC-40

30

NC-30

30

NC-30
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

20

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

20

NC-20

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
0313_D_I

10

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
0314_D_I

MODEL SOUND LEVEL CONDITION SOURCE


90

: SPW-DR483GH56 : HIGH 47 dB(A), NC 42 : Under the unit 1.5 m : 220 - 230 - 240 V, 1 Phase, 50 Hz

2
NC-70

80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

70

60

NC-60

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an anechoic room. NOTE

50

NC-50

40

NC-40 NC-30

30

20

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

To evaluate Noise level the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select the maximum value (vertical axis) among them.

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
0315_D_I

5
I - 93
SM830080

1. Specifications

1-8 Noise Criterion Curves


Outdoor Units
MODEL : SPW-CR253EH5, CR253EH8 SPW-C253EH5, C253EH8 SOUND LEVEL : 52 dB(A), CONDITION SOURCE
90

MODEL

: SPW-CR363EH8 SPW-C363EH8

NC 44 Height 1m

SOUND LEVEL : 53 dB(A), NC 45 CONDITION SOURCE


90

: Distance 1m,

: Distance 1m, Height 1m : 380 - 400 - 415 V, 3 Phase, 50 Hz

: 220 - 230 - 240 V, 1 Phase, 50 Hz 380 - 400 - 415V, 3 Phase, 50 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)

80

80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)

70

NC-70

70

NC-70

60

NC-60

60

NC-60

50

NC-50

50

NC-50 NC-40 NC-30

40

40

NC-40 NC-30

30 20 APPROXIMATE THRESHOLD OF CONTINUOUS NOISE 10 60 125 250

30 APPROXIMATE 20 THRESHOLD OF HEARING FOR CONTINUOUS NOISE 10 63 125 250

NC-20

NC-20

500 1000 2000 4000 8000


0598_C_S

500

1000 2000 4000 8000


0597_C_S

BAND CAENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

MODEL

: SPW-CR483EH8 SPW-C483EH8

SOUND LEVEL : 55 dB(A), NC 47 CONDITION SOURCE : Distance 1m, Height 1m : 380 - 400 - 415V, 3 Phase, 50 Hz

2 1
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)

90

80

70

NC-70

60

NC-60

50

NC-50

40

NC-40 NC-30

30 APPROXIMATE 20 THRESHOLD OF HEARING FOR CONTINUOUS NOISE 10 63 125 250

NC-20

500

1000 2000 4000 8000


0599_C_S

BAND CENTER FREQUENCIES, Hz

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an anechoic room. NOTE To evaluate Noise level the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select the maximum value (vertical axis) among them.

I - 94

SM830080

1. Specifications

1-9 Indoor Fan Performance


Concealed Duct Type
If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: (1) Remove 2 screws on the electrical component box and remove the cover plate. Disconnect the fan motor sockets in the box. Take out the booster cable (sockets at both ends) clamped in the box. Securely connect the booster cable sockets between the disconnected fan motor sockets in step 2 as shown in the Fig. 1-1. Place the cable neatly in the box and reinstall the cover plate.
Electrical component box Fan motor Booster cable Booster cable

Fan motor socket (At shipment)

(Connected booster cable)

Fig. 1-1
(2) (3) (4)

1743_M_I

(5)

Indoor Fan Performance SPW-UR253GHN56 SPW-UR363GHN56


e

SPW-UR483GHN56
e

it lin

(mmAq)

Lim

(mmAq)

Lim

150
(Pa)
line

15
External Static Pressure

150
(Pa)

15
External Static Pressure

it lin

150
(Pa)

15
(mmAq)

External Static Pressure

Limit

ne

Lim

it lin

HT

Lim

Lim

100

10

100

HT 10

it li

it li

ne

100

HT

10

H 50 L M 5

H 50 L M 5

50 M L 0 10

0 20
1746_U_I

0 20 30 Air Flow Volume (m3/minute)

0 20 30 40 Air Flow Volume (m3/minute)

Air Flow Volume (m3/minute)

1747_U_I

1748_U_I

NOTE

HT : Using the booster cable H : At shipment Fig. 1-2

s How to read the diagram


The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (m3/minute). The characteristic curves for HT, H, M and L fan speed control are shown. The nameplate values are shown based on the H air flow. For the 25 type, the air flow is 18 m3/minute, while the external static pressure is 49 Pa at H position. If external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above.

5
I - 95
SM830080

1. Specifications

1-9 Indoor Fan Performance


Concealed Duct High Static Pressure Type
How to Read the Diagram
The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR FLOW (m3/minute). The characteristic curve for the H, Med, and Lo fan speed control. The name plate values are shown based on the H air flow. Therefore in the case of the 25 type the flow is 23 m3/ minute, while the EXTERNAL STATIC PRESSURE is 19 mmAq at H position. If the external static pressure is too great (due to long extention of duct, for example), the air flow volume may drop too low at each air outlet.

SPW-DR253GH56

SPW-DR363GH56

SPW-DR483GH56

(Pa)

(Pa)

lin

25
Lim it l ine

25
ine

25
Li m

External Static Pressure (mmAq)

External Static Pressure (mmAq)

External Static Pressure (mmAq)

20
M
L

20

Lim

200

it l

200
H

20
H

200

15

H M

150

15

150
H

15

150

10

100

10

100

10
H,M

100

Lim

it lin

50

5
Lim e it lin

50

5
tl Limi

50
ine

0 20 25 30
0846_D_I

0 25 30
Air Flow (m3/minute)
0847_D_I

2 1

35

30

35
Air Flow (m3/minute)

40
0848_D_I

Air Flow (m3/minute)

5
I - 96
SM830080

(Pa)

it

M
L

1. Specifications

1-10 Air throw Distance Chart


4-Way Air Discharge Semi-concealed Type
Model: 25 Type

HORIZONTAL DISTANCE (m) 0 0 1 2 3 4 5 6

AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m)

AXIS AIR VELOCITY

4
0276_X_I

Model:

36, 48 Type

HORIZONTAL DISTANCE (m) 0 0


AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m)

AXIS AIR VELOCITY

2
0277_X_I

3
: LOUVER ANGLE 20 in Cooling mode : LOUVER ANGLE 60 in Heating mode Condition Fan Speed : Hi Room air temp. : 27 C DB in cooling mode 20 C DB in heating mode

5
I - 97
SM830080

1. Specifications

1-10 Air throw Distance Chart


Ceiling Mounted Type
Model: 25 Type
0 1 2 HORIZONTAL DISTANCE (m) 3 4 5 6 7 8 9 10

AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m)

0 1 2 3 4 5 HORIZONTAL DISTANCE (m) 0 1 2 3 4 5 6 7 8 9 10


1225_T_I

AXIS AIR VELOCITY

Model: 36 Type
AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m) 0 1 2 3 4 5

AXIS AIR VELOCITY

1226_T_I

Model: 48 Type
0
AXIS AIR VELOCITY (m/s) VERTICAL DISTANCE (m)

HORIZONTAL DISTANCE (m) 1 2 3 4 5 6 7 8 9 10

0 1 2 3 4 5 COOLING HEATING HIGH 20 54 : COOLING : HEATING


1227_T_I

AXIS AIR VELOCITY

2 1

FAN SPEED

HIGH 27 7

ROOM AIR TEMP. LOUVER ANGLE

5
I - 98
SM830080

1. Specifications

1-11 Installation Instructions


Tubing Length
(A) Single type q Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. q The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the two units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H) as short as possible. Refer to Table 1-1 for the details. Table 1-1 (R407C Models) Installation Example 1
INDOOR UNIT Tubing length (L)

Elevation difference (H)

OUTDOOR UNIT

0419_M_I

Models SPW-CR253E(H)L5 SPW-CR363E(H)L8 SPW-CR483E(H)L8 Tubing Data CR253E(H)L8 Tubing size Narrow tube mm (in.) 6.35 (1/4) 9.52 (3/8) 9.52 (3/8) outer diameter Wide tube mm (in.) 15.88 (5/8) 19.05 (3/4) 19.05 (3/4) Limit of tubing length (m) 50 50 50 Outdoor unit is placed Limit of elevation 50 50 50 upper (m) difference between Outdoor unit is placed the two units 30 30 30 lower (m) Max. allowable tubing length at shipment (m) 30 30 30 Required additional refrigerant *1 (g/m) a) 45 b) 50 b) 50 Refrigerant charged at shipment (kg) 3.2 4.0 4.5 No additional charge of compressor oil is necessary. *1 If total tubing length becomes 30 to 50 m, charge additional refrigerant (R407C) by a) 45 or b) 50 g/m.

5
I - 99
SM830080

1. Specifications

1-11 Installation Instructions


Selecting the Installation Site
Indoor Unit AVOID: q areas where leakage of flammable gas may be expected. q places where large amounts of oil mist exist.
25 cm min. 25 cm min. Front view

Ceiling-Mounted Type
Ceiling

Wall

q direct sunlight q locations where nearby heat sources may affect performance of the unit. q locations where nearby external air may enter the room directly. This may cause sweating on the air discharge ports, causing them to spray or drip. q locations where the remote controller will be splashed with water or affected by dampness or humidity. q installing the remote controller behind curtains or furniture.

NOTE NOTE
The rear of the indoor unit can be installed flush against the wall.
Air discharge

30 cm min.

Air intake

Side view
0020_T_I

2-Way, 4-Way Semi-Concealed Type

DO: q select an appropriate position from which every corner of the room can be uniformly cooled. q select a location where the ceiling is strong enough to support the weight of the unit.
1m 1m

1m 1m 1m

2 1

q select a location where tubing and drain pipe have the shortest run to the outside. q allow room for operation and maintenance as well as unrestricted air flow around the unit. q install the unit within the maximum elevation difference (H) above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 1-1. q allow room for mounting the remote controller about 1 m off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit. NOTE Air delivery will be degraded if the distance from the floor to the ceiling is greater than 3 m.

0021_X_I

1-Way Semi-Concealed Type


Ceiling

1 m min.

5 cm min. Wall

Obstacle Air discharge

Air intake 5 cm min.

Wall

0022_AS_I

Wall-Mounted Type

15 cm min

15 cm min. 15 cm min

5
0023_K_I

Front View

I - 100

SM830080

1. Specifications

1-11 Installation Instructions


Selecting the Installation Site
Exhaust fan

Outdoor Unit AVOID: q heat sources, exhaust fans, etc. (Fig. 1-3) q damp, humid or uneven locations.

Hot air Heat source Outdoor unit

0591_C_I

DO: q choose a place as cool as possible. q choose a place that is well ventilated and outside air temperature does not exceed maximum 45 C constantly.

Fig. 1-3 Table 1-2 A Dimensions Model Min. (cm) 25 type 10 36, 48 type 20
Obstacle above

q allow enough room around the unit for air intake / Min. exhaust and possible maintenance. (Fig. 1-4) q provide a solid base; about 15 cm above ground level to reduce humidity and possible water damage in unit and decrease service life. (Fig. 1-5) q use lag bolts or equal to bolt down unit, reducing vibration and noise.

1 cm

Min. 1 cm
Min. 2m Air discharge
1548_C_I

Min. 2m

Min.50 cm

Obstacle

Ground

In case of multiple installations


Unit spacing if air discharge chamber is not used. Min. 1m Min. 1.5m Min. 1m

Fig. 1-4
Unit spacing when air discharge chamber is used. Min. 1m Min. 20cm Min. 1m Air discharge chamber

0486_C_I

Min. 30cm

Min. 35cm

Min. 3.5m Min. 35cm Min. 20cm If you would like to make the separation smaller on the air discharge side, use an air discharge chamber. You can install any number of units side-by -side. Min. 30cm Only up to 3 units can be installed side-by-side under the above conditions. The next group must be spaced at least 30 cm away from the first group.
0424_C_I

Min. 30cm

q provide a solid base (concrete block, 10 40 cm beams or equal), a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 1-5) q use lug bolts or equal to bolt down unit, reducing vibration and noise.

Air in Air in

Air discharge

Anchor bolts (4 pieces)

5
Min. 15cm

Fig. 1-5 I - 101

0425_C_I

SM830080

1. Specifications

1-11 Installation Instructions


Selecting the Installation Site
s Air Discharge Chamber for Top Discharge

Air discharge

Be sure to install the air discharge chamber in the filed when: q it is difficult to keep a space of min. 50 cm between the air discharge outlet and the obstacle. 0426_C_I q the air discharge outlet is facing to the sidewalk and Fig. 1-6 discharged hot air annoys the passers. In regions with snow fall, the outdoor unit should be provided with a platform and snow-proof duct. Refer to Fig. 1-6. s Installing the Unit in Heavy Snow Areas In positions with strong wind, snow-proof ducting should likewise be fitted and direct exposure to the wind should be avoided as much as possible. Countermeasures against snow and wind in regions with snow and strong wind, the following problems may occur when the outdoor unit is not provided with a platform and snow-proof ducting. a) b) c) d) The outdoor fan may not run and damage of the unit may be caused. There may be no air flow. The tubing may freeze and burst. The condenser pressure may drop because of strong wind, and the indoor unit may freeze.
Without snowproof ducting (Low platform) Without snowproof ducting (High platform)
0487_C_I

Fig. 1-7
Outdoor Unit

Fig. 1-8

s Precautions for Installation in Heavy Snow Areas

Duct Duct

2 1

(1) (2)

(3) (4)

The platform should be higher than the max. snow depth. (Fig. 1-7) The two fixing feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit. The platform foundation must be firmer and the unit must be secured with anchor bolts. In case of installation on a roof subject to strong wind, countermeasures must be taken to prevent the unit from being blown over.

Higher than the maximum snow depth

Air Intake

Air Intake Platform (foundation) About 1/2 of the unit height

Fig. 1-9
0488_C_I

s Dimensions of Snow / Wind-proof Ducting and Refrigerant Tubing Space for Installation

Example of Installation

Min. 100 Duct 300

5
Min. 100

Duct

Outdoor Unit

300

Unit: mm

0489_C_I

0490_C_I

I - 102

SM830080

1. Specifications

1-11 Installation Instructions


Selecting the Installation Site
s Wind Shield for EHL, EL Model Important It is recommended to install wind shields for cooling operation in low outdoor temperature condition. (Fig. 1-10) General When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air temperature in winter), wind shield must be installed on the outdoor unit. This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is exposed to strong wind, the system pressure drops because of the freeze protector. For outer dimensions of wind shield, please see Fig. 1-11.
567
3 6 - 0h ole

Wind shield (air discharge side)

Front

0935_C_I

Fig. 1-10

Recommended outer dimensions of wind shield (field supply)


0h ole

3
300 100

4 -

250

8-

ho

le

554
450

2
66h ole

250

1116

3
132

570 13

250

132

592

131
1545_C_I

554
1546_C_I

24

27

250

250

549

596

131

For 363, 483 type

For 253 type Fig. 1-11

5
I - 103
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Wiring
s General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. (3) To prevent possible hazards due to insulation failure, the unit must be grounded. (4) Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged. (5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. (6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes. (7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning. You must insure that installation complies with all relevant rules and regulations. (8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows: q The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring. q Use shielded wires for inter-unit control wiring between units and ground the shielded on both sides. (9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required.

s Recommended Wire Length and Wire Diameter for Power Supply System

* AWG = American Wire Gauge (1) Single Type (One indoor unit / one outdoor unit) Type SPW-CR253E(H)L8 (A) Power Supply (B) Inter-unit wiring Time Delay Power Supply Terminal Base Fuse or Capacity Max. Wire Circuit 2 2 4 mm 2.5 mm Diameter Capacity 97 m 60 m 54 m 17 m 50 m 50 m 50 m 50 m 15 A 20 A 25 A 40 A 25 A 25 A 25 A 50 A 5.5 mm2 (AWG#10) 5.5 mm2 (AWG#10) 5.5 mm2 (AWG#10) 14 mm2 (AWG#10)

2 1

R407C SPW-CR363E(H)L8 models SPW-CR483E(H)L8 SPW-CR253E(H)L5

5
I - 104
SM830080

1. Specifications

1-11 Installation Instructions


s Electrical Wiring
Indoor Unit Type X, S, AS, T, U, SL K D Control Wiring (C) Inter-Unit Control Wiring 0.75 mm2 (AWG#18) Use Shielded Wiring Max. 1000 m (D) Remote Control Wiring 0.75 mm2 (AWG#18) Max. 500 m (E) Control Wiring For Group Control 0.75 mm2 (AWG#18) Max. 500 m (F) Power Supply 2.5 mm2 245 m 588 m 89 m
Time Delay Power Supply Terminal Base Fuse or Capacity Max. Wire Circuit Diameter Capacity

15 A 15 A 15 A

50 A 25 A 50 A

14 mm2 (AWG#6) 5.5 mm2 (AWG#10) 14 mm2 (AWG#6)

1)

NOTE Refer to the Wiring System Diagrams (Ref. next page) for the meaning of A, B, C, D, E, and F in the above tables. Inter-Unit Control Wiring (c) has no polarity. But for other wiring, respect polarity. Be sure to connect as shown in the Wiring System Diagram. The basic connection diagram of the indoor unit shows the 8P terminal board, so the terminal boards in your equipment may differ from the diagram. In accordance with conformity of EC Directive No. 89/336/EEC, when connecting power supply, it should be considered guidance showing below. * * Do not share a common installation group with other equipment. Be sure that supply network impedance is sufficiently low ( ZSYS R). It may be necessary to consult the power supply authority before connection of the air conditioner to a low-voltage public network.
8P terminal board
5P terminal board + 3P terminal board

2)

1
1 2 U1 U2 R1 R2 R3
1 2 3 4 5

3)

1(L)2(N) Power supply

R1 R2 R3 Remote U1 U2 controller Inter-unit control wiring


0511_M_I

1(L)2(N) 4 5 1 2 3 Power Inter-unit Remote supply control wiring controller


0512_M_I

Only for K type

4)

I I[

R407C Models Models R Remarks 25 type (3 phase) Not necessary to consider supply network impedance 36 type (3 phase) 0.192 Conforms to the local code 48 type (3 phase) 0.167 Ditto 25 type (1 phase) 0.126 Ditto

5
I - 105
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Wiring
q Wiring System Diagrams (1) Basic wiring diagram for standard control 1 Single type (one indoor unit) 1-1. 3-phase outdoor unit
Indoor Unit B Inter-unit power wiring (Line voltage) 1 2 Ground Inter-unit control wiring (Low voltage) RED WHT BLK 1 2 3 1 2 3 D A Ground
0499_M_I

Outdoor Unit 1 2
0 R.C. Address on the PCB: 0 (S2, BLK) (0: Factory shipped state)

U1 U2 R1 R2 R3 C

1 2

4 L1 L2 L3 N
L1 L2 L3 N Power supply 380 - 415 V - 3 N 50 Hz

Remote controller (Option)

1-2. Single-phase outdoor unit


Indoor Unit B Outdoor Unit 1 2 Ground Inter-unit control wiring (Low voltage) U1 U2 R1 R2 R3 Ground A
0500_M_I

Inter-unit power wiring (Line voltage)

1 2

R.C. Address on the PCB: 0 (S2, BLK) (0: Factory shipped state)

1 2 C

4 L N
L N Power supply 220 - 240 V 50 Hz

2 1

RED WHT BLK

1 2 3

1 2 3

Remote controller D

2 Use shielded wires for inter-unit control wiring (c) and ground the shielded on both sides.

Shielded wire

0160_M_I

5
I - 106
SM830080

1. Specifications

1-11 Installation Instructions


s Electrical Characteristics
Indoor Unit : SPW-XR253GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 130 / 150 1/1 0.13 / 0.15 1/1 2.8 / 2.88 67 / 73 3.06 / 3.18 69 / 75 130 / 150 0.6 / 0.63 0.13 / 0.15 0.62 / 0.65 2.55 / 2.7 13.44 / 13.48 2.81 / 3.0 14.66 / 14.76 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 12.1 / 12.3 13.32 / 13.58

