Type PM, 121-169 kV, up to 63 kA Power Circuit Breaker

Standard features - Dead tank design, with one self-blast interrupter per tank on a galvanized steel frame - National Board certification of interrupter tanks per the ASME Pressure Vessel and Boiler Code - All tanks factory leak tested in a hard-vacuum chamber with a helium mass spectrometer - Certified per ANSI C37.04, C37.06, and C37.09 standards - FSA-2 spring mechanism applied for interrupting ratings through 40 kA; HMB-1 class spring-hydraulic mechanism standard for 169 kV, 50 kA applications and through 145 kV for 50/63 kA duty - Frame mounted NEMA-3R steel control cabinet protected with TGIC polyester powdercoat finish - Single tank-mounted gas density monitor and pressure gauge - Porcelain bushings - Continuous current ratings through 4000 A - Ships fully assembled and factory tested with 5 psig SF6 gas (bushings may be removed for export transit) Options and accessories - Condition monitoring with the Circuit Breaker Sentinel (CBS) - Density monitor and temperature-compensated pressure gauge directly-mounted on each tank - Extra creep and/or extra strike bushings for special applications - Silicone rubber composite bushings, which eliminates cost of hot washing porcelain bushings while providing excellent mechanical and superior dielectric properties - Tank heaters for operation in ambient temperatures below -30C - High seismic designs - HMB-1 class spring-hydraulic mechanism for 40 kA breaker applications subject to extended numbers of repetitive operations FSA-2 and HMB-1.5 mechanisms Breakers rated 40 kA are driven by a type FSA-2 spring mechanism, located in the control cabinet. The mechanism is simple and relatively low powered, resulting in minimal mechanical stresses during breaker operation and lower overall maintenance costs. The 50 and 63 kA rated breakers employ an HMB-1.5 class spring-hydraulic mechanism, located within the control cabinet, to operate the interrupters. The fully-integrated mechanism is self-lubricating and hermetically sealed to the atmosphere, affording excellent reliability and long term stability.

With a large installed base and proven track record, the PM breaker offers unequalled performance and reliability. ABB advantages - Interrupting ratings through 63 kA at applications through 145 kV, and through 50 kA at 169 kV - High performance interrupters for definite purpose breaker reduce potential for overvoltages caused by restrikes during capacitor bank switching - One-piece interrupter assembly simplifies field change-out whenever end of life is reached by eliminating need for internal tank mounting of separate parts and alignment - Simple, low powered motor-charged spring mechanism for 40-kA applications, imparts minimal mechanical stress to the breaker, reducing maintenance costs - Compact, fully-integrated spring-hydraulic mechanism for 50- and 63-kA applications, is self-lubricating and self-damping. It is also hermetically sealed to the atmosphere, which eliminates corrosion and helps provide maintenance-free performance with long term stability - Externally accessible current transformers enable simple field change-out without degassing breaker and bushing removal - Extensive range of available field services, from technical assistance to turn-key installation, can dramatically reduce construction costs and speed time to commercial operation

SHIPPING AND INSTALLED WIDTH MAXIMUM 84 7/16 DIM. FOR BUSHING REMOVAL

SHIPPING AND INSTALLED WIDTH 149 1/4" (3790)

84 7/16" (2145)

MAXIMUM DIM. FOR BUSHING REMOVAL

101 5/8" (2582)

PHASE SPACING 73 9/16" (1868)


PHASE SPACING

PHASE (1868) 73 9/16" SPACING


PHASE SPACING

35 5/16" (897)
ADDITIONAL HEIGHT REQUIRED FOR BUSHING REMOVAL

92 1/16" (2339) 85 11/16" (2176) 70 5/8" (1794)


METAL TO METAL

20" (508) 60 5/16" (1532) 1532


METAL TO METAL

508

18

30

46 1/16" (1170)
BUSHING STRIKE

178 3/8" (4530)


INSTALLED HEIGHT

1 1/8" (29)

VACUUM / FILLING CONN.

