show the entry list INSYS Modem 336 for Teleservice with SIMATIC S7-200 QUESTION: Which entries are required for STEP 7 Micro/WIN 32 V3.1 to use the INSYS Modem 336? ANSWER: Proceed as follows to configure the industry modem INSYS Modem 336: 1. In STEP 7 Micro/WIN open the communications window via the menu bar "View > Communication". 2. Double-click the icon of the interface card. A window opens for setting the PG/PC interface.

3. In the window "Interface Parameter Assignment Use:" select the setting "PC/PPI cable (PPI)". 4. Then press the "Properties..." button. In this window you select the transmission rate of 19.2 kbps and "Local Modem" as the modem connection. Then close the window for interface settings. 5. Now two modems appear in the Communications Setup window, which you still have to configure.

http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 2 of 5

6. Entry for STEP 7 Micro/WIN32 for the local modem: Open the "Modem Setup" window by double-clicking the icon for the local modem.

http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 3 of 5
7. Now you must reinsert the INSYS modem. Click the "Add..." button and enter the name of the modem. A window then opens in which you must specify the following entries:

Initialization string: AT&F%C0&D0E0\G0&K0\N0X3 Communications string: S23 = 12 8. Description of the AT command: AT &F %C0 &D0 E0 \G0 &K0 \N0 X3 S0=1 S23=12 &W0 Reset to factory setting Do not permit data compression Ignore DTR Switch off echo from modem Switch off the modem-modem data flow control No data flow control Switch off error clearance No ringback identification Pick-up after first call signal (remote modem only) Set the protocol 19200, 8, E, 1 Save the initialization in the Profile 0 (remote modem only)

9. Click the "Program/Test" button. The text "Successful" must appear in the "Status" field. 10. Entry for STEP 7 Micro/WIN 32 for the remote modem: Open the "Modem Setup" window by double-clicking the icon for the remote modem. Now select the newly added modem and click the "Configure..." button. Now re-enter the character string given below:

http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 4 of 5

Initialization string: AT&F%CO&D0E0\G0&K0\N0X3S0=1S0=1 Communications string: S23 = 12 Suffix: &W0^M 11. Complete the entries by pressing the "OK" button. This complete configuration of the modem. The settings are retained even after power off. Note: The functionality of the communications connection was tested with the modem firmware version V2.200-V34_ACF_DS1. Please check the version of your modem firmware using the command ATI3. If a different firmware is loaded in the modem and no connection is set up, then please get in touch with the manufacturer of the modem. For data exchange later you must set the transmission rate of the PPI interface in the S7-200 CPU also to 19.2 kbps. You must make the following settings of the PC/PPI cable: Baud rate Switch 4 Switch 5 19.2 kbps OFF (11 Bit) ON (DTE)

Note: When using the PC/PPI cable (MLFB 6ES7 901-3BF00-0XA0) the "DTE" setting cannot be activated. This is why it is necessary to have an additional zero modem adapter between the remote modem and the PC/PPI cable. More information on data communications via modem is available in the S7-200 System Manual, section 7.4 "Communicating with Modems".

http://support.automation.siemens.com/WW/llisapi.dll/5267250?func=ll&objId=5267250... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 5 of 5
Keywords: Remote maintenance, Remote interfacing Entry ID:5267250 Date:2001-10-01 I regard this article.... Copy link