06DA,DE,DH
06EV,EW
Compressor Units
3 to 40 Nominal Tons

06D,06E Compressors

A quality compressor for the


right application
The Carlyle line of 06D, 06E semihermetic compressors is designed for
light, medium, or heavy duty applications
from 3 through 40 tons. Use them with
complete confidence for air conditioning or
refrigeration, with either water-cooled, aircooled, or evaporative condensers.

Features/Benefits
System dependability
Reliable trouble-free operation and long unit
life is assured with this motor-compressor. The
hermetically sealed unit eliminates dirt, air,
and moisture contamination in the refrigeration system, and also eliminates shaft seal and
alignment problems. Compressor wear is minimized by the positive pressure lubrication
provided with a built-in oil pressure regulator
and an automatically reversible oil pump.

Operating efficiency

06E COMPRESSOR UNIT

Copyright 2002 Carrier Corporation

Power conserving capacity control valves on


Carlyle compressors provide the most efficient operation at the lowest cost. These
valves automatically match the compressor
capacity to system load variations.
Suction cutoff unloading further reduces
energy usage during unloaded operation.
Valve body shuts off passage from suction
manifold, preventing charge from unnecessarily being pulled into cylinder. This results in an
EER (Energy Efficiency Ratio) improvement of
as much as 39.5% at 33% load.
Rely with confidence on the overall protection devices built into these fine compressors.
The Time Guard circuit prevents rapid compressor cycling. High- and low-pressure
switches protect against excessive motor loads
due to refrigeration system problems.
A lightweight crankcase, made of fine grain
cast iron, meets all code pressure requirements. Large refrigerant gas passages guarantee low pressure losses and higher compression efficiency as well as providing for motor
cooling.
Sound level is kept at a minimum with a discharge line muffler. This muffler is an accessory for the 06D and 06E compressors.

Form 06D,E-3PD

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Base Unit Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,5
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-15
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16,17
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-20
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Model number nomenclature


06D

37

Product Series
06D Base Mounted Compressor
and Panel

1
Packaging
1 Domestic
Unit Design
0 Original

Capacity Control
Unloaders
2 Cyl 4 Cyl 6 Cyl
A 0
1

2
H
1

Motor Size
Horsepower*
2 Cyl 4 Cyl 6 Cyl
3
5
10
5

15
8 3
6-1/2
7-1/2

Displacement Cfm/Nominal Capacity Tons (R-22)


Example 18 = 18 Cfm = 8 Tons
CFM Cyl
Tons
08
2
3
13
4
5
18
4
8
25
6
10
28
6
12
37
6
15

Unit
1 Compressor and Panel
Installed on Base
*Standard hp ratings for R-22 units. Consult Carrier Sales Representative
for other refrigerant ratings.

V-Ph-Hz
1 575-3-60
5 208/230-3-60
6 460-3-60

Motor Design
0 Original
Motor Protection
A,E External Overloads and
Internal Thermostat

Suction Valve Location

Model number nomenclature (cont)


06E

22

---

Product Series
06E Base Mounted Compressor
and Panel

Packaging
1 Domestic

Capacity Control
V One Unloader
W 2 Unloaders

Design Revision
0 Original
1 First Revision
2 Second Revision

Not Used
V-Ph-Hz
1 575-3-60
5 208/230-3-60
6 460-3-60

Motor Design
0 Original

Not Used
Nominal Capacity Tons (with R-22)
22 20
27 25
33 30
44 40

Physical data
UNIT 06D
OPERATING WEIGHT (lb)
REFRIGERANT
COMPRESSOR 06D*
Cylinders
Bore (in.)
Stroke (in.)
Displacement (cfm at 1750 rpm)
Maximum Rpm
Oil Charge (pt)
High Side Maximum Pressure
Low Side Maximum Pressure
CONNECTIONS (in.)
Suction Valve (ODF)
Discharge Valve (ODF)

A8081
180
R-22
M808
2
2
11/4
8

H3131
250

4.5

7/
8
5/8

7/
8
5/8

A8181
E8251
E3281
265
325
325
R-134a, R-22, R-507/404A
A818
A825
A328
4
6
6
2
2
2
17/16
11/4
115/32
18.3
23.9
28
1750
5.5
8
8
450 PSIG
245 PSIG

M313
4
2
1
13

11/8
7/8

13/8
7/8

13/8
7/8

E5371
330
A537
6
2
115/16
37.1
8

13/8
11/8

*Compressors listed are for R-22 applications. For R-134a and R-507/404A an 06DR compressor is standard.
Factory compressor substitutes may be made. Contact Carrier Sales Representative.
NOTE: The 06DE8251 compressor unit with the 06DA825 compressor replaces the 06DE8241 once inventory of the
06DA824 compressor is depleted.

UNIT 06E
OPERATING WEIGHT (lb)
REFRIGERANT
COMPRESSOR 06E*
Cylinders
Bore (in.)
Stroke (in.)
Displacement (cfm at 1750 rpm)
Maximum Rpm
Oil Charge (pt)
High Side Maximum Pressure
Low Side Maximum Pressure
CONNECTIONS (in.)
Suction Valve (ODF)
Discharge Valve (ODF)

V022
600
A250
4
211/16
23/16
50
14

15/8
11/8

W027
W033
640
650
R-134a, R-22, R-507/404A
A265
A275
6
6
211/16
211/16
2
23/16
68
75
1750
19
19
450 PSIG
245 PSIG
15/8
13/8

21/8
13/8

W044
670
A299
6
211/16
27/8
99
19

21/8
15/8

LEGEND
ODF Outside Diameter Female
*Compressors listed are for R-22 applications. For R-134A an 06EM compressor is standard offering;
an 06ER compressor is standard for R-507/404A. Factory compressor substitutes may be made.
Contact Carrier Sales Representative.

Base unit dimensions


06D COMPRESSOR UNIT
NOTES:
1. For standard service practices, such as troubleshooting and refrigerant charging, allow a minimum 2-6
clearance around the unit.
2. For compressor removal, allow a minimum 3 wide
access aisle to and from the unit.
3. Local codes or jurisdiction may prevail for unit clearances.

06E COMPRESSOR UNIT


NOTES:
1. For standard service practices, such as troubleshooting and refrigerant charging, allow a minimum 2-6
clearance around the unit.
2. Recommended service space for condenser tube
removal is one condenser length at either end.
3. For compressor removal, allow a minimum 3 wide
access aisle to and from the unit.

DIMENSIONS (in.)
06E UNIT
V022
W027
W033
W044

VOLTAGE
208/230
460,575
208/230
460,575
208/230
460,575
208/230
460,575

A
481/4
481/4
501/4
501/4
501/4
501/4
501/4
501/4

B
35
29
35
29
35
29
35
35

C
367/8
367/8
367/8
367/8
367/8
367/8
367/8
367/8

D
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2

E
271/2
26
271/2
26
271/2
26
271/2
271/2

F
1
1
1
1
1
1
1
1

G
191/2
191/2
191/2
191/2
191/2
191/2
191/2
191/2

Selection procedure
I Determine refrigerant, load, saturated suction
temperature,
and
saturated
discharge
temperature.
Given:
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . R-22
Cooling Load . . . . . . . . . . . . . . . . . . . . . 40 Tons
Saturated Suction Temperature . . . . . . . . . . .40 F
Saturated Discharge Temperature . . . . . . . . .105 F
II Enter Compressor Capacities table for correct
refrigerant at required suction and discharge
temperatures. Read across until a suitable
capacity is found. Determine motor-compressor

selection, power input (kW) requirements, and


total heat rejection (THR). (Use direct interpolation where job requirements fall between
values shown. Do not extrapolate.)
Select an 06EW044 which has a cooling capacity of
42.7 tons at a saturated suction temperature of 40 F
and saturated discharge temperature of 105 F. Motorcompressor power input is 37.3 kW and total heat rejection is 53.3 tons.
Refer to Compressor Capacities notes for information
concerning basis for compressor ratings and capacity
corrections due to refrigerant superheat or subcooling.