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5

220 - 240 V / 1 phase / 50 Hz 0.6 / 0.63 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 80 / 100 1/1 0.13 / 0.15 1/1 3.25 / 3.29 67 / 73 3.46 / 3.54 69 / 75 80 / 100 0.37 / 0.42 0.13 / 0.15 0.62 / 0.65 2.86 / 2.96 15.6 / 15.2 3.07 / 3.21 16.59 / 16.27 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 13.7 / 13.5 14.69 / 14.57

220 - 240 V / 1 phase / 50 Hz 0.37 / 0.42 0.62 / 0.65

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 107
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-XR253GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 130 / 150 1/1 0.13 / 0.15 1/1 2.98 / 3.02 25 / 28 3.24 / 3.32 27 / 30 130 / 150 0.6 / 0.63 0.13 / 0.15 0.62 / 0.65 2.5 / 2.52 5.3 / 5.32 2.76 / 2.82 5.67 / 5.69 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 4.45 / 4.35 4.82 / 4.73

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8

220 - 240 V / 1 phase / 50 Hz 0.6 / 0.63 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 5 / 4.8 2.79 / 2.81 5.1 / 4.9 2.87 / 2.89 25 / 28 5.31 / 5.12 3 / 3.06 5.41 / 5.22 3.08 / 3.14 27 / 30

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 0.37 / 0.42 80 / 100 0.37 / 0.42 80 / 100 1/1 0.62 / 0.65 0.13 / 0.15 0.62 / 0.65 0.13 / 0.15 1/1

2 1

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 108
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-XR363GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 200 / 220 2/2 0.26 / 0.29 3/3 3.98 / 4.02 42 / 45 4.44 / 4.53 47 / 50 200 / 220 0.92 / 0.93 0.26 / 0.29 1.24 / 1.31 3.46 / 3.51 7.2 / 7.24 3.92 / 4.02 7.86 / 7.9 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 6.35 / 6.39 7.01 / 7.05

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8

220 - 240 V / 1 phase / 50 Hz 0.92 / 0.93 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 140 / 160 2/2 0.26 / 0.29 3/3 4.08 / 7.12 42 / 45 4.48 / 4.57 47 / 50 140 / 160 0.65 / 0.68 0.26 / 0.29 1.24 / 1.31 3.86 / 3.88 7.4 / 7.44 4.26 / 4.33 7.98 / 8.04 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7 / 7.04 7.58 / 7.64

220 - 240 V / 1 phase / 50 Hz 0.65 / 0.68 1.24 / 1.31

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 109
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-XR483GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 200 / 220 2/2 0.26 / 0.29 3/3 5 / 5.04 48 / 53 5.46 / 5.55 53 / 58 200 / 220 0.92 / 0.93 0.26 / 0.29 1.24 / 1.31 4.14 / 4.16 8.8 / 8.82 4.6 / 4.67 9.47 / 9.49 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7.7 / 7.72 8.35 / 8.37

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8

220 - 240 V / 1 phase / 50 Hz 0.92 / 0.93 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 8.89 / 8.91 5.06 / 5.08 9.4 / 9.41 5.38 / 5.42 48 / 53 9.48 / 9.52 5.46 / 5.53 9.99 / 10.02 5.78 / 5.87 53 / 58

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 0.65 / 0.68 140 / 160 0.65 / 0.68 140 / 160 2/2 1.24 / 1.31 0.26 / 0.29 1.24 / 1.31 0.26 / 0.29 3/3

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 110
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-TR253GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 90 / 100 1/1 0.13 / 0.15 1/1 2.8 / 2.88 67 / 73 3.02 / 3.13 69 / 75 90 / 100 0.43 / 0.43 0.13 / 0.15 0.62 / 0.65 2.55 / 2.7 13.44 / 13.48 2.77 / 2.95 14.49 / 14.56 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 12.1 / 12.3 13.15 / 13.38

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5

220 - 240 V / 1 phase / 50 Hz 0.43 / 0.43 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 70 / 80 1/1 0.13 / 0.15 1/1 3.25 / 3.29 67 / 73 3.45 / 3.52 69 / 75 70 / 80 0.33 / 0.34 0.13 / 0.15 0.62 / 0.65 2.86 / 2.96 15.6 / 15.2 3.06 / 3.19 16.55 / 16.19 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 13.7 / 13.5 14.65 / 14.49

220 - 240 V / 1 phase / 50 Hz 0.33 / 0.34 0.62 / 0.65

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 111
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-TR253GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 90 / 100 1/1 0.13 / 0.15 1/1 2.98 / 3.02 25 / 28 3.2 / 3.27 27 / 30 90 / 100 0.43 / 0.43 0.13 / 0.15 0.62 / 0.65 2.5 / 2.52 5.3 / 5.32 2.72 / 2.77 5.62 / 5.64 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 4.45 / 4.35 4.77 / 4.67

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8

220 - 240 V / 1 phase / 50 Hz 0.43 / 0.43 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 5 / 4.8 2.79 / 2.81 5.1 / 4.9 2.87 / 2.89 25 / 28 5.29 / 5.1 2.99 / 3.04 5.39 / 5.2 3.07 / 3.12 27 / 30

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 0.33 / 0.34 70 / 80 0.33 / 0.34 70 / 80 1/1 0.62 / 0.65 0.13 / 0.15 0.62 / 0.65 0.13 / 0.15 1/1

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 112
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-TR363GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 200 / 220 2/2 0.26 / 0.29 3/3 3.98 / 4.02 42 / 45 4.44 / 4.53 47 / 50 200 / 220 0.95 / 0.98 0.26 / 0.29 1.24 / 1.31 3.46 / 3.51 7.2 / 7.24 3.92 / 4.02 7.86 / 7.91 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 6.35 / 6.39 7.01 / 7.06

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8

220 - 240 V / 1 phase / 50 Hz 0.95 / 0.98 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 180 / 200 2/2 0.26 / 0.29 3/3 4.08 / 7.12 42 / 45 4.52 / 4.61 47 / 50 180 / 200 0.86 / 0.9 0.26 / 0.29 1.24 / 1.31 3.86 / 3.88 7.4 / 7.44 4.3 / 4.37 8.04 / 8.09 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7 / 7.04 7.64 / 7.68

220 - 240 V / 1 phase / 50 Hz 0.86 / 0.9 1.24 / 1.31

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 113
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-TR483GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 200 / 220 2/2 0.26 / 0.29 3/3 5 / 5.04 48 / 53 5.46 / 5.55 53 / 58 200 / 220 0.95 / 0.98 0.26 / 0.29 1.24 / 1.31 4.14 / 4.16 8.8 / 8.82 4.6 / 4.67 9.47 / 9.5 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7.7 / 7.72 8.35 / 8.38

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8

220 - 240 V / 1 phase / 50 Hz 0.95 / 0.98 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 8.89 / 8.91 5.06 / 5.08 9.4 / 9.41 5.38 / 5.42 48 / 53 9.54 / 9.56 5.5 / 5.57 10.05 / 10.07 5.82 / 5.91 53 / 58

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 0.86 / 0.9 180 / 200 0.86 / 0.9 180 / 200 2/2 1.24 / 1.31 0.26 / 0.29 1.24 / 1.31 0.26 / 0.29 3/3

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 114
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-UR253GHN56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 180 / 210 1/1 0.13 / 0.15 1/1 2.8 / 2.88 67 / 73 3.11 / 3.24 69 / 75 180 / 210 0.84 / 0.9 0.13 / 0.15 0.62 / 0.65 2.55 / 2.7 13.44 / 13.48 2.86 / 3.06 14.9 / 15.03 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 12.1 / 12.3 13.56 / 13.85

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5

220 - 240 V / 1 phase / 50 Hz 0.84 / 0.9 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 180 / 210 1/1 0.13 / 0.15 1/1 3.25 / 3.29 67 / 73 3.56 / 3.65 69 / 75 180 / 210 0.84 / 0.9 0.13 / 0.15 0.62 / 0.65 2.86 / 2.96 15.6 / 15.2 3.17 / 3.32 17.06 / 16.75 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 13.7 / 13.5 15.16 / 15.05

220 - 240 V / 1 phase / 50 Hz 0.84 / 0.9 0.62 / 0.65

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 115
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-UR253GHN56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 180 / 210 1/1 0.13 / 0.15 1/1 2.98 / 3.02 25 / 28 3.29 / 3.38 27 / 30 180 / 210 0.84 / 0.9 0.13 / 0.15 0.62 / 0.65 2.5 / 2.52 5.3 / 5.32 2.81 / 2.88 5.74 / 5.76 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 4.45 / 4.35 4.89 / 4.8

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8

220 - 240 V / 1 phase / 50 Hz 0.84 / 0.9 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 5 / 4.8 2.79 / 2.81 5.1 / 4.9 2.87 / 2.89 25 / 28 5.44 / 5.25 3.1 / 3.17 5.54 / 5.35 3.18 / 3.25 27 / 30

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 0.84 / 0.9 180 / 210 0.84 / 0.9 180 / 210 1/1 0.62 / 0.65 0.13 / 0.15 0.62 / 0.65 0.13 / 0.15 1/1

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 116
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-UR363GHN56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 290 / 340 2/2 0.26 / 0.29 3/3 3.98 / 4.02 42 / 45 4.53 / 4.65 47 / 50 290 / 340 1.43 / 1.54 0.26 / 0.29 1.24 / 1.31 3.46 / 3.51 7.2 / 7.24 4.01 / 4.14 7.99 / 8.05 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 6.35 / 6.39 7.13 / 7.19

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8

220 - 240 V / 1 phase / 50 Hz 1.43 / 1.54 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 290 / 340 2/2 0.26 / 0.29 3/3 4.08 / 7.12 42 / 45 4.63 / 4.75 47 / 50 290 / 340 1.43 / 1.54 0.26 / 0.29 1.24 / 1.31 3.86 / 3.88 7.4 / 7.44 4.41 / 4.51 8.19 / 8.25 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7 / 7.04 7.79 / 7.84

220 - 240 V / 1 phase / 50 Hz 1.43 / 1.54 1.24 / 1.31

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 117
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-UR483GHN56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 310 / 360 2/2 0.26 / 0.29 3/3 5 / 5.04 48 / 53 5.57 / 5.69 53 / 58 310 / 360 1.48 / 1.58 0.26 / 0.29 1.24 / 1.31 4.14 / 4.16 8.8 / 8.82 4.71 / 4.81 9.62 / 9.66 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7.7 / 7.72 8.5 / 8.53

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8

220 - 240 V / 1 phase / 50 Hz 1.48 / 1.58 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 8.89 / 8.91 5.06 / 5.08 9.4 / 9.41 5.38 / 5.42 48 / 53 9.71 / 9.75 5.63 / 5.73 10.23 / 10.25 5.95 / 6.07 53 / 58

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 1.48 / 1.58 310 / 360 1.48 / 1.58 310 / 360 2/2 1.24 / 1.31 0.26 / 0.29 1.24 / 1.31 0.26 / 0.29 3/3

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 118
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-DR253GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 480 / 530 3/3 0.13 / 0.15 1/1 2.8 / 2.88 67 / 73 3.41 / 3.56 71 / 77 480 / 530 2.29 / 2.31 0.13 / 0.15 0.62 / 0.65 2.55 / 2.7 13.44 / 13.48 3.16 / 3.38 16.35 / 16.44 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 12.1 / 12.3 15.01 / 15.26

Outdoor Unit : SPW-CR253EHL5 SPW-CR253EL5

220 - 240 V / 1 phase / 50 Hz 2.29 / 2.31 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 480 / 530 3/3 0.13 / 0.15 1/1 3.25 / 3.29 67 / 73 3.86 / 3.97 71 / 77 480 / 530 2.29 / 2.31 0.13 / 0.15 0.62 / 0.65 2.86 / 2.96 15.6 / 15.2 3.47 / 3.64 18.51 / 18.16 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 1 phase / 50 Hz 13.7 / 13.5 16.61 / 16.46

220 - 240 V / 1 phase / 50 Hz 2.29 / 2.31 0.62 / 0.65

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 119
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-DR253GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 480 / 530 3/3 0.13 / 0.15 1/1 2.98 / 3.02 25 / 28 3.59 / 3.7 29 / 32 480 / 530 2.29 / 2.31 0.13 / 0.15 0.62 / 0.65 2.5 / 2.52 5.3 / 5.32 3.11 / 3.2 6.15 / 6.14 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 4.45 / 4.35 5.3 / 5.19

Outdoor Unit : SPW-CR253EHL8 SPW-CR253EL8

220 - 240 V / 1 phase / 50 Hz 2.29 / 2.31 0.62 / 0.65

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 5 / 4.8 2.79 / 2.81 5.1 / 4.9 2.87 / 2.89 25 / 28 5.85 / 5.64 3.4 / 3.49 5.95 / 5.74 3.48 / 3.57 29 / 32

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 2.29 / 2.31 480 / 530 2.29 / 2.31 480 / 530 3/3 0.62 / 0.65 0.13 / 0.15 0.62 / 0.65 0.13 / 0.15 1/1

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 120
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-DR363GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 520 / 570 4/4 0.26 / 0.29 3/3 3.98 / 4.02 42 / 45 4.76 / 4.88 49 / 52 520 / 570 2.46 / 2.47 0.26 / 0.29 1.24 / 1.31 3.46 / 3.51 7.2 / 7.24 4.24 / 4.37 8.29 / 8.31 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 6.35 / 6.39 7.43 / 7.45

Outdoor Unit : SPW-CR363EHL8 SPW-CR363EL8

220 - 240 V / 1 phase / 50 Hz 2.46 / 2.47 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 520 / 570 4/4 0.26 / 0.29 3/3 4.08 / 7.12 42 / 45 4.86 / 4.98 49 / 52 520 / 570 2.46 / 2.47 0.26 / 0.29 1.24 / 1.31 3.86 / 3.88 7.4 / 7.44 4.64 / 4.74 8.49 / 8.51 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7 / 7.04 8.09 / 8.1

220 - 240 V / 1 phase / 50 Hz 2.46 / 2.47 1.24 / 1.31

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 121
SM830080

1. Specifications

1-11 Installation Instructions


Electrical Characteristics
Indoor Unit : SPW-DR483GH56 q Cooling
Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 600 / 710 4/4 0.26 / 0.29 3/3 5 / 5.04 48 / 53 5.86 / 6.04 55 / 60 600 / 710 2.8 / 3 0.26 / 0.29 1.24 / 1.31 4.14 / 4.16 8.8 / 8.82 5 / 5.16 10.02 / 10.06 Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 7.7 / 7.72 8.87 / 8.92

Outdoor Unit : SPW-CR483EHL8 SPW-CR483EL8

220 - 240 V / 1 phase / 50 Hz 2.8 / 3 1.24 / 1.31

q Heating (Heat pump only)


Indoor Unit Fan Motor Outdoor Unit Complete Unit Fan Motor Compressor 380 - 415 V / 3 phase / 50 Hz 8.89 / 8.91 5.06 / 5.08 9.4 / 9.41 5.38 / 5.42 48 / 53 10.11 / 10.15 5.92 / 6.08 10.62 / 10.66 6.24 / 6.42 55 / 60

Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

220 - 240 V / 1 phase / 50 Hz 2.8 / 3 600 / 710 2.8 / 3 600 / 710 4/4 1.24 / 1.31 0.26 / 0.29 1.24 / 1.31 0.26 / 0.29 3/3

2 1

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Cooling: Rating Conditions

27C DB / 19C WB 35C DB 35C DB / 23C WB 43C DB 20C DB 7C DB / 6C WB 24C DB 21C DB / 15.5C WB

5
I - 122
SM830080

2. Processes and functions

2. PROCESSES AND FUNCTIONS


2-1 Room Temperature Control ......................................................................II - 2 (A) Cooling ................................................................................................II - 2 (B) Heating ................................................................................................II - 3 Cold Draft Prevention (Heating Cycle) ......................................................II - 4 Automatic Fan Speed (Indoor Unit) ..........................................................II - 5 (A) Cooling ................................................................................................II - 5 (B) Heating ................................................................................................II - 5 Outdoor Fan Speed Control ......................................................................II - 6 (A) Cooling ................................................................................................II - 6 (B) Heating ................................................................................................II - 6 Freeze Prevention (Cooling) .....................................................................II - 7 Condensing Temperature Control (Cooling) .............................................II - 8 Overload Protection (Heating) ..................................................................II - 9 Discharge Temperature Control (Cooling and Heating) ........................... II - 10 Auto. Mode for Automatic Heating/Cooling Switching ..............................II - 11 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) ....................II - 12 4-Way Valve, Solenoid Control .................................................................II - 13 (A) Normal Control Mode ..........................................................................II - 13 (B) AUTO Control Mode ............................................................................II - 14 Automatic Restart after Power Interruption ...............................................II - 14 Electronic Expansion Control Valve ..........................................................II - 15 Compressor Discharge Gas Temperature ................................................II - 15 (A) Cooling ................................................................................................II - 15 (B) Heating (Except During Defrosting) .....................................................II - 15 Compressor Current Detection Circuit ......................................................II - 16 Dehumidifying Operation ..........................................................................II - 17 Auto-flap Control .......................................................................................II - 18 Controlled by Electronic Expansion Valve ................................................II - 19 Voltage Detection Control .........................................................................II - 20

2-2 2-3

2-4

2-5 2-6 2-7 2-8 2-9 2-10 2-11

2-12 2-13 2-14

2-15 2-16 2-17 2-18 2-19

5
II - 1
SM830080

2. Processes and functions

2-1 Room Temperature Control


The unit adjusts room temperature by turning the outdoor units compressor ON and OFF. This process is controlled by the thermostat located in the indoor unit. The figures on this and the next page show how each part of the system performs as the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 1 shows about the cooling cycle, and Fig. 2 shows about the heating cycle.

(A) Cooling
(THERMO. OFF) THERMO. OFF (THERMO. ON) BODY SENSOR T+1C SET TEMP. TC T1C MORE THAN 5 MINUTES 3 MINUTES COMPRESSOR 1 OUTDOOR FAN (H, M or L) INDOOR FAN ON OFF MORE THAN 3 MINUTES OFF MORE THAN 5 MINUTES ON ROOM TEMP. THERMO. ON

5 MINUTES ON

ON

OFF

ON

OFF

ON

SET SPEED

DRAIN PUMP

ON

OFF

ON

OFF

ON

2 1

DEW PROOF HEATER

ON

OFF

ON

OFF

ON
1573_X_S

1. Refer to 2-4 Outdoor Fan Speed Control

Fig. 1

Chart Summary and Explanations


u u u u Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode (HEAT, DRY, COOL, or FAN) during the cooling cycle, the control circuit stops the compressor for 3 minutes. For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off, the compressor is not controlled by the room sensor. Thermo ON: When room temperature rises 1C (2C when set on body sensor) above the set temperature T, (T+1C or T+2C when set on body sensor): Compressor u ON

Thermo OFF: When the room temperature is 1C below the set temperature T: Compressor OFF

II - 2

SM830080

2. Processes and functions

(B) Heating
REMOTE CONTROL SENSOR (Only for wireless remote controller) SET. +1C SETTING TEMP. SET. 1C

THERMO. ON THERMO. OFF

THERMO. ON THERMO. OFF THERMO. ON

THERMO. OFF BODY SENSOR +1C SET TEMP.+4C SHIFT 1C SET TEMP. MORE THAN 5 MINUTES ON THERMO. ON THERMO. ON

THERMO. OFF THERMO. ON

5 MINUTES COMPRESSOR 1 OUTDOOR FAN (H, M or L) 2 INDOOR FAN 2 STANDBY OFF ON

3 MINUTES OFF

MORE THAN 3 MINUTES OFF ON

OFF

ON 3 SECONDS

OFF

ON

OFF

ON

OFF

L LL L

SET SPEED

LL

SET SPEED

LL

SET SPEED

OFF

ON

OFF

ON

OFF

ON

OFF

(31C) INDOOR HEAT EXCH. COIL 27C TEMP. 25C E2 SOLENOID COIL (4-WAY) TEMP. OPERATION OFF BUTTON

ON (REVERSING CYCLE)

2
ON
1574_X_S

1. Refer to 2-4 Outdoor Fan Speed Control 2. Refer to 2-2 Cold Draft Prevention (Heating)

Chart Summary and Explanations


u u u u Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode (HEAT, DRY, COOL or FAN) during the heating cycle, the control circuit stops the compressor for 3 minutes. For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off, the compressor is not controlled by the room sensor.

