Documente Academic
Documente Profesional
Documente Cultură
Presentation Content Standardization of Power Transformers in the network Design and design reviews Quality Control Testing
Interchangeability and standardization Philosophy All transformers are specified, designed, tested, maintained and operated to meet at least the expected operational life span of approximately 40 years when used in normal operation.
Interchangeability and standardization New transformers are specified to be designed for minimum maintenance requirements and oil leaks i.e. vacutapminimum 300000 operation, and welded top covers All the units are easily interchangeable in terms of their electrical & physical parameters and must work optimally when connected in parallel.
Interchangeability and standardization Eskom Transmission has standardized on all transformers and is reaping practical and economic benefits. All units are interchangeable, spares are common, less time is needed to check designs, performing design reviews, approval of drawings, test certificate and time is saved in preparing specifications & drawings for new Capital projects. Field maintenance staff have fewer different types of equipment to deal with
Interchangeability and standardization Power transformers are required to interconnect the system voltages of 765, 400, 275 and 220kV step down from these voltages to 132 and 88kV to give supplies to distribution or other end users. Selecting these transformers generally involves deciding on the number of type of units i.e. MVA ratings, insulation, winding Connection, vector grouping and voltage ratio. Furthermore, impedance, type of tapchanger and tapping range plays a crucial role
HV 765 400 400 400 400 275 275 220 220 132 132 132 88 132 132 132 88 88 88 88 66 66 44 44 33 22
1 2000/* 1000/*
500/40 500/40 315/40 500/40 160/20 315/40 160/20 80/10 80/10 80 40 20 80 40 20 10 40 20 20 100 20 20
800/40 630/40 250/40 250/40 160/20 250/40 80/10 160/20 80/10 40/10 40/10 40 20 10 40 20 10 5 20 10 10 5 10 10
400/40 215/40 125/20 125/20 80/10 125/20 40/10 80/10 40/10 20/5 20/5 20 10 20 10 5 10 5 5 2.5 5 5 10 5
YNa0d1
Ynd1
YNyn0
CORE
3A2
Tertiary Winding
11 11
Tapping Winding
a2 a2
MV Winding
A13
12
HV Winding
Adoption of this arrangement, Cont This policy has been abolished in the recent past due to the line faults failures experienced from the tertiary feeders which is a dangerous practice as a direct short-circuit fault on the tertiary winding can lead to very high forces on that winding, resulting in the destruction of the whole transformer.
ZnO Varistors
3A 2
a2
11
A 13
Tertiary Winding
CORE
MV Winding
Tap Winding
12
HV Winding
Challenges Tertiary impedance dropped due to the relocation of the tapping winding into the main field. Tertiary reactor was introduced to increase the impedance thereby dropping the fault level to < 20kA. Impedance slope differed due to the different winding arrangement.
Im p e d a n c e (% )
14 12 10 8 6 4 2 0 1 3 5 7 9 11 13 15 17
Tap position
Temperature Rise of Metallic Parts at Rated MVA. The hot spot temperature rise above ambient of metallic parts in contact with cellulose material outside the winding block shall not exceed 68 The rise above ambient of other metallic C. parts in contact with oil including core and tank shall not exceed 75 for the surface in contact C with the oil.
The winding hot spot temperature rises above ambient at nameplate MVA rating has been changed from 73 to 68 C C. The top oil temperature rise above ambient has been changed from 55 to 50 If forced oil flow C. through the winding is applied (ODAF/ODWF) the oil flow through the core must also be forced so that the oil at top of the core does not exceed a 50 temperature rise above ambient. C
Changes and adoption of the new Specification 20% Insulation safety margin as per international standard as demonstrated by field plots. Increase the radial build of tap winding, reducing paper insulation within limits Fitting ZnO varistors across the tap winding to limit voltage transients that causes oscillation Using low chip epoxy to improve mech. strength of the tap Wdgs.
Design reviews
international Consultant is engaged Design Review is performed on every new design and the ff: is verified as per Cigre Guideline Focus area is on conformity and performance data with both ordering specification and IEC/IEEE Standards. Reliability aspects such as design safety margins crosschecks calculations, material quality, and quality assurance in terms of designs and manufacturing. Lifetime expectancy aspects such as thermal aspects focussing on hot spots in the windings and metal parts, Dissolved Gas Analysing limits, short circuit behaviour, overload condition behaviour as per IEC 600767 Loading guide.
Factors considered during the design reviews ELECTRICAL DESIGN Winding Arrangement Arrangement of windings. Describe type of windings to be used. Conductor configuration in each winding. Location and type of tap windings or tap sections to be used.
Insulation clearances between windings and between windings and ground. Electrostatic shielding around the core, at ends of windings, and adjacent to line coils or disks. Insulation spaces between disks. Calculated impulse voltages between disks. Conductor insulation on each winding. Calculated turn to turn voltage in each winding. Drawing of the insulation assembly between and around windings. Transient voltage distribution
the voltages with and without the metal oxide varistors. Study of oil spaces and creepage stresses
Calculation methods used to determine the field magnitudes. Determination of losses in the various elements. Cores and core supports. Frame and tank wall heating. Shielding used to reduce losses and prevent heating.
Workshop Inspection
Quality control
Focus area is on Tests to prove that the transformer has been built correctly: This include ratio, polarity, resistance and taphange operation. Tests to prove the guarantees: These are the losses, impedance, and temperature rise and noise level. Test to prove that the transformer will be satisfactory in service for at least 35 years. The tests in this category are the most important and the most difficult to frame. These tests are performed as per IEC 60076-3
Transformer testing
Main test required as per IEC: Temperature rise test (only on the first unit) Short time duration heat run test Short circuit test Lightning impulse test Switching impulse test Routine Induced over voltage test Chopped impulse test Routine Type Routine, on subsequent units Calculation for the short circuit capability should be submitted Routine Routine Routine Routine Type Type Routine Routine Routine Routine withstand
Acoustic noise level measurement Overload test Dielectric loss angle test and capacitance (Doble instrument) Vibration test SFRA Fully assembled filled with oil. (Doble instrument) SFRA Fitted with test bushing and gas filled. (Doble instrument)
Transformer testing
Thank You