GD Midea Commercial Air-conditioning Equipment Co., Ltd.

Add: Midea Industrial City, Shunde, Foshan, Guangdong, 528311, P.R.China Tel: +86-757-26339642 Fax: +86-757-26339337

E-mail: mcac@midea.com.cn Http: //www.midea.com.cn Http: //www.mdvchina.com (customer service)

2007

Midea Air Conditioners


Chiller System

Midea Is Your Idea

Midea Creates A Better Life

Midea produced its first Air Conditioner in 1985. Currently we are the leader of Air conditioner manufacturing and export. Midea has been exporting Air Conditioners for the last 16 years, and during this time Midea has cultivated strong partnerships with hundreds of overseas companies.

We provide Global technical training and a comprehensive online customer service. All our customers from over 110 countries and regions receive top quality service at all times.

Our vertically integrated supply chain enables us to achieve maximum efficiency in production and product development.

Midea is dedicated to continuous improvement. Over 1000 engineers work together to push the improvement of AC technology. Every year over 300 new products are developed and 100 new patents are filed. New products account for 30% of total sales volume and 35% of gross profit.

Our goal is to deliver the highest quality products to our costumers. Quality is one of the core competencies of Midea.

TUV Rheiniand
CERTIFIED COMPANY
CERTIFIED COMPANY

ION
IZAT
AN
B IA

NRTL/C

AL

CO

NFOR

MI T Y C ERT

IFIC

AT

E U R OV E N T

CERTIFIED PERFORMANCE

TUV Rheiniand Group

Production inspected

N433

IO

NP

geprufte sicherheit

ISO 9001 : 2000 Certificate No.: CC 454

ISO 14001: 1996 Certificate No.:CC1417

L I S T E D

ROG

068

068

RAM

SA U D I
AR
A

INTE RN

RG N ST A N D AR D S O

.. geprufte Sicherheit

ATI

ON

2007 Midea Commercial A/C Model Line Up


[ L ] Centrifugal Chiller system
5-21

[ W ] Water-Cooled Package Unit


45-48
35kW 60kW~80kW 100kW~145kW

R123 single-stage compression: 200RT~800RT R123 dual-stage compression: 900RT~1200RT R134a single-stage compression: 350RT~1100RT R134a dual-stage compression: 1200RT~2000RT

[ R ] Heating Water System


49-53 22-33
Dry expansion evaporator: Single-compressor: 40RT~245RT Dual-compressor: 280RT~490RT Flooded type evaporator: Single-compressor: 120RT~255RT Dual-compressor: 290RT~510RT

[ C ] Water-cooled Screw Chiller system

7kW

9kW

17.5kW

35kW

[ S ] Water-Source Heat Pump


54-61
5.0-14.0kW
Water source four way cassette Water source low static pressure duct Water source high static pressure duct

[ A ] Air-cooled Modular Chiller System


34-44

[ K ] Air Handling Unit & Fan Coil Unit


Air Handling Unit

Single wall horizontal type

Single wall vertical type

Dual wall horizontal type

Dual wall vertical type

Wall-mounted type

Fan Coil Unit

Digital scroll or constant speed scroll: 30~520kW

Constant speed scroll:185kW~1480kW

Four way cassette (compact)

Four way cassette

One way cassette

Duct type

Concealed floor standing

Expoded floor standing

62-71
4

[ L ] Series

Centrifugal Chiller system

Centrifugal Chiller system HOW TO READ THE MODELS ?


Brief introduction of R-134a series

M H C - A S 650 S / A N3
Refrigerant Type: N3 R134a N5 R123 - R22

R-134a series hermetic centrifugal chiller system, are developed to replace the current CFC centrifugal chiller series for the project national scheme of China ozone layer consuming material gradually falling into disuse. The series take the environmental friendly refrigerant HFC-134a as refrigerant. On august 1999, the first sample170H-6P centrifugal chilled system gained the approval as national class new product, professional team's appraisal: unit's main technical performance is advanced among the same kind of products, with
Power Type: A 6000V/50Hz/3Ph B 10000V/50Hz/3Ph C 380V/50Hz/3Ph

friendly environmental quality and excellent energy-saving effect, the market prospect is expansive.

Compressor Type: H Hemetic S Semi-hermetic O Opening

Nominal Cooling Capacity (USRT)

Compression-stage: S Single-stage Compression D Dual-stage Compression

Compression Quantity: A Single Compressor D Dual Compressor

Centrifugal Chiller

Heavy Commercial Chiller System

Midea

Centrifugal Chiller system


Features
Adopt new-type environmental friendly refrigerant
R-123 series centrifugal chiller system take HCFC-123 as refrigerant. HCFC-123 is an optimal choice considering ozone depleting, greenhouse effect and energy effect. R-134a series centrifugal chiller system take HCFC-134a as refrigerant. HCFC-134a is the green refrigerant accepted internationally, without destructive effect to ozone, and accords to the standards of international environmental protection pact and national scheme of china consume ozone material gradually falling into disuse.

Reliable gearing & long-span operation


Less moving parts in compressor and high quality components guarantee a common lifespan over 20 years. The propeller is made of peculiar cast aluminium alloy and proved to be of sufficient mechanical strength and high erosion resistance after high precision dynamic balance test and over-speed test. The keyless connection between propeller and axis avoids the stress concentration and accessional unbalance of rotor. It will improve the reliability considerably. The technology obtained the national patent, the patent serial number is ZL01256825.2. Peculiar design of high precision helical gear counteracts the

Advanced technology & high efficiency


The pneumatic part of compressor is designed through NREC pneumatic software which is one of the most advanced design softwares in the world. Adopts high-efficiency and three-dimension hermetical impeller designed for refrigerant HCFC-123/HFC134a, avoids performance fluctuation caused by gap change between semi-open impeller and scrollcase. The heat transfer pipes of condenser and evaporator adopt high efficiency heat transfer pipes designed individually according to boil principle and concreting principle, improve gross heat transfer coefficient and as well as be able to realize the heat transfer with small temperature difference. The optimal matching of advanced compressor with new-style & highefficiency heat exchanger guarantees a high efficiency unit. Special designed guide vane can adjust refrigerant mass flow to fulfil partial load requirement, and by pre-regulating gas entering direction, refrigerant can flow into the propeller in optimal angle and Propellor overspeed test on overspeed unit efficiency is improved greatly.
experiment device of German Schenk

axial thrust force caused by propeller, reduces the gearing's load and makes the transmission smoothly. Hermetic motor is cooled efficiently by evaporative refrigerant ejecting. Therefore, it ensures unit safety and long lifespan and also can prevent the refrigerant from leakage.

Reliable lubricating system


The closed oil pump immersed in oil can send the pressure oil to the surface of each high-speed gear. Plate oil cooler cooled with refrigerant ensures the oil pumped by oil pump to be cooled to a low temperature. Impurity in oil is filtered by high precision papery filter. ensures the dynamic pressure oil film forming on high-speed gearing, and filter core can be replaced conveniently. The high oil box on top of compressor ensures the oil quantity used for gearing when emergent poweroff occurs, and avoids the gearing from abrasion.

An extra high-efficiency cooler in condenser subcools liquid refrigerant and improves the efficiency. The energy saver between double stage compressors reduces unit power consumption by 5%, so as to increase cooling capacity of refrigerant per mass unit and compressed quantity of refrigerant entering into the first stage reduces, otherwise, refrigerant at intermediate pressure between evaporator and condenser will flash and the refrigerant between stages cooled by flash gas will improves unit*s efficiency. Optimize the pipe arrangement, reduce the refrigerant friction loss, and guarantee excellent operation efficiency.

Wide range of adjustable capacity


The chiller system of medium & large capacity adopts nonvane pressure enlarger and inlet guard vane, hence enlarge cooling adjusting range, and the unit's coolingcapacity can be adjusted optionally from 10% to 100% at a invariable cooling water inlet temperature.

Inlet guide vane

10

Centrifugal Chiller system


Features
Low noise & stable running
All the gears are rectified in height and width in order to reduce the mesh noise. The double-layer noise proof structure of gear box minimizes the noise level. Flux passage with optimized design reduces the noise level and refrigerant flow speed. Noise-proof device fixed on the inlet of condenser can reduce the refrigerant flow impact noise. The special design of compressor assembled with hermetic motor cooling by refrigerant saves the connecting and hermetic device between motor and compressor which is necessary for unclosed motor, and reduces damageable process, as well as reduces the motor outline dimension and motor noise. The unit's mean-time to failure can be more than five years.

Advanced Micro-computer control system


The special designed micro-computer control system can optimize control logic, improve operation efficiency, is reliable with long-term running. Touchpad display makes the operation easy and direct. Operation data and malfunction alarms can be displayed on the indicator, so to monitor unit instantly. The micro-computer control system can execute more than 30 control and protection actions and record the latest 10 error parameters, main control unit adopting advanced import components which have better disturbance resistance and guarantee the units work safely and reliably. The built-in RS422 communication port can realize central control. It also can connect with user's PC, and realizes remote control start, operation and stop. Adopts the PLC controller of CQM1-Japanese Omilong series to precisely control temperature. The control system adopts EL highlight touchpad display of GP-477 series produced by Japanese DIGITAL, and the moving picture will display operation interface, and operates each control by slight touch refer to wok condition indicator. In central monitor system, the micro-computer is connected with the CPU modules of multi sets of centrifugal chiller systems micro-computer control system (PC-LXZ-H) through RS422 port, can control maximum 32 sets of centrifugal refrigerators and the water pump, cooling tower and other accessories.

Reliable performance test


Reliable performance test The assemblage of propeller with gear is tested in dynamic balance experiment with an over-speed which is 120% of the rated. Heat exchanger and power saver are strictly tested by pressure experiment according the national norm JB4750 defined by pressure container for refriferation quipment. Must carry out gas seal test and vacuum test after whole unit is assembled. The performance test is operated on special experiment table according to national standard, strictly tested each norm, and can't leave factory until it fulfil the design demand.

balance test on Schenck Dynamic balancing machine (Germany)

Wider application
Be able to customize special centrifugal compressor with large cooling capacity and dual-compressor according to user's demand, capacity of single unit can reach up to 4000RT. Be able to design high-voltage products of 6000v or 10000v, reduces the impact to electric network, as well as save the transformer, has wider application. Be able to design non-standard products based on actual temperature of water inlet and outlet, so as to achieve the best energy-saving effect, fulfil user's demand.
Standing-by interface Malfunction display interface Coefficient display interface

Approval
Design, manufacture and experiment of unit are all according to the national standard GB/T 18430.12001 vapor compression cycle Water chilling (heat pump) packages and JB 4750 pressure container for refrigerating device. Our company has obtained ISO 9001 certification, and it is the first to obtain environment product approval in national trade.

