LG
CAUTION
BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL. ONLY FOR AUTHORIZED SERVICE PERSONNEL.
TABLE OF CONTENTS
Table of contents Page
1. Models List .......................................................................................................................3 2. Safety Precautions ...........................................................................................................4 3. Feature & Benefits ...........................................................................................................8 4. List of Functions .............................................................................................................11 5. Function of Remote Control ...........................................................................................12 6. Specifications .................................................................................................................14 7. Dimensional Drawings ...................................................................................................16 8. Wiring Diagrams.............................................................................................................19 9. Refrigerant Cycle Diagrams ...........................................................................................21 10. Installation ....................................................................................................................22 11. Trouble Shooting Guide................................................................................................32 12. (3-Way)Valve ................................................................................................................48 13. Electronic Control Device.............................................................................................52 14. Exploded View and Replacement Parts List ................................................................53
Models List
Models List
1. Model line up
1.1 Indoor units
Category Type Chassis 7.03(24) Model names Capacity, kW(kBtu/h) 9.96(34)
Ceiling cassette
4-way
TH
AT-C243HLF0
AT-C343HLF0
1 9.96 34
Chassis
Service Manual 3
Safety Presautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. I Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
I Meanings of symbols used in this manual are as shown below.
I Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
Safety Presautions Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
Moisture may condense and wet or damage furniture.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
I Operational
Do not touch(operate) the product with wet hands.
There is risk of fire or electrical shock.
Service Manual 5
Safety Presautions Do not store or use flammable gas or combustibles near the product.
There is risk of fire or failure of product.
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
nilosaG
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
I Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
90
I Operational
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of personal injury.
x Wa Thinner
Do not insert hands or other objects through the air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Service Manual 7
Pre-filter
Dusts Collection
Polluted Air
+ + + + +
Odour
Generating plasma
........
16
Group Control :
- It enables to control as much as 16 units with the help of one wired remote controller. All the units will follow same setting of temperature & other sub functions.
........
Central Control :
- It enables to control 16 x 8 = 128 units with the help of 8 controllers. All units can be put on and off from one Central Room. For Setting Temperature, Fan Speed and other sub functions, access the respective LCD wired remote controller of each unit.
Main PCB
M 1 Sub 1
M 2 Sub 2
M 16 Sub 16
M 17 Sub 17
M 18 Sub 18
Jet Cool :
-In this mode, quick and fast cooling is done. Cold and high velocity air is supplied to the room till the indoor temperature reaches 18C(64F). The unit will continue to run in jet cool mode till the Indoor temperature reaches 18C(64F).
Controller #1
Controller #2
Controller #8
Swirl Swing
- It is the function for comfort cooling/heating operation. - The diagonal two louvers are opened the more larger than the other louvers. After one minute, it is opposite.
2.4% 100% Improved 4.8% Comparison of Floor Temp. Distribution(20C)
4- Open(Conventional) Swirl Swing(New)
Vane 2
Vane 1
Vane 3
Space Control
Vanes angle can be controlled by pair, considering its installation environment. - For example direct drafts can be annoying, leading to discomfort and reduced productivity vane control helps to eliminate this problem. - Easily controlled by wired remote control. - Air Flow can be controlled easily regarding any space environment.
Service Manual 9
5~6W
30m
0.5W Others LG 30m
List of Functions
List of Functions
Ceiling Cassette
Category Function Air supply outlet Airflow direction control (left & right) Airflow direction control (up & down) Auto swing (left & right) Auto swing (up & down) Airflow steps(Fan / Cool / Heat) CHAOS swing CHAOS wind (Auto wind) Jet cool (Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(Washable) Drain pump E.S.P. control Electric heater (Operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(Artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer (On/Off) Timer (weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote controller General central control(Non LGAP) Dry contact Simple central control(LGAP) PDI(Power Distribution Indicator) PI 485 CTIE Zone control Thermistor AT-C243HLF0 4 X Auto X O 3/4/X X O O X O O O O X O O X X O O O O Option O O O O PQWRHSF0 Option Option Option Option Option X X AT-C343HLF0 4 X Auto X O 3/4/X X O O X O O O O X O O X X O O O O Option O O O O PQWRHSF0 Option Option Option Option Option X X -
Air flow
Air purifying
Installation
Reliability
Convenience
Individual Control
Note : O : Applied, X : Not applied, : No relation Option: Model name & price are different according to options, and assembled in factory with main unit. Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Service Manual 11
Signal transmitter
5 6
1 3
4 2 7 11 8 13 15 10
CANCEL ON OFF SET AUTO CLEAN
9 12 17 18 14 16
C/F
Operation Mode
Cooling Operation Auto Operation
SUB FUNCTION
2ndF Timer
On Off Set no. Time 01
Time
AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4
17 19 21 23
3 17 10 11 12 13 14 15 16 18
Timer Cancel 2ndF
2 5 6 4 7 8 9
Program
Week
Hour
Min
RESET
1 Operation display
Displays the operation conditions.