Performance data
COMPRESSOR CAPACITIES (Tons)*
R-134a
SST

10

20

30

40

50

Cap.
kW
SDT
SST
THR

SDT
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145

Cap.
1.37
1.21
1.05
0.90
0.76
0.62
0.55
1.90
1.70
1.51
1.32
1.14
0.97
0.89
2.55
2.31
2.07
1.84
1.62
1.41
1.30
3.34
3.05
2.77
2.49
2.21
1.95
1.82
4.31
3.95
3.61
3.26
2.93
2.60
2.44
5.46
5.04
4.62
4.20
3.79
3.40
3.20

06DH3131
kW
1.78
1.83
1.84
1.83
1.78
1.70
1.64
2.02
2.12
2.19
2.23
2.24
2.21
2.18
2.22
2.38
2.51
2.62
2.68
2.71
2.71
2.36
2.59
2.79
2.96
3.10
3.19
3.23
2.42
2.72
3.00
3.25
3.46
3.64
3.71
2.44
2.77
3.13
3.46
3.76
4.02
4.14

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

*Refer to compressor capacity notes, page 14.

THR
1.88
1.73
1.58
1.42
1.27
1.10
1.02
2.47
2.30
2.13
1.96
1.78
1.60
1.51
3.18
2.99
2.79
2.59
2.39
2.18
2.08
4.02
3.79
3.56
3.33
3.10
2.86
2.74
5.00
4.73
4.46
4.19
3.92
3.64
3.50
6.16
5.83
5.51
5.19
4.87
4.54
4.38

Cap.
2.25
2.06
1.87
1.69
1.52
1.36
1.28
3.00
2.76
2.52
2.29
2.07
1.85
1.75
3.94
3.63
3.32
3.03
2.75
2.47
2.34
5.09
4.70
4.32
3.95
3.59
3.24
3.07
6.50
6.01
5.53
5.07
4.62
4.18
3.96
8.20
7.59
7.00
6.42
5.86
5.31
5.16

06DA8181
kW
2.70
2.83
2.93
3.01
3.08
3.12
3.13
3.03
3.22
3.38
3.52
3.63
3.72
3.76
3.30
3.57
3.81
4.02
4.20
4.35
4.41
3.48
3.85
4.19
4.48
4.74
4.97
5.07
3.54
4.03
4.48
4.88
5.24
5.56
5.71
3.60
4.06
4.64
5.17
5.65
6.09
6.30

THR
3.02
2.86
2.71
2.55
2.40
2.25
2.17
3.87
3.67
3.48
3.29
3.10
2.91
2.82
4.88
4.64
4.41
4.18
3.94
3.71
3.60
6.08
5.79
5.51
5.22
4.94
4.66
4.52
7.50
7.15
6.81
6.46
6.11
5.76
5.59
9.22
8.75
8.32
7.90
7.47
7.05
6.95

Cap.
2.81
2.51
2.21
1.92
1.64
1.37
1.25
3.86
3.48
3.11
2.75
2.40
2.07
1.90
5.15
4.69
4.24
3.79
3.36
2.94
2.74
6.72
6.16
5.61
5.07
4.53
4.02
3.76
8.61
7.94
7.27
6.61
5.96
5.32
5.01
10.89
10.07
9.26
8.46
7.67
6.89
6.51

06DE8251
kW
3.29
3.40
3.48
3.50
3.48
3.39
3.30
3.78
3.98
4.13
4.25
4.32
4.33
4.31
4.25
4.53
4.77
4.98
5.14
5.26
5.30
4.69
5.05
5.38
5.68
5.95
6.17
6.26
5.08
5.53
5.95
6.35
6.72
7.04
7.19
5.42
5.96
6.48
6.98
7.45
7.89
8.09

THR
3.75
3.48
3.20
2.91
2.63
2.33
2.19
4.94
4.62
4.29
3.96
3.64
3.30
3.13
6.36
5.98
5.60
5.21
4.83
4.44
4.25
8.05
7.60
7.14
6.68
6.23
5.78
5.55
10.06
9.51
8.96
8.42
7.87
7.33
7.06
12.43
11.77
11.11
10.45
9.79
9.14
8.81

Performance data (cont)


COMPRESSOR CAPACITIES (Tons)* (cont)
R-134a (cont)
SST

10

20

30

40

50

Cap.
kW
SDT
SST
THR

SDT
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145

Cap.
3.47
3.18
2.89
2.60
2.31
2.02
1.88
4.58
4.24
3.89
3.54
3.19
2.84
2.67
5.93
5.52
5.10
4.68
4.25
3.83
3.62
7.54
7.04
6.54
6.03
5.52
5.01
4.75
9.46
8.86
8.26
7.65
7.03
6.41
6.10
11.73
11.02
10.29
9.56
8.81
8.07
7.69

06DE3281
kW
4.22
4.42
4.58
4.69
4.75
4.75
4.73
4.69
4.99
5.25
5.47
5.64
5.75
5.79
5.10
5.51
5.88
6.21
6.49
6.73
6.82
5.41
5.94
6.43
6.88
7.29
7.66
7.82
5.62
6.27
6.89
7.47
8.02
8.52
8.75
5.67
6.46
7.23
7.95
8.64
9.29
9.59

THR
4.67
4.44
4.20
3.94
3.66
3.37
3.23
5.92
5.66
5.39
5.10
4.80
4.48
4.32
7.38
7.09
6.77
6.45
6.10
5.75
5.56
9.08
8.74
8.37
7.99
7.60
7.19
6.98
11.06
10.65
10.22
9.78
9.32
8.84
8.59
13.35
12.86
12.35
11.82
11.28
10.71
10.42

Cap.
4.79
4.43
4.05
3.67
3.28
2.88
2.68
6.23
5.82
5.38
4.95
4.49
4.02
3.78
7.98
7.48
6.98
6.44
5.91
5.36
5.08
10.04
9.45
8.84
8.22
7.59
6.93
6.61
12.49
11.78
11.05
10.31
9.55
8.77
8.38
15.38
14.53
13.66
12.76
11.85
10.92
10.44

06DE5371
kW
5.76
6.08
6.35
6.57
6.72
6.78
6.77
6.33
6.76
7.17
7.52
7.83
8.06
8.15
6.85
7.40
7.92
8.41
8.86
9.26
9.43
7.31
7.96
8.61
9.23
9.82
10.40
10.60
7.69
8.46
9.22
9.97
10.70
11.40
11.70
7.99
8.87
9.76
10.64
11.51
12.36
12.78

THR
6.43
6.16
5.86
5.55
5.20
4.81
4.61
8.04
7.75
7.43
7.09
6.72
6.32
6.11
9.93
9.59
9.23
8.84
8.43
8.00
7.77
12.12
11.72
11.29
10.85
10.39
9.90
9.63
14.68
14.19
13.68
13.15
12.60
12.02
11.72
17.66
17.06
16.44
15.80
15.13
14.44
14.08

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

*Refer to compressor capacity notes, page 14.