TOP OF TERMINAL PAD

60 PSIG 40

80 100120

20 140

DENSITY MONITOR

156 3/4" (3981)


LIVE PARTS

MINI MONITOR CLOSEST POLE

RUPTURE DISC

142 1/4" (3613)


SHIPPING HEIGHT

49 5/16" (1253) 70 3/4" (1797)


HEIGHT OF CONTROL CABINET

BREAKER OPERATION COUNTER MOTOR COUNTER BREAKER POSITION INDICATOR WIDTH OF CONTROL CABINET

MINIMUM BUSHING HEIGHT

119" (3022)

HEIGHT TO C OF BREAKER

98 5/8" (2505)

85 3/16" (2164)

BOTTOM OF CONTROL CABINET

33 9/16" (852)

1 1/4" (32)

DEPTH OF CONTROL CABINET

18 1/4" (464)

LOCATION OF EXTERNAL ELECTRICAL OUTLET

31 13/16" (808)
LEG EXTENSIONS

ANCHOR BOLT SPACING

60 1/4" (1530)

CLEARANCE TO REMOVE INTERRUPTER

73 13/16" (1875)

ANCHOR BOLT SPACING

46 1/8" (1172)

Rated capabilities
Circuit Breaker Type 121PM40-20 121PM40-30 121PM40-40 121PM50-20 121PM50-30 121PM50-40 121PM63-20 121PM63-30 121PM63-40 145PM40-20 145PM40-30 145PM40-40 145PM50-20 145PM50-30 145PM50-40 145PM63-20 145PM63-30 145PM63-40 169PM40-20 169PM40-30 169PM40-40 169PM50-20 169PM50-30 169PM50-40 Rated Maximum Voltage (kV, rms) 123 123 123 123 123 123 123 123 123 145 145 145 145 145 145 145 145 145 170 170 170 170 170 170 Short Circuit and Short Time Current (kA, rms) 40 40 40 50* 50* 50* 63* 63* 63* 40 40 40 50* 50* 50* 63* 63* 63* 40 40 40 50* 50* 50* Maximum Continuous Current (A, rms) 2000 3000 4000 2000 3000 4000 2000 3000 4000 2000 3000 4000 2000 3000 4000 2000 3000 4000 2000 3000 4000 2000 3000 4000 Rated Interrupting Time (Cycles) 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Full Wave Withstand Voltage (kV, Peak) 550 550 550 550 550 550 550 550 550 650 650 650 650 650 650 650 650 650 750 750 750 750 750 750 Power Frequency Insulation Withstand Voltage (kV, rms) 260 260 260 260 260 260 260 260 260 310 310 310 310 310 310 310 310 310 365 365 365 365 365 365 2 -sec Chopped Wave Impulse Voltage (kV, rms) 710 710 710 710 710 710 710 710 710 838 838 838 838 838 838 838 838 838 968 968 968 968 968 968 Closing and Latching Current (kA, Peak) 104 104 104 130 130 130 164 164 164 104 104 104 130 130 130 164 164 164 104 104 104 130 130 130

For more information please contact: ABB Inc. High Voltage Products Westmoreland Distribution Park East 100 Distribution Circle Mount Pleasant, Pennsylvania, USA Phone: +1 (724) 696-1500 Fax: +1 (724) 696-1502 www.abb.com/highvoltage

* 12 nF/phase line-to-ground capacitance required for ANSI 90% short line fault interrupting performance. Types 121PM and 145PM breakers are shipped with standard 98" creep porcelain bushings; 143" creep RTV composite units are optionally available. Type 169PM breakers have standard 118" creep porcelain bushings or optionally available 146" composites. Additional creep lengths are available for all designs.

Document Number - 2GNM110054 / January 2009

167 11/16" (4259)

MINIMUM DIM. FOR BUSHING REMOVAL

208" (5283)