Fig. 2

When set on remote control sensor Thermo ON: When room temperature is 1C below the set temperature T. Compressor ON Thermo OFF: When the room temperature is 1C above the set temperature T, (T+1C) Compressor OFF When set on body sensor NOTE: In case of Body sensor, operating temperature is shifted to setting temperature +4C .

5
SM830080

II - 3

2. Processes and functions

2-2 Cold Draft Prevention (Heating Cycle)


The cold draft prevention function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coils have warmed up. u STANDBY shows on the remote controller when the indoor fan speed is LL (very low) or OFF. This condition occurs in the following 3 cases: During Thermo OFF (refer to 2-1 B). Room Temperature Control, Heating) During the defrosting operation (refer to 2-10 Defrosting Control, Heating) Until either the coil temperature E2 reaches 27C or when a maximum of 6 minutes has past. The indoor fan motor operates in L instead of LL for 3 seconds as it starts to give the fan an initial boost.

33 MAX. 6 MINUTES 31 INDOOR UNIT COIL TEMP. E2 (C)

27

25

10

2 1

SET FAN SPEED

AUTO OR H M L

LL LL LL

LL/OFF LL/OFF LL/OFF

LL LL LL

L L L

M M L

H M L

STANDBY INDICATOR

STANDBY APPEARS LL= Very low speed L= Low speed M= Medium speed H= High speed

0673_X_S

Fig. 3 Chart Summary and Explanations

u u u

The main idea of this chart is to show that the indoor fan speed increases and gets closer to the set fan speed as the coil temperature E2 rises. The indoor units coil temperature is taken from sensor E2 located in the middle of the indoor heat exchange coil. The dotted line shows that the indoor fan motor is OFF. When the temperature at sensor E2 falls below 10C, the indoor fan motor stops running.

5
II - 4
SM830080

2. Processes and functions

2-3 Automatic Fan Speed (Indoor Unit)


By pressing the FAN SPEED button on the remote controller, the fan speed can be set at one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed will be automatically adjusted to the room temperature as the two charts shown below. (A) Cooling
ROOM TEMP. (deg) +3 +2 +1 SET TEMP.

INDOOR FAN SPEED

H : High L : Low M : Middle LL: Very low


0433_M_S

Fig. 4 Chart Explanations and notes


u When the fan speed changes, it keeps the speed step for at least 3 minutes, even if the temperature changes to another speed step during the time.

(B) Heating

2
ROOM TEMP. (deg) SET TEMP. 2 4

INDOOR FAN SPEED H : High L : Low M : Middle LL: Very low

4
0434_M_S

Fig. 5 Chart Explanations and notes


u When the fan speed changes, it keeps the speed step for at least 1 minute, even if the temperature changes to another speed step during the time.

5
SM830080

II - 5

2. Processes and functions

2-4 Outdoor Fan Speed Control


To optimize performance in air conditioner, the outdoor fan speed is selected automatically according to the outdoor temperature. u Note that in both Cooling and Heating modes, the fan comes on at first at high speed (H mode) for 5 seconds. Since outdoor conditions sometimes make it difficult for the fan to start, this sudden surge of power may be necessary. The outdoor fan operates in H mode for 3 minutes after the compressor stops (excluding defrosting operation period). Charts below show how the outdoor fan speed changes with the change in outdoor temperature. Cooling
*Outdoor Air temperature 25C or more less than 25C Outdoor fan motor (FMo) H M
OUTDOOR AIR TEMPERATURE (C)

(A)

25 M 19 L

less than 19C L * This is supposed to be coil temp [C2] when operating outdoor fan without running comp.

2 1
(B) Heating
Outdoor coil temperature [C2] 14C or more less than 14C Outdoor fan motor (FMo) M H
OUTDOOR COIL TEMPERATURE (C)

Fig. 6

14

Fig. 7

5
II - 6
SM830080

2. Processes and functions

2-5 Freeze Prevention (Cooling)


Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost build up on the coil blocks cool air circulation from the indoor unit's fan.

MIN. VALUE OF EITHER E1 OR E2 INDOOR UNIT COIL TEMP. 3 1 0.5 0 0.5 (C) ELECTRONIC EXPANSION VALVE SIGNAL COMPRESSOR CONTINUOUS DETECTION FOR 2 MINUTES OPEN (+60 step/30 sec) OPEN (+60 step/30 sec) MINIMUM 3 MINUTES L M

ON

ON

FMI CONTROL

1
1563_M_S

Fig. 8

Note: Freeze prevention is controlled by the temperature at the indoor heat exchanger coil as sensed by either sensor E1 (located at the entrance of the coil) or sensor E2 (located on the middle of the coil). Freeze prevention cycle is controlled by the lower temperature sensed at either of the two sensors.
Chart Explanations and notes
u u This chart shows when the electronic expansion valve opens to regulate the temperature of the indoor unit coil to prevent freezing. If the refrigerant control is not effective and the temperature continues to drop and stays below 0C for 2 minutes continuously, the control circuit stops the compressor. The compressor does not start again until the temperature rises above 1C. The compressor stops for 3 minutes minimum.

Note: When low fan speed is selected and the air conditioner is in cooling operation at a low outdoor temperature of less than 10C, the air conditioner may automatically switch to medium fan speed. Cut the jumper wire (JP11) on the outdoor P.C.B. when the above FMI control (LM) is not needed.

5
II - 7
SM830080

2. Processes and functions

2-6 Condensing Temperature Control (Cooling)


Condensing temperature is controlled by the outdoor heat exchanger coil temperature as sensed by sensor C2.
(C) 60 57

C2

40

FMO H, L or LL ELECTRONIC CONTROL VALVE H or L

LL

+50 step /30 sec

+50 step /30 sec


1906_M_I

Fig. 9

Chart Explanations and notes

u u u

This chart shows how the outdoor fan speed and the electronic refrigerant control valve react to coil temperature to control condensing temperature. Sensor C2 is located in the middle of the outdoor unit heat exchange coil. When C2 rises above 60C the electronic control valve opens 50steps / 30 seconds, and the outdoor for speed increases by one step. The outdoor fan speed doese not change for 5 minits. When C2 falls below 40C, the outdoor fan speed decreases by one step.

2 1

5
II - 8
SM830080

2. Processes and functions

2-7 Overload Protection (Heating)


This function prevents the air conditioner from overloading.

(C) 64 61 INDOOR UNIT COIL TEMP. (E2) 60 59 55 53 OVERLOAD PROTECTION FUZZY CONTROL

OVERLOAD PROTECTION FUZZY CONTROL

ELECTRONIC EXPANSION VALVE

OPEN

OPEN START UP COMPENSATION OFF

OUTDOOR FM

H or M

H or M
1565_M_S

Fig. 10 Chart Explanations and notes


u u u u u This chart shows how the outdoor fan speed and the electronic refrigerant control valve react to coil temperature to keep the indoor heat exchanger coil from overloading. When sensor E2 rises above 60C the electronic refrigerant control valve opens at 50 steps/ 30 seconds until E2 falls below 59C. Sensor E2 is located in the middle of the indoor unit heat exchange unit. When sensor E2 rises above 62C, the control circuit stops the outdoor fan motor till the temp. drops to 55C Fuzzy control controls the electronic refrigerant control valve.

5
II - 9
SM830080

2. Processes and functions

2-8 Discharge Temperature Control (Cooling and Heating)


This function prevents the compressor motor from burn out by overheating.
115 105 95 93 DISCHARGE GAS TEMP. (C) 90 85

OUTDOOR FAN SPEED COMPRESSOR ELECTRONIC EXPANSION VALVE (DISCHARGE TEMP.)

H or M

L ON OPEN

H or M

OPEN TRIP IS OPERATED.

1
Chart Summary and Explanations
u u Discharge temperature is sensed by TH8 (discharge gas sensor).

1566_M_S

Fig. 11

When the temperature rises above 95C the electronic refrigerant control valve opens at 50 steps/30 seconds until the temperature falls below 93C. During HEATING operation, when the temperature rises above 105C, the control circuit stops the outdoor fan motor until the temperature falls below 90C. Please note that this control does not function during COOLING operation. For both COOLING and HEATING modes, if the temperature reaches 115C (135C for 48 type) the operation shuts down and alarm P3 appears on the remote controller. The outdoor fan speed is controlled on discharge temp. at heating mode.

2 1

u u

3
2-9 Auto. Mode for Automatic Heating/Cooling Switching

When the AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to the COOLING or HEATING mode to maintain the desired temperature. Room temp. ] Set temp. COOLING Room temp. < Set temp. HEATING This means that if the room temperature is higher or equal to the set temperature, COOLING operation starts. If the room temperature is lower than the set temperature, HEATING operation starts.
II - 10
SM830080

2. Processes and functions

2-9 Auto. Mode for Automatic Heating/Cooling Switching

A COOLING SELECTION TEMP. +2.5 deg SHIFT SET TEMP. +2 deg

REMOTE CONTROLLED SET TEMP.

SHIFT SET TEMP. 2 deg HEATING SELECTION TEMP. 3 deg C

HEATING

COOLING

HEATING
0440_M_S

Fig. 12

Chart summary and Explanations


u This chart shows how the Operation Mode (COOLING or HEATING) is determined by the microprocessor taking the room temperature into consideration. It also shows the temperature points at which the cooling or heating mode is switched, when the AUTO mode is selected. After operation starts, the set temperature shifts automatically by +2 deg. at cooling and by 2 deg. at heating. For example, if cooling is selected, the set temperature changes from 20 C to 22 C. (The display of the remote controller remains 20 C.) The change of the operation mode (heating to cooling, cooling to heating) by the change of the room temperature during the operation is as follows. Heating to Cooling; Room temp. Shifted temp + 0.5 deg. Cooling to Heating; Room temp. Shifted temp -1.0deg. For example, if the room temperature rises above 22.5 C (=22+0.5) during the cooling operation at the room temperature 20 C set by the remote controller, the operation changes to cooling. When the room temperature lowers below 17 C (=18-1.0) thereafter, the operation changes to heating again. u In heating operation, using the body sensor, room temperature control is designed so that room air temp. is sensed as 4 deg. lower than suctioned air at indoor unit taking into account of the temperature gap between upper part and lower part of the room. Within 10 minutes after the compressor turns OFF, the operation does not change to cooling (heating), even when the room temperature changes from C to A (A to C). When switching from cooling (heating) to heating (cooling), the actuation of the 4 way valve will delay about 30-50 seconds after the compressor turns ON.

u u

5
II - 11
SM830080

2. Processes and functions

2-10

Defrosting Control, Outdoor Heat Exchanger Coil (Heating)

When the outdoor temperature is low, frost may form on the outdoor heat exchanger coil. When this occurred, the defrosting system operates. The microprocessor in the outdoor unit monitors the relationship between the temperature of the outdoor heat exchanger coil and the outdoor temperature so it can defrost when necessary.
Flow of Defrosting OUTDOOR COIL TEMP. C1 (C) Y RELEASE OF DEFROSTING RANGE 10 OUTDOOR AIR TEMP. (C) 10 X -3 -8 Detecting the frost -20 Stand by time for defros: 25 minutes Either continuous 8 minutes or cumulative 60 minutes are required to detect frost in the Frosting range. The area below the heavy line is the frost detection area.

Heating operation

No counting time for detecting frost : 15 minutes

-13.7

Defrosting

Refer to time chart. *Minimum continuous operating time by defrosting is 48 minutes (= 15 + 8 + 25). Occurs either when the temperature of C1 (the outdoor heat exchanger coil) has reached 10C or above, or when the maximum defrosting time (9 minutes) has elapsed.
0441_M_S

Release of defrosting

Time Chart for Defrosting

Fig. 13
MAX. 9 MINUTES 1 MINUTE

2 1
COMPRESSOR

1 MINUTE

ON

ON

ON

SOLENOID COIL (4 WAY VALVE)

ON

ON

3
OUTDOOR FAN (H or M) ON ON INDOOR FAN (SET SPEED) OFF OR LL OFF OR LL

STANDBY INDICATOR Defrosting Start

STANDBY APPEARS Release of Defrosting

1575_M_S

Fig. 14

u u

During the defrost cycle, STANDBY appears on the remote controller. *......Cold Draft Prevention may operate occasionally

II - 12

SM830080

2. Processes and functions

2-11 4-Way Valve, Solenoid Control


The basic function of the 4-way valve is to direct the refrigerant in the correct direction according to the Operation Mode (COOLING or HEATING) selected. The following two charts show conditions of the controls and functions listed in the left hand column when the solenoid is ON or OFF. Chart (A) on this page shows the relationships when the temperature control is in NORMAL mode, and Chart (B) on the next page shows the relationships when the remote controller is set to AUTO mode. (A) Normal Control Mode

POWER SOURCE OFF

ON

OPERATION BUTTON

ON

OFF

ON

COOL MODE BUTTON HEAT

COOL HEAT 2 3 MINUTES TURN ON TURN OFF OFF ON THERMO OFF THERMO OFF THERMO THERMO ON ON OFF 2 1 1 ON OFF 2. . . More than 3 minutes 1 ON
0443_M_S

HEAT

COMPRESSOR

ON

ON

OFF 2

ON

SOLENOID COIL (4-WAY VALVE)

OFF

1. . . More than 5 minutes

Fig. 15

Chart Summary and Explanations


u u u For the first 3 minutes after power is applied, the 4way valve remains OFF and the compressor will not operate, even if the ON button is pushed. If the 4way valve is turned OFF with the compressor operating, the air conditioner operates in COOLING mode. See Table below. If the 4way valve is turned ON with the compressor operating, the air conditioner operates in HEATING mode. See Table below. Operation Mode COOLING HEATING 4-way valve solenoid OFF ON Compressor ON

5
II - 13
SM830080

2. Processes and functions

(B) AUTO Control Mode

POWER SOURCE OFF

ON

OPERATION BUTTON MORE THAN 10 MINUTES (THERMO. OFF) AUTO COOL MODE CONTROL HEAT

ON MORE THAN 10 MINUTES (THERMO. OFF)

COOL HEAT HEAT THERMO. OFF THERMO. ON 3 MINUTES MORE THAN 3 MINUTES OFF ON OFF ON OFF ON

COMPRESSOR

OFF

ON

MORE THAN 30 50 SECONDS SOLENOID COIL (4-WAY VALVE) OFF ON OFF

MORE THAN 30 50 SECONDS ON


0445_M_S

Fig. 16

When the Compressor has stopped while in AUTO mode, the 4-way valve switches on (heating) or off (cooling) within 1 minute according to the following conditions:

Compressor has stopped under the operation of AUTO mode condition.

2 1
4-way valve delays its switching for 30 50 seconds after compressor has been turned ON.

0446_M_S

Fig. 17

2-12 Automatic Restart after Power Interruption

This air conditionner has a power failure recovery function.

5
II - 14
SM830080

2. Processes and functions

2-13 Electronic Expansion Valve


u This valve allows very precise and smooth control of the amount of refrigerant flow in the system. Since the valve is operated by a step motor, the control circuits can open or close it in very exact amounts, so the degree of heating or cooling can be changed by just a little, or changed very quickly or slowly. (Completely close 0 step) (Full open................ 480 step)

Model
25 type 36 type 48 type

Min. open HEAT 100 step 85 step 85 step COOL 120 step 85 step 85 step

Max. open

Standard condition 100 200

480 step

100 200 100 200

u Fuzzy Control Fuzzy Control is a controlling system to control electronic refrigerant control valve using fuzzy logic. It regulates the functions of heating and cooling, as well as some of the processes inside the unit, by taking account of many different conditions of temperature, fan speed, etc. These control circuits work automatically to send just the right amount of refrigerant through the Electronic Expansion Valve.

2-14 Compressor Discharge Gas Temperature


(A) Cooling
20 25 13 or below 40 80 14 16 40 90 26 28 27 35 60 100 29 32 36 43 70 105

Indoor temp. (C) Outdoor temp. (C) Compressor discharge gas temp. (C)

(B)

Heating (Except During Defrosting)


18 21 0 or below 40 80 1 10 50 90 0 or below 40 90 22 25 1 10 11 21 0 or below 50 90 26 30 1 10 11 21

Indoor temp. (C) Outdoor temp. (C) Compressor discharge gas temp. (C)

50 100 60 105

60 100 70 105

4
u u Operate the unit at least 30 minutes to stabilize the discharge temperature. The above discharge temperature was measured with a 15m tubing length. The temperature may vary with tubing length.

5
II - 15
SM830080

2. Processes and functions

2-15 Compressor Current Detection Circuit


u The Compressor Current Detection Circuit detects the compressor current and, depending on the current range, can stop the compressor motor so it will not be damaged by overcurrent. u Overcurrent can be caused by several factors, particularly mechanical seizing of the compressor or liquid backflow. Either of these conditions can hold the compressor to run, and thus drawing so much current that the motor can burn out.
Comp. Amps.(A) Locked Comp. Cut-off Range Is Is 1.4 Overload Protection Range 1.17 Normal Operation Range
+ +

Is Rated Current value

0447_M_S

Fig. 18
Rated Current Value ls (A) 23.1 7.1 10.3 13.6 Overload Protection ls x 1.17 (A) 27.0 8.31 12.05 15.9 Locked Compressor Cut-off Is x 1.4 (A) 32.3 9.94 14.42 19.0

Outdoor Model SPW-CR253E(H)L5

SPW-CR253E(H)L8 SPW-CR363E(H)L8 SPW-CR483E(H)L8

2 1

Chart Summary and Explanations


u Overload Protection When the detected current is 1.17 1.4 times greater than the rated current value (Is) and continues for 30 seconds, both compressor and outdoor fan stop (Thermostat OFF). After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if the condition mentioned above repeats twice within 30 minutes, the remote controller displays the alarm message H01, compressor overload. u Locked Compressor Cut-off When the detected current is 1.4 times greater than the rated current value (ls) and continues for 2 seconds, both compressor and outdoor fan stop (Thermostat OFF). After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if the condition mentioned above repeats twice, the remote controller displays the alarm message H02, compressor locked. u Failure of Compressor Current Detection When the Compressor Current Detection Circuit fails to detect the compressor current within 2 seconds after compressor starts, both compressor and outdoor fan stop (Thermostat OFF). After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, when the circuit fails to detect the current twice in a row, the remote controller displays alarm message H03, Failure of compressor Current Detection.

5
II - 16
SM830080

2. Processes and functions

2-16 Dehumidifying Operation


Dehumidifying operation uses the cooling cycle to remove moisture from the air, but by running an indoor fan at a low speed, to dehumidify without greatly lowering room temperature. In this mode, the microprocessor automatically controls the ON-OFF operation between +2 deg. and -2 deg. of the set temperature.
ROOM TEMP. (DEG) A

+2deg SET TEMP. B 2deg

C
0448_M_S

Fig. 19

A range: When the room temperature is in this range, cooling operation starts. However, when the temperature is below 18C, the cooling operation does not start. B range: When the room temperature is in this range, the air conditioner automatically repeats the dehumidifying cycle of 5 minutes ON, 3 minutes OFF see Fig. 20 for details. C range: When the room temperature is in this range, the microprocessor shuts off the air conditioner.
ROOM TEMP T+2C (T+1C) SET TEMP. TC T2C (T1C) AREA A B C 5 MINUTES 3 MINUTES

2
COMPRESSOR ON OFF ON OFF ON OUTDOOR FAN ON OFF ON OFF ON

INDOOR FAN Body sensor

L
0449_M_S

3
Fig. 20

u u u

The indoor fan speed is automatically set to L and cannot be adjusted to M or H. When the set temperature is either 18 or 19C, the set temperature is considered the same as 20C. Room temperature is monitored every 8 minutes when it is in the B range to select the best operation mode.

5
II - 17
SM830080

2. Processes and functions

2-17 Auto-flap Control (Indoor Unit : 4-Way Air Discharge Semi-Concealed Type Ceiling-Mounted Type)
Auto flap can control the air flow in 5 steps.

