Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 51

Swirl diffuser NWCA

Swirl diffuser NWCA is suitable for public premises such as offices, hotels, hospitals, restaurants, conference halls etc. The diffusers are preferably being used in industrial buildings, where good heat comfort is required. Diffusers are mounted in false ceiling or under the ceiling. Full spread of air flow at relatively short distance from diffuser allows using this type of diffusers in premises from 2.2 to 4.5 m high. Swirl diffuser NWCA has an air flow range of between 11 and 267 l/s (40 - 960 m3/h) and it is also possible to use NWCA as an exhaust device. Swirl diffuser NWCA is easy to install together with connection devices such as connection box or duct socket. The connection box is provided as standard with measurement sockets for measurement of the air flow. The connection box can be equipped with a control damper or a blade damper regulated manually. Connection box can be insulated with sound attenuating material on request.

Product facts
Swirl diffuser NWCA
Intended for ceiling installation Two connection alternatives, with connection box or with duct socket Broad flow range

Product code example:


Swirl diffuser NWCA-31-1 Terminal of size 31, painted in RAL 9010 colour. Connection box SKZA-16-12-1-0 Size 12 to fit diffuser size 16, insulated without blade damper.

Quick selection
Size l/s 11 11 17 21 39 56 111 32 36 61 83 133 194 267 Air flow m3/h Installation height above the flooor, m 2.2 2.2 2.4 2.4 2.7 2.7 2.9 3.5 3.4 4.0 4.0 4.0 4.0 4.5 Sound level LA10, dB(A) 20 20 20 20 22 20 20 48 48 40 41 43 42 39

NWCA-10 NWCA-12 NWCA-16 NWCA-18 NWCA-25 NWCA-31 NWCA-35

40 - 115 40 - 130 60 - 220 75 - 300 140 - 480 200 - 700 400 - 960

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 52

Installation height, throw length


Installation height selection diagram
Hp = diffuser installation height above the floor.

5
18 25 16 31

4
size 10 12

35

H P [ m]

25

3
siz e1 0 12

16

18

40

50

60 70 80

100 120

160 200

V [ m /h] V [l/s]

300

400 500 600

31

35

1000

1400

11

15

20

25

30

40

50

60 70 80

100

150

200 250 300

390

Throw length
5 4 3 3
-10K

6 5 4

0K

L 0, 2 [ m]

2 1, 5
e1 0 12

1, 5

1 0, 8 1 40
50

60 70 80

siz

100 120

16

160 200

18

V [ m 3/h] V [l/s]

300

25

400 500 600

31

35
1000

1400

11

15

20

25

30

40

50

60 70 80

100

150

200 250 300

390

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 53

Air flow, pressure drop, sound level


Installation alternative SKZA pressure drop and sound level
100 80 70 60 50
35 dB(A)
SKZA

P [ Pa ]

40
e1

30 dB(A) 25 dB(A)

30

20
25 31 12 16 18 35

15

10

40

siz

50

60 70 80

100 120

160 200

V [ m 3/h] V [l/s]

300

400 500 600

800 1000

1400

11

15

20

25 30

40

50

60 70 80

100

150

200 250 300

390

Installation alternative PKAA pressure drop and sound level


100 80 70 60 50

35 dB(A) 30 dB(A) 25 dB(A)


PKAA

P [ Pa ]

40 30
siz e1 0

20 15

16

12

18

10

40

50

60 70 80

100 120

160 200

25

31

V [ m 3/h] V [l/s]

300

35

400 500 600

800 1000

1400

11

15

20

25

30

40

50

60 70 80

100

150

200 250 300

390

In the above graphs the sound levels are indicated in dB(A) for a reference room with 10 m2 room absorption, equivalent to 4 dB room attenuation.

Maximum temperature difference at heating tv 5K Maximum temperature difference at cooling tk 12K

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 54

Exhaust air device, installation alternatives


Air flow, pressure drop, sound levels
PKAA

150 100 80 60
45 dB(A) 40 dB(A) 35 dB(A)
e1 0 siz

P [ Pa ]

50 40 30 20 15
12 16

30 dB(A) 25 dB(A)
25 31 18 35

10

40

50

60 70 80

100 120

160 200

V [ m 3/h] V [l/s]

300

400 500 600

800 1000

1400

11

15

20

25 30

40

50

60 70 80

100

150

200 250 300

390

In the above graph the sound levels are indicated in dB(A) for a reference room with 10 m2 room absorption, equivalent to 4 dB room attenuation.

Installation alternatives
Connection box can be equipped either with a blade damper or a measurement and adjustment damper ZAED

SKZA

PKAA

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 55

Sound data, definitions


Sound power level
Installation alternatives SKZA
Size 63 10 12 16 18 25 31 35 11 8 12 10 10 11 8 Correction of sound level Kok in dB for octave bands, mean frequency (Hz) 125 250 500 1000 2000 4000 10 7 11 9 9 10 7 2 5 8 5 5 5 4 2 1 0 3 3 1 4 4 5 3 4 3 0 0 15 8 11 7 10 9 11 20 8 16 12 15 14 16 8000 25 18 25 19 22 23 21 10 12 16 18 25 31 35

Sound attenuation
Diffuser with uninsulated connection box
Size 63 0 0 0 1 2 1 3 125 2 4 4 1 4 4 2 Sound attenuation in dB for octave band, mean frequency (Hz) 250 500 1000 2000 4000 2 5 2 4 4 4 3 8 10 9 6 9 11 3 8 10 9 6 9 11 7 10 8 6 7 5 7 4 3 2 3 1 4 3 3

