DATA U1

GENERAL LINE-UP..............................................................................................................................

GENERAL LINE-UP ..................................................................................................................................................... OD-1


R2 SERIES....................................................................................................................................................................R2-1

Y SERIES ............................................................................................................................................. Y - 1

Y SERIES ........................................................................................................................................................................Y- 1
Optional
parts for
PUHY-P-TGMU, PURY-P-TGMU ..................................................................................................... OP-1
R2 SERIES
...........................................................................................................................................
R2 - 1

Optional parts for PUHY, PURY-P-TGMU ............................................................................................ Op -1

OUTDOOR UNITS

OD-1

OUTDOOR UNITS

CITY MULTITM
OUTDOOR UNITS

OUTDOOR UNITS

OUTDOOR UNITS

OD-2

R2 SERIES
R2-SERIES

DATA U1

OUTDOOR UNITS
I.R2 SERIES

1. SPECIFICATIONS................................................................................................................................................ R2- 3
1. SPECIFICATIONS..................................................................................................................................................R2-3
2. EXTERNAL DIMENSIONS ................................................................................................................................... R2- 8
2. EXTERNAL DIMENSIONS.....................................................................................................................................R2-5
3. ELECTRICAL WIRING DIAGRAMS ..................................................................................................................... R2- 14
3. ELECTRICAL WIRING DIAGRAMS.......................................................................................................................R2-7
SOUNDLEVELS....................................................................................................................................................R2-8
LEVELS .................................................................................................................................................. R2- 16
4. 4. SOUND

OUTDOOR UNITS

R2-1

R2

5. 5. REFRIGERANT
DIAGRAMS
AND
THERMAL
SENSORS.....................................................................R2-9
REFRIGERANTCIRCUIT
CIRCUIT
DIAGRAMS
AND
THERMAL
SENSORS................................................................... R2- 18
6. 6. CAPACITY
TABLES..............................................................................................................................................R2-10
CAPACITY TABLES ............................................................................................................................................. R2- 20
6-1.
byby
temperature
............................................................................................................................R2-10
6-1.Correction
Correction
temperature
............................................................................................................................ R2- 20
6-2.
Correction
by
total
indoor
..............................................................................................................................R2-12
6-2. Correction by total indoor.............................................................................................................................. R2- 23
6-3.
byby
refrigerant
piping
length
..........................................................................................................R2-14
6-3.Correction
Correction
refrigerant
piping
length..........................................................................................................
R2- 29
6-4.Correction
Correction
frosting
and
defrosting.............................................................................................................
R2- 30
6-4.
at at
frosting
and
defrosting
.............................................................................................................R2-15
6-5.Temp.
Temp.
range
of running
................................................................................................................................ R2- 30
6-5.
range
of running
.................................................................................................................................R2-15

DATA U1
I.R2 SERIES

CITY MULTI

R2 SERIES

R2

OUTDOOR UNITS

Outdoor unit
To BC controller (Sub-unit) (3-pipe)
Meeting room
(Cooling)

BC controller Main-unit

Office
(Cooling)

Refrigerant piping: 2-pipe type

OA room
(Cooling)

Meeting room
(Heating)
Indoor unit

Office (Heating)

Office
compartment
(Heating)

Heat recovery: PURY-P-TGMU-A(-BS)

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P72

P96

P108

P126

P144

P168

P192

P204

P216

P234

8HP
72,000
80,000

10HP
96,000
108,000

12HP
108,000
120,000

14HP
126,000
140,000

16HP
144,000
160,000

18HP
168,000
188,000

20HP
192,000
216,000

22HP
204,000
228,000

24HP
216,000
248,000

26HP
234,000
268,000

R2 Heat recovery

* Nominal conditions *1, *2 are referable at the Specification sheet.

OUTDOOR UNITS

R2-2

1. SPECIFICATIONS

DATA U1

1. SPECIFICATIONS

Model

PURY-P72TGMU-A(-BS)

Power source

PURY-P96TGMU-A(-BS)
3-phase 3-wire 208-230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW

72,000
21.1

28.1

Power input

kW

6.48

8.67

Current input(208-230)

19.9-18.0

26.7-24.1

COP (kW / kW)


Temp. range of

Indoor

cooling

Outdoor

96,000

3.25

3.24
59 to 75 degFW.B. (15 to 24 degCW.B.)
23 to 109 degFD.B. (-5 to 43 degCD.B.)