Performance data (cont)


COMPRESSOR CAPACITIES (Tons)* (cont)
R-134a (cont)
SST

90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145

10

20

30

40

50

Cap.
kW
SDT
SST
THR

SDT

Cap.
5.11
4.55
3.99
3.46
2.95
2.22
1.77
7.03
6.33
5.65
4.99
4.35
3.44
2.86
9.39
8.54
7.71
6.89
6.10
4.96
4.23
12.28
11.24
10.22
9.22
8.24
6.83
5.92
15.77
14.51
13.27
12.05
10.85
9.11
7.98
19.96
18.44
16.93
15.45
13.99
11.85
10.46

06EV022
kW
6.83
6.88
6.85
6.73
6.53
6.07
5.80
7.84
8.04
8.15
8.17
8.09
7.80
7.49
8.78
9.17
9.45
9.63
9.71
9.63
9.44
9.57
10.20
10.70
11.10
11.30
11.50
5.70
10.10
11.00
11.80
12.40
12.90
13.40
13.60
10.40
11.61
12.67
13.58
14.36
15.25
15.67

THR
7.06
6.51
5.95
5.38
4.81
3.95
3.41
9.26
8.62
7.97
7.32
6.65
5.66
5.00
11.89
11.15
10.40
9.63
8.86
7.70
6.92
15.01
14.15
13.27
12.38
11.46
10.11
7.55
18.65
17.65
16.63
15.58
14.53
12.92
11.86
22.92
21.75
20.54
19.32
18.08
16.19
14.92

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

*Refer to compressor capacity notes, page 14.

Cap.
6.64
5.73
4.82
3.92
3.05
1.75
0.96
9.40
8.32
7.25
6.18
5.14
3.64
2.69
12.77
11.50
10.22
8.96
7.71
5.90
4.75
16.84
15.33
13.82
12.32
10.83
8.66
7.26
21.72
19.93
18.14
16.35
14.58
11.96
10.27
27.54
25.42
23.28
21.15
19.04
15.90
13.85

06EW027
kW
8.52
8.39
8.08
7.56
6.83
5.20
4.20
10.10
10.30
10.20
10.00
9.53
8.40
7.33
11.55
12.04
12.33
12.40
12.24
11.55
10.78
12.69
13.57
14.24
14.68
14.88
14.71
14.28
13.40
14.80
15.90
16.70
17.30
17.80
17.70
13.64
15.49
17.09
18.44
19.54
20.67
21.07

THR
9.07
8.12
7.12
6.08
4.99
3.22
2.17
12.28
11.26
10.15
9.03
7.86
6.03
4.78
16.07
14.93
13.73
12.49
11.20
9.20
7.82
20.46
19.20
17.88
16.50
15.07
12.85
11.33
25.54
24.15
22.67
21.11
19.51
17.04
15.31
31.43
29.83
28.15
26.41
24.61
21.79
19.86

Cap.
8.13
7.25
6.35
5.45
4.55
3.22
2.36
11.09
10.05
9.01
7.95
6.84
5.33
4.31
14.64
13.43
12.20
10.96
9.72
7.87
6.65
18.90
17.47
16.02
14.56
13.09
10.89
9.43
23.96
22.27
20.56
18.82
17.08
14.46
12.71
29.95
27.95
25.92
23.86
21.79
18.66
16.56

06EW033
kW
10.30
10.40
10.40
10.10
9.68
8.55
7.48
11.90
12.30
12.50
12.60
12.40
11.80
11.00
13.20
13.97
14.56
14.96
15.15
15.02
14.62
14.25
15.40
16.37
17.15
17.72
18.16
18.16
14.90
16.50
17.90
19.10
20.10
21.20
21.60
15.07
17.13
19.00
20.67
22.14
23.91
24.80

THR
11.07
10.21
9.31
8.33
7.31
5.66
4.50
14.48
13.56
12.57
11.54
10.37
8.69
7.45
18.40
17.41
16.35
15.23
14.04
12.15
10.82
22.96
21.86
20.69
19.45
18.14
16.06
14.60
28.20
26.97
25.66
24.27
22.81
20.50
18.87
34.25
32.83
31.33
29.75
28.10
25.47
23.63

Cap.
10.92
9.84
8.78
7.77
6.79
5.40
4.53
14.81
13.46
12.14
10.87
9.63
7.86
6.74
19.62
17.95
16.31
14.72
13.17
10.94
9.52
25.49
23.44
21.42
19.45
17.53
14.74
12.95
32.61
30.10
27.63
25.20
22.82
19.36
17.12
41.17
38.11
35.09
32.12
29.21
24.93
22.15

06EW044
kW
14.70
14.90
15.00
14.90
14.70
14.10
13.60
17.00
17.40
17.70
17.90
17.90
17.60
17.20
19.10
19.90
20.60
21.00
21.30
21.40
21.20
21.10
22.30
23.30
24.20
24.80
25.30
25.50
22.70
24.50
26.00
27.20
28.30
29.40
29.90
23.90
26.20
28.30
30.10
31.60
33.50
34.40

THR
15.11
14.08
13.06
12.01
10.98
9.42
8.41
19.66
18.42
17.19
15.97
14.73
12.88
11.65
25.06
23.62
22.19
20.71
19.24
17.04
15.56
31.51
29.80
28.06
26.35
24.60
21.95
20.22
39.08
37.08
35.04
32.95
30.89
27.74
25.64
47.98
45.58
43.16
40.70
38.21
34.48
31.95

COMPRESSOR CAPACITIES (Tons)* (cont)


R-22
SST

10

20

30

40

50

Cap.
kW
SDT
SST
THR

SDT
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145

Cap.
1.48
1.34
1.20
1.05
0.92
0.78
0.72
1.96
1.79
1.62
1.46
1.29
1.14
1.06
2.52
2.33
2.13
1.94
1.75
1.57
1.48
3.18
2.96
2.73
2.51
2.28
2.08
1.97
3.96
3.70
3.44
3.18
2.91
2.68
2.55
4.79
4.51
4.23
3.95
3.67
3.38
3.24

06DA8081
kW
1.90
1.98
2.04
2.10
2.10
2.00
2.00
2.05
2.19
2.30
2.39
2.44
2.50
2.50
2.16
2.35
2.52
2.66
2.77
2.90
2.90
2.20
2.45
2.67
2.87
3.05
3.20
3.30
2.18
2.48
2.77
3.03
3.27
3.50
3.60
2.10
2.40
2.80
3.10
3.40
3.70
3.80

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

THR
2.02
1.90
1.78
1.64
1.50
1.36
1.29
2.54
2.41
2.28
2.14
1.99
1.84
1.76
3.13
3.00
2.85
2.70
2.54
2.38
2.30
3.81
3.66
3.50
3.33
3.15
2.99
2.90
4.58
4.41
4.23
4.04
3.85
3.67
3.57
5.38
5.21
5.03
4.84
4.64
4.44
4.33

Cap.
2.26
2.02
1.78
1.54
1.32
1.11
1.00
3.02
2.74
2.46
2.18
1.91
1.66
1.54
3.94
3.61
3.28
2.95
2.63
2.33
2.18
5.04
4.65
4.26
3.87
3.49
3.15
2.97
6.32
5.87
5.41
4.96
4.52
4.12
3.91
7.70
7.21
6.72
6.23
5.75
5.26
5.02

06DH3131
kW
3.02
3.11
3.16
3.20
3.10
3.00
2.90
3.29
3.46
3.59
3.68
3.71
3.70
3.70
3.47
3.73
3.95
4.13
4.25
4.30
4.30
3.56
3.91
4.23
4.50
4.72
4.90
5.00
3.52
3.98
4.39
4.77
5.10
5.40
5.50
3.30
3.90
4.40
4.90
5.40
5.80
5.90

THR
3.12
2.90
2.68
2.44
2.21
1.96
1.84
3.96
3.73
3.48
3.23
2.97
2.71
2.58
4.93
4.67
4.41
4.13
3.84
3.57
3.42
6.05
5.76
5.46
5.16
4.84
4.54
4.38
7.32
7.00
6.66
6.32
5.97
5.65
5.47
8.65
8.32
7.98
7.63
7.27
6.90
6.71

