Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m) Main Cable(mm2)

DB Basement 50.0 5X6

Main M.C.B(A) MAIN LIGHT M.C.B(A) MAIN POWER M.C.B(A) Drop Voltage %

3X25

.
Load

3X20 1.0

Calculations
Lighting Section I (A)

Lighting Cir. No. L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20

No. of Phases 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Load(kw)

M.C.B (A)

Cable (mm2)

1/8

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Total Load Dem. Factor Main Light Section 3

0.00 1.00 0.00 Power Section

Power Cir. No. P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18 P19 P20 Total Load Dem. Factor Main Power Section

No. of Phases 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Load(kw) 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50

I (A) 2.53 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84

M.C.B (A) 16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16 3X16

Cable (mm2) 3X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5 5X2.5

7.50 0.90 3 6.75 11.40 Main Panel 3X20

Main

6.75

11.40

3X25

5X6 3(3X240+2X120)

2/8

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m)

MDB Basement 40.0

Main M.C.B(A) Main Cable(mm2) Drope Voltage %

3X800 2(3X185+2X95) 0.9

.
Load Calculations
Distance (m) 100.00 I (A) 531.77 C.B (A) 3X600

DB. No.

No. of Phases 3

Load(kw) 315.00

Cable (mm2) 2(3X120+2X70)

Drope Voltage % 2.59

65.00

100.00

109.73

3X125

3X35+2X16

3.32

3/8

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m)

MDB Basement 40.0

Main M.C.B(A) Main Cable(mm2) Drope Voltage %

3X800 2(3X185+2X95) 0.9

.
Load Calculations
Distance (m) I (A) C.B (A)

DB. No.

No. of Phases

Load(kw)

Cable (mm2)

Drope Voltage %

4/8

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m)

MDB Basement 40.0

Main M.C.B(A) Main Cable(mm2) Drope Voltage %

3X800 2(3X185+2X95) 0.9

.
Load Calculations
Distance (m) I (A) C.B (A)

DB. No.

No. of Phases

Load(kw)

Cable (mm2)

Drope Voltage %

Main Panel Total Dem. Factor Main Panel 3 380.00 1.00 380.00 40.00 641.50 3X800 2(3X185+2X95) 0.91

5/8

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m)

MDB Basement 250.0

Main M.C.B(A) Main Cable(mm2) Drope Voltage %

485.26 3(3X240+2X120) 3.77

.
Load Calculations
C.B (A) 80 Load(kw) 37.91

DB. No. DB1

Distance (m) 20.00

No. of Phases 3

Cable (mm2) 5X16 5X4

Drope Voltage % 1.05

DB2

200.00

300

142.17

3X120+2X70 5X4

5.84 0.00

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB3 100.00 3

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB4 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB5 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB6 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB7 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB8 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to

5X4

Page6

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m)

MDB Basement 250.0

Main M.C.B(A) Main Cable(mm2) Drope Voltage %

485.26 3(3X240+2X120) 3.77

.
Load Calculations
C.B (A) Load(kw)

DB. No. DB9

Distance (m) 100.00

No. of Phases 3

Cable (mm2)

Drope Voltage %

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB10 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB11 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB12 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB13 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB14 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB15 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB16 100.00 3

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to

5X4

Page7

Load Calculations

Designed by:

Eng. Sami Mahmoud Za'rour

Distribution Board Name Location Distance (m)

MDB Basement 250.0

Main M.C.B(A) Main Cable(mm2) Drope Voltage %

485.26 3(3X240+2X120) 3.77

.
Load Calculations
C.B (A) Load(kw)

DB. No. DB17

Distance (m) 100.00

No. of Phases 3

Cable (mm2)

Drope Voltage %

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB18 50.00 1

5X4

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB19 200.00 3 500 236.94

5X4 3X240+2X120 5X4 189.56 3X185+2X95 5X4 5.53 0.00 2.74

Drop voltage is Unacceptable, so you must increase the cross section of cable to DB20 100.00 3 400

Main Panel Total Dem. Factor Main Panel 250.00 3 3X1000 606.58 0.80 485.26 2(3X240+2X120) 3(3X240+2X120) 5.66 3.77

Drop voltage is Unacceptable, so you must increase the cross section of cable to