11

12

Centrifugal Chiller system


R-123 single-stage series (200-400RT)
Unit Model RT Refrigerating capacity kW 104kcal/h Cooling water flow Cooling water pressure drop Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop Number of pass Connect pipe nominal diameter Capacity Motor Power supply Coolingsystem R123 charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Width (B) Height (C) kg kg kg kg mm mm mm 540 45 8090 8300 3560 1580 2430 540 45 8290 8500 3560 1580 2430 mm kW V-ph-HZ mm m3/h KPa 4 DN150 150 72 3 DN150 150 4 DN150 183 76 3 DN150 180 4 DN150 226 78 3 DN150 200 380/6000/10000-3-50 Refrigerant ejecting 700 45 8490 8700 3560 1580 2430 700 45 9870 8300 4552 1580 2430 700 45 10090 8300 4552 1580 2430 Unit dimensions 4 DN200 264 50 3 DN200 235 4 DN200 302 54 Condenser 3 DN200 260 Motor Number of pass Connect pipe nominal diameter Capacity Power supply Coolingsystem R123 charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Width (B) Height (C) kg kg kg kg mm mm mm 920 45 11920 12590 4620 1890 2720 mm kW V-ph-HZ 2 DN250 320 2 DN250 385 2 DN300 455 2 DN300 515 m3/h KPa MHC-AS(200-400)H/A(B)(C)N5 200 200 703 60.5 121 136 250 250 879 75.5 151 142 300 300 1055 90.7 181.4 143 350 350 1230 105 212 134 400 400 1406 120 242 143 Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop mm m3/h KPa 3 DN250 378 53 3 DN250 452 53 2 DN300 529 107 2 DN300 604 107 Cooling water flow Cooling water pressure drop Refrigerating capacity

R123 single-stage series (500-800RT)


Unit Model RT kW 104kcal/h m3/h KPa MHC-AS(500-800)H/A(B)(C)N5 500 500 1755 151 302 141 600 600 2110 181 362 144 700 700 2461 211.5 423 84 800 800 2813 241.9 484 85

Condenser

380/6000/10000-3-50 Refrigerant ejecting 920 76 12285 13080 4620 1890 2950 1100 76 14330 14900 5450 1890 2950 1100 76 14700 15500 5450 1890 2950

Unit dimensions

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

13

14

Centrifugal Chiller system


R-123 dual-stage series (900-1200RT)
MHC-AD(900-1200)H/A(B)(C)N5 900 RT Refrigerating capacity kW 104kcal/h Cooling water flow Cooling water pressure drop Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop Condenser Number of pass Connect pipe nominal diameter Capacity Motor Power supply Coolingsystem R123 charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Unit dimensions Width (B) Height (C) kg kg kg kg mm mm mm 1600 71 23400 24280 6285 2190 3522 mm kW V-ph-HZ 2 DN350, PN1.0 573 2 DN350, PN1.0 595 2 DN350, PN1.0 650 2 DN350, PN1.0 710 Motor 2150 71 24700 26550 6285 2190 3522 Support Unit dimensions mm m3/h KPa 2 DN300, PN1.0 669 94 2 DN300, PN1.0 744 94 2 DN300, PN1.0 818 94 2 DN300, PN1.0 839 98 Condenser Number of pass Connect pipe nominal diameter Capacity Power supply Coolingsystem R134a charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Width (B) Height (C) D E F G Connect pipe setting dimensions H J K L kg kg kg kg mm mm mm mm mm mm mm mm mm mm mm 420 63 9210 8510 4310 1620 2395 3340 1420 510 490 460 790 760 1060 mm kW V-ph-HZ 3 DN200 244 3 DN200 274 3 DN200 308 3 DN200 350 m3/h KPa 900 3165 272 544 102 1000 1000 3516 302 605 102 1100 1100 3867 332 665 102 1200 1200 4220 363 726 102 Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop mm m3/h KPa 3 DN200 265 82.2 3 DN200 302 81.4 3 DN200 340 83.1 3 DN200 378 85 Cooling water flow Cooling water pressure drop Refrigerating capacity

R134a single-stage series (350-500RT)


MHC-AS(350-500)H/A(B)(C)N3 350 RT kW 104kcal/h m3/h KPa 350 1230 105 212 114 400 400 1406 120 242 115 450 450 1582 136 272 106 500 500 1758 151 302 106

Unit Model

Unit Model

380/6000/10000-3-50 Refrigerant liquid ejecting-evaporating 1780 71 23900 25100 6285 2190 3522 1970 71 24300 25850 6285 2190 3522

380/6000/10000-3-50 Refrigerant ejecting R134a charging volume 450 63 9440 8810 4310 1620 2395 3340 1420 510 490 460 790 760 1060 550 63 9930 9420 4310 1775 2460 3340 1575 510 500 510 855 790 1140 565 63 10130 9700 4310 1775 2460 3340 1575 510 500 510 855 790 1140

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

15

16

Centrifugal Chiller system


R-134a single-stage series(550-650RT)
MHC-AS(550-650)H/A(B)(C)N3 550 RT Refrigerating capacity kW 104kcal/h Cooling water flow Cooling water pressure drop Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop Condenser Number of pass Connect pipe nominal diameter Capacity Motor Power supply Coolingsystem R134a charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Unit dimensions Width (B) Height (C) Support D E F G Connect pipe setting dimensions H J K L kg kg kg kg mm mm mm mm mm mm mm mm mm mm mm 83 13160 12770 4390 1965 2666 3340 1730 585 540 620 940 877 1277 mm kW V-ph-HZ 640 3 DN250 372 3 DN250 402 380/6000/10000-3-50 Refrigerant ejecting R134a charging volume 670 83 13360 13040 4390 1965 2666 3340 1730 585 540 620 940 877 1277 700 83 13590 13340 4390 1965 2666 3340 1730 585 540 620 940 877 1277 Connect pipe setting dimensions Support Unit dimensions 3 DN250 428 Motor mm m3/h KPa 3 DN250 415 92 3 DN250 452 92 3 DN250 490 92 Condenser Number of pass Connect pipe nominal diameter Capacity Power supply Coolingsystem R134a charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Width (B) Height (C) D E F G H J K L kg kg kg kg mm mm mm mm mm mm mm mm mm mm mm mm kW V-ph-HZ 700 83 14650 13990 5638 1890 2646 4740 1690 495 540 440 920 860 1280 2 DN250 464 2 DN250 495 2 DN250 527 2 DN300 563 m3/h KPa 550 1934 166 332 112 600 600 2110 181 362 112 650 650 2285 196 393 112 Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop mm m3/h KPa 2 DN250 529 72 2 DN250 567 75 2 DN250 604 78 2 DN300 627 81 Cooling water flow Cooling water pressure drop Refrigerating capacity

R-134a single-stage series (700-850RT)


MHC-AS(700-850)H/A(B)(C)N3 700 RT kW 104kcal/h m3/h KPa 700 2461 211 424 92 750 750 2637 226 454 92 800 800 2813 242 484 94 850 850 2988 257 514 110

Unit Model

Unit Model

380/6000/10000-3-50 Refrigerant ejecting R134a charging volume 760 83 14890 14310 5638 1890 2646 4740 1690 495 540 440 920 860 1280 760 83 15060 14560 5638 1890 2646 4740 1690 495 540 440 920 860 1280 890 83 16230 15650 6013 2020 2830 5040 1820 610 590 510 980 992 1448

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

17

18

Centrifugal Chiller system


R-134a single-stage series (900-1100RT)
MHC-AS(900-1100)H/A(B)(C)N3 900 RT Refrigerating capacity kW 10 kcal/h Cooling water flow Cooling water pressure drop Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop Condenser Number of pass Connect pipe nominal diameter Capacity Motor Power supply Coolingsystem R134a charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Unit dimensions Width (B) Height (C) Support D E F G Connect pipe setting dimensions H J K L kg kg kg kg mm mm mm mm mm mm mm mm mm mm mm 890 102 16560 16070 6013 2020 2830 5040 1820 610 590 510 980 992 1448 mm kW V-ph-HZ 2 DN300 584 2 DN300 610 2 DN300 651 2 DN300 724 Motor 1000 102 17720 17500 6013 2180 2830 5040 1940 610 590 510 1050 935 1448 Connect pipe setting dimensions Support Unit dimensions mm m3/h KPa 2 DN300 658 81 2 DN300 696 81 2 DN300 735 78 2 DN300 830 95 Condenser Number of pass Connect pipe nominal diameter Capacity Power supply Coolingsystem R134a charge volume Lubricant oil charge volume Unit weight Unit transport Weight Unit running weight Length (A) Width (B) Height (C) D E F G H J K L kg kg kg kg mm mm mm mm mm mm mm mm mm mm mm 1020 125 23700 25500 6150 2900 3070 1130 930 700 660 600 1230 1140 1660 mm kW V-ph-HZ 1080 125 24600 26400 6150 2900 3070 1130 930 700 660 600 1230 1140 1660 2 DN350 740 2 DN350 830 2 DN350 922 2 DN350 1014 2 DN400 1108 2 DN400 1228 m3/h KPa
4

R-134a double-stage series (1200-2000RT)


MHS-AD(1200-2000)H/A(B)(C)N3 1200 RT Refrigerating capacity kW 10 kcal/h Cooling water flow Cooling water pressure drop Evaporator Number of pass Connect pipe nominal diameter Chilled water flow Chilled water pressure drop mm m3/h KPa 2 DN350 874 83 2 DN350 987 83 2 DN350 1096 85 2 DN350 1208 86 2 DN400 1320 86 2 DN400 1465 88 m3/h KPa
4

Unit Model

950 950 3340 287 574 105

1000 1000 3516 302 605 86

1100 1100 3516 332 664 109

Unit Model

1350 1350 4747 408 816 108

1500 1500 5274 453 907 103

1650 1650 5800 500 998 104

1800 1800 6329 544 1088 106

2000 2000 7032 605 1210 110

900 3164 272 544 108

1200 4219 363 726 108

380/6000/10000-3-50 Refrigerant ejecting R134a charging volume 950 102 16820 16070 6013 2020 2830 5040 1820 610 590 510 980 992 1448 950 102 17290 16070 6013 2020 2830 5040 1820 610 590 510 980 992 1448

380/6000/10000-3-50 Refrigerant liquid ejecting-evaporating 1150 125 25600 27750 6150 3000 3120 1230 930 750 715 600 1280 1140 1660 1250 150 28150 29350 6150 3160 3120 1230 1030 750 715 600 1330 1160 1740 1500 150 28800 30800 6150 3200 3270 1330 1030 820 765 650 1380 1260 1840 1600 150 29500 32100 6150 3200 3270 1330 1030 820 765 650 1380 1260 1840

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

Remarks: 1. cooling water inlet/outlet temperature :12/7 OC chilled water inlet/outlet temperature: 32/37OC waterside fouling factor : 0.086m2OC/kW 2. Designed waterside pressure of both cooling water and chilled water is 1.0 MPa, water connecting pipe flange standard: JB/T81-94. Inform us specificallywhen ordering the unitif the waterside working pressure is higher than 1.0MPa. 3. The listed data in those samples may change, please refer to factory drawings offered by our company for standard.

