Emergency lighting modules with self test facility T5, T8, TC-DD, TC-F, TC-L linear and compact

lamps

EM SELFTEST 220240 V 50/60 Hz


self
Mo Di Mi Do
2 9 16 23 30 3 10 17 24 31

RoHS

Fr Sa So
4 11 18 25 5 12 19 26 6 13 20 27

21 mm

7 14 21 28

1 8 15 22 29

boost start

smart charging

test

280 270

Description: Low profile emergency lighting modules with self testing facility to cover 1 hour and 3 hour duration operating from NiCd and NiMh batteries. All modules incorporate five pole technology for use with HF ballasts and have preheat starting and permanent cathode heating during the emergency operation. Boost starting for 55 seconds at higher power levels is provided for all lamps to ensure rapid warm up, optimised lamp life and improved initial visibility during an emergency operation. Power control technology ensures maximum emergency ballast lumen factors for all lamps on a given module.

4 30

21

Self testing is conducted on a weekly functional and annual duration basis with adaptive duration testing feature to minimise risk. An easy commissioning feature ensures synchronisation of tests and automatic initiation of commissioning tests. Features: Module Self testing in accordance with pr IEC 62034 Low profile cross section (21 mm x 30 mm) 5 pole technology For use with HF ballasts

EM SELFTEST 3 h duration NiCd 4.0 Ah D cells or NiMh 4.0 Ah Cs cells type article number EM 34 ST 89899680 EM 35 ST 89899681 EM 36 ST 89899682 EM SELFTEST 1 h duration standard BLF NiCd 1.5 Ah or NiMh 2.0 Ah Cs cells type article number EM 14 ST 89899683 EM 15 ST 89899684 EM 16 ST 89899685 EM HO SELFTEST 1 h duration high output NiCd 4.0 Ah D cells or NiMh 4.0 Ah Cs cells type article number EM 14 HO ST 89899686 EM 15 HO ST 89899687 EM 16 HO ST 89899688 NiCd 1.5 Ah Cs cells Accu-NiCd C 4A Accu-NiCd C 4B * Accu-NiCd C 4C * Accu-NiCd C 5A Accu-NiCd C 5B * Accu-NiCd C 5C * Accu-Nicd C 6A Accu-NiCd C 6C NiCd 4.0 Ah D cells Accu-NiCd 4A Accu-NiCd 4B Accu-NiCd 4C Accu-NiCd 5A Accu-NiCd 5B Accu-NiCd 6A type stick side by side stick + stick stick side by side stick + stick stick stick + stick type stick side by side stick + stick stick stick + stick stick + stick number of cells 4 4 2+2 5 5 3+2 6 3+3 number of cells 4 4 2+2 5 3+2 3+3 article number 89899692 89899693 89899694 89899695 89899696 89899697 89899698 89899699 article number 89895961 89895977 89895978 89895973 89895962 89895963 NiMh 2.0 Ah Cs cells Accu-NiMh C 4A Accu-NiMh C 4B * Accu-NiMh C 4C * Accu-NiMh C 5A Accu-NiMh C 5B * Accu-NiMh C 5C * Accu-NiMh C 6A Accu-NiMh C 6C NiMh 4.0 Ah Cs cells Accu-NiMh C 4A Accu-NiMh C 5A Accu-NiMh C 6A Accu-NiMh C 6C type stick side by side stick + stick stick side by side stick + stick stick stick + stick type stick stick stick stick + stick

number of cells 4 5 6

number of cells 4 5 6

NiCd or NiMh battey options 1015 hour accu recharge time 3 hour and 1 hour operation High and standard BLF for 1 hour versions Bi-colour LED to indicate status AC operation of lamps Pre-heating of cathodes during emergency operation Permanent cathode heating during emergency operation Boost starting facility for all lamps Rest mode facility Adaptive mode for testing with minimum risk Easy commissioning feature Deep discharge protection Electronic multilevel charging system Self testing Battery condition Lamp condition Charge condition Weekly functional test Annual duration test

number of cells 4 5 6 number of cells 4 4 2+2 5 5 3+2 6 3+3 number of cells 4 5 6 3+3 article number 89899700 89899701 89899702 89899703 89899704 89899705 89899706 89899707 article number 89899850 89899851 89899852 89899853 * on request