8000 3 3 3 0 1 0 1

Installation alternative PKAA


Size 63 10 12 16 18 25 31 35 9 6 8 9 7 7 10 Correction of sound level Kok in dB for octave bands, mean frequency (Hz) 125 250 500 1000 2000 4000 8 5 7 8 6 6 9 7 6 6 3 2 2 6 4 4 1 4 4 4 1 7 3 1 3 1 3 1 10 10 4 6 9 5 6 15 15 9 11 15 10 11 8000 25 25 19 21 25 20 19

Diffuser with insulated connection box


Size 63 10 12 16 18 25 31 35 0 0 0 1 2 1 3 125 3 4 5 1 5 5 3 Sound attenuation in dB for octave band, mean frequency (Hz) 250 500 1000 2000 4000 4 8 4 7 5 7 6 10 13 13 10 13 15 8 12 12 8 11 10 12 6 7 9 8 7 10 6 9 5 8 9 7 9 9 9 8000 5 9 9 8 9 8 7

Exhaust air device (PKAA)


Size 63 10 12 16 18 25 31 35 5 7 4 10 10 9 8 Correction of sound level Kok in dB for octave bands, mean frequency (Hz) 125 250 500 1000 2000 4000 4 5 3 9 8 7 7 5 7 4 4 1 4 1 5 4 4 2 4 3 4 14 5 4 0 1 2 1 15 11 6 9 11 4 11 19 16 12 15 17 13 15 8000 25 25 22 25 25 23 24

Diffuser without connection box


Size 63 10 12 16 18 25 31 35 0 1 1 2 3 2 4 125 1 3 3 0 4 3 1 Sound attenuation in dB for octave band, mean frequency (Hz) 250 500 1000 2000 4000 1 4 1 3 3 2 2 7 8 7 5 7 10 5 9 6 4 5 4 5 3 4 3 3 2 2 1 3 2 1 2 0 3 2 2 8000 2 2 2 1 1 0 0

The sound power levels for different octave bands are obtained by adding together the sound pressure level LA10, in dB(A), and the corrections Kok for the octave bands in the table with the help of the following formula:

Definitions
q pt Hp L02 LA10 LW Kok L air flow total pressure drop installation height throw sound pressure level with a room attenuation of 4 dB (10 m2 room absorption area) sound power level octave band correction sound attenuation from the duct to the room l/s, m3/h Pa m m dB(A) dB dB dB

LW = LA10 + Kok
Correction Kok is the mean value for the range of application of NWCA.

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 56

Dimensions
Installation alternative SKZA with connection box

Size 10-10 12-10 16-12 18-16 25-20 31-25 35-25

D1 104 129 164 184 254 319 359

D2

D1

D2 97 97 122 157 197 247 247

L 310 310 390 390 490 580 640

K 167 167 192 227 267 317 317

B 125 125 165 165 200 252 292

Xmin 43 50 49 51 74 66 67

Xmax 63 93 93 121 125 162 176

All dimensions are indicated in mm.

Installation alternative PKAA for duct connection with duct socket


D5 D4 L3 9 D1 H2 9 H4 H3 H1

DN D2 D3

Size 10-10 12-10 16-12 18-16 25-20 31-25 35-25

D1 99 124 159 179 249 314 354

D2 138 165 208 240 314 420 441

D3 165 200 250 282 375 494 515

D4 100 100 125 160 200 250 250

D5 128 153 188 208 278 343 383

L3 30 30 30 30 30 40 40

H1 50 80 80 112 116 150 163

H2 62 103 121 130 145 165 178

H3 88 114 138 148 175 206 230

H4 176 197 220 232 260 308 340

All dimensions are indicated in mm.

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 57

Adjustment, distance between two terminals descriptive text, product code


Adjustment ZAED damper
q = k pm (l/s) (Pa) q = 3,6k pm (m3/h) (Pa) Example
Total air flow, qtot Nominal diameter, DN Height above the floor, Hp Number of diffusers, n Air flow per diffuser
D3

24 000 m3/h 250 mm 3.4 m 80 pcs. 300 m3/h 2.6 m

Distance between diffusers, tmin

Descriptive text
Swirl diffuser NWCA for ceiling installation manufactured by Flkt Woods.

Product code
pm

Swirl diffuser
N, mm 1-7xD3 1-7xD3 1-7xD3 1-7xD3 1-7xD3

NWCA-aa-b

D3, mm 100 125 160 200 250

k 7.0 11.7 20.0 31.6 50.5

Size 10, 12, 16, 18, 25, 31, 35 Colour 1 = standard RAL 9010 X = any other colour from RAL palette Connection box Size 10-10, 12-10, 16-12, 18-16, 20-16, 25-20, 31-25, 35-25, (diffuser size - duct connection size) Type 0 = uninsulated 1 = insulated Damper 0 = without 1 = blade damper 2 = measurement and adjustment damper ZAED (standard) SKZA-aa-bb-c-d

N - distance between ZAED damper and the nearest bend.

Distance between two diffusers


q, l/s q, m3/h tmin, m Hp, m

Duct socket Diffuser size - duct connection size 10-10, 12-10, 16-12, 18-16 20-16, 25-20, 31-25, 35-25 Duct connection type 0 = without rubber gasket 1 = with rubber gasket

PKAA-aa-bb-c

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.

Swirl diffuser NWCA

TECHNICAL DATA - 2010 page 58

Flkt Woods

PLBOV 2010.11

Specifications are subject of alteration without further notice.