show the entry list Using an INSYS Pocket 56k modem QUESTION: Which entries are required STEP 7-Micro/WIN V3.1 to be able to use an INSYS Pocket 56k modem? ANSWER: The INSYS Pocket 56k modem is a standard modem that also supports 11-bit protocols. The following communication settings are required for an 11-bit connection:
Modem connection (local connection) CPU212, 214, 215 (Port 0), 216, 221, 222, 224, 226
Important: When using the PC/PPI cable (MLFB 6ES7 901-3BF00-0XA0), the "DTE" setting cannot be enabled. This is why it is necessary to have an additional zero modem adapter between the remote modem and the PC/PPI cable. Open the communications window in STEP 7-Micro/WIN V3.1 and select the Properties of the PC/PPI cable. The further procedure is described in the manual "S7-200 Automation System, CPU22x" in the section 7.4 "Communicating with Modem" (see Entry ID: 1109582). If you want to set up a connection between your PC and an S7-200 controller, then please proceed as follows: 1. Connect the local modem to the PC. 2. Connect the remote modem to the SIMATIC S7-200 controller via the PC/PPI cable.
http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286... 10.09.2010
Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 2 of 5
3. Take the following entry in STEP 7-Micro/WIN V3.1 as the local (upper) modem: Initialization string: AT&F&D0E0\G0&K0\N0X3 Communications string: S23=12
http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286... 10.09.2010
Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 3 of 5
4. Click "Program/Test" to transfer the initialization string to the modem. After a few seconds the message "Successful" is displayed in the "Status" area. 5. Take the following entry in STEP 7-Micro/WIN V3.1 as the remote (lower) modem: Initialization string: AT&F&D0E0\G0&K0\N0X3S0=1 Communications string: S23=12 Suffix: &W0^M
http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286... 10.09.2010
Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 4 of 5
6. Click "Program/Test" to transfer the initialization string to the modem. After a few seconds the message "Successful" is displayed in the "Status" area. Description of the AT command:
AT
Reset to works settings Ignore DTR Switch off echo from modem Switch off the modem-modem data flow control No data flow control Switch off error correction No call-connected recognition Pick-up after first ringing Setting of the protocol 19200, 8, E, 1 Saving the initialization in the Profile 0
Note: The settings are retained on the modem even after a power failure. The firmware of the tested INSYS Pocket 56k modem had the following version: V2.100-V90_2M_DLS. If a different firmware is loaded in the modem and a connection is not set up, then please get in touch with the manufacturer of the modem: INSYS GmbH Contact: Ms Anna Wels Waffnergasse 8
http://support.automation.siemens.com/WW/llisapi.dll/6242286?func=ll&objId=6242286... 10.09.2010
Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 5 of 5
D-93047 Regensburg Postfach 10 03 42 D-93016 Regensburg
With the command "ATI3" you can check whether the firmware version of your modem matches that of the tested modem. Search terms: Teleservice Entry ID:6242286 Date:2001-10-01 I regard this article.... Copy link