Cap.
3.35
3.02
2.69
2.36
2.04
1.73
1.58
4.44
4.05
3.67
3.28
2.90
2.55
2.37
5.73
5.28
4.84
4.39
3.94
3.52
3.31
7.26
6.74
6.22
5.69
5.17
4.69
4.44
9.04
8.44
7.83
7.23
6.62
6.07
5.78
10.95
10.31
9.66
9.00
8.35
7.69
7.36

06DA8181
kW
4.16
4.32
4.42
4.45
4.40
4.30
4.20
4.57
4.85
5.07
5.22
5.30
5.30
5.30
4.86
5.26
5.61
5.90
6.12
6.30
6.30
5.01
5.55
6.03
6.46
6.82
7.10
7.20
4.99
5.67
6.30
6.88
7.40
7.80
8.00
4.80
5.60
6.40
7.10
7.80
8.40
8.70

THR
4.54
4.25
3.95
3.63
3.29
2.95
2.78
5.74
5.44
5.11
4.77
4.41
4.06
3.87
7.12
6.78
6.43
6.07
5.68
5.30
5.11
8.68
8.32
7.93
7.53
7.11
6.71
6.50
10.46
10.05
9.63
9.19
8.72
8.30
8.07
12.31
11.90
11.48
11.03
10.57
10.08
9.83

*Refer to compressor capacity notes, page 14.


NOTE: To ensure proper motor cooling, it is required that all 6-cylinder
compressors operating with R-22 at 20 F SST or below have one of the
2 unloaders disconnected. Cylinder head fan required at SST of 0 F
and below for R-22 for all compressors.

Performance data (cont)


COMPRESSOR CAPACITIES (Tons)* (cont)
R-22 (cont)
SST

10

20

30

40

50

Cap.
kW
SDT
SST
THR

10

SDT
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145

Cap.
4.23
3.81
3.40
3.01
2.64
2.30
2.13
5.63
5.12
4.62
4.15
3.69
3.27
3.06
7.34
6.72
6.12
5.53
4.97
4.46
4.20
9.39
8.65
7.92
7.21
6.53
5.91
5.60
11.83
10.94
10.08
9.23
8.40
7.67
7.30
14.50
13.51
12.55
11.61
10.69
9.79
9.34

06DE8251
kW
5.27
5.54
5.75
5.90
5.99
6.00
6.00
5.76
6.15
6.49
6.77
6.99
7.10
7.20
6.15
6.67
7.14
7.56
7.91
8.20
8.30
6.41
7.07
7.68
8.24
8.75
9.20
9.40
6.50
7.31
8.08
8.79
9.46
10.10
10.30
6.40
7.40
8.30
9.20
10.00
10.80
11.20

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

THR
5.73
5.39
5.04
4.70
4.35
4.01
3.84
7.27
6.87
6.47
6.08
5.68
5.30
5.11
9.09
8.62
8.15
7.69
7.22
6.79
6.57
11.22
10.66
10.11
9.56
9.02
8.53
8.27
13.68
13.03
12.38
11.74
11.10
10.54
10.24
16.32
15.61
14.92
14.22
13.54
12.86
12.52

Cap.
5.25
4.81
4.38
3.97
3.58
3.22
3.04
6.86
6.31
5.79
5.28
4.78
4.34
4.12
8.82
8.15
7.50
6.87
6.26
5.71
5.44
11.19
10.37
9.58
8.81
8.05
7.39
7.05
14.01
13.02
12.06
11.13
10.21
9.42
9.01
17.09
15.99
14.92
13.87
12.85
11.86
11.37

06DE3281
kW
6.55
6.90
7.21
7.47
7.68
7.90
7.90
7.10
7.58
8.02
8.40
8.74
9.90
9.10
7.50
8.14
8.73
9.27
9.74
10.20
10.40
7.72
8.55
9.31
10.01
10.65
11.20
11.50
7.71
8.74
9.70
10.60
11.42
12.20
12.50
7.40
8.70
9.90
11.00
12.00
13.00
13.40

THR
7.11
6.77
6.44
6.10
5.77
5.45
5.29
8.88
8.47
8.07
7.67
7.27
6.91
6.72
10.96
10.47
9.99
9.51
9.04
8.60
8.39
13.39
12.81
12.23
11.66
11.09
10.59
10.33
16.20
15.51
14.83
14.15
13.47
12.89
12.58
19.20
18.47
17.74
17.01
16.27
15.57
15.19

Cap.
7.29
6.72
6.17
5.64
5.13
4.66
4.43
9.44
8.74
8.06
7.40
6.76
6.18
5.89
12.06
11.20
10.36
9.55
8.75
8.04
7.68
15.20
14.15
13.13
12.13
11.16
10.30
9.86
18.93
17.67
16.44
15.23
14.05
13.02
12.49
22.99
21.59
20.22
18.88
17.56
16.28
15.65

06DE5371
kW
9.17
9.67
10.11
10.48
10.79
11.00
11.20
10.03
10.74
11.37
11.93
12.41
12.80
13.00
10.69
11.65
12.52
13.29
13.98
14.60
14.90
11.05
12.30
13.44
14.49
15.42
16.30
16.60
11.02
12.61
14.08
15.43
16.66
17.80
18.30
10.50
12.50
14.30
16.00
17.60
19.00
19.70

THR
9.90
9.48
9.06
8.63
8.20
7.80
7.62
12.30
11.80
11.30
10.80
10.30
9.83
9.60
15.11
14.52
13.93
13.33
12.73
12.20
11.93
18.35
17.66
16.96
16.26
15.55
14.95
14.59
22.07
21.26
20.45
19.63
18.80
18.09
17.71
25.98
25.15
24.30
23.44
22.58
21.70
21.26

*Refer to compressor capacity notes, page 14.


NOTE: To ensure proper motor cooling, it is required that all 6-cylinder
compressors operating with R-22 at 20 F SST or below have one of the
2 unloaders disconnected. Cylinder head fan required at SST of 0 F
and below for R-22 for all compressors.

COMPRESSOR CAPACITIES (Tons)* (cont)


R-22 (cont)
SST

90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145
90
100
110
120
130
140
145

10

20

30

40

50

Cap.
kW
SDT
SST
THR

SDT

Cap.
9.85
9.01
8.20
7.41
6.61
5.75
5.30
12.78
11.75
10.77
9.80
8.83
7.81
7.28
16.31
15.05
13.85
12.68
11.50
10.28
9.65
20.50
18.99
17.53
16.11
14.69
13.24
12.49
25.43
23.63
21.89
20.18
18.49
16.76
15.89
31.19
29.05
26.99
24.97
22.96
20.93
19.90

06EV022
kW
12.30
12.90
13.40
13.90
14.30
14.70
14.90
13.40
14.20
14.90
15.60
16.20
16.80
17.10
14.30
15.40
16.30
17.20
18.10
18.90
19.30
14.80
16.20
17.50
18.70
19.80
20.90
21.50
15.00
16.80
18.40
19.90
21.30
22.80
23.50
14.80
16.90
18.90
20.80
22.60
24.30
25.20

THR
13.36
12.68
12.02
11.38
10.68
9.94
9.55
16.60
15.80
15.02
14.25
13.44
12.60
12.15
20.38
19.44
18.50
17.58
16.65
15.67
15.15
24.71
23.60
22.52
21.44
20.33
19.20
18.62
29.71
28.42
27.13
25.86
24.56
23.26
22.58
35.40
33.87
32.38
30.90
29.40
27.86
27.08

