Problem 8-6:

For St. Louis:


For cooling, outside db temperature:
For cooling, outside mwb temperature:
For cooling, outside humidity ratio, W:

95
76
0.0152

Inside cooling design db temperature is:


Inside cooling design wb temperature is:
Inside cooling design humidity ratio, W is:

75
63
0.0098

CLTDcorr = CLTDtable + (78 - 75) + [(95 - 18/2) - 85]


CLTDtable + 4
Assume the peak load will occur at 3 pm.
Cooling:
U value, SC,
or other
factor
0.033

CLTD
CLTDcorr
Area or
correction or Watts
Quantity CLTDtable
or SCL
per unit
Roof/Ceiling
42
24
1008
65
4
69
East wall, gross
42
10
420
windows
conduction
0.87
3
6
90
14
4
18
5 solar
0.58
3
6
90
48
net wall
0.08
330
28.5
4
32.5
South wall, gross
24
10
240
windows
conduction
0.87
3
6
72
14
4
18
4 solar
0.58
3
6
72
67
net wall
0.08
168
13.5
4
17.5
Lights
3.412
20
2
40
31
Computers
3.412
15
125
Printers
3.412
4
160
People
250
200
15
Subtotals
Ventilation rate:
SHR
5 cfm/person x 15 people + 0.06 cfm/sf x 1008 sf =
135 cfm
Duct heat gain fraction =

26,096.0 x 0.1/2 =

CLF

q total

1,409.4
2,505.6
858.0

0.92
0.89
0.89
0.89

1,127.5
2,797.9
235.2
3,892.4
5,693.8
1,943.5
3,337.5
26,096.0

3,000.0
3,000.0

29,096.0

2,926.4

3,423.9

6,350.2

1,304.8
30,327.2

6,423.9

36,751.0

0.90

1,304.8
Totals
SHR

q sensible
q latent
2,295.2

0.83

Evaporation:
For evaporation, outside mdb temperature:
For evaporation, outside wb temperature:
For evaporation, outside humidity ratio, W:

90
79
0.019

CLTDcorr = CLTDtable + (78 - 75) + [(90 - 18/2) - 85]


CLTDtable - 1

U value, SC,
or other
factor
0.033

CLTD
CLTDcorr
Area or
correction or Watts
Quantity CLTDtable
or SCL
per unit
Roof/Ceiling
42
24
1008
65
-1
64
East wall, gross
42
10
420
windows
conduction
0.87
3
6
90
14
-1
13
5 solar
0.58
3
6
90
48
net wall
0.08
330
28.5
-1
27.5
South wall, gross
24
10
240
windows
conduction
0.87
3
6
72
14
-1
13
4 solar
0.58
3
6
72
67
net wall
0.08
168
13.5
-1
12.5
Lights
3.412
20
2
40
31
Computers
3.412
15
125
Printers
3.412
4
160
People
250
200
15
Subtotals
Ventilation rate:
SHR
5 cfm/person x 15 people + 0.06 cfm/sf x 1008 sf =
135 cfm
Duct heat gain fraction =

25,025.8 x 0.1/2 =

CLF

q total

1,017.9
2,505.6
726.0

0.92
0.89
0.89
0.89

814.3
2,797.9
168.0
3,892.4
5,693.8
1,943.5
3,337.5
25,025.8

3,000.0
3,000.0

28,025.8

2,194.8

5,833.2

8,028.0

1,251.3
28,471.9

8,833.2

37,305.1

0.89

1,251.3
Totals
SHR

q sensible
q latent
2,128.9

0.76

Dehumidification:
For dehumidification, outside db temp:
For dehumidification, outside wb temp:
For dehumidification, outside HR, W:

85
78
0.0192

CLTDcorr = CLTDtable + (78 - 75) + [(85 - 18/2) - 85]


CLTDtable - 6
U value, SC,
or other
factor
0.033

CLTD
CLTDcorr
Area or
correction or Watts
Quantity CLTDtable
or SCL
per unit
Roof/Ceiling
42
24
1008
65
-6
59
East wall, gross
42
10
420
windows
conduction
0.87
3
6
90
14
-6
8
5 solar
0.58
3
6
90
48
net wall
0.08
330
28.5
-6
22.5
South wall, gross
24
10
240
windows
conduction
0.87
3
6
72
14
-6
8
4 solar
0.58
3
6
72
67
net wall
0.08
168
13.5
-6
7.5
Lights
3.412
20
2
40
31
Computers
3.412
15
125
Printers
3.412
4
160
People
250
200
15
Subtotals
Ventilation rate:
SHR
5 cfm/person x 15 people + 0.06 cfm/sf x 1008 sf =
135 cfm
Duct heat gain fraction =

23,955.6 x 0.1/2 =

37,800.0

Summary:
Cooling
Evaporation
Dehumidification
Table 8.15

Sensible
Latent
Total
30,327.2
6,423.9 36,751.0
28,471.9
8,833.2 37,305.1
26,616.5
8,960.0 35,576.6
37,800.0

Btuh
Btuh
Btuh
Btuh

q sensible
q latent
1,962.6

q total

626.4
2,505.6
594.0

0.92
0.89
0.89
0.89

501.1
2,797.9
100.8
3,892.4
5,693.8
1,943.5
3,337.5
23,955.6

3,000.0
3,000.0

26,955.6

1,463.2

5,960.0

7,423.2

1,197.8
26,616.5

8,960.0

35,576.6

0.89

1,197.8
Totals
SHR

Typical load from Table 8.15:


Using 320 SF/Ton for exterior office

CLF

0.75

Problem 8-7:
For St. Louis:
For heating, outside db temperature:

Inside heating design db temperature is:


Temp Diff:

Roof/Ceiling
East wall, gross
windows
conduction
5 solar
net wall
South wall, gross
windows
conduction
4 solar
net wall
Floor Slab

U value or
other factor
0.033
0.87
0.58
0.08
0.87
0.58
0.08
0.7

70
68

42
42
3
3

24
10
6
6

24
3
3

10
6
6

42

24

Area or
Quantity Temp Diff
1008
68
420
90
68
90
330
68
240
72
68
72
168
68
66
68

q sensible
2,262.0
5,324.4
1,795.2
4,259.5

Subtotals
Ventilation rate:
5 cfm/person x 15 people + 0.06 cfm/sf x 1008 sf =
Duct heat loss fraction =

17,696.6 x 0.1/2 =

135 cfm

913.9
3,141.6
17,696.6
9,949.7

884.8
Totals

884.8
28,531.1 Btuh