F1 F2 60 F3 F4 F5 Cooling F1~F3 Heating F1~F5


1328_M_I

Fig. 21

Flap position Operation mode Cooling/dehumidifying Fan Automatic setting F2 F2 F4 Optional setting F1 F2 F3 Swing F1 F2 F3 F4 F5 Swing F1 F2 F3 F4 F5 Swing

Heating Standby for heating

F2 (The flap returns to the original position after release of the standby mode.)

2 1

(1) When the unit is stopped, the Auto-flap returns to F5 position. (2) When the airflow direction is set (an optional setting), the auto and Swing settings will be released. To return the mode to auto-flap control, change the operation mode. (3) Once Auto-flap is set, the flap position will be input in the memory. (4) When the operation mode is changed, the unit starts to search flap position. (if a search action for sensing flap position is not succeeded in one minute, only the swing is operated.)

5
II - 18
SM830080

2. Processes and functions

2-18

Controlled by Electronic Expansion Valve

The circulation volume of the refrigerant is controlled by a pulse type electronic control valve. When the power is switched ON, the opening degree of the electronic control valve is controlled between 90 and 480 steps after setting the initial step at the time when the thermostat is ON. Contents and Order of control
Cooling Start Heating Start

Discharge gas temperature control

Discharge gas temperature control

Outdoor unit coil temperature control

High load prevention control

Freeze prevention control

Heating start up control

Refrigerant flow distribution control

Refrigerant flow distribution control

Discharge gas target temperature control (Fuzzy control)

Discharge gas target temperature control (Fuzzy control)

1
*
0451_M_S

* * Repeat control in accordance with the priority order.

Even though the operation is performed every 30 seconds, the control of discharge gas temperature, high load prevention, outdoor unit coil temperature and freeze prevention activates when it occurs. (1) Refrigerant flow distribution control At the control of flexible combination (a plural number of indoor units are set), the opening degree of the electronic control valve is controlled by the indoor unit coil temperature. Cooling: indoor unit coil E2 temperature (located at the middle of coil) Heating: indoor unit coil E1 temperature (located at the outlet of coil) (2) Fuzzy control (optimal refrigerant flow rate control) By outputting the fuzzy estimation result corresponding to the fuzzy input variables (the indoor unit coil temp., the deviation between the actual discharge gas temp. and the target discharge gas temperature calculated from the outdoor unit coil temperature and the change thereof), the electronic refrigerant valve is controlled so that the unit can perform its maximum ability in accordance with the indoor and outdoor temperature conditions at the operation.
SM830080

II - 19

2. Processes and functions

2-19

Voltage Detection Control

When the power voltage falls below 160 V (voltage between N phase and each phase) or rises above 260 V, the P2 alarm is issued to protect the compressor and electrical components.

2 1

5
II - 20
SM830080

3. Electrical data

3. ELECTRICAL DATA
3-1 Indoor Units (Electric Wiring Diagram, Schematic Diagram) ................. III - 2 4-Way Air Discharge Semi-concealed Type ...........................................III - 2 Ceiling Mounted Type ..............................................................................III - 4 Concealed Duct Type ..............................................................................III - 6 Concealed Duct High Static Pressure Type ............................................III - 12 Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ................ III - 16

3-2

5
III - 1
SM830080

PNK BRN BLK YEL ORG VLT WHT GRY GRY

BRN BRN PNK

S 1 2 3 4 5 6 7 8 9 Connector P 1 2 3 4 5 6 7 8 9 9P(WHT)

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

ORG

AC 230V

YEL WHT BLK BRN GRY PNK

RED BRN

PNK BLU

RED RED BRN BRN

RED WHT BLK

WHT WHT

YEL ORG VLT WHT

GRY GRY

YEL BLU BLK WHT GRY PNK

1 3 1 3 1 3 5 7

1 2

1 2 3

1 2 3 4

1 4

1 3

1 3

1 3

1 3

R N RN1(BLK)

SG1 SG2 OC(BLU) R N RN2(WHT) VCC(WHT)

SG 12V G RC(BLU) T20(GRY)

LL L H HH R N RN3(WHT) FM (WHT)

DPH (BLU)

LM (GRN)

LS (WHT)

Controller (CR-X253GH)
DP (BLU)
1 3 1 2 3 4 5

E
1 3

FS (RED)

T6 (WHT)

(YEL) Room Temp


1 2

(RED) Coil E1
1 2

(BLK) Coil E2
1 2

(BRN) Coil E3
1 3

BLK BLK

BLK BLK

BLK BLK

BLK BLK

GRN/YEL

BLK BLK

DP

GRN/YEL

FS

ORG RED YEL BLK GRY

MOV

TH1

TH2

TH3

TH4

1 4-Way Air Discharge Semi-concealed Type : SPW-XR253GH56, SPW-XR363GH56, SPW-XR483GH56

3. Electrical data

SM830080

W 854-2-5268-470-00-3 (X)

BRN BRN

ORG BRN

5
3-1

4
Electric Wiring Diagram
To Remote Control Switch DPH LSW 1 GRN/YEL 3 RC1 2 LM GRN/YEL

Power Supply

Unit Control Line

3
Indoor Units
FMI
49FI TR1 S P Connector 8P(RED)

2 1

3 U1 U2 R1 R2 R3

Terminal Plate(8P)

III - 2

1 2 3

PNL (GRN)

3. Electrical data

3-1 Indoor Units


1 4-Way Air Discharge Semi-concealed Type : SPW-XR253GH56, SPW-XR363GH56, SPW-XR483GH56

Schematic Diagram
RCS

1 2 3

CR-X253GH Controller 8P-1(L) 1 R 1X 8P-2(N) 2X RY2 RY1 49FI 1 3 9 3X 3X T20 3 LS LL 1 L H HH 3 5 7 R 1 DP 3 DPH 1 LM 1 1X 2X 3 LL 4 L 5 6 7 HT 2 4 RY1 LM 3X FS RN2 PNL 8 AC 230V F1(5A) T20 1 TR1 1 2 3 4 SG RC12V G VCC T6

8P-R1 1 8P-R2 2 8P-R3 3 1 2 3 4 5 1 2 1 3 1 3 Room Thermistor 1 2 1 2 1 2 1 3 TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4 7 8 6 5 LSW FS

MOV

H HH

FMI
1 RC1 2

DP

DPH

LM RY2 DP.DPH DC12V

3 N N

OC

SG1 SG2

1 2 8P8PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1 LM TR1 1X-3X RY1-RY2 MOV RCS TH1 TH2

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Auto Louver Motor Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Remote Control Switch Room Thermistor Thermistor (Indoor Coil E1)

Symbols
TH3 TH4

Description
Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3)

CR-X253GH Indoor Controller Terminal Plate Connector Terminal DP DPH LSW FS Drain Pump Dew Proof Heater Limit Switch Float Switch

S 854-2-5268-470-00-3 (X)

5
III - 3
SM830080

WHT WHT

BRN BRN PNK

S 1 2 3 4 5 6 7 8 9 Connector P 1 2 3 4 5 6 7 8 9 9P(WHT)

PNK BRN BLK YEL ORG VLT WHT GRY GRY

S 1 2 Connector P 1 2 2P(BLK)

RED RED BRN BRN

YEL ORG VLT WHT

GRY GRY

RED BRN

PNK BLU

RED WHT BLK

BLK BLK

BLK

WHT BLK

PNK GRY

ORG

BLK BLK

BLK BLK

BLK BLK

GRN/YEL

P 1 2 3 4 Connector S 1 2 3 4 4P(WHT) BLK WHT GRY PNK BLU WHT

LM LSW

Connector P 1 2 2P(WHT) TH1 TH2 TH3 TH4

2 Ceiling Mounted Type : SPW-TR253GH56, SPW-TR363GH56, SPW-TR483GH56

W 854-2-5268-665-00-0 (TR)

BRN BRN

III - 4
1 2 3 1 3 1 2 3 4 1 4 1 3 1 3 5 7 1 3

1 3

1 2

RN1(BLU) RN2(WHT) RN3 (WHT)

OC(BLU)

RC(BLU)

VCC(WHT) FM(WHT)

T20 (GRY)

FS (RED)

Controller (CR-X253GH)
LM (GRN) LS (WHT)
1 3 1 3 1 2 3 1 3

PNL (GRN)

DP (BLU)

ORG RED YEL BLK GRY

5
Electric Wiring Diagram
To Remote Control Switch GRN/YEL GRN/YEL RC1 49FI TR1 AC 230V

4
3-1 Indoor Units
FMI MOV
1 2 3 4 5

Power Supply

Unit Control Line

3
T6 (WHT) (YEL) Room Temp
1 2

2 1

3 U1 U2 R1 R2 R3

Terminal Plate(8P)

(RED) Coil E1
1 2

(BLK) Coil E2
1 2

(BRN) Coil E3
1 3

3. Electrical data

SM830080

3. Electrical data

3-1 Indoor Units


2 Ceiling Mounted Type : SPW-TR253GH56, SPW-TR363GH56, SPW-TR483GH56

Schematic Diagram
RCS
CR-X253GH Controller 8P-1(L) 1 R 1X 8P-2(N) 2X RY2 RY1 49FI 1 3 9 3X RN2 8 AC 230V F1(5A) T20 1 TR1 1 2 3 4

1 2 3

SG RC12V G VCC

1 2 3

8P-R1 8P-R2 8P-R3

1 T6 2 3 4 5 1 2 3 1 3 4 3

MOV

PNL

LL 1

L H HH 3 5 7

DP 1

LM 1 3

T20 LS LSW

1 3 LL 4 L 5 H HH 6 7 HT 2 2 2

1 3

FS 1 2 1 2 1 2 1

Room Thermistor TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4

FMI
1 RC1 2 1

LM 2X 3X 1 RY2

1X

RY1

LM DP DC12V OC SG1 SG2

3 1 2

3 N N

1
8P8PU2 U1 To Outdoor Unit

Symbols
FMI MOV 49FI RC1 TR1 LM LSW TH1 TH2 TH3

Description
Indoor Fan Motor Motor Operated Valve Indoor Motor Thermal Protector Running Capacitor Power Transformer Auto Louver Motor Limit Switch Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2)

Symbols
TH4 F1 1X-3X RY1-RY2 CR RCS

Description
Thermistor (Indoor Coil E3) Fuse Auxiliary Relay Auxiliary Relay Indoor Controller Remote Control Switch Terminal Plate Connector Terminal

3
S 854-2-5268-665-00-0 (TR)

5
III - 5
SM830080

PNK BLU

RED WHT BLK

WHT WHT

RED RED BRN BRN

BRN BRN PNK

S 1 2 3 4 5 6 7 8 9 Connector P 1 2 3 4 5 6 7 8 9 9P(WHT)

YEL ORG VLT WHT

PNK BRN BLK YEL ORG VLT WHT GRY GRY

GRY GRY

RED BRN

1 3 1 4

1 2

1 2 3 1 3 1 2 3 4 1 3

1 3 5 7

BLK BLK

WHT BLU

ORG RED YEL BLK GRY

ORG

BLK BLK

BLK BLK

BLK BLK

BLK
ORG RED YEL BLK GRY
1 2 1 2

1 2 3 4 5 1 2 3 4 5 1 2 1 2

GRN/YEL

Connector P 2P(BLK) S P S
BLK BLK BLK

Connector 2P(BLK) P 1 2 Connector 2P(WHT)

S P Connector 5P(WHT)

3 Concealed Duct High Static Pressure Type : SPW-DR253GH56

MOV
FS

TH1

TH2

TH3

TH4

3. Electrical data

SM830080

W 854-2-5268-693-00-0 (DR)

BRN BRN

III - 6
SG 12V G RC(BLU) R N RN2(WHT) VCC(WHT) LL L H HH R N RN3(WHT) FM (WHT) T20(GRY)

R N RN1(BLK)

SG1 SG2 OC(BLU)

Discharge Air (GRN)

Controller (CR-X253GH)
DP (BLU)
1 3 1 2 3 4 5

E
1 3

FS (RED)

T6 (WHT)

BLK BLK

5
Electric Wiring Diagram
To Remote Control Switch GRN/YEL GRN/YEL RC1

4
FMI
49FI TH5

Power Supply

Unit Control Line

3
3-1 Indoor Units
TR1 AC 230V
1 2

2 1

3 U1 U2 R1 R2 R3

Terminal Plate(8P)

PNL (GRN)
1 2 3

(YEL) Room Temp


1 2

(RED) Coil E1
1 2

(BLK) Coil E2
1 2

(BRN) Coil E3
1 3

3. Electrical data

3-1 Indoor Units


3 Concealed Duct High Static Pressure Type : SPW-DR253GH56

Schematic Diagram
RCS

1 2 3

CR-X253GH Controller 8P-1 1 R 1X 8P-2 2X RY2 49FI 1 3 9 3X 3X T20 3 FS LL 1 L H HH 3 5 7 R 1 DP 3 1X 2X 3 LL 4 L 5 6 7 HT 1 3X H HH RN2 PNL 8 AC 230V F1(5A) T20 1 TR1 1 2 3 4 VCC T6 SG RC12V G

8P-R1 8P-R2 2 8P-R3 3 1 2 3 4 5 1 2 1 3 1 2 1 2 Room Thermistor FS 1 2 3 4 5

MOV

1 2 1 2 1 2

TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4 Discharge Air TH5

FMI
RY2 1 RC1 2 2 DP DC12V

1 3 1 2 1 2

3 N N

SG1 OC SG2

8P8PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1 TR1 1X-3X RY2 MOV RCS TH1 TH2 TH3

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Remote Control Switch Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2)

Symbols
TH4 TH5

Description
Thermistor (Indoor Coil E3) Thermistor (Discharge Air)

CR-X253GH Indoor Controller Terminal Plate Connector Terminal FS Float Switch

3
S 854-2-5268-693-00-0 (DR)

5
III - 7
SM830080

PNK BRN BLK YEL ORG VLT WHT GRY GRY

BRN BRN PNK

PNK BLU

RED WHT BLK

WHT WHT

RED RED BRN BRN

YEL ORG VLT WHT

RED BRN

1 3 1 4

1 2 1 3

1 2 3 1 2 3 4 1 3

1 3 5 7

GRY GRY

BLK BLK

WHT BLU

ORG RED YEL BLK GRY

ORG

BLK BLK

BLK BLK

BLK BLK

BLK ORG RED YEL BLK GRY


1 2 1 2

1 2 3 4 5 1 2 3 4 5 1 2 1 2

GRN/YEL

Connector P 2P(BLK) S P S BLK P 1 2 Connector 2P(WHT) BLK BLK

Connector 2P(BLK)

S P Connector 5P(WHT)

4 Concealed Duct High Static Pressure Type : SPW-DR363GH56

MOV
FS

TH1

TH2

TH3

TH4

3. Electrical data

SM830080

W 854-2-5268-694-00-0 (DR)

BRN BRN

III - 8
SG 12V G RC(BLU) R N RN2(WHT) VCC(WHT) LL L H HH R N RN3(WHT) FM (WHT) T20(GRY)

R N RN1(BLK)

SG1 SG2 OC(BLU)

Discharge Air (GRN)

Controller (CR-X253GH)
DP (BLU)
1 3 1 2 3 4 5

E
1 3

FS (RED)

T6 (WHT)

PNL (GRN)
1 2 3

BLK BLK

5
Electric Wiring Diagram
To Remote Control Switch GRN/YEL GRN/YEL RC1

4
FMI
49FI TH5

Power Supply

Unit Control Line

3
3-1 Indoor Units
TR1 AC 230V S P
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

2 1

3 U1 U2 R1 R2 R3

Terminal Plate(8P)

Connector 9P(WHT)

1 2

(YEL) Room Temp


1 2

(RED) Coil E1
1 2

(BLK) Coil E2
1 2

(BRN) Coil E3
1 3

3. Electrical data

3-1 Indoor Units


4 Concealed Duct High Static Pressure Type : SPW-DR363GH56

Schematic Diagram
RCS
CR-X253GH Controller 8P-1 1 R 1X 8P-1 RY2 49FI 1 3 9 3X 3X T20 3 RN2 8 AC 230V F1(5A) T20 1 TR1 1 2 3 4 VCC

1 2 3

SG RC12V G

1 2 3 1

8P-R1 8P-R2 8P-R3 1 2 3 4 5

T6

2X

2 3 4 5 1 2 1 3

MOV

PNL

1 2 1 2

FS LL 1 L H HH 3 5 7 R 1 DP 3 1X 2X 3 LL 4 6 7 5 H 1 3X L HH HT

FS

Room Thermistor 1 2 1 2 1 2 TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4 Discharge Air

FMI
RY2 1 RC1 2 2 DP DC12V

1 3

1 2
1 2

TH5

3 N N

SG1 OC SG2

8P8PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1 TR1 1X-3X RY2 MOV RCS TH1 TH2 TH3

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Remote Control Switch Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2)

Symbols
TH4 TH5

Description
Thermistor (Indoor Coil E3)

Thermistor (Discharge Air)

CR-X253GH Indoor Controller Terminal Plate Connector Terminal FS Float Switch

3
S 854-2-5268-694-00-0 (DR)

5
III - 9
SM830080

Terminal Plate(8P) BRN PNK BRN BRN PNK


7 5 1 4 2 6 5 1 4 2Z 8 3 1Z 8 3 7

F0 S P
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

PNK BRN YEL ORG VLT WHT GRY GRY

GRN/YEL

PNK BLU

RED WHT BLK

RED BRN

WHT WHT

RED RED BRN BRN

1 3 1 4 1 3 5 7

1 2

1 2 3 1 2 3 4 1 3

1 3

BLK BLK

WHT BLU

ORG RED YEL BLK GRY

BLK BLK

BLK BLK

BLK BLK

BLK ORG RED YEL BLK GRY

1 2 3 4 5 1 2 3 4 5

GRN/YEL

Connector P 2P(BLK) S

1 2 1 2

P S

1 2 1 2

Connector 2P(BLK)

S P Connector 5P(WHT)

BLK BLK

BLK

P 1 2 Connector 2P(WHT)

5 Concealed Duct High Static Pressure Type : SPW-DR483GH56

MOV

ORG

TH1

TH2

TH3

TH4

BRN BRN

TH5

FS

3. Electrical data

SM830080

W 854-2-5268-695-00-0 (DR)

BLK BLK

III - 10
T20(GRY) R N LL L H HH RN3(WHT) FM (WHT)

R N RN1(BLK)

SG1 SG2 OC(BLU)

SG 12V G RC(BLU)

R N RN2(WHT)

VCC(WHT)

Controller (CR-X253GH)
T6 (WHT) PNL (GRN)
1 2 3 1 2 3 4 5

E
1 3

FS (RED)

DP (BLU)

GRY GRY

5
GRN/YEL PNK 49FI

Electric Wiring Diagram


FMI

2 1

Power Supply

Unit Control Line

To Remote Control Switch

1
RC1 RC2 BRN BRN
6 2

3 U1 U2 R1 R2 R3

3-1 Indoor Units

RED

Connector 8P(WHT)

TR1 PNK

AC 230V

Connector 6P(WHT) S P WHT 6 6 WHT VLT 5 5 VLT ORG 4 4 ORG YEL 3 3 YEL PNK 2 2 PNK BRN 1 1 BRN PNK BRN
7 4Z 8 3 5 1 4 6 2

BRN
7 3Z 8 3 5 1 4 6 2

YEL ORG VLT WHT

PNK

PNK

(YEL) Room Temp


1 2

(RED) Coil E1
1 2

(BLK) Coil E2
1 2

(BRN) Coil E3
1 3

Discharge Air (GRN)


1 2

1 3

3. Electrical data

3-1 Indoor Units


5 Concealed Duct Type : SPW-DR483GH56

Schematic Diagram
RCS

1 2 3

CR-X253GH Controller 8P-1 F0(6.3A) 1 R 2 8P-2 2X RY2 49FI 1 3 3X 4Z 3Z 2Z 1Z 3 3 LL 4 4 L 5 5 H 6 6 HH 2X LL L H HH DP 1 3 5 7 3 1X 9 T20 3 FS RN2 PNL 1X 8 AC 230V F1(5A) T20 1 TR1 1 2 3 4 VCC T6 SG RC12V G

