CONTENTS
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. FIRE PUMP HOUSE FIRE BOOSTER PUMP HOUSE FIRE FOAM PUMP HOUSE FIRE ALARM CONTROL PANELS PANEL MAIN CARDS/EQUIPMENTS INSTRUMENTS USED IN FIELD SIMPLE WIRING DIAGRAM OF INPUT DEVICES LOGIC FOR WATER SPRAY IN CABLE GALLARY WATER SPRAY SYSTEM IN COVEYOR INERGEN GAS YSTM
MAIN PUMPS
HYDRANTS PUMPS
ELECTRICAL HYDRANT PUMP-1 HM-1 START 8.5 KG/CM2 F ELECTRICAL HYDRANT PUMP-2 HM-2 START 8.0 KG/CM2 F ELECTRICAL HYDRANT PUMP-3 HM-3 START 7.5 KG/CM2 F DIESEL HYDRANT PUMP-4 START 7.0 KG/CM2 F
HD-1
MAIN PUMPS
SPRAY PUMPS
ELECTRICAL WATER SPRAY PUMP-1 START 9.50 KG/CM2 F DIESEL WATER SPRAY PUMP-1 START 9.0 KG/CM2 F WS-M-1
WS-D-1
MAIN PUMPS
JOCKY PUMPS
JOCKY PUMP MOTOR ±1 JOCKY PUMP MOTOR ±2 JPM-1 HI-HI LO JPM-2 LO-LO HPT
COMPRESSORS
AIR COMPRESSOR MOTOR-1 AC-1 START 10.2 KG/CM2 F OF HPT PRESSURE AIR COMPRESSOR MOTOR-2 AC-2 START 10.0 KG/CM2 F OF HPT PRESSURE
THESE PUMPS MAINTAIN PR. AT BUNKER LEVEL AND 72.0 METER LEVEL.
RESPONSE INDICATOR HEAT DETECTOR(HD) LINE ISOLATOR INFRA RED DETECTOR(IRD) LINEAR HEAT SENSING CABLE (LHS) SIREN& HOOTER EVACUATION HOOTER MANUAL CALL POINT(MCP) ABORT SWITCH MANUAL RELEASE SWITCH
PS/IAM
DV OPEN
SOLENOID
RIAM
DV
S P R A Y EQUIPMENT
SPRAY ON
FACP
F/B OF SPRAY ON
PS/IAM
DV OPEN
SOLENOID
RIAM
FIRE ALARM LED GLOW & MASSEGE WILL APPEAR ON SCREEN & GLOBAL HOOTER WILL START
FACP OS
EER U#4 A M
U#3 A
SW-1
U#4 M
TP-2
QBD
CONV. A
IAM OF Z-1
IAM OF Z-2
IAM Z-3
CONV.-B WHEN LHS SHORTED OR QBD BROKEN DUE TO I I FIRE ±IAM WILL OPERATED ± SIGNAL GOES TO I AOPERATED± SOLENOID OPERATED FACP3± RIAM A M SPRAY TAKE PLACE± SPRAY INDICATION IN FACP3 M I A
+
ELR
PS
_
FROM FACP 24VDC
DPSW
IAM MODULE
LINE ISOLATOR
IDNET IN FROM PREVIOUS DEVICE
+ _
DPSW
+ _
NC
COM
NO
DPSW
NOT USED
_ + TO NEXT DEVICE +
1 NOT USED 2
RIAM NC
COM
NO
DPSW
NOT USED
_ + TO NEXT DEVICE +
JP1
JP1
WSD1 START 9.0KGF
AC2 9.8 KGF STOP 10.7 KGR AC1START 10. 2 KGF STOP 10.7 KGR
TANK 1
TANK 2
FROM CW P/H
HD
FOAM TANK 2
FP M1
WATER
DV
*FIRE SENSED BY HEAT DETECTORS AND SENT TO FACP1 COMMAND SENT THROUGH RIAM TO PLC PLC GENERATE COMMAND TO START FOAM P/Ps
* HEAT DETECTOR SENSES HEAT OR RATE OF RISE IN THE AIR TEMPARATURE , BASICALLY IT CONSIST THERMISTER WHICH WORK ON NEGATIVE TEMP. COFFICIENT OF RESISTENCE. WHEN TEMP. INCREASES, RESISTENCE DECREASES IN THE DETECTER SO IT DRAW MORE CURRENT , WHEN INCREASE IN THE CURRENT REACH THE PREDETERMINED VALUE THE DETECTOR GIVES THE ALARM. .
SPRAY ON
PS/IAM
FIRE DETECTION
PS/IAM
PG
TRANSFORMER
QBD
DV
EQUIPMENT
SPRAY ON
PS/IAM
RIAM/SV
PG
CABLE GALLERY
FACP DV
SPRAY ON
PS/IAM
RIAM/SV
PG
LHS/IAM
CABLE GALLERY
FACP DV