19

20

Centrifugal Chiller system

Notices for order


Users should offer technical requirements as follow: Cooling capacity Inlet temperature of chilled water Outlet temperature of chilled water Inlet/outlet temperature of cooling water Cooling/chilled water side fouling factors for special requirement (m2.0C/kW) Whether there is different piping azimuth comparing with the sample Voltage level of main motor Special control requirements Cooling/chilled water pressure for special requirement

[ C ] Series

Special instruction
User should self-supply base steel plate and cables between start cabinet and motor. We suggest utilizing special refrigerant filler and charger to avoid refrigerant loss and leakage. We supply two types of refrigerant fillers and chargers and relative refrigerant storages for user, which is not belong to supply scope of our company, please contact with sale department of our company for order.

Water-cooled Screw Chiller system

Supply scope of a set centrifugal chiller system


A centrifugal compressor (include speeding-up device) A main motor (motor cooled with refrigerant) An evaporator and condenser A refrigerant purifier (only applicable to series of R-123 single and dual-stage unit) One lubricating system An electric control cabinet (self-supply cables between electric box start cabinet) A start cabinet (will supplied by user when main motor voltage is 6000v or 10000v) A power saver (available for R123 and R-134a dual-stage series)

21

Screw Chiller system HOW TO READ THE MODELS ?


M H S - A F 650 S / A N3
Refrigerant Type: N3 R134a N5 R123 - R22

Power Type: A 6000V/50Hz/3Ph B 10000V/50Hz/3Ph C 380V/50Hz/3Ph

Advanced screw dual-compressor technology


Adopts advanced industrial generation * compressor with 5-6 asymmetry dentiform design, the mechanical
Compressor Type: H Hemetic S Semi-hermetic O Opening

configuration of which is manufactured by CNC high precision screw rotor, each part is well-proportioned, no gap matching, minimizes the friction resistance, guarantees quiet running and well duration. Comparing with single screw compressor has the advantages of no clearance loss, high volume efficiency, low running noise, less damageable parts, etc.

Nominal Cooling Capacity (USRT)

Evaporator Type: F Flooded Type D Dry Type

Compression Quantity: A Single Compressor D Dual Compressor

Screw Chiller

Heavy Commercial Chiller System

Midea

23

24

Screw Chiller system


Variable volume adjustment, High efficiency & energy-saving
Owning the biggest single compression ratio, the ratio can reach up to 18. Compressor with adjustable variable volume and special volume control valve for precise control enables to adjust compressor's refrigerant compressed amount precisely matching with load change. Realizes 4-stage capacity output control (25%, 50%, 75%, and 100%) and stepless capacity control (need special instruction for the function on order). The high precise adjustable volume directly saves user's operation cost.
Capacity output 100%

Introduction of components
Adopting the world-famous brand key components, ensures the unit running with reliability & safety.

Compressor
Adopts high efficiency screw compressor of generation * with 5-6 asymmetry dentiform, the screw rotor of which gained patent by improving the shape of German rotor GHH, proved having well balance, small vibration, low noise due to balance testing by balance machine. Heat efficiency of the rotor with main and subsidiary rotor adopting 5-6 dentiform increases by 10-12% and energy saves by 25%, comparing with Chinese normal screw rotor with 4-6 dentiform. The rotor shape also gained British and American patent. Adopts compressor bearing SKF from Sweden, the long lifespan of which ensure screw-type main unit to run continuously more than 50000 hours.

75%

50%

Four-step capacity adjustment

25%

Oil separator
The product comes from MANN of German, has reliable qualification, oil content can be controlled below 3ppm (oil content treated by oil-gas separator of common domestic like screw-type air compressor is not less than 8-10ppm). oil-gas separated amount is double of same kind of products, the large oil filtering area reduces refrigerant flux speed, and has better separating effect and long lifespan by adopting secondary reflux technology.

Stepless capacity adjustment 25% 50% 75% 100% Capacity demand

Refrigerant circulation and lubricating system Condenser


Midea screw chiller is equipped with high efficiency shell and tube condenser, it is constructed by seamless steel tube with anti-corrosive treatment, the pressurization is 1.9Mpa, and the pressurization of water pipe side is 1.0Mpa. water pipe constructed with seamless integrally finned copper attains optimal heat exchange efficient, two return passages of water flow and the straight water pipe is easy for cleaning and maintenance, both end covers are made of iron, the covers attached with protection valve and snuffle valve and etc are removable, makes it available for altering water piping arrangement. The condenser is mounted with devices as protection valve and snuffle valve, etc.

Evaporator
The pressurization of direct expanding shell and tube evaporator wrapped with heat insulating and flameproof material is 1.4Mpa, the inner refrigerant evaporation pipe of which is constructed with seamless
Item 1 2 3 4 5 6 7 8 9 Filter Refrigerant (low pressure) Motor Oil filter Bearing Compressor rotor Bearing Discharge pipe Refrigerant (high pressure mix with oil) Contents Item 10 11 12 13 14 15 16 17 Lubricant Oil separator Refrigerant (high pressure) Capillary Electromagnetic valve (starting) Electromagnetic valve (50% energy output) Electromagnetic valve (75% energy output) Capability adjustment device Contents

steel pipe together with internal-screw cooling fin, guarantees a high efficient heat transmission, the pressurization is 1.0 MPa. Water flowing along refrigerant pipe outside and the installation of the flashing PP makes chilled water to flow up-down along the chilled water clapboard, improves heat transmission efficiency.

Refrigeration cycle
Consists of the high pressure check-valve, expansive valve, electromagnetic valve, bulbiform valve, display panel, water indicator, dry filter, etc. Each multiple evaporator inside has independent refrigerant cycle pipes, avoiding system imbalance.

25

26

Screw Chiller system

Dry type (single compressor series)


MHS-AD(40-70)S/C 40 USRT kW kW mm 37 130 28 2520-800-1720 50 48 167 35 Grey 2540-800-1740 2940-800-1740 2940-800-1740 55 54 189 41 70 72 253 55

Dry type (single compressor series)


MHS-AD(85-140)S/C 85 USRT kW kW mm 83 292 60 2970-850-1820 90 91 318 69 Grey 2970-850-1850 2990-850-1965 2995-1350-1465 115 114 400 85 140 139 485 100

Model

Model

Cooling capacity Power input Unit color Dimension (L x W x H) Compressor type Compressor starting mode Power supply Fouling factor Design working pressure Capacity adjustment Refrigerant type No. of refrigerant circuits Refrigerant flux adjustment device Refrigerant weight Condenser type Condenser model and number Condenser inlet pipedimension Condenser outlet pipe dimension Cooling water flux volume Evaporator type Evaporator model and number Evaporator inlet pipe dimension Evaporator outlet pipe dimension Chilled water flux volume Protection device Unit weight Unit running weight

Cooling capacity Power input Unit color Dimension (L x W x H) Compressor type Compressor starting mode Power supply Fouling factor Design working pressure Capacity adjustment Refrigerant type No. of refrigerant circuits Refrigerant flux adjustment device

'5-6 Asymmetry Dentiform Semi-hermetic Screw Y-* 380V, 3N~50Hz 0.086m2 . 0C/kW Water side pressure is 1.0MPa 50%,75%,100% R22 1 Thermo-expansive valve
kg 25 30 35 40

'5-6 Asymmetry Dentiform Semi-hermetic Screw Y-* 380V, 3N~50Hz 0.086m2 . 0C/kW Water side pressure is 1.0MPa 50%,75%,100% R22 1 Thermo-expansive valve
kg 50 60 80 90

Refrigerant weight Condenser type Condenser model and number

Shell and tube UCW050A/2


mm mm m /h
3

Shell and tube UCW050A/2


mm mm m /h
3

DN80 DN80 27

DN80 DN80 35

DN80 DN80 40

DN100 DN100 53

Condenser inlet pipe dimension Condenser outlet pipe dimension Cooling water flux volume Evaporator type Evaporator model and number Evaporator inlet pipe dimension Evaporator outlet pipedimension Chilled water flux volume Protection device Unit weight Unit running weight

DN100 DN100 61

DN100 DN100 67

DN100 DN100 84

DN100 DN100 101

Dry shell and tube UCH050A/1


mm mm m3/h DN80 DN80 22 DN80 DN80 29 DN80 DN80 33 DN80 DN80 44

Dry shell and tube UCH050A/1


mm mm m3/h DN100 DN100 50 DN100 DN100 55 DN100 DN100 69 DN125 DN125 83

High/low pressure protections, over load protection, phase sequence protection, water flux volume protection, oil level protection, discharge temperature protection.
kg kg 1160 1260 1320 1470 1400 1550 1670 1820

High/low pressure protections, over load protection, phase sequence protection, water flux volume protection, oil level protection, discharge temperature protection.
kg kg 1830 2030 1870 2070 2250 2550 2610 2910

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

27

28

Screw Chiller system

Dry type (single compressor series)


MHS-AD(165-245)S/C 165 USRT kW kW mm 163 572 118 180 179 628 132 Grey 2995-1380-1550 3620-1350-1580 3620-1450-1700 3620-1460-1700 220 220 771 167 245 245 859 180

Dry type (dual compressor series)


MHS-DD(280-360)S/C 280 USRT kW kW mm 277 970 200 300 302 1057 218 Grey 3800-1540-1600 3800-1540-1640 4100-1640-1700 4600-1640-1760 330 327 114 236 360 359 1256 264

Model

Model

Cooling capacity Power input Unit color Dimension (L x W x H) Compressor type Compressor starting mode Power supply Fouling factor Design working pressure Capacity adjustment Refrigerant type No. of refrigerant circuits Refrigerant flux adjustment device Refrigerant weight Condenser type Condenser model and number Condenser inlet pipe dimension Condenser outlet pipe dimension Cooling water flux volume Evaporator type Evaporator model and number Evaporator inlet pipe dimension Evaporator outlet pipedimension Chilled water flux volume

Cooling capacity Power input Unit color Dimension (L x W x H) Compressor type Compressor starting mode Power supply Fouling factor Design working pressure Capacity adjustment Refrigerant type No. of refrigerant circuits Refrigerant flux adjustment device

'5-6 Asymmetry Dentiform Semi-hermetic Screw Y-* 380V, 3N~50Hz 0.086m2 . 0C/kW Water side pressure is 1.0MPa 50%,75%,100% R22 1 Thermo-expansive valve
kg 100 120 150 180

'5-6 Asymmetry Dentiform Semi-hermetic Screw Y-* 380V, 3N~50Hz 0.086m2 . 0C/kW Water side pressure is 1.0MPa 50%,75%,100% R22 2 Thermo-expansive valve
kg 120+150 120+180 150x2 180x2