8P-R1 8P-R2 2 8P-R3 3 1 2 3 4 5 1 2 1 2 3 4 5

MOV

1 3

1 2 1 2 Room Thermistor

FS

1 2 1 2 1 2

FMI
3Z 1 2 1Z 1 4Z 2Z

3X

TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4 Discharge Air TH5

RY2 2 RC1 RC2 3 N N 1 4 1

DP DC12V

1 3 1 2 OC SG1 SG2 1 2

1
8P8PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1, 2 F0, 1 TR1 1X-3X RY2 MOV RCS TH1 TH2 TH3

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Remote Control Switch Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2)

Symbols
TH4
TH5

Description
Thermistor (Indoor Coil E3) Thermistor (Discharge Air)

CR-X253GH Indoor Controller Terminal Plate Connector Terminal FS 1Z-4Z Float Switch Auxiliary Relay

S 854-2-5268-695-00-0 (DR)

5
III - 11
SM830080

BRN BRN PNK

PNK BRN BLK YEL ORG VLT WHT GRY GRY

WHT WHT

PNK BLU

RED WHT BLK

RED RED BRN BRN

RED BRN

YEL ORG VLT WHT

GRY GRY

1 3 1 4

1 2

1 2 3 1 3 1 2 3 4 1 3

1 3 5 7

R N RN1(BLK)

SG1 SG2 OC(BLU)

SG 12V G RC(BLU)

R N RN2(WHT)

VCC(WHT)

R N LL L H HH RN3(WHT) FM (WHT)

T20(GRY)

Discharge Air (GRN)

Controller (CR-X253GH)
DP (BLU)
1 3 1 2 3 4 5

E
1 3

FS (RED)

T6 (WHT)

PNL (GRN)
1 2 3

(YEL) Room Temp


1 2

(RED) Coil E1
1 2

(BLK) Coil E2
1 2

BLK BLK

5
Electric Wiring Diagram
To Remote Control Switch GRN/YEL

4
3-1 Indoor Units
RC1 TR1 49FI AC 230V GRN/YEL

3
FMI
TH5

2 1

Power Supply

Unit Control Line

3 U1 U2 R1 R2 R3

Terminal Plate(8P)

P S
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

Connector 9P(WHT)

BLK BLK

BLU BLU

ORG RED YEL BLK GRY

BLK BLK

BLK BLK

BLK BLK

GRN/YEL

FS GRN/YEL

DP

MOV
TH1 TH2 TH3 TH4

ORG

6 Concealed Duct Type : SPW-UR253GH56, SPW-UR363GH56, SPW-UR483GH56

3. Electrical data

SM830080

W 854-2-5268-843-00-0 (UR93GHN56)

BRN BRN

III - 12

1 2

(BRN) Coil E3
1 3

3. Electrical data

3-1 Indoor Units


6 Concealed Duct Type : SPW-UR253GH56, SPW-UR363GH56, SPW-UR483GH56

Schematic Diagram
RCS

1 2 3

CR-X253GH Controller 8P-1(L) 1 R 1X 8P-2(N) 2X RY2 49FI 1 3 9 3X 3X T20 3 FS LL 1 L H HH 3 5 7 R 1 DP 3 DPH 1 1X 2X 3 LL 4 L 5 6 7 HT 3X H HH RN2 PNL 8 AC 230V F1(5A) T20 1 TR1 1 2 3 4 VCC T6 SG RC12V G

8P-R1 8P-R2 2 8P-R3 3 1 2 3 4 5 1 2

MOV

1 3 Room Thermistor 1 2 1 2 1

FS

TH1 Indoor Coil E1 TH2 Indoor Coil E2

FMI
1 RC1 2

DP RY2 DP.DPH DC12V

2 1 3 1 2 OC SG1 SG2 1 2

TH3 Indoor Coil E3 TH4 Discharge Air TH5

3 N N

8P8PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1 FS TR1 1X-3X RY2 MOV RCS TH1 TH2

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Float Switch Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Remote Control Switch Room Thermistor Thermistor (Indoor Coil E1)

Symbols
TH3 TH4 TH5

Description
Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3) Thermistor (Discharge Air)

CR-X253GH Indoor Controller Terminal Plate Connector Terminal DP Drain Pump

S 854-2-5268-843-00-0 (UR93GHN56)

5
III - 13
SM830080

RED

WHT

BRN

BLU BLU

WHT RED

WHT WHT

52C

ORG GRY

V W

32 AC230V

TR AC14V

1 SPW-CR253EHL5, SPW-CR253EL5

WHT

RC PNK BRN GRY BLK WHT VLT YEL

RC2 Connector 1 2 P 2P (YEL) 1 2 S BLU BLU

RED

WHT

BLK

YEL BRN

GRN/YEL

P 1 2 Connector S 1 2 2P (RED) PNK BRN GRY GRY WHT VLT YEL

Connector 1 2 3 4 5 6 7 8 P 8P (WHT) 1 2 3 4 5 6 7 8 S

BRN BRN

BRN

63PH 20S

CM FMO
GRN/YEL

CH

49FO

Parts surrounded by chain line

are used for heat pump model W 854-2-5268-778-00-0 (CR253EHL5)

BRN BRN

5
Electric Wiring Diagram
BLU PNK C1 1 (BLK) 2 BLK BLK BLK BLK WHT WHT C2 1 (RED) 2 Discharge 1 Gas (GRN) 2 2 CN2 1 2P (BLU)

2 1

Power Supply

3-2 Outdoor Units

1 2 3 4

L N

Terminal Plate (6P)

To Indoor Unit Terminal 1 2 Plate (2P)

TH6 TH7 TH8

Controller (CR-CR253GHL5)
N

WHT

BRN

RED RED L1 GRN/YEL E L 3P(WHT) CT1 1 3 3P(BLK) 52C 1 3 9P(WHT) CN26 1 3 5 7 9 3P(YEL) 20S 1 3 3P(RED) 3P(WHT) 63PH RS 1 3 3 1

GRN/YEL

RED

BLK

CT

BLK

2P VCC (WHT) 1 2

S T

31

III - 14

3. Electrical data

SM830080

3. Electrical data

3-2 Outdoor Units


1 SPW-CR253EHL5, SPW-CR253EL5
Terminal Plate (6P) -1 -2 -3 -4 -L -N 52C L1 F1(3.15A) RY4 3 RY5 H 3 5 RY6 M L 20S 52C 3 3 49 FO 7 RS

Schematic Diagram
63PH RY2 RY3 1 63PH

CR-CR253GHL5 Controller 2P-1 1 2 1 3 AC 230V 2P-2

CN2

TR

RY2 3 RY3 49FO RY4 4

20S VCC 52C FM1 FM2 2 1 1 2 1 2 1 2 1 3 TH8 TH7 AC 14V TH6

Outdoor Coil C1 Outdoor Coil C2 Discharge gas

1 CT

5 6 7 H M L

20S

RY5 52C RY6 9 49 C

52C

CH

FMO
1 RC2 2 1

RC

DC12V CT1 N

R 1 1 1 N

CM

Symbols
CM FMO 52C 49FO 63PH CT RC,RC2 TR CH 20S F1 TH6 TH7 TH8

Description
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch Current Transmitter Running Capacitor Power Transformer Crank Case Heater Four Way Valve Fuse Thermistor (Outdoor Coil C1) Thermistor (Outdoor Coil C2) Thermistor (Discharge Gas)

Symbols
RY2~6

Description
Auxiliary Relay Terminal Plate Terminal Connector

CR-CR253EHL5 Outdoor Controller

3
are used for heat pump model. S 854-2-5268-778-00-0 (CR253EHL5)

Parts surrounded by chain line

5
III - 15
SM830080

RED

WHT

BLU

BLU BLU

WHT RED

WHT WHT

52C

ORG GRY

BRN

V W

32 AC230V

TR AC14V

2 SPW-CR253EHL8, SPW-CR253EL8

RC2 PNK BRN GRY WHT VLT YEL Connector 1 2 P 2P (YEL) 1 2 S BLU BLU

RED

WHT

BLU

GRY

GRY

YEL BRN

GRN/YEL

P 1 2 Connector S 1 2 2P (RED) PNK BRN GRY GRY WHT VLT YEL

Connector 1 2 3 4 5 6 7 8 P 8P (WHT) 1 2 3 4 5 6 7 8 S

BRN BRN

49C

BRN

III - 16
20S

CM
GRN/YEL

63PH

CH

FMO
49FO

Parts surrounded by chain line

are used for heat pump model W 854-2-5268-779-00-0 (CR253EHL8)

BRN BRN

5
Electric Wiring Diagram

C1 1 (BLK) 2 BLK BLK BLK BLK WHT WHT C2 1 (RED) 2 Discharge 1 Gas (GRN) 2 BLU PNK N L3 L2 L1 GRN/YEL E L 3P(WHT) CT1 1 3 3P(BLK) 52C 1 3 9P(WHT) CN26 1 3 5 7 9 3P(YEL) 20S 1 3 3P(RED) 3P(WHT) 63PH RS 3 1 1 3 2 CN2 1 2P (BLU)

4
3-2 Outdoor Units
TH6 TH7 TH8

2 1

Power Supply

L1 L2 L3 N

1 2 3

4 5 6 7

Terminal Plate (8P)

To Indoor Unit Terminal 1 2 Plate (2P)

Controller (CR-CR483GHL8)

BRN RED RED

BRN BLU WHT RED GRN/YEL BLK

CT

BLK

2P VCC (WHT) 1 2

S T

31

3. Electrical data

SM830080

3. Electrical data

3-2 Outdoor Units


2 SPW-CR253GHL8, SPW-CR253EL8
Terminal Plate (8P) -1 -2 -3 -4 -5 L1 F1(3.15A) RY4 3 RY5 H 3 L1 L2 L3 N 5 RY6 M L 20S 52C 3 3 49 FO 49FO TR 4 2 52C -7 -8 1 5 6 7 H M L RY4 49C 20S RY5 52C RY6 9 49 C FM2 Outdoor Coil C2 Discharge gas DC12V CT1 N L3 L2 1 L2 L3 N F2(3.15A) 1 1 1 3 1 2 1 2 TH8 TH7 FM1 RY2 RY3 20S VCC 52C 2 1 1 2 AC 14V TH6 7 3 RS

Schematic Diagram
63PH RY2 RY3 1 63PH

CR-CR483GHL8 Controller 2P-1 1 2 1 3 AC 230V 2P-2

CN2

-6

Outdoor Coil C1

CT 52C

CH

FMO
1 RC2 2 1

CM

Symbols
CM FMO 52C 49C 49FO 63PH CT RC2 TR CH 20S F1,2 TH6 TH7 TH8

Description
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Compressor Motor Termal Protector Outdoor Fan Motor Thermal Protector High Pressure Switch Current Transmitter Running Capacitor Power Transformer Crank Case Heater Four Way Valve Fuse Thermistor (Outdoor Coil C1) Thermistor (Outdoor Coil C2) Thermistor (Discharge Gas)

Symbols
RY2~6

Description
Auxiliary Relay Terminal Plate Terminal Connector

CR-CR483EHL8 Outdoor Controller

3
are used for heat pump model S 854-2-5268-779-00-0 (CR253EHL8)

Parts surrounded by chain line

5
III - 17
SM830080

RED

WHT

BLU

BLU BLU

WHT RED

RED RED

WHT WHT

BRN

WHT VLT

52C

ORG GRY

YEL

V W

32 AC230V BRN BLK

TR AC14V

PNK

RED

BLK GRY GRY

YEL BRN

WHT VLT YEL

BRN

GRY WHT VLT YEL

RED

WHT

BLU

GRN/YEL

PNK

PNK

BRN BRN

BRN GRY GRY WHT VLT YEL

BRN GRY GRY WHT VLT YEL

BLU BLU

3 SPW-CR363EHL8, SPW-CR363EL8, SPW-CR483EHL8, SPW-CR483EL8

III - 18
RC2 RC3 Connector 1 2 P 2P (YEL) 1 2 S Connector 1 2 3 4 5 6 7 8 P 8P (WHT) 1 2 3 4 5 6 7 8 S Connector 1 2 3 4 5 6 7 8 P 8P (WHT) 1 2 3 4 5 6 7 8 S 63PH 20S

P 1 2 Connector S 1 2 2P (RED)

CM FMO1
GRN/YEL 49FO1 GRN/YEL

63PL

CH

FMO2
49FO2

Parts surrounded by chain line

are used for heat pump model W 854-2-5268-787-00-1 (CR363EHL8)

BRN BRN

5
Electric Wiring Diagram

C1 1 (BLK) 2 BLK BLK BLK BLK WHT WHT BLU PNK N L3 L2 L1 GRN/YEL E L 3P(WHT) CT1 1 3 9P(WHT) 3P(BLK) CN26 52C 1 3 1 3 5 7 9 3P(YEL) 20S 1 3 3P(RED) 3P(GRN) 3P(WHT) RS 63PH 63PL 1 3 1 3 3 1 C2 1 (RED) 2 Discharge 1 Gas (GRN) 2 2 CN2 1 2P (BLU)

4
3-2 Outdoor Units
TH6 TH7 TH8

2 1

Power Supply

L1 L2 L3 N

1 2 3

4 5 6 7

Terminal Plate (8P)

To Indoor Unit Terminal 1 2 Plate (2P)

Controller (CR-CR483GHL8)

BRN RED RED

BRN BLU WHT RED GRN/YEL BLK

CT

BLK

2P VCC (WHT) 1 2

S T

31

3. Electrical data

SM830080

3. Electrical data

3-2 Outdoor Units


3 SPW-CR363EHL8, SPW-CR363EL8, SPW-CR483EHL8, SPW-CR483EL8
Terminal Plate (8P) -1 -2 -3 -4 -5 L1 F1(3.15A) RY4 3 RY5 H 3 L1 L2 L3 N 5 RY6 M L 20S 63PL 52C 3 1 3 49 FO 49FO1 7 3 RS

Schematic Diagram
63PH RY2 RY3 1 63PH

CR-CR483GHL8 Controller 2P-1 1 2 1 3 AC 230V 2P-2

CN2

TR RY2 20S VCC RY3 RY4 52C FM1 FM2 2 1 1 2 1 2 1 2 1 3 TH8 TH7 AC 14V TH6

-6 2 52C -7 3 -8 1 5 6 7 H M L 5 6 7 H M L 4

Outdoor Coil C1 Outdoor Coil C2 Discharge gas

20S

52C

49FO2

RY5 RY6

CT 52C

CH

FMO1
1 RC2 2

FMO2
1 RC3 2 1

63PL

4 9 49 C

DC12V CT1 N L3 L2

W 1 1 3 1 L2 L3 N F2(3.15A)

CM

Symbols
CM FMO1,2 52C 49FO1,2 63PH 63PL CT RC2,3 TR CH 20S F1,2 TH6 TH7 TH8

Description
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch Low Pressure Switch Current Transmitter Running Capacitor Power Transformer Crank Case Heater Four Way Valve Fuse Thermistor (Outdoor Coil C1) Thermistor (Outdoor Coil C2) Thermistor (Discharge Gas)

Symbols
RY2~6

Description
Auxiliary Relay Terminal Plate Terminal Connector

CR-CR483EHL8 Outdoor Controller

3
are used for heat pump model S 854-2-5268-787-00-1 (CR363EHL8)

Parts surrounded by chain line

5
III - 19
SM830080

4. Service procedures

4. SERVICE PROCEDURES
4-1 Troubleshooting ...................................................................................... IV - 2 (1) Check before and after Troubleshooting.......................................... IV - 3 (2) General Troubleshooting Flow Chart: Diagnosis and Remedy ........ IV - 5 (3) Meanings of alarm messages .......................................................... IV - 7 (4) LED Indication on the Outdoor Units P.C.B. Assy.......................... IV - 9 (5) Symptoms and parts to inspect........................................................ IV - 10 (6) Procedures When a Specific Component Does Not Work............... IV - 20 (7) Service Functions of Remote Controller .......................................... IV - 22 Checking the Electrical Components ...................................................... IV - 36 (1) Measurement of Insulation Resistance ............................................ IV - 36 (2) Measurement of Insulation Resistance for Electrical parts .............. IV - 37 (3) Checking the Protective Devices ..................................................... IV - 38 (4) Checking the Electrical Parts ........................................................... IV - 39 (5) Sensor and Solenoid Layout Diagram ............................................. IV - 42 (6) Thermistor Characteristic Curve ...................................................... IV - 47 (7) P.C.B. Setting .................................................................................. IV - 48 (8) R.C Address Setting Method ........................................................... IV - 49 (9) Automatic Address Setting Method.................................................. IV - 50 (10) Displaying Indoor / Outdoor Unit Combination Numbers ................. IV - 50 (11) Items to Check Prior to Test Run ..................................................... IV - 51 (12) Test Run Procedure ......................................................................... IV - 52

4-2

5
IV - 1
SM830080

4. Service procedures

4-1

Troubleshooting

This section explains:

u u u u

What the LED codes mean What the remote control unit display screen messages mean How to use the flow charts to find and solve problems How to use the self-diagnostic tests to find parts that arent working right

2 1

This unit is made to be trouble free, and not need much service. However, with time, moving parts wear out, electronic components break down, and sometimes misuse damages the unit. The purpose of this section is to help you when the unit is not working properly. Sometimes your experience will tell you right away where to look for a problem, and when you find it you will know how to fix it at once. Often, however, all you have is a symptom like poor cooling or outside fan doesnt come on. Now you must find out the cause of the problem, and then how to fix it. This section provides several ways to help you go from the symptom to the cause and then the solution. The first chart, General Troubleshooting Flow Chart is divided into two sections: Poor heating and Poor Cooling. Under each heading you will find the main things that can go wrong and cause either of these problems. Sometimes you can start with this chart and find the problem right away, but often you will come here for more suggestions after you have looked at the error code on the remote control unit display. This chart gives you the "big picture" of problems and solutions. The other main tool we explain here is the use of the Alarm Messages. When a certain part fails or a safety device has shut the unit down, any alpha-numeric codes appears on the display to guide you to the problem. By understanding the code you can often go right to the problem area and then, with this manual and your knowledge of air conditioning, find the solution.

5
IV - 2
SM830080

4. Service procedures

(1)-1 Check before and after Troubleshooting (SPW-CR253EHL5) Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first. 1 . Check power supply wiring u Check the power supply wires are correctly connected between terminal No. 1 & 2 on the 3P terminal plates in the indoor unit and the outdoor unit. 2 . Check inter-unit wiring u Check that inter-unit control wiring (DC low voltage) is correctly connected between the indoor unit and outdoor unit. Power Supply: 50 Hz, single-phase, 220-230-240 V
Indoor Unit B Inter-unit power wiring (Line voltage) 1 2 Ground Inter-unit control wiring (Low voltage) RED WHT BLK 1 2 3 1 2 3 U1 U2 R1 R2 R3 Ground A
0500_M_I

Outdoor Unit 1 2
0 R.C. Address on the PCB: 0 (S2, BLK) (0: Factory shipped state)

1 2 C

4 L N
L N Power supply 220 - 240 V 50 Hz

Remote controller D

Fig. 22

2
3 . Check power supply u Check that voltage is within the specified range (10% of the rating). u Check that power is being supplied.

3
If the following troubleshooting must be done with power being supplied, be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK. 4 . Check the lead wires and connectors in indoor and outdoor units. u Check that the sheath of lead wires is not damaged. u Check that the lead wires are firmly connected at the terminal plate. u Check that the wiring is correct.