32 to 109 degFD.B. ( 0 to 43degCD.B. ) Outdoor unit below Indoor unit


*2 BTU / h

(Nominal)

*2 kW

80,000
23.4

31.7

Power input

kW

6.33

8.56

Current input(208-230)

19.5-17.6

26.4-23.8

COP (kW / kW)


Temp. range of

Indoor

heating

Outdoor

Indoor unit

Total capacity

connectable

Model / Quantity

3.70
-4 to 60 degFW.B. (-20 to 15.5 degCW.B.)

Liquid (High press.)

refrigerant pipe
(O.D.)

3.69
59 to 81 degFD.B. (15 to 27 degCD.B.)

Noise level (measured in anechoic room)


Diameter of

108,000

R2

Heating capacity

Gas (Low press.)

50-150% of outdoor unit capacity

50-150% of outdoor unit capacity

P06-P96 / 1-15

P06-P96 / 1-19

dB <A>
in. (mm)

56

57

5/8 (15.88) Brazed + Flare

3/4 (19.05) Brazed + Flare

3/4 (19.05) Brazed

7/8 (22.2) Brazed

in. (mm)

External finish

Pre-coated galvanized sheets(+powder coating for -BS type)


<MUNSELL 5Y 8/1 or similar>

External dimension H x W x D

in.
mm

Net weight

72-15/32 x 39 x 33-3/32

72-15/32 x 39 x 33-3/32

1,840 x 990 x 840

1,840 x 990 x 840

lbs(kg)

Heat exchanger
Compressor

536 (243)

574 (260)

Salt-resistant cross fin & copper tube

Salt-resistant cross fin & copper tube

Inverter scroll hermetic comp.

Inverter scroll hermetic comp.

Type
Manufacturer

AC&R Works,MITSUBISHI ELECTRIC CORPORATION

Starting method

Inverter
kW

4.7

6.7

Case heater

kW

0.057(230V)

0.057(230V)

MEL32

MEL32

7,050

7,050

Lubricant
FAN

Inverter

Motor output

Airflow rate

cfm
m3 / min
L/s

External static press.

in.WG(Pa)

Motor output

200

3,333

3,333

0 (0)

0 (0)

Propeller fan x 1

Propeller fan x 1

Inverter-control , Direct-driven

Inverter-control , Direct-driven

Type x Quantity
Control, Driving mechanism

200

kW

0.38 x 1

0.38 x 1

HIC circuit (HIC: Heat Inter-Changer)


Protection

High pressure protection

High pressure sensor, High pressure switch 601 psi (4.15 MPa)

Inverter circuit (COMP. , FAN)

Over-current protection,Over-heat protection

Compressor

Over-heat protection

Fan motor

Thermal switch

Defrosting method
Refrigerant

Auto-defrost mode (Reversed refrigerant circle)


Type x Original charge

Drawing

lbs + oz (kg)

R410A x (23 lbs + 3 oz) (10.5kg)

R410A x (28 lbs + 11 oz) (13.0kg)

Control

indoor LEV and BC controller

External

W659655

Wiring

W274647

Refrigerant cycle

Standard

Document

Installation Manual

Installation Manual

attachment

Accessory

Details refer to External Drw W659655

Details refer to External Drw W659655

Optional parts

High static pressure motor : PAC-KBU04MT-U-F


Joint : CMY-Y102S-G,CMY-R160-J
BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G
Main BC controller:CMB-P108,1010,1013,1016NU-GA
Sub BC controller: CMP-P104,108NU-GB

Remark

Note :

Details on foundation work,duct work,insulation work,electrical wiring,power source switch,and other items shall be referred to the Installation Manual.