Batteries NiCd or NiMh options D or Cs cells High temperature cells Spade terminals for easy connection Certified EN 55015: 2006 + A1: 2007 EN 601347-2-7 EN 60925 pr IEC 62034 Allows compliance with EN 60598-2-22 EN 61000-3-2 EN 61547 IEC 60068-2-6 IEC 60068-2-29 IEC 60068-2-30

type LED bi-colour LED bi-colour high brightness type Test switch EM 2

article number 89899720 89899753 article number 89805277

Data sheet 03/08-269-7 We reserve the right to make technical changes without prior notice.

Emergency lighting modules with self test facility T5, T8, TC-DD, TC-F, TC-L linear and compact lamps

Technical data:
EM SELFTEST Rated mains supply voltage Mains frequency Mains supply current Mains supply power Overvoltage protection Max. working voltage U-OUT Recharge period Discharge current Charge current: Initial Fast Trickle Earth leakage current Ambient temperature range Maximum case temperature tc Mains change over voltage Min. lamp starting temperature (emergency mode) Ingress protection Safety class Function test Duration test Timer Boost starting time Rest mode: Max units Max cable length 3 hour 220240 V 50/60 Hz 60 mA max < 10.0 W 320 V for 1 hour 460 V 15 hours 1.1 A 330 mA 330 mA 130 mA < 0.5 mA -5 C to +60 C 70 C in accordance with EN 60598-2-22 -5 C IP20 class I weekly 30 seconds test annual 3 hr duration test crystal controlled 55 seconds 100 1000 m 1 hour 220240 V 50/60 Hz 60 mA max < 10.0 W 320 V for 1 hour 460 V 10 hours 1.1 A 130 mA 210 mA 50 mA < 0.5 mA -5 C to +60 C 70 C in accordance with EN 60598-2-22 -5 C IP20 class I weekly 30 seconds test annual 1 hr duration test crystal controlled 55 seconds 100 1000 m

Accu-NiCd case temperature range to ensure 4 years design life storage life in temperate conditions battery voltage capacity D capacity Cs Accu-NiMh 4.0 Ah case temperature range to ensure 4 years design life storage life in temperate conditions battery voltage capacity Cs Accu-NiMh 2.0 Ah case temperature range to ensure 4 years design life storage life in temperate conditions battery voltage capacity Cs

0 C to +55 C 4 years 1.2 V 4.0 Ah 1.5 Ah

0 C to +50 C 4 years 1.2 V per cell 4.0 Ah

0 C to +55 C 4 years 1.2 V per cell 2.0 Ah

Mechanical details: Channel manufactured from galvanised steel. Cover manufactured from white pre-coated steel. LED bi-colour status indicator Green / red Mounting hole 6.5 mm dia Lead length 1000 mm Test switch Mounting hole 7.0 mm dia Lead length 550 mm Battery leads Quantity: 1 red and 1 black Length: 1300 mm Wire type: 0.5 mm2 solid conductor Insulation rating: 90 C Battery end termination Push on 4.8 mm receptacle to suit battery spade fitted with insulating cover Module end termination 8.0 mm stripped insulation Two-piece batteries are supplied with a 200 mm lead with 4.8 mm receptacles at each end and insulating covers to connect the separate sticks together. Batteries: Connection method: 4.8 x 0.5 mm spade tag welded to end of cell For stick packs this connection is accessible after the battery caps have been fitted. To inhibit inverter operation disconnect the batteries by removing the connector from the battery spade tag. For battery data see separate data sheet.