2 On/Off Button
Operation starts when this button is pressed, and stops when the button is pressed again.
12 Week Button
Used to set a day of the week.
13 Program Button
Used to set the weekly timer.
14 Holiday Button
Used to set a holiday of the week.
17 Swirl Button
Used to select swirl swing mode.
18 Reset Button
Used to set the current time and clear the setting time.
Service Manual 13
Specifications
Specifications
Indoor unit type Model Power supply Cooling capacity Heating capacity Current Fan Nominal running current Motor Type Fan Type Motor Output(W) * number of units Air flow rate (H/M/L) Capacitor Drive Coil Dimensions (W*D*H) Net Weight Gross Weight Air filter Sound Level (H/M/L) Piping Connections Liquid Gas Drain Dehumidification rate Safety Devices Temperature sensor Refrigerant Refrigerant control Connectable outdoor Unit Power and Transmission interunit cable No.* mm2 (No. AWG) OD/ID dB(A)+3 mm(inch) mm(inch) mm(inch) l/h(pts/h) Row * stages * FPI Body Decorative Panel Body Decorative Panel Body Decorative Panel mm mm(inch) mm(inch) kg(lbs) kg(lbs) kg(lbs) kg(lbs) cmm cfm mF/V Phase/Volts/Hz kW Btu/h kW Btu/h A Ceilling Cassette - 4way AT-C243HLF0 (LCN240CP / LC240CPI) 1 / 208-230 / 60 7.03 24,000 1.0 BLDC Turbo Fan 50.6 * 1 18.4/17.0/15.6 650/600/550 DC 2R * 9C * 18 840 * 840 * 225(331/16 * 331/16 * 87/8) 950 * 950 * 30(3713/32 * 3713/32 * 13/16) 26(57.3) 3(6.61) 30(66) 4(9) Long Life filter 38/35/32 6.35(1/4) 12.7(1/2) 32/25(1.26/0.98) 3.0(6.3) Thermistor R410A EEV Single 4 * 2.1(14) AT-C343HLF0 (LCN340CP / LC340CPI) 1 / 208-230 / 60 9.96 34,000 1.0 BLDC Turbo Fan 50.6 * 1 24.1/22.7/21.2 850/800/750 DC 2R * 9C * 18 840 * 840 * 225(331/16 * 331/16 * 87/8) 950 * 950 * 30(3713/32 * 3713/32 * 13/16) 26(57.3) 3(6.61) 30(66) 4(9) Long Life filter 40/37/34 6.35(1/4) 15.88(5/8) 32/25(1.26/0.98) 3.7(7.8) Thermistor R410A EEV Single 4 * 2.1(14)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7C(80F) DB /19.4C(67F) WB - Outdoor Temperature 35C(95F) DB /23.9C(75F) WB Piping Length - Interconnecting Piping Length 7.5m(25ft) - Level Difference of Zero.
Specifications
Outdoor Unit Rated Capacity Cooling Heating Rated Input Cooling Heating kW Btu/h kW Btu/h kW kW
Energy Label Testing combination Running current Cooling A Heating A Starting current (Cooling/Heating) A Power supply Phase / Volts / Hz Power supply Cable(outdoor) No. * mm2(No. AWG) Power and transmission cable No. * mm2(No. AWG) Dimensions W*H*D mm(inch) Net weight kg(lbs) Gross weight kg(lbs) Maximum number of connectable unit Compressor Type (constant) Qty * model Motor Type Oil charge volume cc Oil type Refrigerant Charge(at 7.5m(25ft)) g(oz) Type Control Heat Exchanger Rows * Column * FPI Defrosting method Fan Capacitor mF/Vac Drive Discharge Direction Side / Top Air flow rate cmm(cfm) Noise level(H) Sound press, 1m db (A) + 3 Piping connections Liquid mm(inch) Gas mm(inch) Max. piping length Main piping m(ft) Indoor unit - Outdoor unit m(ft) Max. elevation
AT-C243HLFO (LCU240CP / LC240CPO) 7.03 24,000 2.5 11.5 24 1 / 208-230 / 60 3 * 2.1(14) 4 * 2.1(14) 870 * 800 * 320(341/2 * 311/2 * 1219/32) 73(160) 78(172) 1 ROTARY 2*GK120KAA Induction 700 PVE 2100(74.1) R410A EEV 2R * 36C * 20 6 / 370 Direct Drive Side discharge 51(1801) 55 6.35(1/4) 12.7(1/2) 30(100) 15(50)
AT-C343HLFO (LCU340CP /LC340CPO) 9.96 34,000 3.6 17 38 2 / 208-230 / 60 3 * 3.3(12) 4 * 2.1(14) 900 * 1160 * 370(357/16 * 4511/16 * 149/16) 86(190) 93(205) 1 ROTARY GJ151KAA + GJ208KAA Induction 1200 PVE 2500(88.2) R410A EEV 2R * 52C * 18 6 / 370 Direct Drive Side discharge 105(3708) 58 6.35(1/4) 15.88(5/8) 35(115) 20(66)
Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 26.7C(80F) DB /19.4C(66.9F) WB - Outdoor Temperature 35C(95F) DB /23.9C(75F) WB Piping Length - Interconnecting Piping Length 7.5m(25ft) - Level Difference of Zero.