5
SM830080

IV - 3

4. Service procedures

(1)-2 Check before and after Troubleshooting (SPW-CR253EHL8, CR363EHL8, CR483EHL8) Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first. 1 . Check power supply wiring u Check that power supply wires are correctly connected to terminal No.5 through No.8 on the 8P terminal plate in the outdoor unit. u Check the power supply wires are correctly connected between terminal No.1 and 2 on the 3P terminal plate in the indoor unit and terminal No.1 and 2 on the 8P terminal plate in the outdoor unit. 2 . Check inter-unit wiring u Check that inter-unit control wiring (DC low voltage) is correctly connected between the indoor unit and outdoor unit. Power Supply: 50 Hz, 3-phase, 380-400-415 V
Indoor Unit B Inter-unit power wiring (Line voltage) 1 2 Ground 1 2
0 R.C. Address on the PCB: 0 (S2, BLK) (0: Factory shipped state)

Outdoor Unit

Inter-unit control wiring (Low voltage) RED WHT BLK 1 2 3 1 2 3 D

U1 U2 R1 R2 R3 C

1 2

4 L1 L2 L3 N
L1 L2 L3 N Power supply 380 - 415 V - 3 N 50 Hz

2 1

Remote controller (Option)

Ground

0499_M_I

Fig. 23

3 . Check power supply u Check that voltage is within the specified range (10% of the rating). u Check that power is being supplied.

If the following troubleshooting must be done with power being supplied, be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK. 4 . Check the lead wires and connectors in indoor and outdoor units. u Check that the sheath of lead wires is not damaged. u Check that the lead wires are firmly connected at the terminal plate. u Check that the wiring is correct.
IV - 4
SM830080

4. Service procedures

(2) General Troubleshooting Flow Chart: Diagnosis and Remedy When you have found a major problem, such as refrigerant not flowing in the system or reduced air circulation, come to this section and find the box listing the problem. Connected to the box are the main causes of the problem and their remedies. To find out which malfunction is happening in your case, check the remote controller for an Alarm Message, and follow the steps in section 3).

(A) Cooling
a. Cooling Poor cooling

Is setting temp. suitable ?

Change the setting temp.

Is cooling load too heavy ?

Review cooling load estimate.

Refrigerant flow failure

4-way valve is defective.

Replace the 4-way valve.

Refrigerant shortage

Charge refrigerant gas.

Electronic refrigerant control valve is defective.

Replace the valve.

Compressor is defective.

Replace the compressor.

Service valves are not fully open.

Open the valves fully.

Not enough air circulation

Air filter is clogged.

3
Clean the filter. Set the fan speed to either MEDIUM or HIGH.

Is fan speed set to LOW ?

4
Refrigerant tubes between indoor and outdoor units are not insulated. Insulate wide and narrow tubes separately.
0458_M_I

5
IV - 5
SM830080

4. Service procedures

(B)

Heating
b. Heating Poor heating

Is setting temp. suitable ?

Change the setting temp.

Is heating load too large ?

Review heating load estimate.

Refrigerant flow failure

4-way valve is defective.

Replace the valve.

Refrigerant shortage

Charge with refrigerant.

Electronic refrigerant control valve is defective.

Replace the valve.

Compressor is defective.

Replace the compressor.

1
Not enough air circulation

Service valves are not fully open.

Open the valves fully.

Air filter is clogged.

Clean the filter.

2 1

Is fan speed set to LOW ?

Set the fan speed to either MEDIUM or HIGH.

Refrigerant tubes between indoor and outdoor units are not insulated.

Insulate wide and narrow tubes separately.

3
Cold air is discharged. 4-way valve is defective. Replace the valve.

Cold draft prevention is not working.

STANDBY is displayed.

Replace indoor P.C.B. Ass'y.

Indoor coil sensor E2 is defective.

Replace the sensor.


0459_M_I

5
IV - 6
SM830080

4. Service procedures

(3)

Meanings of alarm messages

If an error occurred in the air conditioner, the error condition is presented by indicating the error code in the wired remote controller display or by the combination of lamp statuses for operation, timer and heat stand-by (OFF status and flashing status).
Possible causes of troubles Remote controller is detecting unusual signal from indoor unit. Error receiving of serial communications signal. Error transmitting of serial communications signal. Wired remote Wireless remote controller controller display display E01 E02 E03 E08 E09 E11 Operation lamp flashes O: Operation lamp : Timer lamp :Heat standby lamp

Serial communication errors Mis-setting

Indoor unit is detecting unusual signal from the remote controller or group control. (No serial communications signal) Improper setting of indoor unit or remote controller. Indoor unit is detecting unusual signal from signal option. Improper setting of indoor unit or remote controller. Indoor unit is detecting unusual signal from outdoor unit. Outdoor unit is detecting unusual signal from indoor unit. Indoor unit address setting is duplicated. Remote controller address (RCU.ADR) is duplicated. Error receiving of serial communications signal.

When using flexible combination control, main indoor unit address setting is duplicated. (judged by outdoor unit.) Error receiving of serial communications signal. Error transmitting of serial communications signal Error receiving of serial communications signal. (Confirmation error of unit numbers included) Error transmitting of serial communications signal.

E14 E04 E05 E06 Heat stand-by lamp flashes :Operation lamp : Timer lamp O: Heat standby lamp

E07 E15 E16 E18

Auto. address setting is not correct. Indoor unit is detecting unusual signal from another indoor unit. Improper setting of indoor unit or remote controller.

No. of judged indoor units or total capacity of indoor units is small. No. of judged indoor units or total capacity of indoor units is large. Error receiving of serial communications signal.

1
Model setting of indoor unit is not matching the outdoor unit. When using group control, main indoor unit address setting is duplicated. (judged by indoor unit.) Improper wiring between indoor units. (There is a group connection wiring in case of individual control.) Capacity code of indoor unit is not set. Improper wiring of group control wiring. L02 L03 L07 L09 L11 P09 P01 P10 P02
Operation lamp and heat standby lamp flash at the same time.

Mis-setting

O: Operation lamp : Timer lamp O: Heat standby lamp


: Operation lamp O: Timer lamp O: Heat standby lamp
Operation lamp and heat stand-by lamp flash alternately.

Improper wiring connections of ceiling panel. Activation of protective device Protective device in indoor unit is activated. Protective device in outdoor unit is activated. Thermal protector in indoor fan motor is activated. Float switch is activated. Thermal protector in outdoor fan motor is activated. PC or AC Compressor thermal protector is activated. Power supply voltage is unusual. (The voltage is more than 260 V or less than 160 V between L and N phase.) Discharge gas temperature of PC comp. is unusual. High pressure switch is activated. Negative phase or voltage drops. Other indooor unit is warning.

P03 P04 P05 P31

O: Operation lamp : Timer lamp O: Heat standby lamp

5
IV - 7
SM830080

4. Service procedures

Possible causes of troubles Indoor thermistor is either open or short. Indoor coil temp. (E1 = TH2) cannot be detected. Indoor coil temp. (E2 = TH3) cannot be detected. Indoor room temperature cannot be detected. Outdoor thermistor is either open or short. Discharge gas temp.A (PC compressor=TH0A) cannot be detected. Outdoor coil liquid temp. (C1 = TH0E) cannot be detected. Outdoor coil gas temp. (C2 = TH0C) cannot be detected. Protective device for compressor is activated. PC compressor motor is overloaded. PC compressor motor is locked. Compressor current detection circuit is defective. Low-pressure protector is activated. (Low pressure switch or low pressure prevention.) Standard comp. contactor (Mg SW)is chattering. O: flashes : OFF

Wired remote Wireless remote controller controller display display F01 F02 F10 F04 F06 F07 H01 H02 H03 H06 H18 :Operation lamp O: Timer lamp :Heat standby lamp
Operation lamp and heat stand-by lamp flash alternately.

Thermistor failure

O: Operation lamp O: Timer lamp :Heat standby lamp

2 1

5
IV - 8
SM830080

Fault with compressor and its circuit

4. Service procedures

(4) LED Indication on the Outdoor Units P.C.B. Assy If something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Assy light up to show the cause of the trouble, in addition to the Alarm message on the remote controller.

LED 2 on LED 1 on Remote P.C. board P.C. board controller No message E06, E07, L04 * No message P02 P04, P05 * * * F04~F09 H01, H02 H04, H05

Possible cause of trouble Normal Outdoor unit serial communication signal is abnormal. Outdoor unit address is duplicated. Other outdoor units are performing auto address and detecting refrigerant shortage. FMo CM thermal protection is in operation. Power supply voltage is abnormal. High voltage SW activates Negative phase protector activates. Sensor is abnormal. (Open or short) Abnormal compressor current value is detected. Scroll thermal protection failure is detected. Auto address failure Auto address is in operation.

* * E15, E16 Flash at the same time * * Flash alternately NOTE SETTING flashes.

: LED lamps OFF

: LED lamps ON (lights up) *: LED lamps ON (flashes)

2
LED 1 LED 2

3
0654_C_I

Fig. 24

CAUTION

* REFRIGERANT SHORTAGE Note particularly that a shortage of refrigerant is only shown by the outdoor P.C.B. Assy LEDs and the Alarm Message does not appear on the Indoor Remote Controller . The compressor keeps running even when the refrigerant is less, so when you find the LED indication on the outdoor P.C.B. Assy, stop the air conditioner immediately to avoid the compressor damage.

IV - 9

SM830080

4. Service procedures

(5) 1)

Symptoms and parts to inspect Symptom: LCD on the remote controller does not display and remote controller does not operate.
Start

Is the LED (D80) on Yes the indoor unit PCB lit? No

Is there 12 V DC Yes between R2 and R3 on the 8P terminal plate of the indoor unit? No

Is there 12 V DC between 2 and 3 of the remote controller? Yes

No

Repair the remote controller wiring.

Miswiring of power supply wires and indoor/outdoor control lines

Yes Is there 220-240 V AC between U1 and U2 of the 8P terminal plate? No

No

Is there 220-240 V AC between R and S of the indoor PCB? Yes

Replace the remote controller.

1
Correct the wiring. Remove the socket connected to the OC plug on the PCB and connect to the EMG plug instead. Check and repair the power breaker etc.

2 1
Correct the connections No Are the connections for the 4P connector for the indoor units PCB power transformer good? Yes No Has the indoor unit PCB fuse blown? Yes

3
Replace the indoor unit power transformer.

No Is there 15 V AC between 1 and 2 of the 4P connector for the indoor units power transformer? Yes

Is the primary side of the indoor power transformer shorted? Yes

No

Is the 220-240 V AC No Replace the circuit shorted? indoor unit PCB. Yes

Replace the indoor unit PCB.

Replace the indoor units power transformer.

Replace or repair.

5
IV - 10

0332_M_I

SM830080

4. Service procedures

2) Symptom: LCD on the remote controller displays CHECK E01. (Unusual communication between remote controller and indoor unit.)
Start

Remote controller judges itself with self-diagnostic functions OK

NG

Replace the remote controller.

Is there an open or a contact defect in the No. 1 line of the remote controller? No

Yes

Correct the wiring.

Is there 220 -240 V AC between U1 and U2 of 8 P terminal plate? No

Yes

Mis-wiring between the power supply line and indoor/ outdoor unit operation lines.

Yes

Correct the wiring, and pull out the socket connected to the OC plug to replace with the EMG plug.

Is the setting for the non-volatile memory IC on the indoor unit PCB inappropriate? No

Yes

Correct the setting.

Is the indoor unit PCBs forced OPR pin shorted? No

Yes

1
Open the forced OPR pin.

Replace the indoor unit PCB.


1905_M_I

3) Symptom: LCD on the remote controller displays CHECK E02. (Unusual communication between remote controller and indoor unit)
Start

3
Is the No. 1 line wire (red) for the remote controller connected to another line (2 or 3) or are No. 1 and No. 3 (black) wired reversed? No Yes Repair the wiring.

4
Remote controller judges itself with self-diagnostic functions. (To avoid misjudgment, always remove the No. 1 line of the remote controller wiring from the indoor unit terminal plate.) OK Replace the indoor unit PCB.
0334_M_I

NG

Replace the remote controller.

5
IV - 11
SM830080

4. Service procedures

4)

Symptom: LCD on the remote controller is displaying CHECK E04. (Unusual communication between the indoor and outdoor units.)
Start

Cut the breaker and remove the indoor/outdoor unit control lines connected to U1 and U2 of the indoor unit 8P terminal plate. After shorting the test pin (CN2) on the indoor unit PCB, switch the breaker on. Does the LED (red) on the PCB light up? Yes

No

Is the contact good at the 2P connector for indoor serial communications on the outdoor unit PCB? Yes Replace the indoor unit PCB.

No

Correct the connections.

Cut the breaker, remove the indoor/outdoor unit control lines connected to U1 and U2 of the outdoor unit 8P terminal plate. After shorting the test pin (CN11) on the outdoor unit PCB, switch the breaker on. Do the LEDs (red, 2) on the PCB flash? Yes

No

Is the contact good at the 2P connector for indoor serial communications on the outdoor unit PCB?

No

Correct the connections.

Indoor/outdoor unit control lines are cut off

Replace the indoor unit PCB.

Correct the wiring.

0335_M_I

2 1

5)

Symptom: LCD on the remote controller is displaying CHECK E05. (Unusual communication between the indoor and outdoor units)
Start

3
Indoor unit PCB transmission/ reception circuit defect

Replace the indoor unit PCB.

0336_M_I

5
IV - 12
SM830080

4. Service procedures

6)

Symptom: LCD on the remote controller is displaying CHECK E06. (Unusual communication between the indoor and outdoor units)
Start

Is there a cut line or contact defect between an indoor and outdoor units control line? No Influenced by external noise

Yes

Correct wiring.

1903_M_I

* See the section of INSTALLATION INSTRUCTION concerning with flexible combination system. 7) Symptom: LCD on the remote controller is displaying CHECK E08. (Duplicate indoor unit address setting)
Start

Is the setting for the non-volatile memory IC on the indoor unit PCB inappropriate? (Are there two units with the same address?) No Influenced by external noise

Yes

Correct the setting.

1
1904_M_I

* See the section of INSTALLATION INSTRUCTION concerning with flexible combination system. 8) Symptom: LCD on the remote controller is displaying CHECK E09. (Duplicate setting of RCU address switch of remote controllers)
Start

3
Yes Correct the setting. *

Are there two remote controllers (master-slave) installed with both remote controllers set as masters? No Replace the remote controller.

4
0339_M_I

* See the section of INSTALLATION INSTRUCTION concerning with controlling remote controller switches when there are two remote controllers.

5
IV - 13
SM830080

4. Service procedures

9)

Symptom: LCD on the remote controller displays CHECK P01. (Indoor fan protection thermostat operation warning)
Start

Is there 220-240 V AC between S4 and T20-3 on the indoor unit PCB? Yes No

Yes Is there 220-240 V AC between T20-3 and S4 after T20-1 and T20-3 on the indoor unit PCB shorted? No Is the indoor fan wire winding protection thermostat (49FI) off? Yes

No Correct the connection

Replace the indoor fan. Replace the indoor unit PCB.


0340_M_I

2 1

5
IV - 14
SM830080

4. Service procedures

10) Symptom: LCD on the remote controller displays CHECK P02. (Compressor / outdoor fan protection thermostat operation warning / power supply voltage abnormality)
Start

Is the power supply to the outdoor No unit normal? (Voltage / defective phase?) Yes Yes

Check the power breaker etc. and repair.

Is the fuse on the outdoor unit PCB blown (F1 and F2)? No

Replace the fuse.

Is the high voltage switch (63 PH) off? No

Yes

Replace the outdoor unit PCB.

Yes Is there 220-240 V AC between CN19-9 and CN19-1 on the outdoor unit PCB? No

Replace the outdoor unit PCB.

No Is the outdoor fan wire winding protection thermostat (49FO) off? Yes

Is the compressor protection thermostat (49C) off except 48 type? Yes

No

Replace the outdoor fan.

No refrigerant High load 4-way valve defect Clogged refrigerant circuit Electronic refrigerant control valve defect (indoor unit)

3
Yes

Is there connector contact defect? No

Correct the connection

4
0342_M_I

Replace the outdoor unit PCB.

5
IV - 15
SM830080

4. Service procedures

11) Symptoms: LCD on the remote controller displays CHECK P03. (Alarm for unusual discharge temp. of compressor)

Start

Unusual discharge gas temperature Refrigerant shortage Clogged refrigerant circuit Electronic refrigerant control valve defect (indoor unit)
0343_M_I

12) Symptom: LCD on the remote controller displays CHECK P04. (High-pressure switch activation warning)
Start

The system does not operate again.

No

Yes

Are there connection defects in the wiring? No

Yes

Repair the wiring.

High-pressure switch activation (Both cooling and heating) Electronic refrigerant control valve defect Refrigerant over-charged (Cooling) Outdoor unit, heat exchanger dirty, clogged Outdoor unit air short Outdoor fan stopped (Heating) Outdoor unit air short Indoor unit, heat exchanger dirty, clogged Large pipe side service valve closed Indoor fan stop Air filter clogged

High-pressure switch defect

2 1

0344_M_I

5
IV - 16
SM830080

4. Service procedures

13) Symptom: LCD on the remote controller displays CHECK P05. (Negative phase detection operation warning)
Start

Is the power supply to the outdoor unit normal? (Voltage defective phase?) Yes

No

Check the power breaker etc. and repair

Does the outdoor unit operate when two of the three phases are changed? (Actuation of negative phase protector) No

Yes

No problem

Is the fuse (F1, F2) on the indoor unit PCB blown? No

Yes

Replace the fuse.

Is there a contact defect in the 3P connector? No

Yes

Correct the connection

Replace the outdoor PCB


0345_M_I

14) Symptom: LCD on the remote controller displays CHECK E15.


Start

2
Yes Repair the wiring.

When the group of the units are installed, is there any mis-cross between interunit control wiring and refrigerant tubing? No

3
Yes Select an indoor unit which matches with the outdoor capacity.

Are the total capacities of indoor units to that of outdoor units less than 93%? No

Are there no contact failure between outdoor and indoor units? No

Yes

Check the contact.

Perform the same as CHECK E04.


0646_M_S

5
SM830080

IV - 17

4. Service procedures

15) Symptom: LCD on the remote controller displays CHECK E16.


Start

When the group of the units are installed, is there any mis-cross between inter unit control wiring and refrigerant tubing? No Are the total capacities of indoor units to that of outdoor units more than 107%? No

Yes

Repair the wiring.

Yes

Select indoor units which match with the outdoor capacity.

Confirm less than 5 indoor units are connected. No


0647_M_S

16) Check P9 is displayed on the remote control unit.

Start

Is 15P connector socket (RED) being attached to panel connected firmly with 15P plug?

Yes

Connect firmly.

2 1

Yes

Replace P.C.B. Assy in the indoor unit.


0649_M_S

5
IV - 18
SM830080

4. Service procedures

17) Symptom: LCD on the remote controller displays CHECK H01, H02, H03. (PC compressor current detection) * Please check the related part described in the following chart after confirming the code setting (S4) of the outdoor units capacity on the PCB in the outdoor unit.
Start

CHECK H01 display Compressor overload detection

CHECK H02 display Compressor lock detection

CHECK H03 display Compressor current detection circuit defect

Insufficient voltage Comp. motor magnetic contactor defect Refrigerant over-charged

Compressor lock

L3 phase wire disconnected Comp. motor magnetic contactor defect Outdoor unit PCB defect
0346_M_I

18) Check the indoor unit (When the alarm of communication failure is not activated) If the electronic control valve failure occurred in Flexible Combination system (simultaneous operation system), one indoor unit would not be operated normally, then the other units wont be operated either. Due to this, try to detect the troubled unit and correct it.
Operate the unit in cooling mode. (30 minutes after its operation)

2
Cooled air comes out. Is the temperature of each indoor coil sensor almost the same? (Refer to the sensor temperature display function of the remote controller.) No Yes Normal

3
Yes Failure in the electronic control valve activation.

Does each indoor coil sensor detect the temperature correctly? (Is there any leakage from the pipe of the temperature detection section?) No

Replace the sensor.


0460_M_I

5
IV - 19
SM830080

4. Service procedures

(6) 1)

Procedures When a Specific Component Does Not Work Indoor fan does not operate.
Is fan motor capacitor normal ? Yes Is there voltage output of P.C.B. Ass'y for fan motor ? Yes No Replace the capacitor.

No

Replace the P.C.B. Ass'y in the indoor unit.

Check resistance of fan motor winding. Out

Replace the fan motor.


0650_M_S

2)

Flaps in indoor units air outlet does not operate, when you press SWEEP button.
No Check the louver motor resistance. Is auto louver motor normal? Yes Replace the motor.