*1 Nominal cooling conditions


Indoor : 80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PURY-P72-96TGMU

OUTDOOR UNITS

R2-3

1. SPECIFICATIONS

DATA U1

Model

PURY-P108TGMU-A(-BS)

Power source

PURY-P126TGMU-A(-BS)
3-phase 3-wire 208-230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW

108,000
31.7

36.9

Power input

kW

9.73

11.36

Current input(208-230)

30.0-27.1

35.0-31.6

COP (kW / kW)


Temp. range of

Indoor

cooling

Outdoor

126,000

3.25

3.24
59 to 75 degFW.B. (15 to 24 degCW.B.)
23 to 109 degFD.B. (-5 to 43 degCD.B.)

32 to 109 degFD.B. ( 0 to 43degCD.B. ) Outdoor unit below Indoor unit


*2 BTU / h

(Nominal)

*2 kW

35.2

41.0

Power input

kW

9.92

11.67

Current input(208-230)

30.6-27.6

36.0-32.5

R2

Heating capacity

120,000

COP (kW / kW)


Temp. range of

Indoor

heating

Outdoor

Indoor unit

Total capacity

connectable

Model / Quantity

3.51
-4 to 60 degFW.B. (-20 to 15.5 degCW.B.)

Liquid (High press.)

refrigerant pipe
(O.D.)

3.54
59 to 81 degFD.B. (15 to 27 degCD.B.)

Noise level (measured in anechoic room)


Diameter of

140,000

Gas (Low press.)

50-150% of outdoor unit capacity

50-150% of outdoor unit capacity

P06-P96 / 1-20

P06-P96 / 1-20

dB <A>
in. (mm)

60

61

3/4 (19.05) Brazed + Flare

3/4 (19.05) Brazed

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

in. (mm)

External finish

Pre-coated galvanized sheets(+powder coating for -BS type)


<MUNSELL 5Y 8/1 or similar>

External dimension H x W x D
Net weight

in.

72-15/32 x 39 x 33-3/32

72-15/32 x 50-13/16 x 33-3/32

mm

1,840 x 990 x 840

1,840 x 1,290 x 840

lbs(kg)

Heat exchanger
Compressor

574 (260)

672 (304)

Salt-resistant cross fin & copper tube

Salt-resistant cross fin & copper tube

Inverter scroll hermetic comp.

Inverter scroll hermetic comp.

Type
Manufacturer

AC&R Works,MITSUBISHI ELECTRIC CORPORATION

Starting method

Inverter
kW

8.0

8.5

Case heater

kW

0.057(230V)

0.057(230V)

MEL32

MEL32

7,050

8,450

Lubricant
FAN

Inverter

Motor output

Airflow rate

cfm
m3 / min
L/s

External static press.

in.WG(Pa)

Motor output

240

3,333

4,000

0 (0)

0 (0)

Propeller fan x 1

Propeller fan x 1

Inverter-control , Direct-driven

Inverter-control , Direct-driven

Type x Quantity
Control, Driving mechanism

200

kW

0.38 x 1

0.64 x 1

HIC circuit (HIC: Heat Inter-Changer)


Protection

High pressure protection

High pressure sensor, High pressure switch 601 psi (4.15 MPa)

Inverter circuit (COMP. , FAN)

Over-current protection,Over-heat protection

Compressor

Over-heat protection

Fan motor

Thermal switch

Defrosting method
Refrigerant

Auto-defrost mode (Reversed refrigerant circle)


Type x Original charge

lbs + oz (kg)

R410A x (28 lbs + 11 oz) (13.0kg)

Control
Drawing

R410A x (36 lbs + 7 oz) (16.5kg)

indoor LEV and BC controller

External

W659655

W659656

Wiring

W274647

W274647

Standard

Document

Refrigerant cycle

Installation Manual

Installation Manual

attachment

Accessory

Details refer to External Drw W659655

Details refer to External Drw W659656

Optional parts

High static pressure motor : PAC-KBU04MT-U-F


Joint : CMY-Y102S-G,CMY-R160-J
BC controller: CMB-P104,105,106,108,1010,1013,1016NU-G
Main BC controller:CMB-P108,1010,1013,1016NU-GA
Sub BC controller: CMP-P104,108NU-GB

Remark

Note :

Details on foundation work,duct work,insulation work,electrical wiring,power source switch,and other items shall be referred to the Installation Manual.