Service Manual 15
Dimensional Drawings
Dimensional Drawings
1. Indoor Units Model No.: LCN240CP/LC240CPI/LCN340CP/LC340CPI
225(8.9)
806(31.7) (hanging bolt)
950(37.4) 950(37.4)
950(37.4)
950(37.4)
840(33.1) 688(27.1)
950(37.4)
2
806(31.7) 30(1.18)
135(5.3) 76(3.0)
840(33.1)
4 5
840(33.1)
* mm(inch)
No. 1 2 3 4 5 6 7
Part Name Decoration panel Air suction grille Air discharge grille Gas pipe connection Liquid pipe connection Drain pipe connection Power supply connection
Remark
225(8.9)
840(33.1)
R3 5( 1. 4)
Dimensional Drawings
320(12.6)
54.6(2.1)
333(13.1)
10(0.4)
340(13.4)
360(14.2)
320(12.6)
782.5(30.8) 392(15.4)
808(31.8)
31(
20.
9)
25.5(1.0)
Service Manual 17
Dimensional Drawings
175(6.9)
15(0.6)
370(14.6) 395(15.6)
370(14.6)
520(20.5)
4
1
1135(44.7)
565(22.2)
1165(45.9)
65(2.6)
273(10.7)
80(3.1)
3 2
124(4.9)
308(12.1)
*mm(inch)
No. 1 2 3 4 5
Part Name Air discharge grille Gas pipe connection Liquid pipe connection Power & transmission connection Earth screw
Remark
Wiring Diagrams
Wiring Diagrams
1. Indoor Unit LCN240CP/LC240CPI/LCN340CP/LC340CPI
Connector Number CN-POWER CN-MOTOR CN-DPUMP CN-DISP CN-FLOAT CN-REMO CN-CC CN-ROOM CN-PIPE1 CN-PIPE2 CN-GRILL CN-PTC CN-HVB
Location AC power supply BLDC fan motor output Drain pump output Display Float switch input Remote control Dry-contact Room sensor In-pipe thermistor Out-pipe thermistor Elevation grille PTC Heater HVB Ass'y (Air cleaner)
Service Manual 19
Wiring Diagrams
Notes: BL RD YL BLUE RED YELLOW BK OR GN/YL BLACK ORANGE GREEN/YELLOW BR WH BROWN WHITE FIELD WIRING
LCU340CP/LC340CPO
Notes: BL RD YL BLUE RED YELLOW BK OR GN/YL BLACK ORANGE GREEN/YELLOW BR WH BROWN WHITE FIELD WIRING
INDOOR UNIT
OUTDOOR UNIT
Thermistor
Thermistor
Gas Side
Check Valve
Constant Compressor 1
Check Valve
Constant Compressor 2
Accumulator
GAS SIDE
E.E.V.
Thermistor
LIQUID SIDE
Service Manual 21
Installation
Installation
1. Select the best location
Install the air conditioner in the location that satisfies the following conditions.
100(39.4) or more
50(19.7) or more
50(19.7) or more
Unit:cm(inch)
Floor
Su
nro
of
More than 30cm(11.8inch)
Su
nro
of
30(11.8) or less
30(11.8) or more
Ceiling Board
Installation
Bolt
Tubing connection
Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model
The following parts is option. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10 CAUTION
Tighten the nut and bolt to prevent unit falling.
Drill the piping hole on the wall slightly tilted to the outdoor side using a 70(2.76inch) hole-core drill.
5~7mm (0.20~0.28inch)
Service Manual 23
Installation
4. Wiring Connection
1. All wiring must comply with LOCAL REGULATIONS. 2. Select a power source that is capable of supplying the current as required by the air conditioner. 3. Feed the power source to the unit via a distribution switch board designed for this purpose. 4. The terminal screws inside the control box may be loose due to vibration during transport. Check the screws for loose connection. (Running the air conditioner with loose connection can overload and damage electrical components.) 5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
1(L) 2(N)
1(L) 2(N)
1(L) 2(N)
CAUTION
The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA
Capacity 24k Btu/h 34k Btu/h 1 Phase 2.1mm2(AWG 14) 3.3mm2(AWG 12)
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA 2.1mm2 (AWG 14)(24k/34k)
20
GN
/YL
20 mm
GN
/YL
mm
(0.
8in
ch
(0.