Refrigerant weight Condenser type Condenser model and number

Shell and tube UCW050A/2


mm mm m /h
3

Shell and tube UCW050A/2


mm mm m /h
3

DN125 DN125 119

DN125 DN125 131

DN150 DN150 162

DN150 DN150 179

Condenser inlet pipe dimension Condenser outlet pipe dimension Cooling water flux volume Evaporator type Evaporator model and number Evaporator inlet pipe dimension Evaporator outlet pipedimension Chilled water flux volume Protection device Unit weight Unit running weight

DN150 DN150 202

DN150 DN150 220

DN150 DN80 238

DN200 DN200 262

Dry shell and tube UCH050A/1


mm mm m /h
3

Dry shell and tube UCH050A/1


mm mm m /h
3

DN125 DN125 98

DN125 DN125 108

DN150 DN150 133

DN150 DN150 148

DN150 DN150 167

DN150 DN150 182

DN150 DN150 197

DN200 DN200 216

Protection device Unit weight Unit running weight


kg kg

High/low pressure protections, over load protection, phase sequence protection, water flux volume protection, oil level protection, discharge temperature protection.
1160 1260 1320 1470 1400 1550 1670 1820

High/low pressure protections, over load protection, phase sequence protection, water flux volume protection, oil level protection, discharge temperature protection.
kg kg 4630 5080 4870 5320 5100 5600 5840 6340

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

29

30

Screw Chiller system

Dry type (dual compressor series)


MHS-DD(400-490)S/C Model 400 USRT kW kW mm 400 1399 299 425 425 1487 312 Grey 4800-1640-1810 4800-1690-1865 4800-1740-1865 4800-1740-1865 440 441 1542 334 490 491 1718 360

Flooded type (single compressor series)


MHS-AF(120-255)S/C Model

120 USRT kW
kW

145 145 510 94 163

170 171 600 110 195

190 188 660 122 218 Automatic

215 214 750 139 250

235 233 820 152 276

255 256 900 166 300

Cooling capacity Power input Unit color Dimension (L x W x H) Compressor type Compressor starting mode Power supply Fouling factor Design working pressure Capacity adjustment Refrigerant type No. of refrigerant circuits Refrigerant flux adjustment device Refrigerant weight Condenser type Condenser model and number Condenser inlet pipe dimension Condenser outlet pipe dimension Cooling water flux volume Evaporator type Evaporator model and number Evaporator inlet pipe dimension Evaporator outlet pipe dimension Chilled water flux volume Protection device Unit weight Unit running weight

Cooling capacity Power input Current (A)

120 420 77 140

Capacity adjustment method Capacity adjustment range (%) Refrigerat Power supply Number of pass Chilled water flow (t/h) Condensor Chilled water pressure drop (kpa) Diam. of inlet/outlet water pipe (mm) Number of pass Cooling water flow (t/h) 85 DN125 3 72 80 DN125 3500 1160 1900 3050 3300 85 DN125 3 88 80 DN125 3500 1310 1900 3500 3800 85 DN125 3 103 80 DN125 3500 1310 1950 3700 4050 3 86 3 104 3 123 Type Charge volume (kg) 210 220 230

'5-6 Asymmetry Dentiform Semi-hermetic Screw Y-* 380V, 3N~50Hz 0.086m2 . 0C/kW Water side pressure is 1.0MPa
45%,75%,100% 42%,75%,100% 50%,75%,100%

25%,50%,75%,100% step or stepless adjustment R22 240 380V, 3N~50Hz 3 136 85 DN150 3 114 80 DN150 3600 1410 2000 3850 4250 3 156 85 DN150 3 129 80 DN150 3600 1460 2000 4150 4560
O O

250

270 3 167 85 DN150 3 141 80 DN150 3600 1460 2100 4550 5030

280 3 185 85 DN150 3 155 80 DN150 3600 1510 2100 5100 5550

R22 2 Thermo-expansive valve


kg 90x2 90+100 100x2 120x2

Shell and tube UCW050A/2


mm mm m /h
3

DN200 DN200 293

DN200 DN200 310

DN200 DN200 323

DN200 DN200 358

Cooling water Evaperator pressure drop (kpa) Diam. of inlet/outlet Water pipe (mm)

Dry shell and tube UCH050A/1


mm mm m3/h DN200 DN200 241 DN200 DN200 256 DN200 DN200 265 DN200 DN200 295

Length (A)(mm) Dimensions Width (B)(mm) Height (C)(mm) Unit weight (kg) Unit running weight (kg)

High/low pressure protections, over load protection, phase sequence protection, water flux volume protection, oil level protection, discharge temperature protection.
kg kg 6240 6790 6490 7090 6620 7220 6930 7630

Same technique parameter

cooling water inlet/outlet temperature:12/7 C. chilled water inlet/outlet temperature:30/35 C. waterside fouling factor:0.086m2 C/kW.
O

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

31

32

Screw Chiller system

Flooded type (dual compressor series)


MHS-DF(290-510)S/C Model

290 USRT kW
kW

340 341 1200 220 390

375 375 1320 244 436 Automatic

430 427 1500 278 500

460 461 1620 304 552

510 512 1800 332 600

Cooling capacity Power input Current (A)

290 1020 188 326

[ A ] Series

Capacity adjustment method Capacity adjustment range (%) Refrigerat Power supply Number of pass Chilled water flow (t/h) Condensor Chilled water pressure drop (kpa) Diam. of inlet/outlet water pipe (mm) Number of pass Cooling water flow (t/h) Cooling water Evaperator pressure drop (kpa) Diam. of inlet/outlet Water pipe (mm) Length (A)(mm) Dimensions Width (B)(mm) Height (C)(mm) Unit weight (kg) Unit running weight (kg) Same technique parameter DN200 4500 14600 1900 5850 6360 DN200 4500 1510 1950 6780 7350 80 80 80 DN200 2 176 DN200 2 206 85 85 85 2 208 2 246 Type Charge volume (kg) 340 400 420 2 271

25%,50%,75%,100% step or stepless adjustment R22 450 2 309 85 DN200 2 258 80 DN200 4600 1660 2000 8470 9230 500 2 334 85 DN200 2 278 80 DN200 4600 1710 2100 9250 10150
O O

520 2 370 85 DN200 2 310 80 DN200 4600 1760 2100 9480 10420

380V, 3N~50Hz

DN200 2 228

DN200 4600 1560 2000 7750 8420

cooling water inlet/outlet temperature:12/7 C. chilled water inlet/outlet temperature:30/35 C. waterside fouling factor:0.086m2 C/kW.
O

Air-cooled Modular Chiller System

Remarks: The cooling capacities above are tested on the following states. Evaporator inlet water 12OC, outlet water 7OC Condenser inlet water 30OC, outlet water 35OC

33

Air-cooled Modular Chiller System HOW TO READ THE MODELS ?


M G A - D 65 W / S N2
Refrigerant N1 R410A N2 R407C - R22

General introduction
Air-cooled heat-pump unit is a kind of central air conditioner which adopts air as the cooling (heating) source and water as cooling (heating) medium. As a sort of integrated equipment, it need no cooling tower cooling water pump boiler and corresponding auxiliary parts such as pipe system etc, which makes the structure simpler, saves installation space, convenient maintenance and energy saving. Thus it is very suitable for areas that are short of water. Air-cooled heat-pump unit is the first priority in the engineering design for the following conditions: Hot summer and cold winter. No heating boiler and heating-supply pipe system.

Power Supply S 380V~, 50Hz, 3Ph

Heating supply pipe system is unstable or the supplying time is short. Need air-conditioning whole year.

Outdoor Unit

Midea Commercial Digital scroll air-cooled heat-pump modular unit is designed and produced on the basement of sufficiently absorbing the top technology in AC areas, adopting self-control components with

Cooling Capacity (Kw)

high quality which made by world famous producers. Moreover, after improvement, unit can run more efficiently and more stably.

Compressor Type D Digital Scroll Compressor F Fixed Speed Scroll Compressor

Midea Commercial air-cooled heat-pump modular unit can be used widely in civil construction of AC engineering and industrial engineering, such as hotel, villa, restaurant, hospital, factory, etc. It is a wise

Product Category A Modular Air-cooled Chiller System P Water-cooled Package Unit H Heating Water System

choice for areas where water is insufficient or there are strict limits on noise level and surroundings.

Light Chiller System

MDV

Accessories
Model Name Function Control on & off and the running parameter of unit. At most can control 8 modules. Check the status of water flow and control the whole system... One unit only need one flowmeter. Dimension (WxHxD)mm 120x120x15 (front) + 87x55x48 (back)

30kW

65kW

185kW

KJR-08B1/E

Wire controller

WFS-1001-H

Target-type flowmeter

1 inch screw thread (connect in the water pipe)

35

36

Air-cooled Modular Chiller System


System features
Modular design, flexible combination. There are 3 types (30kw, 65kw, 200kw) and 5 basic units. The maximum of the system is consisted of one main unit and 7 auxiliary units, and the capacity can be up to 1480kW. Adopts Digital Scroll compressor, capacity can be adjusted. (200kw module just adopt fix-speed scroll compressor.) High reliability and efficiency. Easy connection between main unit and auxiliary unit. Intelligentized control. Strong Micro-computer automatic control function, more than twelve self-protect and self-diagnose functions.
(0%) OFF (100%) ON 75% 50% 25% 0.5% 2.6 130 260 390 520kw capacity output Ratio 100%

A dopt digital scroll technology, new air-cooled modular design


Since traditional air cooled chiller system adjusts energy output by turning ON/OFF the compressor, the capacity output is not accurate as Digital Scroll compressor. Midea modular air-cooled chiller system combines digital scroll compressor with constant speed compressor, which can steplessly adjust the capacity output from 0.5 to 100%. In the state of partial capacity loading, the system can adjust the capacity output precisely according to each indoor unit's requirement.

Advantages
Modular design, easy for capacity extension Adopting modular design, numbers of modules can be assembled by connecting each own inlet & outlet pipeline in series. The integrated system has a bigger capacity. The min. capacity is 30kW and the max. is 1480 kW. Furthermore, any of unit can be set as main unit, so both the design and installation are very flexible.
Energy output for traditional modular air cooled chiller system

Energy output for digital modular air cooled chiller system

Convenient combination, auto control, available capacity adjustment


Digital and constant module unit can be
Capacity output ratio %

combined by simple pipe and signal wiring


100% 95% 90%

connection. The capacity output can be adjusted and the load of different module unit can be distributed uniformly by control system. The unit system can adjust output according to requirement without energy waste.