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

Cap.
12.26
11.14
10.07
9.05
8.07
7.13
6.67
16.18
14.79
13.46
12.18
10.95
9.77
9.20
20.98
19.28
17.63
16.05
14.52
13.04
12.32
26.78
24.71
22.70
20.75
18.87
17.04
16.15
33.71
31.21
28.78
26.42
24.13
21.91
20.82
41.87
38.89
36.00
33.18
30.43
27.76
26.45

06EW027
kW
15.45
16.08
16.59
16.97
17.20
17.30
17.30
17.15
18.12
18.96
19.64
20.17
20.50
20.60
18.53
19.92
21.15
22.20
23.08
23.80
24.00
19.49
21.35
23.04
24.53
25.82
26.90
27.40
19.88
22.29
24.50
26.50
28.27
29.80
30.50
19.60
22.60
25.40
28.00
30.30
32.40
33.30

THR
16.66
15.72
14.80
13.88
12.97
12.06
11.60
21.07
19.96
18.87
17.78
16.70
15.61
15.07
26.26
24.95
23.66
22.37
21.09
19.82
19.16
32.34
30.79
29.26
27.74
26.23
24.71
23.96
39.37
37.56
35.76
33.98
32.19
30.40
29.51
47.46
45.34
43.24
41.16
39.07
36.99
35.94

Cap.
13.66
12.37
11.06
9.75
8.44
7.14
6.50
17.96
16.49
14.99
13.47
11.95
10.44
9.69
23.04
21.35
19.62
17.87
16.11
14.35
13.48
28.99
27.04
25.06
23.04
21.01
18.97
17.95
35.91
33.67
31.39
29.08
26.74
24.38
23.20
43.87
41.32
38.71
36.06
33.38
30.68
29.32

06EW033
kW
17.76
18.28
18.55
18.55
18.30
17.60
17.20
19.70
20.69
21.44
21.92
22.11
22.00
21.80
21.24
22.73
23.99
24.99
25.70
26.10
26.20
22.26
24.30
26.11
27.67
28.94
29.90
30.30
22.68
25.30
27.70
29.85
31.73
33.30
34.00
22.40
25.60
28.70
31.40
34.00
36.20
37.20

THR
18.72
17.58
16.35
15.04
13.66
12.16
11.40
23.58
22.38
21.10
19.72
18.26
16.71
15.90
29.10
27.82
26.46
24.99
23.44
21.79
20.94
35.34
33.97
32.50
30.93
29.26
27.49
26.58
42.37
40.88
39.29
37.58
35.78
33.87
32.89
50.26
48.61
46.89
45.01
43.07
41.00
39.93

Cap.
18.48
17.09
15.74
14.42
13.13
11.87
11.26
23.83
22.13
20.47
18.84
17.24
15.68
14.91
30.30
28.23
26.19
24.20
22.23
20.31
19.35
38.02
35.52
33.06
30.64
28.25
25.90
24.73
47.14
44.15
41.21
38.30
35.43
32.59
31.19
57.80
54.26
50.77
47.32
43.91
40.54
38.87

06EW044
kW
24.40
25.27
25.99
26.55
27.00
27.30
27.40
27.11
28.42
29.53
30.47
31.22
31.80
32.00
29.50
31.34
32.96
34.35
35.54
36.50
36.90
31.40
33.87
36.09
38.05
39.76
41.20
41.90
32.64
35.85
38.76
41.38
43.72
45.80
46.70
33.10
37.10
40.80
44.20
47.30
50.00
51.30

THR
25.44
24.29
23.14
21.98
20.82
19.65
19.06
31.56
30.23
28.88
27.52
26.14
24.74
24.03
38.71
37.16
35.59
33.99
32.36
30.71
29.87
46.97
45.17
43.35
41.48
39.58
37.64
36.68
56.44
54.37
52.25
50.09
47.89
45.65
44.50
67.23
64.84
62.40
59.92
57.39
54.79
53.49

*Refer to compressor capacity notes, page 14.


NOTE: To ensure proper motor cooling, it is required that all 6-cylinder
compressors operating with R-22 at 20 F SST or below have one of the
2 unloaders disconnected. Cylinder head fan required at SST of 0 F
and below for R-22 for all compressors.

11

Performance data (cont)


COMPRESSOR CAPACITIES (Tons)* (cont)
R-507/404A
SST

-30

-20

-10

10

20

Cap.
kW
SDT
SST
THR

12

SDT
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130

Cap.
1.07
0.92
0.79
0.65
0.53
1.54
1.35
1.17
1.00
0.83
2.14
1.90
1.67
1.44
1.21
2.89
2.58
2.28
1.99
1.69
3.80
3.41
3.04
2.67
2.30
4.89
4.41
3.95
3.50
3.05

06DH3131
kW
2.11
2.09
2.05
1.99
1.90
2.59
2.62
2.63
2.60
2.55
3.07
3.16
3.22
3.24
3.24
3.53
3.68
3.80
3.89
3.95
4.00
4.20
4.40
4.50
4.70
4.30
4.70
4.90
5.20
5.40

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

THR
1.67
1.52
1.37
1.22
1.07
2.28
2.10
1.92
1.74
1.56
3.02
2.80
2.58
2.36
2.14
3.90
3.63
3.36
3.10
2.82
4.94
4.61
4.29
3.95
3.64
6.11
5.75
5.35
4.98
4.59

Cap.
1.95
1.76
1.58
1.38
1.18
2.62
2.40
2.17
1.93
1.68
3.41
3.15
2.87
2.58
2.27
4.35
4.03
3.70
3.34
2.97
5.46
5.07
4.67
4.25
3.80
6.73
6.27
5.79
5.30
4.78

06DA8181
kW
3.68
3.78
3.84
3.86
3.84
4.27
4.44
4.58
4.68
4.75
4.82
5.07
5.29
5.48
5.64
5.33
5.66
5.97
6.25
6.50
5.80
6.20
6.60
7.00
7.30
6.20
6.70
7.20
7.60
8.10

THR
3.00
2.84
2.67
2.48
2.27
3.83
3.66
3.47
3.26
3.03
4.79
4.59
4.38
4.14
3.88
5.87
5.65
5.40
5.12
4.83
7.11
6.84
6.55
6.24
5.89
8.50
8.18
7.85
7.46
7.09

Cap.
2.30
2.04
1.77
1.50
1.23
3.19
2.87
2.54
2.21
1.87
4.21
3.88
3.48
3.07
2.65
5.54
5.07
4.59
4.09
3.57
7.23
6.59
5.95
5.30
4.63
9.16
8.37
7.58
6.77
5.98

06DE8251
kW
4.34
4.36
4.34
4.25
4.09
5.14
5.27
5.34
5.36
5.31
5.93
6.15
6.33
6.46
6.53
6.68
7.00
7.29
7.53
7.72
7.37
7.84
8.26
8.60
8.88
7.85
8.51
9.09
9.61
10.00

THR
3.54
3.28
3.01
2.71
2.39
4.66
4.37
4.07
3.74
3.38
5.90
5.63
5.28
4.91
4.51
7.44
7.07
6.67
6.24
5.77
9.33
8.82
8.30
7.75
7.16
11.39
10.80
10.17
9.51
8.83

*Refer to compressor capacity notes, page 14.


NOTE: To ensure proper motor cooling, it is required that all 6-cylinder
compressors operating with R-507/404A at 10 F SST or below have
one of the 2 unloaders disconnected. Cylinder head fan required at SST
of 20 F and below for R-507/404A for all compressors.