8in
ch
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent.
WARNING Make sure that the screws of the terminal are free from looseness.
Installation
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm(0.39inch) in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter).
Air conditioner unit Piping side
Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm(0.39inch))
Decoration panel
Display Key holes Lead wire for louver motor and display
Inlet Grille
CAUTION Install certainly the decoration Good example panel. Cool air leakage causes sweating. Water drops fall.
Bad example
Air conditioner unit Air Air conditioner unit Cool air leakage (no good) Ceiling board Decoration panel
Ceiling board Decoration panel Fit the insulator (this part) and be careful for cool air leakage
Service Manual 25
Installation
Heat insulation material to be prepared... Adiabatic glass wool with thickness 10 to 20mm(0.39 to 0.79inch). Stick glass wool on all air conditioners that are located in ceiling atmosphere. In addition to the normal heat insulation (thickness: more than 8mm(0.31inch)) for refrigerant piping (gas piping: thick piping) and drain piping, add further 10mm to 30mm(0.39inch to 1.18 inch) thickness material.
2. Tape the Pipings, drain hose and Connecting Cable from bottom to top. 3. Form the pipings gathered by taping along the exterior wall and fix it to the wall by saddle or equivalent.
Installation
In case of the Outdoor Unit being installed above position of the Indoor Unit. 2. Tape the Pipings and Connecting cable from bottom to top. 3. Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room. 4. Fix the pipings onto the wall by saddle or equivalent. Seal a small opening around the pipings with gum type sealer. Trap
Drain test
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
Feed water
Main drain pipe Drain port
Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Feed water to the flexible drain hose and check the piping for leakage. Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Drain Pump
1/50~1/100
MAX 700mm (27.6inch)
CAUTION
The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
Installation
8. Test running
1) PRECAUTIONS IN TEST RUN
The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated. CAUTION For test run, carry out the cooling operation first even during winter season. Carry out the test run more than 5 minutes without stopping. (Test run will be cancelled 18 minutes later automatically) The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time. To cancel the test run, press any button.
Thermometer
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).
Service Manual 29
Installation
9. Optional Operation
1) Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. Position 1: The room themperature is controlled by the thermistor of the wired remote-controller, control the temperature according to the position of wired remote-controller. Position 2: The room temperature is controlled by the thermistor of the main body. Position 3: The room temperature is controlled by lower temperature between the temperature of main body and of remote-controller sensor. (3) Move the slide switch to set position.
Slide switch for 2 Thermistor
1 2 3
1 2 3
1 2 3
CAUTION Select the position after counselling with a customer. In case of cooling mode, room temperature is controlled by the main body sensor. To control the room temperature by a wired remote controller, install controller(room temp. sensor) to sense the temperature more accurately. Maunfactured in the position 3.
2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote-controller. 3. Move the slide switch to the set position. 4. Close the rear cover and check if it works nomally.
1 2 3
1 2 3
1 2 3
3) Group Control
It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent. Wiring design
Indoor Unit 1
Terminal(Local Supply) Block Connector
RED(12V) YL(SIGNAL) BR(GND) RED(12V) YL(SIGNAL) BR(GND)
Main PCB
Indoor Unit 2
Terminal(Local Supply) Block Connector
YL(SIGNAL) BR(GND) YL(SIGNAL) BR(GND)
Indoor Unit 16
Terminal(Local Supply) Block Connector
Main PCB #1
Main PCB #2
....
YL(SIGNAL) BR(GND)
YL(SIGNAL) BR(GND)
....
AUTO SWING
OPERATION
SET TEMP
Room Temp
SUB FUNCTION
Time Timer
Operation unit
03 05 07
Program set
09 11 13 15 17
Single Control
S/W GR
Using the supplied Wired Remote Controller, wire them like above. Move S/W GR to "Group Control 1" position. Check the line color of the wire.
CAUTION
Be careful not to exchange the color of wires. The maximum length of connecting wire should be below 200m(656ft)(25) on connecting each units. Use a wire more than 0.5mm2
Service Manual 31
Troubleshooting Guide
Troubleshooting Guide
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current. Temp. difference Current : approx. 0C(0F) : less than 80% of rated current All amount of refrigerant leaked out. Check refrigeration cycle.
Temp. Difference Temp. difference Current Operating Current Temp. difference Current : less than 8C(14.4F) : near the rated current Excessive amount of refrigerant : approx. 8C(14.4F) : less than 80% of rated current Refrigerant leakage Clog of refrigeration cycle Defective compressor
Temp. difference
: over 8C(14.4F)
Normal
Notice: Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Temperature (Compared with the normal value) High Higher Normal Excessive amount of refrigerant Insufficient amount of refrigerant(Leakage) Clogging High pressure does not quickly rise at the beginning of operation. Current is low.
