show the entry list Using ELSA MicroLink 56k FUN Modem for Teleservice with SIMATIC S7-200 Display part number QUESTION: Which entries are necessary for STEP7 Micro/WIN V3 to use the ELSA MicroLink 56k FUN modem for Teleservice? ANSWER: You want to use an ELSA MicroLink 56K FUN modem for Teleservice with SIMATIC S7-200. For this you need the following hardware:
l l l l

SIMATIC S7-200 CPU22x PC/PPI cable (10/11-bit) with MLFB 6ES7 901-3BF20-0XA0 9-pin gender changer with pins on both sides, available in computer specialist stores 2 ELSA MicroLink 56k FUN modem (firmware V1.01), available in computer specialist stores

The following settings must be made in STEP 7 Micro/Win V3: 1. You open STEP 7 Micro/Win and then the communications window STEP 7 Micro/WIN V3. Then select the Properties for the PC/PPI cable. Under "Local Connection" activate the "Modem connection" box. 2. Here the following communications settings are necessary: PC/PPI cable Baud rate: 9600 Switch 4 ON (10-bit) Switch 5 ON (DTE) Modem connection (Local Connection) Baud rate 9600 (PPI) 3. Acknowledge with "OK" and the following window opens: STEP7 Micro/WIN V3

http://support.automation.siemens.com/WW/llisapi.dll/2854900?func=ll&objId=2854900... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 2 of 6

4. Select the local (upper) modem with a double-click. 5. Click the "Add..." button.

6. Enter a name for the connection and close the dialog with "OK".

http://support.automation.siemens.com/WW/llisapi.dll/2854900?func=ll&objId=2854900... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 3 of 6

7. Now click "Configure..." and make the following entries:

8. Complete the input with "OK" and select the 10-bit communications mode. 9. Terminate with "OK". Since the AT command for saving the initialization has to be sent separately, you have to do this either with Hyperterminal or through the entries for the remote (lower) modem. Proceed as follows: 1. Double-click the remote (lower) modem and from the drop-down menu select the name entered previously for the connection (last entry).

http://support.automation.siemens.com/WW/llisapi.dll/2854900?func=ll&objId=2854900... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 4 of 6

2. Select "Configure..." and make the following entries:

3. Complete your entries with "OK". 4. Now the following additional entries are included in STEP7 Micro/Win V3 for a modem connection:
l l

Under "local" (upper) modem there are all the initialization commands required for both the local and the remote modem. Under "remote" (lower) modem there is the statement for saving the initialization in the modem so that it can be reloaded again automatically after a power failure.

http://support.automation.siemens.com/WW/llisapi.dll/2854900?func=ll&objId=2854900... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 5 of 6
Set up a connection from the modem to a SIMATIC S7-200 by working through the following steps: 1. Start STEP 7 Micro/WIN V3 and in the "Communications" window select the PC/PPI cable as communications hardware. 2. Open the Properties for the PC/PPI cable and check or make the following settings: PPI Baud rate 9600 Local Connection COM Port Activate "Modem connection"

3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13.

Select the port to which the modem is connected In the ensuing window click the local (upper) modem. In the drop-down menu select the connection names for the modem. Click the "Configure..." function. Connect the local modem. Select the "Program/Test" function to transfer the initialization statements to the modem. The return message "Successful" must be displayed. Complete initialization with "OK". Check or select the 10-bit communications mode and acknowledge with "OK". Select the remote (lower) modem. Select the "Configure..." function and with "Program/Test" transfer the command for saving the initialization to the modem. The return message "Successful" must be displayed.

Now all the necessary settings have been made on the ELSA MicroLink 56k FUN modem for it to be able to be used for Teleservice with a SIMATIC S7-200. You must proceed in exactly the same way for the second modem. Note: The procedure described is different from that described in the SIMATIC S7-200 system manual. The two entries for the local and remote modems are not used separately in this procedure. Since the command for saving the initialization has to be sent separately to the modem, it is the simplest solution. Description of the initialization: AT&F ATE0 ATQ0 AT&D0 ATX3 ATS0=1 AT+IFC=0,0 AT&W0 Prefix: ATDT Hang up: Tone dialing (ATDP = pulse dialing) Reset to default settings Suppress echo from modem Return messages from modem on Ignore DTR status change Ignore dial tone; evaluate busy tone Lift off after first ring Local data flow control off Save configuration in Profile 0

http://support.automation.siemens.com/WW/llisapi.dll/2854900?func=ll&objId=2854900... 10.09.2010

Siemens - Industry Automation and Drive Technologies - Service& Support - Automation... Page 6 of 6

ATH0 Suffix: ^M

Command to hang up

RETURN

Entry ID:2854900 Date:2000-08-15 I regard this article.... Copy link