Is 15P connector socket (RED) attached to panel connected firmly with 15P plug ?

No

Connect firmly.

2 1

Yes

Replace P.C.B. Ass'y in the indoor unit.


0651_M_S

3)

Flap does not operate, when you press FAN AIM button. (When you press SWEEP button, flap operates.)
No Does limit switch actuate? Yes Replace the switch.

Is 15P connector socket (RED) attached to panel connected firmly with 15P plug ? Yes

No Connect firmly.

Replace P.C.B. Ass'y in the indoor unit.


0652_M_S

IV - 20

SM830080

4. Service procedures

4)

Compressor motor does not operate.


Does compressor motor magnetic No contactor (52C) actuate ? Yes Replace the compressor motor magnetic contactor.

Check resistance of compressor motor winding. NG

Replace the compressor.


0461_M_I

5)

Outdoor fan does not operate.


Are auxiliary relays (1Y, 2Y) normal ? Yes No Replace the relays.

Is fan motor capacitor normal ? Yes

No

Replace the capacitor.

Is there voltage output of P.C.B. Assy for fan motor ? Yes

No

Replace P.C.B. Assy in the outdoor unit.

Check resistance of fan motor winding. NG

Replace the fan motor.


0462_M_I

5
IV - 21
SM830080

4. Service procedures

(7) Service Functions of Remote Controller From the remote controller you can control both the operation and settings of the unit as well as perform several useful service checks. This section explains how to use the remote controller on the following items from (A) to (J). (A) Set service check switches. (B) Use the test run procedure. (C) Check the sensor temperature readings. (D) Find out about past service problems. (E) Check the remote controller itself for correct operation. (F) Excute the auto. address operation. (G) Confirm and change the indoor unit address. (H) Change the shift temperature in heating mode ( I ) Set the indoor unit address. (J) Change the period of the filter timer (A) Set service check switches

The service check switch (RCU.CK) is located on the back of the remote controllers P.C.B. Assy as follows :

2 1

RCU. ADR switch ON OFF

0354_M_I

The followings are the correct switch settings for ordinary use of the unit. Only change the settings temporarily for making service checks. When you finish the settings, be sure to return them to the standard settings shown here. t RCU.CK switch - Refer to section (E) Checking the remote controller for correct operation (Remote Control Unit, Check) t RCU.ADR switch - Keep the switch OFF all the time except in case of sub remote controller (Remote Control Unit, Address)
IV - 22
SM830080

ON OFF RCU. CK switch

4. Service procedures

(B)

Use the test run procedure t The purpose of the test run function is to let you control the operation of the unit directly without turning the unit on or off by thermostat. As indicated in the following procedure, be sure to stop test run operation when you finish the procedure, or the air conditioner may be damaged. t To protect the air conditioner from overloading, the outdoor unit will not start running for 3 minutes after power is applied or the unit is turned OFF.

a Press the TEST / CHK button at the bottom right on the remote controller. b Press the ON / OFF operation button to start the test run. c Press the MODE button to select either COOLING or HEATING mode. d When the test run starts, TEST shows on the remote controllers display. e During the test run, the air conditioner runs continuously and the thermostat does not control the system.
Alarm message
AIR FLOW UNIT FLAP MODE

C
TIMER SET

SET TEMP.

FAN SPEED
A

SET

CL

TEST
ON OFF
TEST / CHK

1
TEST RUN / CHECK button ON / OFF operation button
1152_THS_I

f After the test run, be sure to press the TEST / CHK button once again to finish this mode and make sure TEST is not shown on the display.
CAUTION

The TEST RUN button is used only for servicing the air conditioner. Do not press this button in normal operation, or the system may be damaged.

5
IV - 23
SM830080

4. Service procedures

(C) Check the sensor temperature readings The air conditioner has thermo sensors which are used to control the unit. t Each sensor has an address which is made up of the indoor unit address, and the sensor address. The indoor unit address is used only when several units are hooked up to one remote controller (group control). If there is only one unit, made up of one indoor and one outdoor unit, then only the sensor address should be put in, as shown in the procedure below. Follow this procedure to display the temperature of each sensor: a On the remote controller, press both TEST / CHK and CL buttons at the same time for more than 4 seconds.
AIR FLOW UNIT FLAP

A
UNIT No. R.C.
AIM

MODE

No. CODE No.

SET TEMP.

TIMER SET

SWEEP

SET TEMP.
SETTING

FAN SPEED

SET

CL
ON OFF
TEST / CHK

0356_M_I

b The UNIT No., the address and temperature of the sensors instead of its usual information will flash on the display. t Following example shows the UNIT No. (Indoor unit address) is fixed at 01 01. u In case of group control, select the UNIT NO. (Indoor unit address) which you want to check with UNIT button. t Each time you press the , (SET TEMP.) button you can select a different sensor, and the display shows the sensor address and temperature as shown below.
UNIT No. (Indoor unit address)
AIR FLOW UNIT FLAP MODE

2 1

UNIT No. R.C. No. CODE No.

Sensor address
SET TEMP.

TIMER SET
FAN SPEED
SETTING
DATA

Sensor temperature C

SET

CL

MONITOR

ON OFF
TEST / CHK

4
0357_M_I

NOTE Do not press TIMER SET button during the procedure.

5
IV - 24
SM830080

4. Service procedures

Refer to the table below for the relationship between the sensor address and the location of the sensor.
Relationship between the sensor address and the location of sensor Sensor Address (CODE No.) Indoor Unit 01 02 03 04 05 06 07 08 09 TH1 TH2 TH3 TH4 TH5 Location of Sensor (Themistor): C Indoor air suction Temp. Indoor coil Temp. (E1) Indoor coil Temp. (E2) Indoor coil Temp. (E3) Indoor discharge air Temp.* Discharge gas Temp. A Outdoor coil liquid Temp. (C2) Outdoor coil liquid Temp. (C1)

Outdoor Unit 0A 0B 0C 0D 0E 0F 10 11 12 13 14 NOTE

TH8

TH7 TH6

* Only for unit which has a discharge air temp. sensor (U or D type)

In case there are no sensor equipped with the unit, - - - is shown on the display. C Resetting the remote controller display to previous mode. t To reset the display, press TEST / CHK button, then the remote controller will return to previous mode. (D) Find out about past service problems

The remote controller can memorize the max. 4 most recent alarm messages, so you can see problems the unit has had, if any. Knowing what has already occurred and been fixed helps you to know what to check at present. t This function is usable even if the unit is not working. t To display the past error codes, follow the procedure below. Procedure: a On the remote controller, press both TEST / CHK and SET buttons at the same time for more than 4 seconds. b Once in this mode, display changes from the normal display to service check display as shown in the table below:
Display Change ( )

NORMAL DISPLAY Set temp. UNIT No. Hours, Minutes

SERVICE CHECK DISPLAY Code No. UNIT No. (Indoor unit address) Alarm Message

5
SM830080

IV - 25

4. Service procedures

This picture shows the service check display.


UNIT No.

UNIT No. 11 No. Refrigerant Circuit No.

R.C.

No. CODE No.

CODE No.

Alarm message

CHECK

SERVICE
0358_M_I

c. A maximum of 4 alarm messages can be accessed by pressing either SET TEMP button or as follows. MODE
NOTE
Past

Pressing CL (Clear) button will clear all the service history. Present. Past.

SET TEMP.

Present Present Past


0359_M_I

... accessed in order of Past ... accessed in order of Present

FAN SPEED

For example, if the last four alarm messages were, in order of occurrence from oldest to most recent, P01, P02, P04, and most recently E01, then the display will be shown as button four times. The 5th time you press button you can below when you press repeat the display, then the first message will be shown again.
1 2
UNIT No. R.C. CODE No. No. CODE No.

3
UNIT No. R.C. No. CODE No.

4
UNIT No. R.C. No. CODE No.

2 1

UNIT No. R.C. No.

CHECK

CHECK

CHECK

CHECK

SERVICE

SERVICE

SERVICE

SERVICE

4
If there are no alarm messages, the display shows:

UNIT No. R.C. No. CODE No.

Alarm message

CHECK

SERVICE
0360_M_I

IV - 26

SM830080

4. Service procedures

Important Never press CL (clear) button unless you want to erase the accessed data in memory. Follow the procedure below only when erasing is necessary. t To erase accessed data, press the CL button. t When erasing is finished,---- mark appears on the controllers display.
CAUTION

After checking the alarm messages, be sure to press the TEST / CHK button. (E) Check the remote controller itself for correct operation The remote controller has a self-diagnostic function to check if it works properly. Use this procedure to find out if the remote controller itself is in trouble. a Turn ON the RCU.CK switch on the back of the P.C.B. Assy in the remote controller. See section (A) for exact location. b The appearance of the display will tell you whether or not the remote controller is working correctly or not. t Normal condition All displays appear for 10 seconds, then disappear. t Unusual condition All displays flash ON and OFF for 10 seconds, then disappear.

CAUTION

After checking the panel, be sure to set the RCU.CK switch to this original OFF position.

5
IV - 27
SM830080

4. Service procedures

(F)

Execute the auto. address operation t Auto. address operation is executed by pressing the A. ADD (S1) button of outdoor units PCB usually. For your convenience it can be executed by remote controller also.

a Press the TEST / CHK and seconds. b Set CODE No. A1 with ,

) buttons at the same time for more than 4

(SET TEMP) button. In this mode, the auto. address operation is executed at each R.C. (Refrigerant Circuit) line one by one.

AIR FLOW UNIT FLAP


R.C. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING

SET

CL
ON OFF
TEST / CHK

0361_M_I

c Select R.C. No. which you want to execute the auto. address operation with UNIT button. d Press the SET button. The auto. address operation will start. CODE No. changes from flashing to ON state.

2 1

e If an error occurs during operation, the alarm message will be displayed. Check and remove the cause. If you want to stop the operation, press the CL button then the unit stands in waiting mode (Press the SET button again.) f If the automatic address operation finishes, the display will disappear. g Execute the operation of the other R.C. line in the same way by following the above steps c to d . h Complete the automatic address operation by pressing the TEST / CHK button.

5
IV - 28
SM830080

4. Service procedures

(G) Confirm and change the indoor unit address t The purpose of the above function is to let you confirm the indoor unit address after the auto. address operation, and change the indoor unit address if it is needed. a Press the TEST / CHK and seconds. ( ) buttons at the same time for more than 4

AIR FLOW UNIT FLAP


R.C. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

0362_M_I

b Select the R.C. No. which you want to change with the UNIT (up) or FLAP (down) buttons. c Press the SET button (to confirm the R.C. No.). The smallest registered indoor No. and the selected R.C. No. will be displayed. Ex: R.C. No. 3 is selected. Indoor No. 2 is the smallest indoor No. of the R.C. No. 3.
AIR FLOW UNIT FLAP
UNIT No. No. CODE No.

MODE

R.C.

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

3
0363_M_I

d Select the indoor No. which you want to change with UNIT button. Once in this mode, the fan motor of selected indoor unit will turn on and let you confirm the indoor unit address.

5
IV - 29
SM830080

4. Service procedures

e Set the required new indoor units No. by pressing the

) button.

AIR FLOW UNIT FLAP


R.C. No. CODE No.

MODE

Ex: UNIT No. 3-6: currently registered indoor unit address


SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

Required new indoor No.8: SET DATA

SET

CL
ON OFF
TEST / CHK

* In this case, UNIT No. 3 6 (current) 3 8 (NEW : after pressing the TEST / CHK button)
0364_M_I

f Press the SET button. UNIT No, SET DATA (0008) and

SETTING

changes from flashing to ON state.

g If you made a mistake, press the CL button. h Finally, press the TEST / CHK button.

i If you want to change the indoor unit address of the other R.C. No., follow the step a to h in the same way.

2 1

5
IV - 30
SM830080

4. Service procedures

(H)

Change the shift temperature in heating mode t If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off at heating mode because of the hot air temperature around ceiling level. In order to solve the problem, the shift temp. (valid while heating only) is set when shipped from factory. t If the shift temp. is not enough (ex. the indoor unit is installed at position higher than 3 m), the shift temp. can be set with remote controller from +1 to +10 deg. manually as follows:

a Press the TEST / CHK button for more than 4 seconds.

AIR FLOW UNIT FLAP

UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

0365_M_I

b In case of group control, if you want to change all units in group control collectively, proceed next step remaining ALL displayed. If you want to change a unit individually, select the indoor unit address (UNIT No.) with UNIT button. c Select the CODE No. 06 with d Choose the shift temp with , , ( (SET TEMP) button. ) button.

2
AIR FLOW UNIT FLAP
UNIT No. R.C. No. CODE No.

MODE

EX: UNIT No. 16 CODE No. 06 Shift temp. +5 deg

SET TEMP.

TIMER SET

SET TEMP.
SETTING
SET DATA

FAN SPEED

SET

CL
ON OFF
TEST / CHK

4
0366_M_I

e Press the SET button. CODE No. 06, SET DATA and

SETTING

change from flashing to ON state.

f If you made a mistake, press the CL button. g Finally, press the TEST / CHK button.
IV - 31
SM830080

4. Service procedures

(I)

Set the indoor unit address t This function is usable if the auto. address operation is not available. Indoor unit address can be set one by one by remote controller.
NOTE

1) In case of group control, branch wiring for group control should be removed temporarily. 2) In case of remote controllerless system, remote controller should be connected with the indoor unit temporarily. a Short the two terminals of DISP PIN on indoor unit PCB. (DISP PIN : Refer to P. VI2) b Press the TEST / CHK , SET and CL buttons at the same time for more than 4 seconds.

AIR FLOW UNIT FLAP

UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF

TEST / CHK

0367_M_I

2 1
c Set the CODE No. 12 to set the No. of R. C. with the , (SET TEMP) button.

3
AIR FLOW UNIT FLAP
UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING

SET DATA

SET

CL
ON OFF
TEST / CHK

0368_M_I

5
IV - 32
SM830080

4. Service procedures

d Set the No. of R. C. which you want to set with

) button.

AIR FLOW UNIT FLAP

Ex. No. of R. C. will be set 2.


UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

0369_M_I

e Press the SET button. UNIT No., CODE No. 12,

SETTING

and SET DATA (0002) change from flashing to ON state. , ( (SET TEMP) button. ) button.

f Select the CODE No. 13 to set the indoor unit No. with the g Set the indoor unit No. which you want to set with the ,

AIR FLOW UNIT FLAP

UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

Ex. Indoor unit No. 4 will be set. In this example, indoor unit address (UNIT No.) will be set 24.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

2
0370_M_I

h Press the SET button. UNIT No., CODE No. 13, state.

SETTING

and SET DATA (0004) change from flashing to ON

5
IV - 33
SM830080

4. Service procedures

i Select the code No. 14 to set group setting with the j Set the No. of group setting as shown below with the

, ,

(SET TEMP) button. ( ) button.

AIR FLOW UNIT FLAP

UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

Nos. of group setting. 0 : Standard system (except group control) 1 : Main indoor unit in case of group control 2 : Sub indoor unit in case of group control 99: No setting (at factory shipment)

0371_M_I

k Press the SET button. UNIT No., CODE No. 14,

SETTING

and SET DATA change from flashing to ON state.

l If you made a mistake, press the CL button so that setting returns to the initial state. m Press the TEST / CHK button to finish this mode. The display is disappeared.

n Confirm the indoor unit address (UNIT No.) with the UNIT button after pressing the ON / OFF button. o Finally, remove the short circuit of DISP PIN. And in case of group control, be sure to restore the branch wiring to its original wiring. In case of remote controllerless system, remove the remote controller.

2 1

5
IV - 34
SM830080

4. Service procedures

(J) Change the period of the filter timer t If the period of filter timer is not suitable (for example in case of dirty environment), the period can be shortened to half as follows: a Press the TEST / CHK button for more than 4 seconds.

AIR FLOW UNIT FLAP

UNIT No. R.C. No. CODE No.

MODE

SET TEMP.

TIMER SET
FAN SPEED
SETTING
SET DATA

SET

CL
ON OFF
TEST / CHK

0213_M_I

b In case of group control, if you want to change all units in group control collectively, proceed next step remaining ALL displayed. If you want to change a unit individually, select the indoor unit address (UNIT No.) with UNIT button. c Select the CODE No. 02 with d Change the No. from 0 to 1 with , , (SET TEMP) button. ( ) button. EX: UNIT No. 16 CODE No. 02 T type 150 hr

AIR FLOW UNIT FLAP

UNIT No. R.C. No. CODE No.

MODE

75 hr

SET TEMP.

TIMER SET

SET TEMP.
SETTING
SET DATA

FAN SPEED

SET

CL
ON OFF
TEST / CHK

3
0214_M_I

e Press the SET button. CODE No. 06, SET DATA and

SETTING

change from flashing to ON state.

f If you made a mistake, press the CL button. g Finally, press the TEST / CHK button.

5
IV - 35
SM830080

4. Service procedures

4-2 Checking the Electrical Components


(1) Measurement of Insulation Resistance

The insulation is in good condition if the resistance exceeds 1 M. 1 Power Supply Wires
Earthed wire

Clamp the earthed wire of the Power Supply wires with a lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. 25) Then measure the resistance between the earthed wire and the other power wire. (Fig. 25) 2 Indoor Unit
Probe

Clip

Insulation tester
0638_X_S

Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on high voltage terminal on the terminal plate (Fig. 26) See Fig. 22. 3 Outdoor Unit (SPW-CR253EHL5)

Fig. 25
Terminal plate

Probe

2 1

Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on 1 and then 2 on the 8 or 6P terminal plate. (Fig. 26) See Fig. 22.

Clip Copper tube or metallic part Insulation tester


0639_X_S

Outdoor Unit (SPW-CR253EHL8, SPW-CR363GHL8, SPW-CR483EHL8)

Fig. 26

Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on 5 and then 6, and then 7 on the 8P terminal plate. (Fig. 26) See Fig. 23.

5
IV - 36
SM830080

4. Service procedures

(2)

Measurement of Insulation Resistance for Electrical parts


Probe

Disconnect the connector of the desired electric part from terminal plate, P.C.B. Assy, etc. (Fig. 27) Similary, disconnect the lead wires from compressor, capacitor, etc. (Fig. 28) Measure the resistance in the same manner as illustrated on the right. Refer to Electrical Wiring Diagram.
NOTE
Clip Copper tube or metallic part

Insulation tester

0640_X_S

Fig. 27
From fan motor, compressor and other parts.

If the probe does not enter the hole because the hole is too narrow, use a probe with a thinner pin.
Metallic part Clip

Probe

Insulation tester
0641_X_S

Fig. 28

5
IV - 37
SM830080

4. Service procedures

(3)

Checking the Protective Devices Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device. Then check continuity among plugs (and/or sockets) terminal as in Fig. 29. Normality of the protective device can be judged by the following table. The Protective Device is proved normal if there is a continuity between terminals.
socket

Multimeter

0642_X_S

Fig. 29

Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit Disconnect 9P connector (WHT) which leads to the indoor fan motor (FMI). Check the sockets terminals between No. 8 (GRY lead wire) and No. 9 (GRY lead wire). Only for the SPW-C253EH8 and SPW-C363EH8. Disconnect the 8P connector (white), and the 9P connector (white) on the P.C. board, and check 8P (white) plugs No. 4 (GRY lead wire) and sockets No. 9 (GRY lead wire) on the P.C.board. Disconnect 8P connector(s) (WHT) which lead(s) to the outdoor fan motor (FMO). Check sockets terminal between No. 3 (GRY lead wire) and No.4 (GRY lead wire). Disconnect the socket (63PH) of 3P (red) connecting to the P.C. board, and check both sides (1 (white), 3 (red)).

2 1

Compressor motor thermal protector (49C) . . . . . . Outdoor unit

Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit

High pressure switch (63PH) . . . . . . Outdoor unit

5
IV - 38
SM830080

4. Service procedures

(4)

Checking the Electrical Parts 1 Power transformer (TR1) ................. Indoor unit Primary *Measure the coil resistance.