Lower
Higher
Notice: 1. The suction pressure is usually 4.5~6.0 kg/cm G at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
2
Troubleshooting Guide
Turn off the main power and wait until LED on outdoor PCB is off
Does the Operating LED of indoor unit blink When Operation's ON?
Check the Fuse of outdoor PCB Ass'y. Check the connecting state of wires
* The product's operation starts at three minutes after main power turning on
Service Manual 33
Troubleshooting Guide
Trouble 2
While the compressor has been stopped, the compressor does not operate owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)
When the detect switch (double key) inside the remote controller door is fault, it is impossible to operate temperature regulating(L / M) and wind speed selecting.
Troubleshooting Guide
Trouble 3
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1C at least.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped. Check the indoor temperature sensor is disconnected or not(About 10k / at 25C(77F)).
Check Relay(RY - COMP) for driving compressor. When the power(About AC208V-230V) is applied to the connecting wire terminal support transferred to compressor, PWB Ass'y is normal. Check the circuit related to the relay.
Check point Between two pin of DC part in relay for COMP COMP ON Below DC 1V (app) COMP OFF About DC12V
Service Manual 35
Troubleshooting Guide
Trouble 4
Check the related circuit of indoor Fan Motor. The pin of Micom, and the part for driving SSR Check the pattern Check the SSR - SSR Open: Indoor Fan Motor never operate - SSR short: Indoor Fan Motor always operates in case of ON or OFF.
Check the SSR high speed operation by remote control. (The Indoor Fan Motor is connected) The voltage of PIN NO 1(blue) and 3(yellow) of CN-FAN or CN-MOTOR.
SSR Check
Troubleshooting Guide
Trouble 5
Check the connecting condition of CN-U/D Connector Check the soldering condition(on PWB) of CN-U/D Connector
Check the operating circuit of the Vertical Louver Confirm that there is DC +12V between pin GND. (RED) of CN-U/D and
If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
Service Manual 37
Troubleshooting Guide
Self-diagnosis Function
I Error Indicator The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble. Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table. If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed. After error occurrence, if error is released, error LED is also released simultaneously. To operate again on the occurrence of error code, be sure to turn off the power and then turn on. Having or not of error code is different from Model.
Indoor Error
Error code 00 01 02 03 04 05 06 No Error Indoor Room Thermistor Error Indoor In-Piping Error Remote controller Error Drain Pump Error Communication Error between In and Out Indoor Out-Piping Error 1 time 2 times 3 times 4 times 5 times 6 times Description MPS Variable MPS Inverter LED 1 (Red) LED 2 (Green) Indoor Status ON OFF OFF OFF OFF OFF OFF
Outdoor Error
Error Code
21 22 23 24 25 26 27 28 32 33 40 41 44 45 46 47 51 53 54 60 61 62 63 65
Description
DC Peak(IPM Fault) CT2(Max CT) DC Link Low Volt High/Low Pressure/Heatsink Switch Low Voltage / Over Voltage DC COMP Position Error PSC Fault Error DC Link High Volt D-Pipe High(INV) D-Pipe High(Normal) CT Sensor(open/short) INV. D-Pipe Thermistor Error(Open/Short) Outdoor Air Thermistor Error(Open/Short) Cond Pipe Thermistor Error(Open/Short) Suction Pipe Thermistor Error(Open/Short) Const. D-Pipe Thermistor Error(Open/Short) Capcity Error(High/Low) Signal Error(Indoor_Outdoor) Phase Error EEPROM Check Sum Error Cond Pipe High Heatsink High Cond Pipe Low Heatsink Thermistor Error(Open/Short)
MPS Variable
MPS Inverter
LED 1 (Red)
2 times 2 times 2 times 2 times 2 times 2 times 2 times 2 times 3 times 3 times 4 times 4 times 4 times 4 times 4 times 4 times 5 times 5 times 5 times 6 times 6 times 6 times 6 times 6 times
LED 2 (Green)
1 time 2 times 3 times 4 times 5 times 6 times 7 times 8 times 2 times 3 times 1 times 4 times 5 times 6 times 7 times 1 times 3 times 4 times 1 times 2 times 3 times 5 times
Indoor Status
ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
Troubleshooting Guide
02
Normal resistor : 5K/ at 25C(77F) (Unplugged) Normal voltage : 2.5Vdc / at 25C(77F) (plugged)
06
Normal resistor : 5K/ at 25C(77F) (Unplugged) Normal voltage : 2.5Vdc / at 25C(77F) (plugged)
10k
2.5Vdc
V
Check Point
1. Unplug the sensor on Indoor unit PCB. 2. Estimate the resistance of each sensor. 3. If the resistance of the sensor is 10K/ 5K at 25C(77F), then sensor is normal. 4. If the resistance of the sensor is 0 K or , then sensor is abnormal. Change the sensor. 5. Plug the sensor on Indoor unit PCB and Power ON. 6. Estimate the voltage of each sensor. 7. If the voltage of the sensor is 2.5Vdc at 25C(77F), then sensor is normal. 8. If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.
