Industrial applications
www.bloksma.net
Industrial applications
Single tube
Double tube
Applications - Transformer Oil coolers - Oil coolers where environmental or mechanical damage should be avoided under all circumstances - Process Coolers Principle The principle of the Double Tube cooler is fairly simple. The single wall between the 2 fluids is replaced by 2 walls with an intermediate circuit. Any damage in one of the tube walls will result in a filling of the intermediate circuit. This filling is detected and results in an alarm signal.
As alternative for the Double Tube cooler the use of a secondary circuit could be considered. This alternative however needs a second heat exchanger. This secondary circuit needs conditioned cooling water, extra pumps, piping valves etc. The required heat exchangers are larger due to an adverse LMTD (Logarithmic Mean Temperature Difference) and, as a consequence, more expensive as well as in investment as operation. All design options used for single tube heat exchangers are also possible with the double tube construction, so different material combinations and cooler constructions are possible, depending on the fluids used.
Industrial applications
Construction To realize this principle of 2 walls with an intermediate circuit, an inner and an outer tube are assembled into one physical tube. The outer tube is on the inside provided with longitudinal leak detection grooves. The inner tubes are mechanical bonded over the full length against the outer tube to ensure a perfect metallic contact. Also 2 tube sheets on each side are used instead of one. The grooves are in open connection with the space between the two tube sheets. In case of oil as primary fluid, an increased efficiency is obtained by using externally finned outer tubes, resulting in a compact design. The materials of the tubes can be different. The outer tube is preferably made of copper. In case contact between copper and cooling medium is not allowed it will be possible to provide the tubes with a tin (Sn) layer. It is obvious that the thermal calculation is also based on the material-choice of the tubes. The construction of the Double Tube cooler does not require specific measures for the cooling system, such as a minimum operating pressure. Detection. To detect any fluid in the intermediate space, leakdetection equipment is required. A special connection between the 2 tubeplates is provided for mounting the leakage detector. The principle of the leakage detector is based on a change in capacity between 2 conductors. A switch, which is connected to the alarm system, is activated. This leakage detector is normally included in the supply.
Industrial applications
Bloksma-Fryer, France Bloksma-Asia, Singapore Bloksma International, The Netherlands Bloksma worldwide agent network
For additional information visit our website: Bloksma designs and manufactures its products to the highest standards to ensure a long operational lifetime and durability. If required, the products can be quality assured by all main certification authorities. Bloksma provides a complete after sales service from supply of spare parts to inspection, maintenance and repair.
www.bloksma.net