+
65kW

=
520kW

85% 80% 75% 70% 65% 60% 55% 50% 45% 40% 35% 30% 25% 20%

+
185kW

=
1480kW

15% 10%

65KW

130KW

195KW

260KW

Indoor unit capacity need

325KW

390KW

455KW

520KW

65kw digital model

65kw fixed model

37

38

Air-cooled Modular Chiller System


PMV refrigerant flow adjustment Traditional modular chiller adopts thermo-expansion valve for adjusting, but it cannot adjust refrigerant flow accurately and also will be delay. So it makes the room temperature fluctuating too much that users may be uncomfortable. High efficient heat exchanger For the 30 or 65kw module, we use plate heat-exchanger, and for the 200 kw module, we use shell-andtube heat-exchanger. Chiller water outlet temperature can be adjusted Water outlet temperature can be adjusted according to customers' demand. In cooling mode, the adjustable ranges from 7 C to 12 C, and in heating mode, it ranges from 45 C to 50 C. Simple control The wire connection is very simple between modules. The signal wiring connection between two units of 65kW module is finished before launch. The two-cores Shielded Twisted Pair is used for signal wire. Each unit can be controlled and monitored by the wiring controller that just connects to main unit.
0 0 0 0

Specification
MGA-D(30-240)W/S(N2) or MGA-F(30-240)W/S(N2) 30 kW 1000 kcal/h kW 1000 kcal/h kW kW 30 25.8 32 27.5 10 9.8 60 60 51.6 64 55 20 19.5 90 90 77.4 96 82.6 30 29.3 120 120 103.2 128 110.1 40 39.0 150 150 129 160 137.6 50 48.8 180 180 154.8 192 165.1 60 58.8 210 210 180.6 224 192.7 70 68.3 240 240 206.4 256 220.2 80 78.0

Model Cooling Capacity Heating Capacity

Cooling input Heating input Power supply Control type Safety protection device

380V 3N~ 50Hz Wire control. Manual or automatic startup, the running status display and malfunction alarm, etc. High/low-pressure switch, anti-frost switch, water-flow switch, over-load protection, and power phases sequence protection.
1+0 9 kg Water flow volume m3/h Water resistance loss kPa Waterside heatexchanger Max. Pressure MPa Water inlet/outlet pipeline diameter 4.5x2 5.2 1+2 18 4.5x4 10.3 1+3 27 4.5x6 15.5 1+4 36 4.5x8 20.6 29.4 1+5 45 4.5x10 25.8 1+6 54 4.5x12 30.9 1+7 63 4.5x14 36.0 1+8 72 4.5x16 41.2

Main module + auxiliary module Compressor input kW Refrigerant Refrigerant

Both R22 and R407C are available

Strong and reliable control system


Stepless capacity modulation, more efficiency Operation mode control Automatic and uniform adjusting function among multi compressors Anti-frost and anti-cold air function in heating mode Anti-freezing function of water system in winter Self-protection and Self-diagnosis function:
Compressor low and high pressure protection Phase sequence protection Anti-frost protection on cooling mode Anti-frost protection in winter Start continually protection Compressor over current protection Compressor discharge temp. protection Unit Anti-overheat protection Auxiliary heater protection Water flow switch protection Sensor malfunction protection Ensure compressor operate on proper temp. range. Prevent compressor from damaging by wrong phase sequence Prevent evaporator, water pipe or other parts from damaging by low evaporator temp. Prevent evaporator, water pipe or other parts from damaging by low ambient temp. Prevent compressor from damaging by continually start which come of malfunction Prevent compressor from burning out by over current on abominable weather. Ensure compressor operate in a good condition. Prevent compressor from burning out for running on lacking refrigerant or oil. Prevent auxiliary heater from damaging by over high temperature. Prevent unit from damaging by lack of water. Ensure sensor collect correct information so that control system will not make wrong action.
Dimension Total weight Packing Air side heat-exchanger

Welding, stainless steel, plate heat exchanger


1.0

Water system

133mm Fin coil


12 0.7x1 850 440 7.5 24 0.7x2 2300 880 15 36 0.7x3 2450 1320 48 60 72 0.7x6 6900 2640 84 0.7x7 8050 3080 52.5 96 0.7x8 9200 3520 60 0.7x5 0.7x4 1514 4600 1760 5750 2200 1820 L x W x H (1620 x 1034 x 2041) 37.4 30 22.5 45

Type Air flow volume 103m3/h Fan motor input kW L mm W mm H mm kg mm

Optional auxiliary heater kw

Notes: 1. Each module is packed separately and the packing size refers to one module only. 2. Auxiliary electric heaters are not provided. If necessary the users may refer to the above tables parameter about auxiliary electric 3. Nominal capacities are based on the following conditions: Cooling condition: chilled water inlet/outlet: 12OC/7OC. Outdoor temp:35OC(DB)/24OC(WB) Heating condition: warm water inlet/outlet: 40OC/45OC. Outdoor temp:7OC(DB)/6OC(WB) 4. Water side fouling factor: 0.086m2 . OC/kw.

heater and configure themselves.

39

40

Air-cooled Modular Chiller System


Specification
MGA-D(270-480)W/S(N2) or MGA-F(270-480)W/S(N2) 270 kW 1000 kcal/h kW 1000 kcal/h kW kW 270 23.2 288 247.5 90 87.8 300 300 258 320 275 100 97.5 330 330 283.8 352 302.5 110 107.3 360 360 309.6 384 330 120 117.0 390 390 335.4 416 357.5 130 126.8 420 420 361.2 448 385 140 136.5 450 450 387 480 412.5 150 146.3 480 480 412.8 512 440 160 156.0

Specification
MGA-D(65-520)W/S(N2) or MGA-F(65-520)W/S(N2) 65 kW 1000 kcal/h kW 1000 kcal/h kW kW 65 55.9 69 59.3 21.5 21 130 130 111.8 138 118.7 43 42 195 195 167.7 207 178.0 64.5 63 260 260 223.6 276 237.4 86 84 325 325 279.5 345 296.7 107.5 105 390 390 335.4 414 356.0 129 126 455 455 391.3 483 415.4 150.5 147 520 520 447.2 552 474.7 172 168

Model Cooling Capacity Heating Capacity

Model Cooling Capacity Heating Capacity

Cooling input Heating input Power supply Control type Safety protection device

Cooling input Heating input Power supply Control type Safety protection device

380V 3N~ 50Hz Wire control. Manual or automatic startup, the running status display and malfunction alarm, etc. High/low-pressure switch, anti-frost switch, water-flow switch, over-load protection, and power phases sequence protection.
1+8 81 kg Water flow volume m3/h Water resistance loss kPa Waterside heatexchanger Max. Pressure MPa Water inlet/outlet pipeline diameter 4.5x18 46.4 1+9 90 4.5x20 51.5 1+10 99 4.5x22 56.7 1+11 108 4.5x24 61.8 29.4 1+12 117 4.5x26 67.0 1+13 126 4.5x28 72.1 1+14 135 4.5x30 77.3 1+15 144 4.5x32 82.4

380V 3N~ 50Hz Wire control. Manual or automatic startup, the running status display and malfunction alarm, etc. High/low-pressure switch, anti-frost switch, water-flow switch, over-load protection, and power phases sequence protection.
1+0 18.5 kg Water flow volume m3/h Water resistance loss kPa Waterside heatexchanger Max. Pressure MPa Water inlet/outlet pipeline diameter 4.5x4 11.2 1+1 37 4.5x8 22.4 1+2 55.5 4.5x12 33.6 1+3 74 4.5x16 44.8 29.4 1+4 92.5 4.5x20 56.0 1+5 111 4.5x24 67.2 1+6 129.5 4.5x28 78.4 1+7 148 4.5x32 89.6

Main module + auxiliary module Compressor input kW Refrigerant Refrigerant

Main module + auxiliary module Compressor input kW Refrigerant Refrigerant

Both R22 and R407C are available

Both R22 and R407C are available

Welding, stainless steel, plate heat exchanger


Water system 1.0

Welding, stainless steel, plate heat exchanger


1.0

Water system

133mm Fin coil


108 0.7x9 12450 3960 67.5 120 0.7x10 13900 4400 75 132 0.7x11 25350 4480 144 156 168 0.7x14 19700 6160 180 0.7x15 21150 6600 112.5 192 0.7x16 22600 7040 120 Dimension Total weight Packing 0.7x12 0.7x13 1514 16800 5280 18250 5720 1820 L x W x H (1620 x 1034 x 2041) 105 97.5 90 82.5 Air side heat-exchanger

133mm Fin coil


24 0.7x2 850 700 15 48 0.7x4 2300 1400 30 72 0.7x6 3450 2100 96 120 144 0.7x12 6900 4200 168 0.7x14 8050 4900 105 192 0.7x16 9200 5600 120 0.7x10 0.7x8 2492 4600 1820 2800 3500 L x W x H (2612 x 1034 x 2041) 75 60 90 40 5750

Air side heat-exchanger

Type Air flow volume 103m3/h Fan motor input kW L mm

Type Air flow volume 103m3/h Fan motor input kW L mm W mm H mm kg mm

Dimension Total weight Packing

W mm H mm kg mm

Optional auxiliary heater kw

Optional auxiliary heater kw

Notes: 1. Each module is packed separately and the packing size refers to one module only. 2. Auxiliary electric heaters are not provided. If necessary the users may refer to the above tables parameter about auxiliary electric 3. Nominal capacities are based on the following conditions: Cooling condition: chilled water inlet/outlet: 12OC/7OC. Outdoor temp:35OC(DB)/24OC(WB) Heating condition: warm water inlet/outlet: 40OC/45OC. Outdoor temp:7OC(DB)/6OC(WB) 4. Water side fouling factor: 0.086m2 . OC/kw.

heater and configure themselves.

Notes: 1. Each module is packed separately and the packing size refers to one module only. 2. Auxiliary electric heaters are not provided. If necessary the users may refer to the above tables parameter about auxiliary electric 3. Nominal capacities are based on the following conditions: Cooling condition: chilled water inlet/outlet: 12OC/7OC. Outdoor temp:35OC(DB)/24OC(WB) Heating condition: warm water inlet/outlet: 40OC/45OC. Outdoor temp:7OC(DB)/6OC(WB) 4. Water side fouling factor: 0.086m2 . OC/kw.

heater and configure themselves.