Service Manual 39
Troubleshooting Guide
Troubleshooting CH03
Display code 03 Title Communication Wired R/C Cause of error Open / Short Wrong connection Check point & Normal condition Connection of wire Main PCB Volt. DC12V Noise interference
12Vdc
V
12Vdc
V
Check Point
1. Check the wire connection. (Open / Short) Repair the connection 2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB. 3. Check the volt. Of main PCB power source. (DC 12V, DC 5V) Repair or Change the main PCB. 4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation
Troubleshooting Guide
Troubleshooting CH04
Display code Title Cause of error Check point & Normal condition The connection of wire(Drain pump/ Float switch) Drain pump power input. (220V) Drain tube installation. Indoor unit installation. (Inclination)
04
CN Float
Check Point
1. Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB. 2. Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch. 3. Check the level of water 4. Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.
Service Manual 41
Troubleshooting Guide
05 / 53
Communication poorly
Check Point
1. Check the input power AC230V. (Outdoor, Indoor unit) 2. Check the communication wires are correctly connected. Adjust the connection of wire Confirm the wire of Live, Neutral 3. Check the resistance between communication line and GND. (Normal : Over 2M) 4. Check the connector for communication is correctly connected. 5. Check the connection of GND1, GND2, and main GND. 6. If one indoor unit is operated normally, outdoor PCB is no problem. Check the another indoor unit. * CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.
Troubleshooting Guide
25
Input voltage
Check Point
CH 24 1. Check the connection of CN_PRESS 2. Check the install condition for over load. 3. Check the SVC V/V open. 4. Check the leakage of refrigerant. CH 25 1. Check the power source. 2. Check the components (Trans1, B/Diode, Diode, Resistance)
Service Manual 43
Troubleshooting Guide
33
COMP OFF LEV OPEN/Hz down LEV OPEN/Hz down NORMAL Inverter
Check Point
CH 32 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. CH 33 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerant. 4. Check the constant compressor. (same with CH21)
Troubleshooting Guide
44
Air sensor
Normal resistor : 10K / at 25C(77F) (Unplugged) Normal voltage : 2.5Vdc / at 25C(77F) (plugged)
45
46
47
Normal resistor : 200K / at 25C(77F) (Unplugged) Normal voltage : 4.5Vdc / at 25C(77F) (plugged)
65
Normal resistor : 10K / at 25C(77F) (Unplugged) Normal voltage : 2.5Vdc / at 25C(77F) (plugged)
Check Point
1. Estimate the resistance of each sensor.(Unplugged) 2. Estimate the voltage of each sensor.(Plugged) 3. If the resistance of the sensor is 0 k or , then sensor is abnormal.
Service Manual 45
Troubleshooting Guide
Capacity Error
60
Check Point
CH 51 1. Check the indoor unit capacity. CH 60 1. Check the insertion condition of EEPROM. 2. Check the poor soldering
Troubleshooting Guide
Check the load condition. Check the sensor of Condenser pipe sensor.
62
Normal
OFF
Normal
Check Point
CH 61 1. Check the install condition for over load. (Refrigerant, Pipe length, Blocked, ) CH 62 1. Check the fan is locked. 2. Check the Outdoor temp. is very high.
Service Manual 47
(3-way) Valve
(3-way) Valve
3-way Valve (Liguid Side) 3-way Valve (Gas Side) Valve cap Open position Closed position Pin To piping connection
To outdoor unit
To outdoor unit
Works Shipping
Service port Closed (with cap) Open (push-pin or with vacuum pump) Closed (with cap) Open (connected manifold gauge) Open (connected manifold gauge) Open (with charging cylinder) Open (connected manifold gauge) Open (connected manifold gauge)
1.
Open Open (counter-clockwise) (push-pin or with vacuum pump) Open (with valve cap) Closed (clockwise) Closed (with cap) Closed (with cap)
Operation
2.
3.
Evacuation (Servicing)
Open
Open
4.
Open
Open
5.
Open
Open
6.
Open
Open
(3-way) Valve
Indoor unit
Open
Outdoor unit
Gas side
Closed
3-Way valve
Lo
CLOSE CLOSE
Procedure For pumping down,firstly short the Low Pressure s/w at the outside and then operate below procedure. 1. Confirm that both the gas side and liquid side valves are set to the open position. - Remove the valve stem caps and confirm that the valve stems are in the raised position. - Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the manifold gauge to the service port of the gas side valve. - Connect the hose of the gauge with the push pin to the service port. 4. Air purging of the charge hose. - Open the Low-handle valve on the gauge slightly to air purge from the hose. 5. Set the liquid side valve to the closed position. 6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg/cm g.