*1 Nominal cooling conditions


Indoor : 80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PURY-P108-126TGMU

OUTDOOR UNITS

R2-4

(3-5/32)
80

(2-1/4)
57

5 (7/32)

Cross section Y-Y

(1/2) 12

Note1.Use the opening at the bottom of the unit


when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.

(Attached near the ball valve)

(Already installed on the unit)

(Packaged in the accessory kit)

<Accessories>

80

Cross section X-X

B
Model
A
P72 145(5-23/32) 115(4-17/32)
P96 135(5-11/32) 120(4-3/4)
P108 135(5-11/32) 120(4-3/4)

Conn. pipe
(High pressure)

768 (30-1/4)

(3-5/32)
Knockout hole
<Bottom piping hole>

(2-9/16) 65 160
(6-5/16)

(2-3/32)

20 (13/16)
(2-25/32) 70

Air
inlet

117

(1-15/32) (4-5/8)

37

(13/32)(3-9/16)
10 90

553 (21-25/32)

Air
inlet

37

Left side view

Top view

Knockout hole

207

67

45

(1-25/32)

(8-5/32) (2-21/32)

Front view

<Front piping
83
(3-9/32) hole>
67 207
(2-21/32)(8-5/32)

Refrig. service
valve(Low pressure) 100
<Flange>
(3-15/16)

990(39)

(35-7/16)
900(mounting pitch)

(2-21/32) 67 160(6-5/16)

Refrig. service
valve (High pressure)
<Flare>
X

Knockout hole
<Left piping hole>

(4-5/8) (1-15/32)

117

(1-19/32)
40

Service panel

Knockout hole

(1-25/32)

2X2-14(9/16)X20(13/16) 0val hole


(Mounting hole)
45

(5-11/32) <Left side hole for


135 control wiring>
(3-5/32) 80

Air outlet

<Bottom hole for control wiring>

100
(3-15/16)
134
(5-9/32)
280
(11-1/32)

78 (3-3/32)

Conn. pipe
(Low pressure)

(9-9/32)
235

840 (33-3/32)
(10-7/16)
265
1575 (62-1/32)

<Hole for power supply>

(19/32)
15

(7-1/4)
184

(21/32)
16
(33-9/32)
845(mounting pitch)
(21/32)
16
1840 (72-15/32)

attached conduit mounting plate <Accessory>

PURY-P72,96,108TGMU-A(-BS)

(7/16)11

OUTDOOR UNITS

R2

494 (19-15/32)

2. EXTERNAL DIMENSIONS

2. EXTERNAL DIMENSIONS

DATA U1

Drw. : PURY-TGMU_W659655 1/2


Unit : mm(in)

R2-5

877 (34-17/32)

OUTDOOR UNITS

2.Foundation work

<Side view>

(17-23/32) (17-23/32)
450
450

No restrictions on wall height


<left and right>

450
450
(17-23/32) (17-23/32)

[When inlet air enters from right


and left sides of unit]

Front
<Top view>

450
450
(17-23/32) (17-23/32)

In case of single installation


[Basic rules for spacing the unit]

H
H

Wall height <H>

1000
(39-3/8)

450
450
(17-23/32) (17-23/32)

Wall height <H>

Wall height <H>

* B

Wall height <H>

1000
(39-3/8)

Wall height <H>

1000
(39-3/8)

B Must be open

A Front

450
450
450
450
* 450 (17-23/32) (17-23/32)(17-23/32)(17-23/32) * 450
(17-23/32)
(17-23/32)
B

Wall height <H>

Spacing PURY-P72,96,108TGMU-A(-BS)

M10 Anchor Bolt


<Local supply>

Corner

1000
(39-3/8)
No restrictions on wall height

Wall height <H>

In case of collective installation and continuous installation

450
(17-23/32)
450
(17-23/32)
450
900
450
(17-23/32) (35-7/16) (17-23/32)

1.Space required around unit

h
H

450
(17-23/32)
(35-7/16) 900

R2

2. EXTERNAL DIMENSIONS
DATA U1

Drw. : PURY-TGMU_W659655 2/2


Unit : mm(in)