41

42

Air-cooled Modular Chiller System


Pipe system connection
Specification
MGA-F(200-1600)W/S(N2) 200 kW 1000 kcal/h kW 1000 kcal/h kW kW 185 159 200 172 62 60 400 370 318 400 344 124 120 600 555 477 600 516 186 180 800 740 636 800 688 248 240 1000 1100 955 1200 1032 310 300 1200 1295 1114 1400 1204 372 360 1400 1480 1273 1600 1376 434 420 1600 1480 447.2 1273 1600 496 480
Fan coil water drain valve

Sketch of (30, 65kw) module connection


expansion tank overflow water water drain valve automatically gas discharge valve water supply valve Y shape filter soft connect soft connect water pump

Model Cooling Capacity Heating Capacity

Main modular
cut-off valve

Auxiliary modular1

Auxiliary modular7

water flow switch

auxilary heater

pressure gauge

Cooling input Heating input Power supply Control type Safety protection device

connet PCB box of O# unit

thermometer

380V 3N~ 50Hz Wire control. High/low-pressure switch, anti-frost switch, water-flow switch, over-load protection, and power phases sequence protection.
1+0 56 kg Water flow volume m3/h Water resistance loss kPa Waterside heatexchanger Max. Pressure MPa Water inlet/outlet pipeline diameter 100 100 150 150 70 31.8 1+1 112 140 63.6 1+2 168 210 95.4 1+3 224 1+4 280 1+5 336 420 190.8 1+6 392 490 222.6 1+7 446

Main module + auxiliary module Compressor input kW Refrigerant Refrigerant

Sketch of 200kw module connection Single module:


Water flow switch Water pump(main) Bleeder pipe Bleeder supplier Cutoff valve Water drain valve Water pump (auxiliary) Water inlet Check valve Adjusting valve

R22
280 127.2 15 350 159.0 560 254.4

Shell-and-tube, high efficiency heat-exchanger


1.0 200 200 200 250
Water outlet

Flow gauge Filter Themometer

Water system

Pressure gauge

Air side heat-exchanger

Type Air flow volume 103m3/h Fan motor input kW L mm 78 1.0x6 3210 156 1.0x12 7920 234 1.0x18 12600

Fin coil
312 1.0x24 17340 390 1.0x30 22050 468 1.0x36 26760 546 1.0x42 31470 624 1.0x48 36180
Module

Soft connector Water pump

Expansion tank

Dimension Total weight Packing

W mm H mm kg mm 3000 6000 2720 5440 8160

2060 2430 10880 13600 16320 19040 21000 21760 24000 L x W x H (3450 x 2250 x 2700) 12000 15000 18000 9000

Multi modules (we recommend the following two types:)


No.8 Module Evaporator No.1 Module(main) Evaporator No.8 Module Evaporator No.1 Module(main) Evaporator Temp.sensor of total water outlet Water flow switch Temp.sensor of total water outlet Water flow switch

Optional auxiliary heater kw

Notes: 1. Each module is packed separately and the packing size refers to one module only. 2. Auxiliary electric heaters are not provided. If necessary the users may refer to the above tables parameter about auxiliary electric 3. Nominal capacities are based on the following conditions: Cooling condition: chilled water inlet/outlet: 12OC/7OC. Outdoor temp:35OC(DB)/24OC(WB) Heating condition: warm water inlet/outlet: 40OC/45OC. Outdoor temp:7OC(DB)/6OC(WB) 4. Water side fouling factor: 0.086m2 . OC/kw.

heater and configure themselves.

Water pump

Water pipe

Water pump

Water pipe

Remarks: 1. For the 30kw and 65kw system, if electrical two-way valve used for all terminals and they are all closed when main unit is operating, the plate exchanger may be damaged. So pass-by adjusting valve should be set in the system. 2. If there is no any pass-by adjusting valve in the system, the number of fan coil with two-way water valve should not over 50%.

43

44

Water-Cooled Package Unit


Features
The system adopt compliance scroll compressor with high efficiency, low noise level, stable performance & high reliability.

[ W ] Series

Adopt advanced parallel system just as multi system, each compressor will run according to the load of the system. It can save a lot of energy when operation at partial load; Shell-tube condenser efficiently reduces the water jam and makes it easier to do clearance of water system; Microcomputer control technology makes the water pump and cooling tower can be easily controlled; The touch screen make it is easy to operation; The kinds of protection function makes the system safety and rhathymia; The strong protection and malfunction detect makes the system easy for debugging and maintenance; Polyester treatment technics, makes the beautiful appearance and good anti- erode ability;

Water-Cooled Package Unit

MGP-F35W/S

MGP-F60W/S MGP-F80W/S

MGP-F100W/S~MGP-F145W/S

Refrigerant: R22, R407C


Apply site: Factory, supermarket, restaurant, multiple shop and recreation. Capacity range: 35kW-145kW

46

Water-Cooled Package Unit


Dimension
W Touch screen Filter

Specification
Model Cooling capacity Rated power EER
H Pressure gauge

MGP-F35W/S kW kW W/W A 35 8.75 4 17.8

MGP-F60W/S 60 15.2 3.95 30.9

MGP-F80W/S 80 19 3.95 37.2

MGP-F100W/S MGP-F120W/S MGP-F135W/S MGP-F145W/S 100 23.8 4.07 45 380V,3N~50Hz Scroll Direct start-up 120 29.5 3.97 58.5 135 34.1 3.9 62.5 145 3.9 37.2 68.2

Rated current Power supply Type


585

Installation hole(4- 15)

Start-up mode Compressor Output power kW 3.6x2 3.05x4 4.0x4

F G

Condenser drainage

3.05x6 Mineral oil

8.0x3

9.5x3

10.5x3

Backside

Face

Lubricatin Standard goil L Type Refrigeration kg Wind-wheel Motor kW

1.8x2 8x1 1 1.5 6500 147 7.5 9806 40(1-1/2") 40(1-1/2") 25(1") 25(1") 1839/2047 1090/1250 1055/1230 430/470

1.8x4 8x2 1 2.8 11000 147 12.9 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1420/1640 1055/1230 690/723

1.8x4 9x2 1 3 14000 147 16.5 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1420/1640 1055/1230 700/733

1.8x6 R22 8x3 2 5.3 Strap 18200 147 22.1 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1912/2152 1055/1230 820/870

3.0x3 9.0x3 2 5.5 20600 147 26.7 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/204 1912/21527 1055/1230 830/880

3.3x3 9.5x3 2 5.5 20600 230 28.8 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1912/2152 1055/1230 840/890

3.3x3 9.5x3 2 5.5 22000 250 30.9 9806 65(2-1/2") 65(2-1/2") 25(1") 25(1") 1839/2047 1912/2150 1055/1230 850/900

Cooling water outlet Cooling water inlet

Fan motor

Driving mode Air volume m3/h Static pressure Water Volume Pa m3/h

Emergency drainage

Left side Air outlet Air outlet

Water resistance Pa Cooling Water Side Diameter of inlet mm/inch wate pipe Diameter of outlet mm/inch wate pipe Outlet of evaporator Outlet of plate Height(before/after) length(before/after) width(before/after) Net/Cross weight Protection device High pressure protection kgf/cm2 mm/inch mm/inch mm mm mm kg

Over-load protection, high/low pressure protection, anti-frost protection, and inner temp. Protection of compressor, phase-sequence 24 0.3 60 24 0.3 62 24 0.3 66 24 0.3 70 24 0.3 71 24 0.3 71 24 0.3 72

Top side MGP-F100W/S MGP-F120W/S MGP-F135W/S MGP-F145W/S Model MGP-F35W/S MGP-F60W/S MGP-F80W/S MGP-F100W/S MGP-F120W/S MGP-F135W/S MGP-F145W/S Unit: mm A 241 235 235 206 206 206 206 B / / / 632 632 632 632 C 377 558 558 434 434 434 434 D 1055 1055 1055 1055 1055 1055 1055 E 410 478 478 482 482 482 482 F 1130 1460 1460 1952 1952 1952 1952

Top side MGP-F35W/S MGP-F60W/S MGP-F80W/S

Low pressure protection Noise

kgf/cm2 dB(A)

G 1160 1490 1490 1982 1982 1982 1982

H 1839 1839 1839 1839 1839 1839 1839

W 1090 1420 1420 1912 1912 1912 1912

47

48

Overview of heating water system

R407C

R22

[ R ] Series

Based on reverse Carnot cycle principle, heating water system is one of the most advanced water heater with the highest COP. Heating water system generally consists of compressor, evaporator, expansion valve, strainer, accumulator tank, condenser, water tank.

Integrative

7kW

9.0kW

17.5kW

35kW

The sketch of system connection

Heating Water System


Integrative

Compressor

High temperature

Hot water

Integrated design of main unit and tank makes it very conveniently using only by connecting the water inlet and outlet pipes.
Air inlet Heat exchanger for air Heat exchanger for water Water tank Hot water

Low temp.

Expansion Valve Cool water

50

Heating Water System

Environmental Protection
Heating water system is environmentally friendly and low energy consuming.

Installation sketch for single unit

Economical
Less additional operation charge; No need for transportation and storage of
Heat pump water heater

Water tank

To user

Drain valve

fuel; simple maintenance and reparation. COP up to 4.0.

Pressure meter
Filter Pipe union Water pump Cutoff valve Water supply

Safety
Heating water system does not need storage of fuel and fuel pipe, therefore, it is free of fuel leakage, fire and explosion. The unit has multi-protection functions: high-pressure protection, low-pressure
Heat pump water heater Heat pump water heater Heat pump water heater Heat pump water heater Heat pump water heater Heat pump water heater

Installation sketch for multi units

protection, overflow and overload protection for compressor, startup delay, water switch, water temperature overhigh protection and water level protection of water tank.

ON/OFF

valve

valve

valve

valve

valve

valve

Convenience
Automatic intelligent controlling system defrosts automatically in cold winter. Outdoor installation; no special equipment room needed.
valve valve valve valve valve valve

Durability
Famous brand compressor and plate heat exchanger equipped. Quintuple antirust technique ensures excellent durability.

Pipe choice

Number of unit (set)

1~3

4~6

7~9

10~12

13~16

Widely applicable
Within the temperature range from -10 to 400C, the heating water system can work all year around, and perform well against bad weather.
Pipe diameter (inch) 1~111 4 1 1 1-~14 2 1 1-~2 2 2~3 3~4

51

52

Heating Water System

Specification

Model Heating capacity Rated power Rated current Hot water volume Max power Max current Specification, power supply Controlling method Compressor (power x quantity) Refrigerant Refrigerant charge Outlet water temp Specification of water system Heat exchanger(water side) Diameter,water inlet pipe Diameter,water outlet pipe Max compression resistance Type Heat exchanger (gas side) Motor power Type of air outlet Length Demension Width Height Weight Noise level kg dB(A) kW kW A m3/h kW A

MGH-F35W/S 35 9.0 16.6 1.0 11.8 20.2

MGH-F17.5W/S 17.5 4.5 8.6 0.5 5.8 9.8

MGH-F9W 9.0 2.3 11.0 0.26 3.1 14.8

MGH-F7W 7.0 2.0 10.0 0.16 2.3 14.0

[ S ] Series

380V 3N ~ 50HZ

220V 1N ~ 50HZ

Manual,Auto and failure alarm 4.25kW x 2 2300g x 2 4.25kW x 1 R22/R407C 2200g x 1 60 (default) stainless steel plate heat exchanger DN25 DN25 1.0Mpa 250W x 2 Vertical air discharge 1290mm 750mm 1540mm 290 58 DN20 DN20 1.0Mpa 150W x 2 Side air discharge 940mm 340mm 1245mm 135 54 DN15 DN15 1.0Mpa 125W Vertical air discharge 555mm 555mm 840mm 77 52 tube-tube heat exchanger DN15 DN15 0.8Mpa 100W Side air discharge 900mm 530mm 1200mm 70 50 1300g x 1 1000g x 1 2.2kW x 1 1.9kW x 1

innergroove copper pipe,hydrophilic aluminum coil

Water Source Heat Pump

53

Water Source Heat Pump


System sketch map

HOW TO READ THE MODELS ?