2
7. Immediately set the gas side valve to the closed position. - Do this quickly so that the gauge ends up indicating 1kg/ g. 8. Disconnect the charge set, and mount the liquid side and gas side valve caps and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8kg.m.(4.2kg.m/5.5kg.m) - Be sure to check for gas leakage.
Be sure to short pressure S/W. otherwise Low pressure S/W detect low pressure skete and stops the compressor.
Service Manual 49
(3-way) Valve
(2) Evacuation
(All amount of refrigerant leaked)
Indoor unit
Open
Gas side
3-Way valve
Open
Vacuum pump
Lo
OPEN CLOSE
Procedure
1. Confirm that both the liguid side valve and gas side valve are set to the opened position. 2. Connect the vaccum pump to the center hose of the manifold gauge. 3. Connect the service port of the gas side valve to the low side of the gauge. 4. Evacuation for approximately one hour. - Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less). 5. Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge needle does not move(approximately 5 minutes after turning off the vacuum pump). 6. Disconnect the charge hose from the vacuum pump. - Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted,replenish as needed. 7. Mount the valve caps and the service port caps.
(3-way) Valve
Indoor unit
Open
Outdoor unit
Gas side
Open
Check valve 3-Way valve
Charging cylinder Lo
(1) OPEN CLOSE
Procedure
1. Connect the gauge to the charging cylinder. - Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. - If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged with liquid. 2. Purge the air from the charge hose. - Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder. 3. Open the low handle on the gauge and charge the system with liquid refrigerant. - If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g(5.3oz) each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure(pumping down-pin). 4. Immediately disconnect the charge hose from the gas side valve's service port. This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner. - Stopping partway will allow the gas to be discharged. - If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose. 5. Mount the valve stem nuts and the service port nut. - Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.) - Be sure to check for gas leakage.
Service Manual 51
359012
349480 130911-3 268714 249951 135500-1 337000 130911-2 152510 130911-1 354211 W49800 130911-4
158591
159830
Service Manual 53
Parts List
Part No. LOCATION No. 130411 DESCRIPTION LCN240CP / LC240CPI BASE ASSEMBLY,WELD(INDOOR) LCN340CP / LC340CPI R R R R R R R R R R R R R R R R R R R R R R R R R R 3041A10069A 3091A10075E 3091A10085C 3091A10077A 3091A10075F 3550A30273A 5251A10003A 5859A10006G 5983A10003D 4995A10224E 4995A10224F 6323A30002A 6323AQ3226W 6609A20009L 6711A20127E 6711A20083Q 6871A10366M 6871A10366N 3087A10035H 3700A20036A 4681A20168D 4948A20039A 4960A20080A 5211A10600C 5211A10600A 5421A10062A 5900A10016A 5211A10550B 4981A21011A REMARKS
130911-1 CABINET ASSEMBLY,INDOOR 130911-2 CABINET ASSEMBLY,INDOOR 130911-3 CABINET ASSEMBLY,INDOOR 130911-4 CABINET ASSEMBLY,INDOOR 135500-1 COVER 152510 158591 159830 249951 HOSE ASSEMBLY,DRAIN PUMP ASSEMBLY,WATER FILTER ASSEMBLY,AIR CLEANER CASE ASSEMBLY,CONTROL(INDOOR)
263230-1 THERMISTOR,NTC 263230-2 THERMISTOR,NTC 266090 HVPS,DC/DC 267110-1 REMOTE CONTROLLER ASSEMBLY 267110-2 REMOTE CONTROLLER ASSEMBLY 268714 330870 337000 346810 349480 349600 352118 354211 359012 552111 W49800 PCB ASSEMBLY,MAIN PAN ASSEMBLY,DRAIN MESH,METAL MOTOR ASSEMBLY,DC,INDOOR ORIFICE BRACKET,MOTOR TUBE ASSEMBLY,MENIFOLD(INDOOR) EVAPORATOR ASSEMBLY,FINAL FAN,TURBO TUBE ASSEMBLY,CAPILLARY SUPPORTER ASSEMBLY