Testing: Commissioning test A full commissioning test is carried out automatically after permanent connection of the supply. The easy commissioning feature will set the initial test day and time to ensure random testing of units. Functional test Functional tests are carried out for 30 seconds on a weekly basis under the control of the Micro controller. Initiation and timing of these tests is set during the commissioning of the luminaire. Duration test A full duration test is carried out yearly to check the capacity of the batteries. For a full description of commissioning and test features please refer to application notes. Test switch An optional test switch can be wired to the EM ... SELFTEST. This can be used to to: initiate a 30 seconds function test < 1 second press adjust local timing > 10 second press For a full description of the test switch function refer to application notes. Status indication System status is indicated by a bi-colour LED.
LED Permanent green Fast flashing green Slow flashing green Permanent red Fast flashing red Slow flashing red Double pulsing green Status System OK Function test underway Duration test underway Lamp fault Charging fault Battery fault Rest mode

Data sheet 03/08-269-7 We reserve the right to make technical changes without prior notice.

Emergency lighting modules with self test facility T5, T8, TC-DD, TC-F, TC-L linear and compact lamps

Rest mode: Rest mode can be initiated by applying a short pulse of between 9.5 V d.c. and 22.5 V d.c. in amplitude for a period of between 150 ms and 1.0 second. This should be applied to terminals marked Rest. Terminals are not sensitive to polarity. A mains reset is required to exit the rest mode. Service life: Average service life 50,000 hours under rated conditions with a failure rate of less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.

Packing quantities: EM ... SELFTEST: 25 units per carton Bi-colour LED: 25 pieces per bag

Accu NiCd: 25 pieces per box Accu NiMh: 25 pieces per box

Emergency light output factors (BLF) in %:


Type TC-DD EM 34 ST 37 25 19 14 3 hours EM 35 ST EM 36 ST EM 14 ST 37 25 19 14 1 hour EM 15 ST EM 16 ST EM 14 HO ST 1 hour high output EM 15 HO ST EM 16 HO ST

TC-SEL

TC-DEL

TC-TEL

TC-F

TC-L

T5 FH

T5 FQ

T5 C

T5

T8

10 16 21 28 38 55 5 7 9 11 10 13 18 26 18 26 32 42 57 18 24 36 18 24 36 40 55 14 21 28 35 24 39 49 54 80 22 40 55 4 6 8 13 15 18 30 36 38 58 70

10 4 40 39 39 34 31 26 21 14 21 14 11 7 5 18 12 11 18 12 11 5 6 24 16 14 12 13 8 6 6 5 14 7 7 38 43 40 27 20 16 12 10 10 8 6 38 43 40 27 20 16 12 10 10 8 14 13 24 16 18 12 11 5 18 12 11 40 39 39 34 31 26 21 14 21 14 11

10 4 53 53 53 53 51 47 34 27 36 25 7 5 28 24 19 32 33 26 32 33 26 24 6 47 44 14 12 30 8 6 6 5 30 7 7 70 73 68 52 36 33 27 23 18 27 23 31 22 23 15 42 36 21 19

Data sheet 03/08-269-7 We reserve the right to make technical changes without prior notice.

Emergency lighting modules with self test facility T5, T8, TC-DD, TC-F, TC-L linear and compact lamps

Electrical connections: An earthed starting aid is recommended. The module should be earthed by the fixings used to attach it to the luminaire. Wiring: Lamp/ballast/supply
wire preparation: 0.50.75

IDC interface solid wire with a cross section of 0.5 mm according to the specification from WAGO alternatively a flexible lead with a cross section of 0.75 mm Horizontal interface solid wire with a cross section of 0.50.75 mm according to the specification from WAGO solid wire with a cross section of 1.0 mm with an insulation diameter up to 2.5 mm strip 9 mm of insulation from the cables Loosen wire through twisting and pulling

Batteries/LED/Test switch push terminal with button release: 0.5 mm 6.5 mm strip Maximum lamp lead capacitance terminals 5 and 6 (* hot leads) 100 pF 1) terminals 3 and 4 200 pF 1)
1)

Note: care should be taken not to exceed the total maximum lamp lead capacitance for HF ballast. Leads should always be kept as short as possible.