M S H - 12 W / S

Save energy, environmental, healthy as the thematic of today's AC market, AC industry come into a new stage. The Midea split water source heat pump unit can meet more and more requirement of the thematic, and become the new start of AC industry.

7 6

Power Supply S: 380V~, 50Hz, 3Ph - 220-240V~, 50Hz, 1Ph


Top floor

Outdoor Unit

Nominal Capacity: kW
Vertical pipe

Other heat source

H: Heating And Cooling C: Cooling Only

Horizontal pipe

AC system

Water Source Heat Pump


N Floor

Midea
Copper pipe Copper pipe Copper pipe

First floor

Example: 1. Electronic Water handler 5. water filter

2. Water circle pump

3. Soft connector

4. valve

6. cooling tower

7. water expansion tank

Water Circle Type


Share the flow water in the water pipe as cooling/heating source. It can adopt crude water source as river water, sea water, lake water, etc, even industry waste water or sewage can be adopted as the cooling/heating source.

55

56

Water Source Heat Pump


Features
Environmental-friendly and save energy
Adopt the ground water, lake water, etc, do not pollute the environment. Water cooled type with high heat exchange ratio. It is very suitable for some place where requirement heating and cooling at the same time. Ultra thin body, space saving and easy installation. Quiet operation, low noise.

Water source low static pressure duct

Stable and reliable


Simple system design, reliable performance. Water cooled heat exchange, high efficiency and stable operation.
Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Noise level weight Indoor unit Dimension kW kW kW kW dB(A) kg W(mm) D(mm) H(mm) m3/h mm DN(mm) DN(mm) MTA2-18CR 5.0 / 1.3 / 41/37 26 1247 490 240 1000 12.7 6.35 20 32 12.7 6.35 20 32 R22 15.9 9.53 20 32 MTA2-18HR 5.0 6.0 220V-50Hz 1.3 1.4 41/37 26 1.9 / 42/38 30 1470 490 240 1250 15.9 9.53 20 32 1.9 2.0 42/38 30 MTA2-24CR 7.1 / MTA2-24HR 7.1 8.0

Easy enlarge the capacity, Save investment


It can invest and install the system for some building by stages while do not affect the project design and save early days investment. Set aside water pipe connector on public water source, so that easy for enlarging the capacity.

Various of indoor unit


Various of indoor unit, flexible equipment selection. The system can be installed in covert place, do not affect the holistic layout of the building.

Ari volume Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Noise level weight Indoor unit Dimension

kW kW kW kW dB(A) kg W(mm) D(mm) H(mm) m3/h mm DN(mm) DN(mm)

MTA2-24CR 7.1 / 1.9 / 42/38 30 1470 490 240 1250 15.9 9.53 20 32

MTA2-24HR 7.1 8.0 1.9 2.0 42/38 30

Ari volume Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

15.9 9.53 20 32

MTA2-42CR MTA2-42HR 12.0 12.0 / 14.0 380V-50Hz-3N 3.2 3.2 / 3.3 43/38 43/38 36 36 1610 490 240 1700 19.0 19.0 12.7 12.7 20 20 32 32 R22

MTA2-48CR 14.0 / 3.5 / 43/38 36 1610 490 240 1800 19.0 12.7 20 32

MTA2-48HR 14.0 15.0 3.5 3.6 43/38 36

19.0 12.7 20 32

Remarks: 1. Cooling condition: Indoor temperature: 27OC(DB)/19OC(WB), water inlet temperature: 30OC; 2. Heating condition: Indoor temperature: 20OC(DB), water inlet temperature: 20OC;

57

58

Water Source Heat Pump


Water source four way cassette Water source high static pressure duct

Installed in the ceiling, and save much sapce. Four directions and large scale of air flow, create a much more comfortable space.

Quite high external static pressure, long distance air supply. Fresh air drawing, healthier and more comfortable for you.

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Noise level weight Indoor unit Dimension

kW kW kW kW dB(A) kg W(mm) D(mm) H(mm) m3/h mm DN(mm) DN(mm)

MCA-18CR 5.0 / 1.3 / 39/34 25/6 840/950 840/950 230/46 1020 12.7 6.35 20 32

MCA-18HR 5.0 6.0 220V-50Hz 1.3 1.4 39/34 25/6

MCA-24CR 7.1 / 1.9 / 39/35 25/6 840/950 840/950 230/46 1020

MCA-24HR 7.1 8.0 1.9 2.0 39/35 25/6

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Noise level weight Indoor unit Dimension

kW kW kW kW dB(A) kg W(mm) D(mm) H(mm) m3/h mm DN(mm) DN(mm)

MHA-18CR 5.0 / 1.3 / 44/39 52 850 660 380 1200 12.7 6.35 20 32

MHA-18HR 5.0 6.0 220V-50Hz 1.3 1.4 44/39 52

MHA-24CR 7.1 / 1.9 / 44/39 52 850 660 380 1600

MHA-24HR 7.1 8.0 1.9 2.0 44/39 52

Ari volume Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

12.7 6.35 20 32 R22

15.9 9.53 20 32

15.9 9.53 20 32

Ari volume Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

12.7 6.35 20 32 R22

15.9 9.53 20 32

15.9 9.53 20 32

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Noise level weight Indoor unit Dimension

kW kW kW kW dB(A) kg W(mm) D(mm) H(mm) m3/h mm DN(mm) DN(mm)

MCA-24CR 7.1 / 1.9 / 39/35 25/6

MCA-24HR 7.1 8.0 1.9 2.0 39/35 25/6

Ari volume Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

840/950 840/950 230/46 1020 15.9 9.53 20 32 15.9 9.53 20 32

MCA-42CR MCA-42HR 12.0 12.0 / 14.0 380V-50Hz-3N 3.2 3.2 / 3.3 41/36 41/36 35/6 35/6 840/950 840/950 300/46 1800 19.0 19.0 12.7 12.7 20 20 32 32 R22

MCA-48CR 14.0 / 3.5 / 44/38 35/6

MCA-48HR 14.0 15.0 3.5 3.6 44/38 35/6

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Noise level weight Indoor unit Dimension

kW kW kW kW dB(A) kg W(mm) D(mm) H(mm) m3/h mm DN(mm) DN(mm)

MHA-24CR 7.1 / 1.9 / 44/39 52 850 660 380 1600 15.9 9.53 20 32

MHA-24HR 7.1 8.0 1.9 2.0 44/39 52

840/950 840/950 300/46 1800 19.0 12.7 20 32 19.0 12.7 20 32

Ari volume Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

15.9 9.53 20 32

MHA-42CR MHA-42HR 12.0 12.0 / 14.0 380V-50Hz-3N 3.2 3.2 / 3.3 44/40 44/40 67 67 1200 660 380 3200 19.0 19.0 12.7 12.7 20 20 32 32 R22

MHA-48CR 14.0 / 3.5 / 44/40 67 1200 660 380 3200 19.0 12.7 20 32

MHA-48HR 14.0 15.0 3.5 3.6 44/40 67

19.0 12.7 20 32

Remarks: 1. Cooling condition: Indoor temperature: 27OC(DB)/19OC(WB), water inlet temperature: 30OC; 2. Heating condition: Indoor temperature: 20OC(DB), water inlet temperature: 20OC;

Remarks: 1. Cooling condition: Indoor temperature: 27OC(DB)/19OC(WB), water inlet temperature: 30OC; 2. Heating condition: Indoor temperature: 20OC(DB), water inlet temperature: 20OC;

59

60

Water Source Heat Pump

Entire system design, easier installation and save spacing. High efficiency heat-exchanging,hence brings high EER. Anti-corrosive cabinet, stable running and long life-span.

[ K ] Series

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Water Volume Water resistance Outdoor Noise level unit weight Dimension Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

kW kW kW kW L/s kPa dB(A) kg W(mm) D(mm) H(mm) mm mm DN(mm) DN(mm)

MSC-5W 5.0 / 1.3 / 0.36 24 42 38 754 340 447 12.7 6.35 20 32

MSH-5W 5.0 6.0 220V-50Hz 1.3 1.4 0.36 24 42 40 754 340 447 12.7 6.35 20 32 R22

MSC-7W 7.1 / 1.9 / 0.51 25 42 48 674 340 574 15.9 9.53 20 32

MSH-7W 7.1 8.0 1.9 2.0 0.51 25 42 50 674 340 574 15.9 9.53 20 32

Air Handling Unit

Model Cooling Capacity Heating Capacity Power Supply Cooling Input Heating Water Volume Water resistance Outdoor Noise level unit weight Dimension Connection Gas Pipe Pipe Liquid Pipe Water Inlet/Outlet Pipe Condenser Water Pipe Refregeration

kW kW kW kW L/s kPa dB(A) kg W(mm) D(mm) H(mm) mm mm DN(mm) DN(mm)

MSC-7W/S 7.1 / 1.9 / 0.51 25 42 48 674 340 574 15.9 9.53 20 32

MSH-7W/S 7.1 8.0 1.9 2.0 0.51 25 42 50 674 340 574 15.9 9.53 20 32

MSH-12W/S MSC-12W/S 12.0 12.0 14.0 / 380V-50Hz-3N 3.2 3.2 3.3 / 0.91 0.91 32 45 77 790 340 574 19.0 12.7 20 32 R22 32 45 80 790 340 574 19.0 12.7 20 32

MSC-14W/S 14.0 / 3.5 / 1.02 32 45 77 790 340 574 19.0 12.7 20 32

MSH-14W/S 14.0 15.0 3.5 3.6 1.02 25 45 80 790 340 574 19.0 12.7 20 32

Fan Coil Unit

Remarks: 1. Cooling condition: Indoor temperature: 27OC(DB)/19OC(WB), water inlet temperature: 30OC; 2. Heating condition: Indoor temperature: 20OC(DB), water inlet temperature: 20OC;

61

Air Handling Unit & Fan Coil Unit HOW TO READ THE MODELS ?
Air Handling Unit
M K W1 - 040 W A - 1 Z 3 / M
Design sequence code Drawing off method of filter 3: up draw off Direction of pipe connection Z: Left connection Y: Right connection Supply air direction: type 1 Coil row quantity A: 4 rows B: 6 rows C: 8 rows Structure form of the unit W: horizontal type Nominal airflow volume (x100m /h)
3

Air Handling Unit

Brief introduction
Midea fan coil unit be made from high quality galvanization, the beautiful and thin body makes it save a lot of space and easy for installation. The big air volume makes a symmetrical room temperature so do not get harm to people at the same time. The advanced technology and high quality material reduced the noise level, it is widely used in marketplace, hospital, office, hotel, airport, etc.