R2-6

OUTDOOR UNITS

L3

L2

L1

Ground

Power source
3~
208/230V 60Hz

Central control
transmission line

SV
4b

SV
4d

SV2

Indoor/outdoor *1
transmission line

CH11

21S
4a

SV
4a

SV
4c

SV1

63H1

M2

M1

TB7

M2

red

white

black

L1

L2

L3

1
2
3

1
2
3
4
5
6

1
2
3
4
5
6

1
2
3
4
5
6
7
8
9

L3

CN21
blue

L2

CNTYP1
red

DSA

detection
circuit

1 2 3

CN32

CN33

CN34
red

CN36

1
2 CN35
3 red

1
2 CN38
3 green

F2
AC250V
6.3A T

TB1
(Terminal Block)

Shield

M1

TB3

CN52C

1 yellow
2
X52
3

black

52C

white

F1
AC250V
6.3A T

CNL
black

3 2 1

CNH

3 2 1

1 2 3

63HS

1 2 3

63LS

red
white
black
1

2
1
0
SWU3

CNTYP4

2 1

R22

ZNR4 C5

black

red

LD2

FN1

R1

52C

NF
(Noise Filter)

CNS2
blue

CNS1
blue

FN2

FN3

Unit address setting

SWU2 SWU1

Function setting

*2

10
10
10
10
SW5 SW4 SW3 SW2 SW1

LD1

Function
setting

10

DS
(Diode stack)

L1

CN20

CN01

2 1

TH11

red
white
black

Control circuit board

ZNR1~4

1 2 3 4 5

X01

X03

X04

X05

X06

X07

X08

X09

CN02

8 7 6 5 4 3 2 1

red

21

green
black

Inverter controller box

red

TH7 TH6 TH5

R23

FN4

DCL

CN41

C1

6
7
8

1
2
3

CNVCC1 45

5
6
7

1
2
3

CNRS3B 4

1 2 3 4

FN5

5
6
7

1
2
3

CNAC3 2
black
3

CN40

1
2
3
4
5

CN51

CN3S
red

CNRS3A 4

12V

3
2
1

CN3D 21

1 2 3 4

CNTYP5

3 2 1

black

Z20

SNOW

1 2 3 4

black
DCCT

red
C4

T
(Transformer)

P
4
3
2
1

ACCT

F01
AC250V 3.15A T

IPM

ACCT-U

THHS5

1 2 3 CNVDC

AC250V
15A T
F01

red

CNCT2
blue

1
2
3
4
5
6
7
8
9
10
11
12
13
14

CN15V2

CNDR2

CNDC2
yellow

1
2
3
4
5
6
7
8
9
10
11
12
13
14

1
2
3

1
2
3
4

1
2
3
4
5
6
7
8
9

6
5
4
3
2
1

1
2
3
4
5
6
7
8
9

1
2
3

CNDC1
yellow

ACCT-W

black

CN15V1

SW2

CNINV

Function
setting

white

CNDR1

CNTH
green
1 2

LED1 operation
LED2 error

FAN control board

or STEP DEMAND
*2

Gate amp board

CNDC2

1
2 CNTR
3

1
2
3
4 CNRS2
5
6
7

Compressor ON/OFF
NIGHT MODE

Compressor ON/OFF
Trouble

*1

1 2 3 4

F01
AC250C
2A T
CNCT

G L3 L1

CNAC2 1 2 3 4 5

SW1

1
SW2

THHS1

CNL2
1 2

CNTH
green
1 2

L2

Function setting

LED1 operation
LED2 error
LED3 charge

L1

1 2

CNL1

Power circuit board

CNRS1

CNVCC1

R2

1 2

CN30V
red

X01

3
2
1

CNFAN
red

CNFG 1
blue 2

1234567

12345678

*3

MF1

CN04

MF

MC

Motor
(Compressor)

Fan motor
(Heat exchanger)