89 mm

Loosen wire through twisting and pulling

Wiring guidelines To ensure that a luminaire containing high frequency emergency units complies with EN 55015 for radio frequency conducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout. Within the luminaire the switched and unswitched 50 Hz supply wiring must be routed as short as possible and be kept as far away as possible from the lamp leads. This means, for example, in a linear T8 or T5 luminaire the mains wiring should be routed along one side of the luminaire body, while the wires to the emergency lamp from the emergency module are routed along the other side.

The high frequency emergency lamp wiring contains hot leads at pins 1 and 6, which have high voltage to earth. These should be kept as short as possible and separated from other wiring to minimize coupling. They also have a restriction on capacitance to other wiring and earth of 100 pF, which must be observed to ensure good lamp starting. With an earth connection of the metal case of the emergency module the noise suppression can be further improved. The wiring of the earth should be kept as short as possible. Through wiring may affect the emc performance of the luminaire.

With the use of the fifth pole possible compatibility problems between the products can be prevented. Depending on the luminaire wiring the radio suppression in the emergency mode of operation can be further improved. Capacitive loading limits of lamp leads must not be exceeded. Note the capacitance of the emergency lamp leads adds to the capacitance of the leads from the ballast to the EM BASIC module when considering ballast loading. The LED and test switch wiring should be routed separately and kept as far away as possible from the high frequency lamp leads to avoid coupling.

Data sheet 03/08-269-7 We reserve the right to make technical changes without prior notice.

Emergency lighting modules with self test facility T5, T8, TC-DD, TC-F, TC-L linear and compact lamps

EM ... SELFTEST emergency module wiring diagrams Not for use with magnetic ballasts and switch start circuits
Switched line out to ballast Line in from switch Neutral Rest mode control Rest mode control Permanent line Lout Lin N Rest Rest L 8 7 6 5 4 3 2 1 Switched line out to ballast Line in from switch Neutral Rest mode control Rest mode control Permanent line Lout Lin N Rest Rest L 8 7 6 5 4 3 2 1

EM ... SELFTEST EMERGENCY MODULE

Emergency lamp

EM ... SELFTEST EMERGENCY MODULE

Emergency lamp

+ LED pink () LED orange (+) Switch

+ LED pink () LED orange (+) Switch Optional Test Switch Battery LED L Neutral to ballast N HF BALLAST U-OUT max. 460 V

Optional Test Switch

Battery LED

L Neutral to ballast N HF BALLAST U-OUT max. 460 V

Lamp * Hot leads * Hot leads

Wiring diagram for single lamp high frequency ballasts

Wiring diagram for twin lamp high frequency ballasts with 6 terminals

Switched line out to ballast Line in from switch Neutral Rest mode control Rest mode control Permanent line

Lout Lin N Rest Rest L

EM ... SELFTEST EMERGENCY MODULE

8 7 6 5 4 3 2 1

Emergency lamp

Switched line out to ballast Line in from switch Neutral Rest mode control Rest mode control Permanent line

Lout Lin N Rest Rest L

EM ... SELFTEST EMERGENCY MODULE

8 7 6 5 4 3 2 1

Emergency lamp

+ LED pink () LED orange (+) Switch Optional Test Switch Battery LED L Neutral to ballast N HF BALLAST U-OUT max. 460 V No connection to be made Line in from switch Neutral Rest mode control Rest mode control Permanent line Lout Lin N Rest Rest L EM ... SELFTEST EMERGENCY MODULE + LED pink () LED orange (+) Switch Optional Test Switch Battery LED

+ LED pink () LED orange (+) Switch Optional Test Switch Battery LED L Neutral to ballast N HF BALLAST U-OUT max. 460 V

Lamp * Hot leads * Hot leads

Lamp

Wiring diagram for twin lamp high frequency ballasts with 7 terminals

Wiring diagram for twin lamp high frequency ballasts with 8 terminals

8 7 6 5 4 3 2 1 * Hot leads

Emergency lamp

Wiring diagram for non-maintained operation Note: All hot leads normally marked with an * should be kept as short as possible. For comprehensive wiring diagrams and instructions consult the TridonicAtco website www.tridonicatco.com

Data sheet 03/08-269-7 We reserve the right to make technical changes without prior notice.