; Measure the resistance between No.1 and No.3 (WHT lead wires) terminals of 3P (WHT) socket connected to power transformer. 14V ; Measure the resistance between No.1 and No.2 (RED lead wires). 10V ; Measure the resistance between No.3 and No.4 (BRN lead wires).

Secondary

Refer to 1-3 Other component specifications. 2 Power transformer (TR) ............ Outdoor unit Primary *Measure the coil resistance.

; Measure the resistance between No.1 and No.3 (WHT lead wires) terminals of 3P(WHT) socket jointed to power transformer. 14 V ; Measure the resistance between No.1 and No.2 (BRN lead wires). Refer to 1-3 Other component specifications.

Secondary

Indoor fan motor (FMI) ............... Indoor unit

*Measure the coil resistance.

Measure the resistance between each terminal of 9P (WHT) socket connected to the indoor fan motor. Refer to 12(A) Major component specifications.

4 Outdoor fan motor (FMO) ........... Outdoor unit

*Measure the coil resistance.

Measure the resistance in the same manner as explained above 3. Refer to 12(B)Major component specifications.

2
Multimeter

Fan motor capacitor ............ Both in indoor and outdoor unit Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 30. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value. The capacitor is good if the pointer bounces to a great extent and then gradually returns to its original position.
NOTE

The range of deflection and the deflection time differ according to the capacity of the capacitor.

Fig. 30 IV - 39

Fan motor Capacitor


0643_X_S

5
SM830080

4. Service procedures

Solenoid coil of the electronic refrigerant control valve (ERCV) Indoor unit

*Measure the coil resistance.

Measure the resistance between No. 5 (GRY lead wire) and other terminals (another color of lead wires) of 5P (WHT) plug connected to the solenoid coil. Refer to 1-2-(A) Major component specifications.

Compressor motor (CM) Outdoor unit In case of triple -phase compressor

*Measure the coil resistance.

Measure the resistance between R (RED lead wire) and S (WHT lead wire) terminals, R and T (BLU lead wire) terminals and S and T terminals on the compressor motor magnetic contactor. In case of single -phase compressor Remove the cover of compressor terminal and measure the resistance between terminals. Refer to 1-2 Major component specifications. 8 Compressor motor magnetic contactor (52C) Outdoor unit Measure the resistance between A (ORG lead wire) and B (GRY lead wire) terminals on the compressor motor magnetic contactor. Refer to 1-3 Other component specifications. Check the continuity between contactors. MODEL Push button on the magnetic contactor no press press FMCA1S / FC1SZ607 Pair of terminals RU YES SV YES TW YES 31 32 YES

2 1

Solenoid coil of 4-way valve (20S) Outdoor unit *Measure the coil resistance. Measure the resistance between No.1 (BLU lead wire) and No.2 (BLU lead wire) terminals of 2P (YEL) socket connected to the solenoid coil. Refer 1-3 Other component specifications.

5
IV - 40
SM830080

4. Service procedures

Fuse on indoor and outdoor P.C.B. Assy . Both in indoor and outdoor unit *Check the continuity. Remove the P.C.B. Assy from the electrical component box. Then pull out the fuse from the P.C.B. Assy. (Fig. 31)

Fuses

Fuses

Indoor P.C.B. Assy


0644_X_S

Outdoor P.C.B. Assy


0653_X_S

Fig. 31

Then check the continuity of the fuse by using the multimeter. (Fig. 32)

Fuse

1
0645_X_S

Fig. 32

5
IV - 41
SM830080

4. Service procedures

(5)

Sensor and Solenoid Layout Diagram

Indoor Unit SPW-XR253GH56

SPW-XR363GH56 SPW-XR483GH56
Electronic expansion valve Electronic expansion valve

TH2 (E1), (RED) TH2 (E1), (RED) TH3 (E2), (BLK)

TH4 (E3), (BRN) TH3 (E2), (BLK) TH4 (E3), (BRN)


1250_X_I 1251_X_I

2 1

5
IV - 42
SM830080

4. Service procedures

Indoor Unit SPW-TR253GH56

TH3 (E2), (BLK)

TH4 (E3), (BRN)

TH2 (E1), (RED)

Electronic expansion valve

1218_THS_I

SPW-TR363GH56, SPW-TR483GH56

TH3 (E2), (BLK)

TH2 (E1), (RED) Electronic expansion valve TH4 (E3), (BRN)

1219_THS_I

5
IV - 43
SM830080

4. Service procedures

Indoor Unit SPW-DR253GH56


Electronic expansion valve

SPW-DR363GH56 SPW-DR483GH56
Electronic expansion valve

TH2 (E1), (RED) TH4 (E3), (BRN)


TH4 (E3), (BRN)

TH3 (E2), (BLK) TH2 (E1), (RED)


1255_D_I

TH3 (E2), (BLK)


1256_D_I

TH5 (GRN), (Discharge Air)

Fan Fan motor

1263_C_I

1
SPW-UR253GHN56 SPW-UR363GHN56 SPW-UR483GHN56
TH3 (E2), (BLK)

2 1

TH3 (E2), (BLK) TH4 (E3), (BRN) TH2 (E1), (RED)

TH2 (E1), (RED) TH4 (E3), (BRN)

3
Electronic expansion valve Electronic expansion valve

4
1257_U_I 1258_U_I

Heat exch

5
TH5 (Discharge Air)
1264_C_I

IV - 44

SM830080

4. Service procedures

Outdoor Units SPW-CR253EHL5, SPW-CR253EHL8

TH6, 7, 8 20S, 63PH

TH8 (GRN) ( Discharge gas)

20S

TH7 (C2), (RED)

CM CH
TH6 (C1), (BLK)

0582_C_S

0583_C_S

SPW-CR363EHL8

TH6, 7, 8

TH7 (C2), (RED)

20S

63PH TH8 (GRN) ( Discharge gas)


TH6 (C1), (BLK)

4
0585_C_S

CM CH

0584_C_S

5
IV - 45
SM830080

4. Service procedures

Outdoor Units SPW-CR483EHL8


TH6, 7, 8

20S

TH7 (C2), (RED)

63PH TH8 (GRN) ( Discharge gas)


TH6 (C1), (BLK)

CM CH

0585_C_S

0586_C_S

2 1

5
IV - 46
SM830080

4. Service procedures

(6) Thermistor Characteristic Curve (1) Room temp. sensor : TH1 (KTEC-35) TH5 (KTEC-35) (2) Indoor heat exch. coil sensor : TH2(E1), TH3(E2), TH4(E3) Outdoor heat exch. coil sensor : TH6(C1), TH7(C2) ( PBC-41E)
40 35 30

( PB3M-41E)

10 9

Resistance (kn )

8 7 6 5 4 3 2 1 10 15 20 25 30 35 40

Resistance (kn )

25 20 15 10 5 0 20 15 10 5 0 5 10 15 20
0375_M_I

Temperature (C)

Temperature (C)
0374_M_I

(3) Compressor discharge gas temp. sensor : TH8 (PTC-51H)

7 6

Resistance (kn )

5 4 3 2 1

4
80 90 100 110 120 130
0376_M_I

Temperature (C)

5
SM830080

IV - 47

4. Service procedures

(7) P.C.B. Setting q Setting of outdoor control PCB (A) Standard control (single outdoor unit) In case of single outdoor unit installation, even if in case of twin, triple or quartet type (2, 3 or 4 indoor units), no setting necessary. Keep factory shipment state (R.C. address is set in 0). In this case, auto. address operation takes place automatically for the first time when the power is switched on. This takes about a few minutes. (B) Group control (Multiple outdoor units) In case of group control (up to 8 indoor units can be connected with one remote controller), before turning the power supply on set the R.C. address with S2, S3 on the outdoor control PCB. R.C. address: Refrigerant circuit address 1 ~ 30. Regarding the example of R.C. address for group control, please refer to page 53 and sec. 12-3 (page 87). (C) Central control (when using the system controller) In case of central control (when using the system controller,that is, when linking outdoor units in a network), (a) Before turning the power supply on, set the R.C. address with S2, S3 on the outdoor control PCB. (b) Remove the short plug (CN4, 2P Black) from all outdoor units except any one of outdoor unit. Regarding the example of R.C. address for central control and the position of CN4, please refer to page 54 and sec. 12-3 (page 87).

2 1

q Setting of indoor control PCB No setting necessary. Each indoor unit address (UNIT No.: R.C. No.) is decided after auto. address operation. Indoor unit No. Refrigerant Circuit No. (R.C. address) Manual setting for indoor unit address can be performed also by remote controller.

5
IV - 48
SM830080

4. Service procedures

(8) R.C. Address Setting Method Outdoor unit R.C. address setting method In case of group control or central control, set the R.C. address to 1, 2, 3, ... according to the No. of outdoor units.
Outdoor control PCB CN4 (2P Black) Refrigerant circuit address (factory setting = 0) Refrigerant circuit address (black)
0

: S2

Refrigerant circuit address (2P DIP switch, green or Blue)


10 20 position position ON ON side : S3 1 2 OFF side

A. ADD (S1): Automatic address setting start button Used for central control (link system) and group control (Normally, not used)
1576_C_I

R.C. address 00 auto address (0 when shipped from factory)

R.C. address (S3 2P dip switch, green)


ON ON side

R.C. address (S2 Rotary switch, Black)


0

Both OFF
1 ON 2 OFF side ON side
2

Set to 0

02 (In case of No. 2 outdoor unit)

Both OFF
1
ON

Set to 2
2 OFF side
ON side

03 (In case of No. 3 outdoor unit)

Both OFF
1 ON 2 OFF side ON side

Set to 3

11 (In case of No. 11 outdoor unit)

10s digit ON
1 ON 2 OFF side ON side

Set to 1
1

21 (In case of No. 21 outdoor unit)

20s digit ON
1 2 OFF side

Set to 1
ON ON side
0

30 (In case of No. 30 outdoor unit)

10s digit and 20s digit ON

3
Set to 0

OFF side

5
IV - 49
SM830080

4. Service procedures

(9) Automatic Address Setting Method For group control and central control with multiple outdoor units Carry out automatic address setting with the remote controller. (1) All auto. address operation 1 Press the TEST / CHK and ( ) buttons at the same time for more than 4 seconds. 2 Press the SET button after confirming the CODE No. AA (CODE No. AA: All Auto. address operation).

7 Complete the auto. address operation by pressing the TEST / CHK button.
NOTE

Required time for auto. address operation: In case of group control : a few minutes for each R.C. In case of central control : max. about 20 min. for each R.C. (10) Displaying Indoor / Outdoor Unit Combination Numbers

After addresses are automatically set in order for the outdoor units from Display the indoor / outdoor unit address No. 1 to No. 30, the system returns after automatic address setting. to the normal stopped state. (1) When installing multiple units, match the indoor unit address numbers and (2) Individual auto. address operation for the outdoor R.C. address numbers each refrigerant circuit and display them at an easy-to-check 1 To select each refrigerant circuit location (near the nameplate) with an individually and set addresses autooil-based magic marker or other indelmatically, press the TEST / CHK and ible marker so that the individual ( ) buttons at the same time for indoor and outdoor unit combinations more than 4 seconds, then press the can be checked. , (SET TEMP) button once to Example: set CODE No. A1. Outdoor Unit 1 Indoor Units 1-1, 1(CODE No. A1: Auto. address opera2, 1-3, .... tion) Outdoor Unit 2 Indoor Units 2-1, 22 Select R.C. No. which you want to execute the auto. address operation with UNIT button. 3 Press the SET button. The auto. address operation will start. CODE No. changes from flashing to ON state. 4 If the error is happened during the operation, the alarm message will display. Check and remove the cause. If you want to interrupt the operation, press the CL button then the unit stands in waiting mode (Press the SET button). 5 If the auto. address operation finishes, the display will disappear. 2, 2-3, .... (2) This is necessary for maintenance. Always label these. *Check indoor unit address with the remote controller. Press the TEST / CHK button for at least 4 seconds and check the indoor unit address with the UNIT button. (Each time you press the UNIT button, the address changes 1-1, 1-2, ... 2-1, 2-2, ...) The fan for only the selected indoor unit turns on at high speed, so check which indoor unit runs and label the indoor unit address. (If there is 1 outdoor unit, the addresses are 1-1, 1-2, ...) When you press the TEST / CHK button again, the system returns to normal remote control mode.
SM830080

2 1

6 Execute the operation of the other R.C. line in the same way by following the above steps 2 to 3.

IV - 50

4. Service procedures

(11) Items to Check Prior to Test Run (1) Turn on the power supply switch more than 5 hours before in order to charge the crank case heater. (2) Fully open the outdoor service valve after making the leak inspection of field connected tubing, vacuuming, and gas charging if necessary. (3) Check the capacity code and model code setting. * The factory setting is as shown in the table. Double check it. * The capacity code is set by S4 (green, 4P DIP switch) on outdoor control PCB. The model code is set by S5 (black, 2P DIP switch) on outdoor control PCB.

S4 (green or Blue) capacity code (4P DIP switch) ON ON side

OFF side

S5 (black) model code (2P DIP switch) ON ON side

OFF side
1577_C_I

R407 Models: SPW-CR type


S4. Capacity code No. Model No. 25 type (1 phase) 25 type (3 phase) 36 type (3 phase) 48 type (3 phase) Outdoor PCB 1 2 3 4 ON ON ON OFF ON ON ON OFF OFF ON OFF ON OFF OFF ON ON S5. Model code No. Model No. SPW-CR253EHL5 SPW-CR253EHL8 SPW-CR363EHL8 SPW-CR483EHL8 S5. Model code No. Model No. SPW-CR253EL5 SPW-CR253EL8 SPW-CR363EL8 SPW-CR483EL8 Outdoor PCB 1 2 OFF ON OFF OFF OFF OFF OFF OFF Outdoor PCB 1 2 ON ON ON OFF ON OFF ON OFF

5
IV - 51
SM830080

4. Service procedures

(12) Test Run Procedure


Start

Multiple remote control? No

Yes

Turn on RCU address SW of sub remote control unit

Recheck the test items before test operation.

Check the indoor and outdoor unit combination (wiring).

Yes

Single type? (One indoor unit and one remote controller for one outdoor unit)

No

Multiple indoor units for one outdoor units? No

Yes

Turn on power supply for indoor units side first Then turn on power supply for outdoor unit side. Set the outdoor unit R.C. address. Turn on power supply switch.

Group control for multiple outdoor units? No

Yes

Go next R.C. line or No

Press A. ADD (S1) button Execute auto. address operation with the remote controller.

Yes

Finish all R.C. line?

Central control for multiple outdoor units? No

Yes

CN4: Open (*) Set the outdoor unit R.C. address. Turn on power supply switch.

Go next R.C. line No or

Press A. ADD (S1) button Execute auto. address operation with the remote controller.

2 1

Yes

Finish all R.C. line?

Display the combination number.

3
Set the remote controller to test operation. Is operation possible? No Check according the self-diagnostics function table, and if there is a location to correct, correct it. Note: Check the indoor side drain water. Yes Return the remote controller to normal.

4
NOTE

End
1579_M_I

1) 2)

One of CN4 of all linked outdoor units shold be short. In case of using system controller, zone registration is required after finishing Test run. Regarding the zone registration, please refer to Installation Instructions attached with system controller.
IV - 52
SM830080

5. Appendix

5. APPENDIX
5-1 P.C.B. ..................................................................................................... V - 2

5
V - 1
SM830080

5. Appendix

5-1 P.C.B.
Outdoor Unit Control P.C.B. : SPW-CR253EHL8 , SPW-CR363EHL8 , SPW-CR483EHL8 SPW-CR253EL8 , SPW-CR363EL8 , SPW-CR483EL8
CN9 : CK.H CN8 CK.L CN7 (RED) : CHECK CN6 CN15 (GRN) : DISCH CN14 (RED) : C2 CN13 (BLK) : C1 (Used for Heatpump Type only) CN11 (YEL) : TEST
JP11 JP8 JP7 JP2 JP1

CN1 : VCC

CN10 S5 : Model code

S1 : A. ADD LED POW D13 CN52 CN53 CN51 CN12 (WHT) : CT1 CN3 (BNR) CN2 (BLU) F3 : Fuse 125V / 0.5A S2 (BLK) : R.C. Address S3 : R.C. Address LED2 : Message lamp LED1 : Message lamp S4 : Capacity code

CN4 (BLK)

CR-CR483GHL8

2 1
CN22 (YEL) : 20S (Used for Heatpump Type only)

CN27 CN23 (BLK) : 52C CN26 (WHT)

3
F2 : Fuse 250V / 3.15A F1 : Fuse 250V / 3.15A

CN34 (GRN/YEL)

4
CN33 CN32 CN31 CN30 CN54 : N1

CN25 (GRN) : 63PL (Used for 36, 48 Type only) CN24 (RED) : 63PH CN20 (WHT) : RS
1554_C_S

5
V - 2
SM830080

5. Appendix

5-1 P.C.B.
Outdoor Unit Control P.C.B. : SPW-CR253EHL5 , SPW-CR253EL5

CN9 : CK.H CN8 CK.L CN7 (RED) : CHECK CN6 CN15 (GRN) : DISCH CN14 (RED) : C2 CN13 (BLK) : C1 (Used for Heatpump Type only) CN11 (YEL) : TEST
JP11 JP8 JP7 JP2 JP1

CN1 : VCC

CN10 S5 : Model code

S1 : A. ADD LED POW D13 CN52 CN53 CN51 CN12 (WHT) : CT1 CN3 (BNR) CN2 (BLU) F3 : Fuse 125V / 0.5A CN4 (BLK) S2 (BLK) : R.C. Address S3 : R.C. Address LED2 : Message lamp LED1 : Message lamp S4 : Capacity code

1
CR-CR253GHL5

2
CN27 CN23 (BLK) : 52C CN26 (WHT)

CN22 (YEL) : 20S (Used for Heatpump Type only)

F1 : Fuse 250V / 3.15A

CN34 (GRN/YEL)

4
CN33 CN30 CN54 : N1 CN24 (RED) : 63PH CN20 (WHT) : RS
1578_C_S

5
V - 3
SM830080

5. Appendix

5-1 P.C.B.
Indoor Unit Control P.C.B. (CR-X253GH)
CN79 (RED) : HU1 CN85 (BLU) : DPH CN77 (GRN) : LM CN74 (WHT) : RN2

CN76 (BLK) : OP1 CN78 (BLU) : DP CN84 (WHT) : RN3

CN73 (BLK) : RN1

F1 : Fuse 250V / 5A CN81 (GRY) : T20

CN80 (RED) : 26H D80 (RED) : Power lamp CN75 (WHT) : VCC CN83 (WHT) : FMI JP1 (Jumper wire) : For sellecting the signal of T10. Shipment state : Pulse signal Jumper cut : Static signal

CR-X253GH
CN10 (YEL) T18 (RED) CN72

CN9 (RED) : FS

CN71 (YEL) T10 : External input and output terminal

CN7 CN34

CN8 (WHT) : LS

2 1

CN34 (GRN) : DISCHARGE AIR TEMP E P-ROM CN30 (BRN) : COIL E3 CN6 (RED) EXCT : Forced thermostat OFF input terminal
2

CN70 (WHT) : T6

HU (BLK) CN36

CN32 (BLK) : COIL E2 CN31 (RED) : COIL E1 CN33 (YEL) : ROOM TEMP CN1 (WHT) : DISP PIN CN2 (WHT) : CHECK PIN CN3 (WHT) : TEST PIN CN40 (BLU) : OC F3 : Fuse 125V / 0.5A
CN43 (BLU)

CN44 (BRN) : EMG

CN5 (WHT) : FORCED OPR CN35 (GRN) : PNL

CN41 (BLU) : Wired remote controller CN42 (BLU) : For wireless remote controller
1208_THS_I

Note when replacing the indoor unit P.C.B.

When replacing the indoor unit P.C.B. for service, remove the *E2P-ROM of the original P.C.B. then attach it to the new P.C.B. since the original E2P-ROM has it's own data (ex. indoor unit address) to identify the unit.

V - 4

SM830080

The specifications, designs, and information in this brochure are subject to change without notice.

SANYO Electric Air Conditioning Co., Ltd.


Tochigi, Japan G1100 G 500 Printed in Japan