Ground terminal

Solenoid valve
(Heat exchanger capacity control)
Thermistor Discharge pipe temp. detect
Pipe temp.detect(Hex outlet)
OA temp. detect
liquid outlet temp.detect
at Sub-cool coil
Radiator panel temp. detect
High pressure switch
High pressure sensor
Low pressure sensor
Choke coil(Transmission)
Function device

ON

OFF
SHORT

P126/144

Model
P72/96/108

75%
50%

SHORT
100%
0%

OPEN

<Difference of appliance>
:exist X:not exist

SHORT

CN3D 1-2P
CN3D 1-3P
OPEN

*3

OFF

ON

SW4-7:ON (STEP DEMAND)

MODE

SHORT

ON/OFF

1-3P

NIGHT
1-2P
OPEN

Compressor

CN3D
OPEN

CN3D

SW4-7:OFF (Compressor ON/OFF and NIGHT MODE)

*2 Function according to switch operation.


(SW4-7,CN3D 1-2P,and CN3D 1-3P)

*1 The broken lines indicate field wiring.

,G

THHS1,5
63H1
63HS
63LS
L1,L2
Z20

TH7

TH11
TH5
TH6

SV4a~d

Solenoid valve
(Discharge-suction bypass)

Relay(Inverter main circuit)


Motor Fan Radiator panel
Crank case heater(Compressor)
4-way valve

SV1,2

DC reactor
(Power factor improvement)

52C
MF1
CH11
21S4a

Name
Terminal block
AC Current Sensor
DC Current Sensor

DCL

Symbol
TB1,3,7
ACCT
DCCT

PURY-P72,96,108,126,144TGMU-A(-BS)
PURY-P72,96,108TGMU-A(-BS)

R2

red

<Symbol explanation>

3. ELECTRICAL WIRING DIAGRAMS

3. ELECTRICAL WIRING DIAGRAMS

DATA U1

Drw. :PURY-TGMU_W274647

R2-7

4. SOUND LEVELS

DATA U1

4. SOUND LEVELS

Measurement condition
PURY-P72,96,108TGMU-A(-BS)
PURY-P72,96,108,126,144TGMU-A(-BS)

Sound level of PURY-P108TGMU-A(-BS)


Stand 60Hz
Night 60Hz

Octave band sound level (dB)

80

3-1/4ft.
(1m)

R2

Ref.:NC_PURY-P108TGMU_WYNB0-4273

90

3-1/4ft.
(1m)

Measurement
location

70

NC-70

60

NC-60

50

NC-50

40

NC-40

30

NC-30
Approximate minimum
audible limit on
continuous noise

20

NC-20

10
63

125

250

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Night Mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
63.0 64.0 57.5 55.0 50.5 50.5 54.0 50.0 60.0
64.0 55.0 48.5 46.5 42.5 43.0 41.5 40.0 51.0

When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PURY-P72TGMU-A(-BS)

Ref.:NC_PURY-P72TGMU_WYNB0-4271

Soundlevel
levelof
ofPURY-P96TGMU-A(-BS)
PURY-P126TGMU-A(-BS)
Sound

90

Stand 60Hz
60Hz
Stand

Night 60Hz

70

NC-70

60

NC-60

50

NC-50

40

NC-40

30

NC-30
Approximate minimum
audible limit on
continuous noise

20

125

250

70
70

1k

2k

4k

NC-60
NC-60

50
50

NC-50
NC-50

40
40

NC-40
NC-40

30
30
20
20

500

NC-70
NC-70

60
60

NC-20

10
63

Night 60Hz
60Hz
Night

80
80
Octave
Octave band
band sound
sound level
level (dB)
(dB)

80
Octave band sound level (dB)

Ref.:NC_PURY-P126TGMU_WYNB0-4274
Ref.:NC_PURY-P96TGMU_WYNB0-4272

90
90
Stand 60Hz

NC-30
NC-30
Approximateminimum
minimum
Approximate
audiblelimit
limiton
on
audible
continuousnoise
noise
continuous

10
10
63
63

8k

125
125

Octave band central frequency (Hz)