554031
137213-1
435512 435300
2. OUTDOOR UNITS
268711 435511 559010 552112 447910 554160 552113 552114 437210 430410 550140 567480-1 552117 649950
435301
552203-1 552203-2
Service Manual 55
349480
Parts List
Part No. LOCATION No. DESCRIPTION LCU240CP / LC240CPO 1A00202F 3A02284N 6323A20028B 6323A20023E 4948AP2527A 1A00206B 3041AP2741G 1A00208H 3530A20007J 3550AR2886C 3720AR7035C 3H03266H 1A00197C 4791A30004H 4681A10030C 4980A20001B 4H00982E 5211A25715A 5211A25716A 5211A29916A 5211A29913A 5220A20007A 5220A20006A 5403A20022T 2520UGKK2AA(GK120KAA,2EA) 1A00195B 6141A20018Z 6750U-L035A 4995A10112M 6920AP3400A 3A00988B(35uF) 6120AR2194F(6+35uF) 3A01934B 4986U-L001G 6871A21318D R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R REMARKS
137213-1 PANEL ASSEMBLY,SIDE 137213-2 PANEL ASSEMBLY,SIDE 567480-1 THERMISTOR,NTC 567480-2 THERMISTOR,NTC 349480 349600 430410 435300 435301 435511 237204 435512 437210 447910 546810 W49810 550140 552112 552113 552114 552117 ORIFICE BRACKET,MOTOR BASE ASSEMBLY,OUTDOOR GRILLE,REAR GRILLE,DISCHARGE COVER ASSEMBLY,CONTROL(OUTDOOR) PANEL,SIDE COVER ASSEMBLY,TOP(OUTDOOR) PANEL ASSEMBLY,FRONT(SUB) BARRIER ASSEMBLY,OUTDOOR MOTOR ASSEMBLY,OUTDOOR SUPPORTER ASSEMBLY DAMPER,COMPRESSOR TUBE ASSEMBLY,CONDENSER(IN) TUBE ASSEMBLY,CONDENSER(OUT) TUBE ASSEMBLY,DISCHARGE(OUTDOOR) TUBE ASSEMBLY,SUCTION(OUTDOOR)
552203-1 VALVE,SERVICE 552203-2 VALVE,SERVICE 554031 554160 559010 561410 567502 649950 W6920 CONDENSER ASSEMBLY,BENDING COMPRESSOR FAN ASSEMBLY,PROPELLER SOLENOID OVERLOAD PROTECT CASE ASSEMBLY,CONTROL(OUTDOOR) RELAY,CONTACT
W0CZZ-1 Capacitor,AL,Radial W0CZZ-2 CAPACITOR,FILM,BOX W4810 W4986 268711 BRACKET GASKET PCB ASSEMBLY, MAIN
435512 549610
554031
546810 554031
559010
263230-1 263230-2
548490 552112
437211 447910
55211G
554160-2 554160-1
W49800 552203-1
Service Manual 57
137212
430411
Parts List
Part No. LOCATION No. 135301 135314 137212 DESCRIPTION LCU340CP / LC340CPO GRILLE,DISCHARGE PANEL ASSEMBLY,REAR(OUTDOOR) PANEL ASSEMBLY,SIDE 3530AP1225D 3720AP1202L 3721A20229A 6323A20019C 6323A20023E 3041A20047Z 3A01293X 3550AP1213B 3720AP1212B 4760AP1216C 4681A10030C 5211A00033A 4960A10004A 5211A00034A AJR30109601 5211A19011A AJR30127901 5220A20013A 5220A20007A 5403A20044B TBZ30130501(GJ208KAA) 2520UTBK1AA(GJ151KAA) 1A00195B 6141A20018Z ABQ30144401 6920AP3400A 6120AR2194F(6+35uF) 6120AR2194K(6+45uF) 4980AP2517D 6871A21318E R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R REMARKS
263230-1 THERMISTOR,NTC 263230-2 THERMISTOR,NTC 430411 435511 435512 437211 447910 546810 548490 549610 552112 552113 552114 55211G BASE ASSEMBLY,WELD(OUTDOOR) COVER ASSEMBLY,CONTROL(OUTDOOR) COVER ASSEMBLY,TOP(OUTDOOR) PANEL ASSEMBLY,FRONT(SUB) BARRIER,OUTDOOR MOTOR,UNCLASSIFIED TUBE ASSEMBLY,SUCTION(OUTDOOR) BRACKET,MOTOR TUBE ASSEMBLY,MENIFOLD(OUTDOOR) TUBE ASSEMBLY,CONDENSER(OUT) TUBE ASSEMBLY,DISCHARGE(OUTDOOR) TUBE ASSEMBLY,EXPANSION
552203-1 VALVE,SERVICE 552203-2 VALVE,SERVICE 554031 CONDENSER ASSEMBLY,BENDING 554160-1 COMPRESSOR SET,KOREA 554160-2 COMPRESSOR SET,KOREA 559010 561411 649950 669200 FAN ASSEMBLY,PROPELLER SOLENOID CASE ASSEMBLY,CONTROL(OUTDOOR) RELAY,CONTACT
146811
268712
152312
135314
135802
137211
Service Manual 59
Parts List
Part No. LOCATION No. 137211 135314 135312 146811 268712 135802 DESCRIPTION PT-CDC1 PANEL ASSEMBLY,FRONT(INDOOR) GRILLE ASSEMBLY,FRONT(INDOOR) FILTER ASSY,AIR CLEANER MOTOR ASSEMBLY,STEP PWB(PCB) ASSEMBLY,DISPLAY DOOR 3721A10106M 3531A10066A 5231A10004A 4681A20055A 6871A20096J 3580A20005A R R R R R R REMARKS
P/No.: 3828A20911A
Printed in Korea