COMPRESSOR CAPACITIES (Tons)* (cont)


R-507/404A (cont)
SST

-30

-20

-10

10

20

Cap.
kW
SDT
SST
THR

SDT
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130

Cap.
2.99
2.69
2.37
2.04
1.69
4.04
3.69
3.32
2.93
2.52
5.27
4.86
4.43
3.97
3.47
6.71
6.22
5.71
5.16
4.57
8.37
7.79
7.18
6.54
5.86
10.29
9.60
8.89
8.13
7.33

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

06DE3281
kW
5.52
5.61
5.61
5.51
5.30
6.42
6.67
6.84
6.93
6.91
7.20
7.62
7.97
8.24
8.41
7.83
8.43
8.96
9.42
9.80
8.30
9.10
9.80
10.40
11.00
8.50
9.50
10.40
11.30
12.10

THR
4.56
4.29
3.97
3.61
3.20
5.87
5.59
5.27
4.91
4.49
7.32
7.03
6.70
6.32
5.87
8.94
8.62
8.26
7.85
7.36
10.74
10.39
9.98
9.50
8.99
12.71
12.31
11.85
11.35
10.78

Cap.
4.09
3.69
3.30
2.92
2.55
5.40
4.89
4.38
3.89
3.40
7.03
6.37
5.72
5.09
4.46
9.02
8.19
7.37
6.55
5.75
11.41
10.38
9.36
8.36
7.36
14.26
13.01
11.76
10.53
9.31

06DE5371
kW
7.37
7.59
7.77
7.92
8.04
8.60
8.92
9.20
9.44
9.64
9.85
10.30
10.70
11.10
11.40
11.10
11.70
12.20
12.70
13.20
12.20
13.00
13.70
14.40
15.00
13.20
14.20
15.20
16.00
16.80

THR
6.19
5.85
5.51
5.18
4.84
7.85
7.43
7.00
6.58
6.15
9.83
9.31
8.77
8.25
7.71
12.18
11.52
10.84
10.17
9.51
14.89
14.09
13.27
12.46
11.64
18.02
17.05
16.09
15.09
14.10

*Refer to compressor capacity notes, page 14.


NOTE: To ensure proper motor cooling, it is required that all 6-cylinder
compressors operating with R-507/404A at 10 F SST or below have
one of the 2 unloaders disconnected. Cylinder head fan required at SST
of 20 F and below for R-507/404A for all compressors.

13

Performance data (cont)


COMPRESSOR CAPACITIES (Tons)* (cont)
R-507/404A (cont)
SST

90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130
90
100
110
120
130

-30

-20

-10

10

20

Cap.
kW
SDT
SST
THR

SDT

Cap.
5.40
4.80
4.16
3.48
2.78
7.40
6.71
5.98
5.21
4.39
9.74
8.94
8.10
7.20
6.23
12.46
11.53
10.54
9.48
8.33
15.61
14.50
13.33
12.09
10.78
19.23
17.92
16.55
15.10
13.58

06EV022
kW
11.00
10.90
10.70
10.30
9.57
13.00
13.20
13.30
13.20
12.90
14.90
15.40
15.80
16.00
16.10
16.70
17.50
18.20
18.70
19.10
18.40
19.50
20.50
21.20
21.90
19.90
21.30
22.50
23.50
24.50

THR
8.54
7.90
7.21
6.42
5.50
11.11
10.48
9.77
8.97
8.07
13.99
13.33
12.60
11.76
10.82
17.22
16.51
15.72
14.80
13.77
20.85
20.06
19.17
18.13
17.02
24.90
23.99
22.96
21.80
20.56

Cap.
6.80
5.94
5.11
4.30
3.54
9.35
8.28
7.23
6.21
5.22
12.47
11.14
9.83
8.55
7.30
16.25
14.62
12.99
11.39
9.82
20.74
18.76
16.79
14.84
12.92
26.05
23.68
21.31
18.96
16.63

06EW027
kW
12.80
12.70
12.50
12.10
11.70
15.40
15.50
15.40
15.20
14.90
18.00
18.30
18.50
18.50
18.40
20.70
21.30
21.80
22.00
22.20
23.40
24.30
25.10
25.70
26.20
26.10
27.40
28.50
29.50
30.30

LEGEND
Capacity (tons)
Power Input
Saturated Discharge Temperature (F)
Saturated Suction Temperature (F)
Total Heat Rejection (tons)

THR
10.45
9.56
8.67
7.75
6.87
13.73
12.69
11.62
10.54
9.47
17.60
16.36
15.10
13.82
12.54
22.15
20.69
19.21
17.66
16.14
27.41
25.69
23.95
22.17
20.38
33.49
31.49
29.43
27.37
25.26

Cap.
7.66
6.79
5.89
4.98
4.06
10.61
9.56
8.48
7.37
6.23
14.13
12.87
11.57
10.23
8.82
18.30
16.79
15.23
13.60
11.88
23.20
21.47
19.50
17.56
15.55
28.89
26.73
24.51
22.21
19.83

06EW033
kW
15.30
15.10
14.80
14.30
13.50
18.30
18.40
18.30
18.10
17.60
21.20
21.70
21.90
22.00
21.80
24.20
24.90
25.60
26.00
26.20
26.80
28.20
29.30
30.00
30.60
29.40
31.30
32.80
34.00
35.00

THR
12.02
11.09
10.11
9.06
7.91
15.83
14.80
13.70
12.53
11.25
20.17
19.06
17.81
16.50
15.04
25.20
23.89
22.53
21.01
19.35
30.83
29.51
27.85
26.11
24.27
37.27
35.65
33.86
31.90
29.81

Cap.
10.10
8.98
7.85
6.73
5.62
13.50
12.15
10.79
9.42
8.05
17.56
15.94
14.28
12.61
10.94
22.40
20.43
18.43
16.39
14.34
28.06
25.71
23.31
20.87
18.41
34.67
31.87
29.02
26.13
23.19

06EW044
kW
20.60
20.60
20.40
20.00
19.40
24.30
24.60
24.70
24.70
24.40
28.10
28.80
29.30
29.60
29.70
32.10
33.10
34.00
34.70
35.20
35.80
37.50
38.90
39.90
40.70
39.60
41.80
43.70
45.10
46.40

THR
15.97
14.85
13.66
12.43
11.15
20.42
19.16
17.83
16.46
15.01
25.57
24.15
22.64
21.05
19.40
31.54
29.87
28.12
26.28
24.37
38.26
36.39
34.39
32.24
30.01
45.96
43.79
41.48
38.98
36.42

*Refer to compressor capacity notes.


NOTE: To ensure proper motor cooling, it is required that all 6-cylinder
compressors operating with R-507/404A at 10 F SST or below have
one of the 2 unloaders disconnected. Cylinder head fan required at SST
of 20 F and below for R-507/404A for all compressors.

COMPRESSOR CAPACITY NOTES


1. Compressor capacities are based on 1750 rpm and
15 F subcooling.
2. Liquid subcooling, greater than (less than) the 15 F
incorporated in the ratings, increases (decreases) system capacity by 1/2 of 1% for each degree of subcooling for R-22 and increases (decreases) system
capacity by 6/10 of 1% for R-134A and R-507/
404A. When correcting for subcooling, power input
does not change. Adjusted total heat rejection (tons)
equals adjusted capacity + .285 x kW input.
3. Refrigerant temperatures shown are saturation temperatures corresponding to pressure indicated at compressor. Actual gas temperatures are higher because
of superheat.

14

4. Capacities are based on actual suction gas temperatures to the compressor of 65 F for R-134A and
R-507/404A. (This assumes superheat is obtained
from liquid-suction interchanger or in evaporator.)
Capacity corrections, for other than rated suction gas
temperatures, may be obtained from Rating Basis and
Capacity Multipliers table. R-22 ratings can be used
without adjustment.

