Circuit Breaker 1.1.1.

1 Electrical Features Air break triple pole indoor type draw out type conforming to IS 13947. Rated continuous current as specified.630amp,15ka for 3 sec. Symmetrical breaking capacity and 1 second rating of the breaker not less Than the system short circuit level specified.250mva fault level Performance category: P2 Auxiliary contacts: 6 NO + 6 NC minimum, convertible from NO to NC and vice versa at site. Ratings: Continuous 10 amps AC 11 4 amps at 240 V DC 11 0.5 amps at 110 V 1.1.1.2 Operating Mechanism Manual or power operated mechanism as applicable Spring charged stored energy mechanism to ensure high speed closing and tripping independent of the operating forces. Anti pumping and trip free feature Emergency tripping by mechanically operated trip push button (shrouded to prevent accidental closing) acting directly on the trip bar. Closing operation of the breaker to charge the tripping spring, ready for tripping. Mechanical indication to show : _ Closing spring charged _ Breaker ON/OFF/TRIP Breaker to close only when spring fully charged Non-reset type operation counter For manually operated breakers. _ Independent manual charging of closing spring and closing by handle. _ Alternatively, closing by mechanical push button with spring previously charged by handle. For electrically operated breakers : _ Charging of closing spring by motor _ closing by closing coil _ spring charging motor and closing coil suitable for rated control voltage (240 AC unless otherwise specified).\ Trip coil might be 30v dc/110v dc _ One opening and one closing operation without control supply. _ Provision also for manual closing with spring charging motor automatically decoupled as soon as charging handle is inserted.\
Power Pack 110V AC to 110V DC with RU & RCU Circuit with back up power arrangement

1.1.1.3 Drawout Features 3 distinct positions viz. service, test, and isolated with the door closed.

Mechanical position indication and locking/latching facility for all 3 positions. Power connections - self aligning, plug-in type. Control connections - sliding or plug socket type, mechanically coded, to prevent wrong insertion, continuous rating 16 amps minimum. Automatic safety shutters to prevent accidental contact with live parts when the breaker is withdrawn. 1.1.1.4 Safety Interlocks It shall not be possible to close the breaker in any intermediate position other than the 3 fixed positions. With the breaker closed, it shall not be possible to rack it in from any of the 3 position to another. Mechanical stopper to prevent accidental falling while withdrawing. It shall not be possible to rack in the breaker from isolated to 'test' position with the door open together with provision for defeat of this interlocking, however, it shall be possible to close the door only when the breaker is brought back to 'isolated' position. It shall be possible to open the door only when _ breaker is OFF and _ is in 'Isolated' position. Remote closing of breaker is not permitted with door open. Insertion of breaker into 'Service' position shall not be possible if the shutters are not free. 1.1.1.5 Internal Control Wiring Control wiring by 1100V grade PVC insulated, single core copper conductor of minimum cross section 2.5 sq. mm Flexible wires, protected against mechanical damage for wiring to door-mounted devices. Wires identified at each end in accordance with schematic diagrams by interlocked type ferrules. Colour code for control wiring : AC black Earth wire - Green DC light grey Trip circuit - Red All connections external to a feeder, all the auxiliary contacts of the LT breaker, and all spare contacts of the relays shall be wired on to the terminal blocks. Interconnection between panels of adjacent shipping sections to be brought

out to a separate terminal block, wires for interconnection properly labeled, looped and bunched inside the panel for connection at site. Not more than two connections shall be carried out on one terminal. External Terminations 1.1.1.5 Control Terminations 1100V grade multiway terminal blocks of non-tracking moulded plastic complete with insulated barriers, stud type terminals, washers, nuts and lock nuts and identification strips. Power and control terminals segregated. Control terminals of minimum rating 10 amps suitable to receive 2.5 sq. mm copper conductor. 20% spare terminals in each control terminal block. 1.1.1.6 Power Terminations Suitable for accepting cables/bus trunking as specified in the technical particulars.(120sq. mm ALUMINIUM XLPE GROUNDED cable) 1.1.1.7 Indicating/measuring Instruments Size Incomer and sectionalizer 96 sq. mm Outgoing 96 sq. mm Flush mounting : in front of the cubicle Accuracy class - 1.0 TOD type energy meter is needed,make SECURE/CONZERV/SATEC etc. 1.1.1.8 Protective Devices All control circuits shall be individually fed by MCBs with built in thermal and magnetic releases. HRC fuses shall be provided for protection of spring charged motors of electrically operated breakers. This breaker is needed for protection of 660 KVA induction furnace duty transformer:6.6 kv/575volt.So 1E/F,2O/C relay (numerical/eletromechanical)(AREVA/ESAN REYROLL/EE/ABB/ASHIDA etc)along with Master Trip Relay, Trip circuit supervision Relay, AC/DC Voltage Supervision Relay, Transformer oil and winding temperature, Buch, alarm/trip,oil level alarm is needed. All spare contacts wired upto terminal block of the panels a) Protective relays - with drawable type,if not numerical b) auxiliary, timer relays - fixed type 1.1.1.9 Contactors

Contactors shall break without damage 8 times rated current upto 100 amp rating and 6 times rated current for above 100 amp rating. Continuous current shall not exceed 2 amp and initial pick up shall be limited to 9 amp. Class of insulation shall be E or better. Drop out voltage shall be 45-65% of rated voltage and pick up shall be 85-110% contactor duty shall be AC3 unless otherwise specified in design parameters.