IRIG-B GPS Time Synchronization


TheIRIGBoptionisavailablewithselectedPowerLogicmeters.Thesemeters acceptunmodulatedIRIGBtimecode,compatiblewiththeIRIGB00x1format. ThestandardisoutlinedintheIRIGSTANDARD20004IRIGSerialTimeCode FormatspreparedbytheTimingCommittee,TelecommunicationsandTiming Group,RangeCommandersCouncil. IRIGBistheindustrystandardforGPStimesynchronization.Powerindustry specificIRIGBapplicationsinclude: 1. 2. 3. Powerqualitymonitoringandsequenceofeventsrecording. Highlyaccuratetimestampingforrevenuebilling(1ms). Systemstabilitymonitoring.

NOTE
This option requires a receiver capable of unmodulated IRIG-B time code output (not included).

AllIRIGBequippedmetersareconfiguredinthefactorytosynchronizevia GPSusingunmodulatedIRIGBtimecodedata. YoucannotconfigureIRIGBfromthemetersfrontpanel.SeeConfiguringIRIG Bonpage 2forconfigurationdetails. SeetheIONReferenceforadetaileddescriptionoftheClockModule. Specifications


Accuracy Format Nominal Voltage Maximum Voltage
+/- 1ms.

IRIG-B00x1 format (unmodulated IRIG-B time code) 5 Vdc +/- 10% 8 Vdc

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2007 Schneider Electric. All rights reserved. www.powerlogic.com

1. Coded expressions 4 to 7 are supported but the year data is not used by the meters.

Configuring IRIG-B

IRIG-B Time Synchronization

Configuring IRIG-B
AllIRIGBequippedmetersaresetbydefaulttosynchronizeviaIRIGB. OperationiscontrolledbytheClockmodulesTimesyncSourceandClockSource registers. UseIONSetuporIONEnterprisetoconfirmyourIRIGBsettings.SeetheION ReferenceformoredetailsontheClockModule.

Using the front panel


YoucannotconfigureIRIGBviathemetersfrontpanel.

Using ION Setup


1. 2. IntheSetupAssistant,navigatetoClockandclicktheTimezonetab. SelecttheCL1TimeSyncSourceparameterandclickEdit.

3. 4. 5.

SelectIRIGBandclickOK. SelecttheClockSourceparameterandclickEdit.SelectCOMMandclickOK. Connectthemetertothetimesource(GPSreceiveroutput).

Page 2

2007 Schneider Electric. All rights reserved.

IRIG-B Time Synchronization

Configuring IRIG-B

Using ION Enterprise


1. 2. 3. 4. UsetheManagementConsoletoconnecttothedesiredmeter. OpenyourmeterinDesignerandnavigatetotheClockmodule.Rightclickon theClockmoduletoedit. SelecttheTimeSyncSourcesetupregisterandclickModify. SelectIRIGB.ClickOK.

5. 6. 7.

SelecttheClockSourceparameterandclickEdit. SelectCOMMandclickOK. Connectthemetertothetimesource(GPSreceiveroutput).

Supported GPS Receivers


AnyGPSreceivermaybeusedasatimesynchronizationsource,providingthe receiveroutputsunmodulatedIRIGBtimecodedata.

Security
AccesstoClockModuleconfigurationsarenotavailableviathefrontpanel.ION SetuporIONDesignerisrequired. IONmetersecurityandIONsoftwaresecurityareimplemented.

Diagnostic Module Outputs


ThediagnosticmoduleoutputregistersupdateasdescribedintheTime SynchronizationandTimekeepingtechnicalnote,withthefollowingexceptions: GPSReceiverStatusSettoN/A.

2007 Schneider Electric. All rights reserved.

Page 3

Getting More Information

IRIG-B Time Synchronization

Event Logging
EventsareloggedasdescribedintheTimeSynchronizationandTimekeeping technicalnote,withthefollowingexceptions: GPSlockedNotgenerated. GPSunlockedNotgenerated.

Getting More Information


Installation Guide Thisdocumentprovidesinstructionsonmountingandwiringthemetertothe powersystem,wiringtheCOMports,configuringthemetersbasicsettingsfrom thefrontpanel,andverifyingoperation. Time Synchronization and Timekeeping Technical Note Thistechnicalnoteprovidesprecisesequenceofeventsandpowerquality analysesconfigurationprocedures,includingclocksynchronizationandGlobal PositioningSystem(GPS)timesignalbroadcastsacrossnetworks. Users Guide Thismanualprovidestheoperationandusagedetailsincluding:displayingdata, makingconfigurationchanges,customizingoperationwithIONsoftware,using thestandardinputs/outputs,andmore. ION Reference Thisonlinemodulereferencedescribeshowtomakeconfigurationchangestoan IONcompliantnodewithDesignersoftware,andprovidesadetailedfunctional descriptionofeveryIONmoduleintheIONarchitecture.