RATING BASIS AND CAPACITY MULTIPLIERS

RATED
SUCTION GAS
TEMP (F)

SST
(F)
30
20

30
.810

20
.830
.830

ACTUAL SUCTION GAS TEMPERATURE


TO COMPRESSOR (F)
0
10
20
30
40
.870
.890
.910
.930
.950
.870
.890
.910
.930
.950
.870
.890
.910
.930
.950
.939
.949
.958
.967
.977
.870
.890
.910
.930
.950
.940
.949
.958
.968
.977
.890
.910
.930
.950
.950
.959
.968
.977
.910
.930
.950
.960
.969
.978
.930
.950
.970
.979
.950
.987

10
.850
.850
.850
.930

10
0
10
65
20
30
40
50
R-507/404A

R-134a

SST

ALL 4 CYLINDER
MODELS
ALL 6 CYLINDER
MODELS

NO. OF
CONTR
CYL

60
.990
.990
.990
.995
.990
.995
.990
.995
.990
.996
.990
.996
.990
.997
.990
.999

65
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000

Saturated Suction Temperature

ARI STANDARD RATING CONDITIONS

CAPACITY CONTROL REDUCTION STEPS* AND


PART-LOAD PERFORMANCE

UNIT 06D,06E

50
.970
.970
.970
.986
.970
.986
.970
.986
.970
.987
.970
.987
.970
.992
.970
.997

GROUP
A (R-22)
C (R-134a)
E (R-507/404A)

% Full Load Capacity


100
67
49
32
% Full Load kW
100
73
57
46
Number of Active Cylinders

SST (F)
45
20
10

SDT (F)
130
120
105

RGT (F)
65
65
65

SUBCOOLING (F)
15
15
5

LEGEND
Air Conditioning and Refrigeration Institute
Return Gas Temperature
Saturated Discharge Temperature
Saturated Suction Temperature

ARI
RGT
SDT
SST

NOTE: Ratings are in accordance with ARI Standard 520.

*Compressor cylinders unload in response to a self-contained suctionpressure controlled unloader valve(s) for 06D and 06E compressors.
When suction pressure drops below unloader set point, cylinders
unload. When suction pressure rises above cylinder load set point
pressure, cylinders return to operation. Capacity control unloader set
points and differential (load point unload point) are adjustable.

ARI STANDARD RATINGS


COMPR
06

Cap.
kW
THR

A8081
H3131
A8181
E8251
E3281
E5371
V022
W027
W033
W044

Cap.
3.28
5.12
7.46
9.51
11.49
15.76
20.72
27.26
30.06
39.66

GROUP A
R-22
kW
3.40
5.20
7.60
9.80
11.70
17.20
22.00
29.30
32.90
45.60

THR
4.23
6.61
9.63
12.29
14.83
20.64
26.97
35.60
39.43
52.61

Cap.

1.84
3.02
3.79
4.67
6.43
6.95
9.05
11.05
14.82

GROUP C
R-134A
kW

2.60
4.00
5.00
6.20
8.40
9.60
12.40
15.00
21.00

THR

2.58
4.17
5.20
6.43
8.83
9.68
12.58
15.30
20.79

Cap.

1.69
2.86
3.49
4.41
5.74
8.09
9.95
11.61
14.35

GROUP E
R-507/404A
kW

3.20
5.20
6.20
7.80
10.50
15.70
18.40
21.90
29.10

THR

2.60
4.33
5.27
6.63
8.73
12.56
15.20
17.83
22.64

LEGEND
Capacity (tons)
Power Input
Total Heat Rejection (tons)

NOTE: Ratings are in accordance with ARI Standard 520.

15

Electrical data
COMPRESSOR MOTOR*
COMPRESSOR
PART NUMBER
06D
808
M
313
818
825
A
328
537

VOLTAGE
(3 Ph-60 Hz)
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460

HP
3
5
6.5
7.5
10
15

LEGEND
LRA Locked Rotor Amps
MCC Maximum Continuous Current
RLA Rated Load Amps
*Refer to physical data table to match compressor motor with correct
compressor unit.
NOTES:
1. RLA (rated load amps) value shown is: MCC 1.40 = RLA.
2. For minimum contactor sizing, use RLA value determined by:
MCC 1.40 = RLA.

MCC

RLA

LRA

7
17.4
8.7
10.8
27
13.5
17.6
44
22
22.2
55.5
27.8
25
62
31
32
89
40

5
12.4
6.2
7.7
19.3
9.6
12.6
31.4
15.7
15.9
39.6
19.8
17.9
44.3
22.1
22.9
63.6
28.6

28.4
71
35.5
40
100
50
64
160
80
79
198
99
91
228
114
96
266
120

3. For wiring sizing, the RLA value can be determined by: MCC
1.56 = RLA.
4. Compressor operating amps at any specific conditions can only be
determined from a performance curve.
5. RLA values for 06D compressor protected by a calibrated circuit
breaker will depend on must-trip value of circuit breaker.
6. Ohm values shown for resistance are approximate and shown for
reference only. Motors from different vendors and motors of different efficiencies can differ up to 15% from data shown.
7. Electrical data for motor part numbers 06DR and 50 Hz units (not
shown) are available from Carrier Sales Representative.

ALLOWABLE OPERATING RANGES


NOMINAL VOLTAGE
208/230
460
575

16

MOTOR WINDING
RESISTANCE
(Ohms)
5.0
0.78
3.1
3.3
0.5
2.1
2.6
0.42
1.7
2.0
0.31
1.3
1.7
0.26
1.0
1.2
0.18
0.72

MAXIMUM
254
529
661

MINIMUM
187
414
518

COMPRESSOR MOTOR WITH CIRCUIT BREAKER*


COMPRESSOR MOTOR DATA
Compressor
Voltage
Part Number
Hp
(3 Ph - 60 Hz)
06E
250
265
A
275
299

LRA
MHA
MTA
PW
RLA
XL

208/230
575
460
208/230
575
460
208/230
575
460
208/230
575
460

20
25
30
40

CIRCUIT BREAKER
Motor
Maximum
LRA-PW
Recommended
Winding Circuit Breaker MHA MTA LRA Recommended
Must Trip Maximum LRA-XL
(first
RLA
RLA
Resistance
Amps
winding)
Part No.
(Ohms)
108
87
345
207
0.32
HH83XB336
91 104 350
74.3
45
36
120
72
2.2
XA461
33
38 124
27.1
54
44
173
104
1.3
XA424
42
49 175
35
140
112
446
268
0.27
HH83XC509
110 127 420
90.7
57
46
164
98
1.6
XA469
46
53 164
37.9
70
56
223
134
1.1
XA426
55 643 210
45.7
168
135
506
304
0.22
HH83XC539
142 163 507
116.4
65
52
176
106
1.3
XA430
50
58 168
41.4
84
68
253
152
0.9
XA425
63
73 210
52.1
236
189
690
414
0.15
HH83XC537
187 215 636
153.6
94
75
276
165
1.0
XA551
74
85 236
60.7
118
95
345
207
0.58
XA550
92 106 295
75.7

LEGEND
Locked Rotor Amps
Must Hold Amps
Must-Trip Amps
Part-Winding (Start)
Rated Load Amps
Across-the-Line (Start)

*Refer to physical data table to match compressor motor with correct


compressor unit.
NOTES:
1. Compressor MTA and RLA values are maximum figures.
2. LRA values for PW second winding = 1/2 the LRA XL value.
3. 3-Pole XL circuit breakers shown, other 3-Pole XL alternates and
6-Pole PW breakers available. Terminal lugs for circuit breakers
available in package 06EA660152 (not shown).