Midea air handling unit have six series production as single wall horizontal type, single wall vertical type, single wall-mounted type, dual wall horizontal type, dual wall vertical type and dual wall-mounted type. Air flow volume ranges from 2000m3/h to 60000m3/h, cooling capacity ranges from 6kW to 985kW, heating capacity ranges from 11kW to 1100kW.

Midea air handling unit has been tested by national AC quality supervise testing center, as low noise level, high efficiency, stable operation and low power consumption make it as the advanced production in the world, and it is recommended for users by CRAA (China Refrigeration And Air-Conditioner Industry Association). As room AC, It is widely used in hotel, showplace, marketplace, office room, etc.; as industrial AC, it can meet the requirement of electron, chemical plant, medical treatment, pharmacy, tobacco produce, food produce, etc.

W1: Single-wall air handling unit W2: Duble-wall air handling unit K series Air Handling Unit

Midea

Fan Coil Unit


M K A - 300
Nominal airflow volume (CFM) A: Four way cassette type B: Compact four way cassette C: One way cassette F1: Concealed floor standing F2: Expoded floor standing K series Fan Coil Unit

Midea
63 64

Air Handling Unit

Fan Coil Unit

Single wall horizontal type


Air handle volume: 2000~20000m3/h Cooling capacity: 12~345kW Heating capacity: 18~370kW

Four way cassette(compact)


Model CFM Air volume m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) kg Net weight kg Gross weight MKB-300 300 500 3035 5130 530 10.1 33 580x245x580 750x340x750 21 30 MKB-400 400 630 3790 6425 653 14.5 33 580x245x580 750x340x750 21 30 MKB-450 450 710 4350 6480 740 18.3 34 580x245x580 750x340x750 21 30 MKB-500 500 800 4835 8210 850 27.1 35 580x245x580 750x340x750 21 30

Single wall vertical type AHU


Air handle volume: 2000~20000m3/h Cooling capacity: 12~345kW Heating capacity: 18~370kW

Four way cassette


Dual wall horizontal type
Air handle volume: 2000~60000m3/h Cooling capacity: 12~985kW Heating capacity: 18~1100kW
Model CFM Air volume m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) kg Net weight kg Gross weight MKA-600 600 1000 5709 9660 1005 38 35 840x310x930 1020x330x930 36 46 MKA-750 750 1250 6985 11550 1204 25.2 35 840x310x930 1020x330x930 36 46 MKA-850 850 1400 7860 13640 1382 27 38 840x310x930 1020x330x930 36 46 MKA-950 950 1600 8910 15011 1541 30 38 840x310x930 1020x330x930 36 46 MKA-1200 1200 2000 11250 19065 1928 44 39 840x310x930 1020x330x930 36 46 MKA-1500 1500 2500 13956 22820 2388 46 39 840x310x930 1020x330x930 36 46

Dual wall vertical type


Air handle volume: 2000~60000m3/h Cooling capacity: 12~985kW Heating capacity: 18~1100kW

One way cassette


MKC-400 MKC-300 400 300 Air volume 630 500 Cooling Capacity 3790 3035 Heating Capacity 6425 5130 Water flow 653 530 Water resistance 14.5 10.1 Noise level 33 33 Net dimension 850x235x400 850x235x400 Packing dimension 1080x310x460 1080x310x460 Net weight 23 23 Gross weight 37 37 Remarks: 1.The above design and specifications are subject to change without prior notice for product improvement. 2.The values given in the table for the noise level reflect the levels in anechoic chamber. Model CFM m3/h W W LPH kPa dB(A) mm(WxHxD) mm(WxHxD) kg kg MKC-600 600 1000 5709 9660 1005 27.1 35 1200x198x655 1380x265x775 31 38

Wall-mounted type
Air handle volume: 1500~5000m3/h Cooling capacity: 6~260kW Heating capacity: 11~290kW

65

66

Fan Coil Unit


Exposed floor standing
Model CFM Air volume m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) Net weight kg Gross weight kg MKF2-150 150 250 1800 2000 375 6.3 33 880x225x626 1025x285x810 33 37 MKF2-250 250 425 2000 2400 420 8.2 34 880x225x626 1025x285x810 33 37 MKF2-300 300 500 2200 2600 530 10.1 35 1000x225x626 1145x285x810 38 42 MKF2-400 400 680 2800 3200 653 14.5 35 1000x225x626 1145x285x810 38 42 MKF2-450 450 760 3600 4000 740 18.3 35 1200x225x626 1335x285x610 43 47

Duct type
Model CFM Air volume m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) Net weight kg kg Gross weight MKT-300 300 500 3035 5130 530 10.1 33 808x240x489 1110x340x570 21 30 MKT-400 400 630 3790 6425 653 14.5 33 808x240x489 1110x340x570 21 30 MKT-450 450 710 4350 6480 740 18.3 34 808x240x489 1110x340x570 21 30 MKT-500 500 800 4835 8210 850 27.1 35 1108x240x489 1410x340x570 21 30 MKT-600 600 1000 5790 9660 1005 38 35 1108x240x489 1410x340x570 21 30

MKF2-600 MKF2-500 600 500 1000 850 5600 4500 6300 5000 38 27.1 35 34 39 37 1500x225x626 1200x225x626 1645x285x810 1335x285x810 43 55 47 60 Remarks: 1.The above design and specifications are subject to change without prior notice for product improvement. 2.The values given in the table for the noise level reflect the levels in anechoic chamber. Model CFM m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) Net weight kg Gross weight kg Air volume

MKF2-800 800 1350 7100 8000 45 38 40 1500x225x626 1645x285x810 55 60

MKF2-1000 1000 1700 8000 9000 60 39 42 1500x225x626 1645x285x810 55 60

MKT-1200 MKT-950 MKT-750 MKT-850 1200 950 750 850 2000 1600 1250 1400 11250 8910 6985 7860 19065 15011 11550 13640 1928 1541 1204 1382 44 30 25.2 27 39 38 35 38 1308x240x489 1308x240x489 1308x240x489 1573x240x489 1590x340x570 1590x340x570 1590x340x570 2130x340x570 34 34 34 47 38 38 38 52 Remarks: 1.The above design and specifications are subject to change without prior notice for product improvement. 2.The values given in the table for the noise level reflect the levels in anechoic chamber. Model CFM m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) Net weight kg kg Gross weight Air volume

MKT-1500 1500 2500 13956 22820 2388 46 39 1573x240x489 2130x340x570 450 55

MKT-2000 2000 3400 18900 28350 2848 40 42 1599x367x605 1613x381x619 47 53

Concealed floor standing


Model CFM m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa dB(A) Noise level mm(WxHxD) Net dimension Packing dimension mm(WxHxD) kg Net weight kg Gross weight Air volume MKF1-150 150 250 1800 2000 375 6.3 33 550x212x545 635x265x630 30 34 MKF1-250 250 425 2000 2400 420 8.2 34 550x212x545 635x265x630 30 34 MKF1-300 300 500 2200 2600 530 10.1 35 750x212x545 835x265x630 35 39 MKF1-400 400 680 2800 3200 653 14.5 35 750x212x545 835x265x630 35 39 MKF1-450 450 760 3600 4000 740 18.3 35 950x212x545 1035x265x630 39 44

Model CFM Air volume m3/h Cooling Capacity W Heating Capacity W Water flow LPH Water resistance kPa Noise level dB(A) Net dimension mm(WxHxD) Packing dimension mm(WxHxD) Net weight kg kg Gross weight

MKF1-600 MKF1-500 600 500 1000 850 5600 4500 6300 5000 38 27.1 35 34 39 37 1250x212x545 950x212x545 1335x265x630 1035x265x630 50 39 55 44 Remarks: 1.The above design and specifications are subject to change without prior notice for product improvement. 2.The values given in the table for the noise level reflect the levels in anechoic chamber. 67

MKF1-800 800 1350 7100 8000 45 38 40 1250x212x545 1335x265x630 50 55

MKF1-1000 1000 1700 8000 9000 60 39 42 1250x212x545 1335x265x630 50 55

68

Accessories
Accessorial electric heater
SDS Series
Production feature Adopt high efficiency electric heater, symmetrically heat; It is tested under 10bar water pressure, high security; Small body with high removability, easy for load; It can be customized just according to customer's requirement.

Accessories

C D E E

Model SDS-15/S-A SDS-18/S-A SDS-27/S-A SDS-30/S-A SDS-45/S-A SDS-54/S-A SDS-60/S-A SDS-72/S-A SDS-75/S-A SDS-90/S-A SDS-100/S-A SDS-120/S-A SDS-144/S-A SDS-150/S-A SDS-175/S-A SDS-180/S-A SDS-200/S-A

Voltage(V) 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V 380V

Input(kW) 15KW 18KW 27KW 30KW 45KW 54KW 60KW 72KW 75KW 90KW 100KW 120KW 144KW 150KW 175KW 180KW 200KW

Dimension (mm) A 960 960 1260 1260 1160 1360 1360 1200 1200 1360 1520 1660 1960 1960 1660 1660 1960 B 350 350 350 350 400 450 450 480 480 530 530 600 600 600 650 650 650 C 280 280 280 280 335 390 390 390 390 440 440 492 540 540 598 598 598 D 159 159 203 203 219 245 245 273 273 325 325 426 426 426 480 480 480 E 130 130 180 180 180 220 220 240 240 240 240 240 240 240 280 280 280

Remark: The accessorial electric heater should be additional ordered.

70

Accessories
SDH Series
Production feature Stainless steel structure, and filled in insulating material between the shell and electric heat pipe, and also has high anti-erode capability. Adopt famous temperature controller can avoid destroy the components. Adopt high efficiency electric heater, symmetrically heat.

Waterproof cover Cover Shell

Water outlet Electric heater pipe

Water inlet

Inner flue Heat preservation layer

Wire outlet

Fixed hole Drainage valve

Model

Voltage (V)

Input (kW)

Total length(mm)

Diameter(mm)

Water inlet/outlet

SDH-2-A SDH-3-A SDH-4-A SDH-5-A SDH-6-A SDH-7/S-A SDH-8/S-A SDH-9/S-A SDH-10/S-A SDH-12/S-A SDH-15/S-A SDH-20/S-A

220/380 220/380 220/380 220/380 220/380 380 380 380 380 380 380 380

2kW 3kW 4kW 5kW 6kW 7kW 8kW 9kW 10kW 12kW 15kW 20kW

350 350 400 400 450 450 410 410 510 510 560 560
*190mm *158mm

1.25''

1.5''

Remark: The accessorial electric heater should be additional ordered.

71