ABB is leader in arc guard technology since 35 years. Experience from the highly appreciated TVOC is built into the new TVOC-2, a product for protection of humans and property when having an electric arc.
Reliability Certified according to functional safety (SIL 2) standard. Over 35 years of experience in Arc Guard Systems. Pre-calibrated optical sensors. Flexibility HMI can be mounted on the panel-door. Expand with up to 30 optical sensors. Configure the system according to various needs. Simplicity User-friendly start-up menu. DIN-Rail or wall-mounted. Easy to expand as the switchgear grows. HMI (Human Machine Interface)
Technical data
Reacting time (typical) Optical detectors Approx. 1 ms (depends on light intensity) 10 inputs on Arc Monitor 10 inputs on Extension unit X2 (optional) 10 inputs on Extension unit X3 (optional) Breaker trip contacts Signal relay outputs (K2, K3) Manual or auto resetable Rated voltage Continous carry Ith Make and carry for 0.2 s Breaking capacity 2 CO gold-plated contacts 250 V AC/DC 30 A 250V 250 V 110 V 48 V 30 A 0.3 A 0.6 A 2A AC-15 DC-13 DC-13 DC-13
Leaflet 1SFC170001L0201, March 2010. Prod ABB AB, Cewe-Control
5A
Reinforced insulation between separate contacts Ith = 5 A Min switching load: 1 mA at 5 V DC with contacts not used for switching current > 0.5 A if inductive/capacitive load before Configuration (DIP switches) Manual or auto reset of K1 and K3 Use of CSU or not Trip Configuration Full text display (55 x 26 mm) Yes 100-240 V AC, 50-60 Hz 100-250 V DC 5W 0.95 kg 2000 m above sea level -25 C to +55 C IP20 Arc Monitor IP54 HMI front side CE, RoHS SIL2 (IEC61508) Option (same as for TVOC) 1-60 m optical fibre with lens
Arc Guard System components: Arc monitor (TVOC-2) Extension unit (detector inputs) HMI (display and menu) Optical detectors Current Sensing Unit, CSU (optional) Dimension drawing
HMI / User interface Trip log with time stamp Power supply Rated supply voltage, Us Power consumption Weight Environment Altitude Permissible ambient temperature Degree of protection Complies with Functional safety approval Other system components Current sensing unit (CSU) Optical detectors
Q1 F11 D A1
For more information please contact: ABB AB Cewe-Control SE-72161 Vsters, Sweden Phone: +46 21 32 07 00 Fax: +46 21 12 60 01 www.abb.com/lowvoltage
Copyright 2010 ABB. All rights reserved. Specifications subject to changes without notice.