4. Recommended RLA value shown is determined by: circuit breaker


must trip value 1.40. Use this recommended (and minimum) RLA
value to determine nameplate stamping, minimum contactor sizing, and wire sizing. RECOMMENDED RLA FOR 06E COMPRESSORS EQUALS: MUST-TRIP (MTA) OF CARLYLE APPROVED
OVERCURRENT DEVICE BEING USED 1.40
5. Compressor operating amps at any specific condition can only be
determined from a performance curve.
6. Ohm values for resistance are approximate and shown for reference purposes only. Motors from different vendors and motors of
different efficiencies can differ up to 15% from data shown.
7. Electrical data for motor part numbers 06ER, 06EM and 50 Hz
units (not shown) are available from Carrier Sales Representative.

ALLOWABLE OPERATING RANGES


NOMINAL VOLTAGE
208/230
460
575

MAXIMUM
254
529
661

MINIMUM
187
414
518

17

Typical wiring schematics


CONTROL CIRCUIT AND POWER WIRING FOR 06D UNITS
(SINGLE PUMPOUT CONTROL)

18

CONTROL CIRCUIT WIRING FOR 06E UNITS

NOTE: Wiring is shown for single


pumpout control. Single pumpout
control should not be used on
direct expansion (DX) cooler applications (see lower diagram for wiring when applied with DX cooler).

FIELD CONNECTION WHEN APPLIED WITH DX COOLER

19

Typical wiring schematics (cont)


LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATICS
06D AND 06E
LEGEND
POR
PW
SW
TB
TDR
TM
TR
XL

Auxiliary
Compressor Contactor
Compressor Contactor (XL start and first
step of PW start)
C2
Compressor Contactor (PW second step)
CH
Crankcase Heater
CHR Crankcase Heater Relay
CR
Control Relay
DTS Discharge Temperature Sensor
DX
Direct Expansion
EQUIP Equipment
FU
Fuse
GND Ground
HPS High-Pressure Switch
IP
Internal Protector
LLS
Liquid Line Solenoid Valve
LPS
Low-Pressure Switch
M1
Evaporator Fan or Chilled Water Pump
M2
Cooling Tower pump
M3
Cooling Tower Fan
NEC National Electrical Code
OL
Overload
OPS Oil-Pressure Switch

AUX
C
C1

NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications
or additions must be in compliance with all applicable codes. Use
copper, copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating
must be 25 va.
5. 60 Hz units have 120 volt control circuit. 50 Hz units have 230 volt
control circuit. A separate source of supply at the correct voltage
must be field supplied through a fused disconnect device with a

20

Pumpout Relay
Part Winding
Start-Stop-Reset Switch
Terminal Block
Time Delay Relay
Timer Motor
Timer Relay
Across the Line
Terminal Block Connector
Unmarked Terminal
Marked Terminal
Factory Wiring
Field Control Wiring
To indicate common potential only;
not to represent wiring.
Splice

maximum rating of 15 A to TB2 connections


6.
7.
8.
9.

L1 (Hot Side) and

L2 (Neutral).
Open control circuit disconnect switch for servicing only. Disconnect must remain closed for crankcase heater to operate.
A transformer of the following rating may be field supplied for
60 Hz units: 350 va.
Transformer must be fused and grounded per applicable codes.
If any of the original wiring furnished must be replaced, it must be
replaced with 90 C wire or its equivalent.

Typical piping and wiring

NOTES:
1. Wiring and piping shown are general points-of-connection guides only and are not intended to include
all details for a specific installation.
2. All wiring must comply with applicable local and national codes.
3. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual
for details.
4. On all remote condenser units, a discharge line check valve is required and located after the muffler,
as close to the compressor as possible.

21

Application data
Adequate lubrication depends on proper oil return to
compressor (especially during unloaded operation) and
keeping liquid refrigerant out of crankcase (refrigerant dilutes oil).
Correct system piping design prevents gravity flow of
refrigerant to compressor while permitting oil return. Refer
to Carrier System Design Manual for correct refrigerant
piping techniques.
Crankcase heater energized and Liquid Line Solenoid
closed during shutdown periods restrict refrigerant migration to compressor and absorption of refrigerant by the oil
(minimum protection). A discharge line check valve prevents refrigerant migration from condenser to compressor
and should be installed on air-cooled applications where
condenser or receiver ambient temperature is at or above
compressor ambient temperature.
Single pumpout control incorporates a liquid line solenoid valve and prevents refrigerant migration by allowing
unit to shut off only after all refrigerant has been removed
from evaporator. (Compressor shuts off on low-pressure
cutout.)
Automatic pumpdown control allows compressor to
cycle on for short intervals during normally off periods.
This periodically removes any refrigerant from evaporator
which may have accumulated.
This control should not be used with 06D or 06E compressors having cylinder head unloaders.

22

Direct-expansion cooler applications (excluding


brine) should not incorporate single pumpout or automatic
pump-down control. Crankcase heater and liquid line solenoid (minimum protection) are recommended for these
applications.
Compressors located in a space subject to low-ambient
temperatures require special provision for proper operation during start-up. (Low-ambient temperatures cause
compressor to operate at abnormally low suction pressures
during start-up.)
Proper operation can be maintained by:
1. Heating the space,
2. A time-delay relay installed to bypass the low-pressure
control during start-up, or
3. Use of a suction temperature control to operate compressor, instead of low-pressure control.

Guide specifications
06D and 06E Semi-Hermetic Reciprocating
Compressor Unit
HVAC Guide Specifications
Size Range: 3 to 15 tons
Carrier Part Number: 06D
Size Range: 20 to 40 tons
Carrier Part Number: 06E
Part 1 General
1.01 SYSTEM DESCRIPTION
Reciprocating type, semi-hermetic refrigerant compressor for use with refrigerants R-22, R134a, or
R-507/404A.
1.02 QUALITY ASSURANCE
A. A. Unit performance shall be rated according to ARI
520 latest edition and comply with ANSI/ASHRAE 15
safety code, NEC, and ASME Code.
B. Compressors will be factory run tested to ensure
proper performance.
1.03 DELIVERY, STORAGE AND HANDLING
Unit will be stored and handled according to manufacturers instructions.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory assembled single piece, refrigerant compressor unit. Contained within the package shall be a
semi-hermetic reciprocating compressor, structural
steel base, control panel, power terminal box,
wiring, piping, and controls required prior to field
start-up.
B. Compressors:
Reciprocating semi-hermetic type only, with shutoff
valves, automatically reversible positive displacement oil pump, oil charge, crankcase heater with
relay, and suction pressure actuated cylinder unloaders. Unit mounted on vibration isolators.

C. Controls and Safeties:


1. Included in the control panel are power and
control terminal blocks, contactors, control
relays, on/off switch, and unit designed to start
with controlled cylinders unloaded. Factory
assembled control box to be tested and
mounted on structural base.
2. Safeties in the control box include high- and
low-pressure switches, timer to prevent compressor short cycling, overload relays or circuit
breakers, and control circuit fuse.
D. Electrical Requirements:
All control and power wiring between control box
and compressor shall be factory assembled.
E. Special Features:
Certain standard features are removed and replaced
by those features designated by * below. Consult your
local Carrier sales office for amending specifications.
* 1. Electric Actuated Unloaders:
Includes all necessary hardware to allow field
conversion from suction pressure actuated to
electric solenoid actuated unloaders.
* 2. Water-Cooled Condenser:
Multipass shell and tube with integral finned
copper tubes for field installation. Shall be factory tested to comply with ASME Code for
unfired pressure vessels, ARI Standard 450 for
condensers, and ANSI/ASHRAE safety code.
Equipped with pressure relief, liquid line shutoff, and connection for water regulating valve.
* 3. Discharge Muffler:
Field installed discharge line muffler for noise
reduction.

23

Carrier Corporation Syracuse, New York 13221

7-02

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 4
New Book 3
Pg 24
Catalog No. 520-606
Printed in U.S.A.
PC 802
Form 06D,E-3PD
Replaces: 06D,E-2PD