Standard
60Hz
Night Mode 60Hz

250
250

NC-20
NC-20
500
500

1k
1k

2k
2k

4k
4k

8k
8k

Octaveband
bandcentral
centralfrequency
frequency(Hz)
(Hz)
Octave

63 125 250 500


1k
2k
4k
8k dB(A)
61.5 57.5 54.5 52.5 49.0 48.0 48.0 42.5 56.0
61.0 54.5 50.0 46.0 41.5 39.5 37.0 38.0 49.0

When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Standard 60Hz
60Hz
Standard
NightMode
Mode 60Hz
60Hz
Night

63 125
125 250
250 500
500 1k
1k 2k
2k 4k
4k 8k
8k dB(A)
dB(A)
63
67.5 58.5
68.5 55.5
60.5 53.0
58.5 49.5
54.5 49.0
50.5 49.0
48.0 43.0
42.5 57.0
61.0
62.5
64.0 56.5
55.0 50.0
48.5 45.5
46.5 41.0
44.5 38.5
45.0 38.0
43.5 39.0
42.0 49.0
52.0
60.0

WhenNight
NightMode
Modeisisset,the
set,theA/C
A/Csystem's
system'scapacity
capacityisislimited.
limited.The
Thesystem
systemcould
couldreturn
returntotonormal
normaloperation
operationfrom
from
When
NightMode
Modeautomatically
automaticallyininthe
thecase
casethat
thatthe
theoperation
operationcondition
conditionisissevere.
severe.
Night

OUTDOOR UNITS

R2-8

CJ1

OUTDOOR UNITS

Comp1

TH11

O/S

63H1

ST6

63HS

ST5

SV1

CP1

SV2

ST11 ST10

Acc

CV9a

SV4d

ST17

TH7

SV4c

Check Valves Block

CV10a

HEXf1

HEXf2

HEXf3

SV4b

ST16

HEXb1

ST15

CV8a

TH6

ST14

63LS

Fusible
plug

CJ2

SV4a

Solenoid Valves Block

Orifice

CV5a
CV4a
CV6a

CV7a

CV2a

CV3a

TH5

ST1

BV2

BV1

PURY-P72,96,108,126,144TGMU-A(-BS)
PURY-P72,96,108TGMU-A(-BS)

R2

21S4a

5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

DATA U1

Drw. : RC_PURY-P72-144TGMU

R2-9

6. CAPACITY TABLES

DATA U1

6-1. Correction by temperature

6. CAPACITY TABLES

CITY MULTITM could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value
and the ratio below , the capacity can be observed at various temperature.

P72TGMU P96TGMU
28.1

72,000

96,000

6.48

8.67

R2

21.1

1.3

Indoor Temperature

1.2
Ratio of cooling capacity

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

1.1

24CWB
75.2FWB

1.0

22CWB
71.6FWB

0.9

20CWB
68FWB
18CWB
64.4FWB

0.8

16CWB
60.8FWB

0.7

15CWB
59FWB

0.6

Ratio of power input

1.3

24CWB
75.2FWB

1.2

22CWB
71.6FWB

1.1

20CWB
68FWB
18CWB
64.4FWB

1.0

16CWB
60.8FWB

0.9

15CWB
59FWB

0.8
0.7

-5
23

P72TGMU P96TGMU
31.7

80,000

108,000

6.33

8.56

5
41

10
15
20
25
30
50
59
68
77
86
Ratio of cooling capacity and power input

35
95

40
45 CDB
104
113 FDB
Outdoor temperature

1.4
1.3
Ratio of heating capacity

23.4

1.2
15CDB
59FDB

1.1

21.1CDB
70FDB

1.0
0.9

25CDB
77FDB

0.8
27CDB
80FDB

0.7
0.6

Indoor Temperature

1.1
Ratio of power input

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

0
32

1.0

15CDB
59FDB

0.9
21.1CDB
70FDB

0.8
25CDB
77FDB

0.7

27CDB
80FDB

0.6
0.5
-20
-4

-15
5

-10
-5
0
5
14
23
32
41
Ratio of heating capacity and power input

10
15 CWB
50
59 FWB
Outdoor temperature
Ref:CbT_PURY-P72-96TGMU

OUTDOOR UNITS

R2-10

6. CAPACITY TABLES

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

P108TGMU P126TGMU
31.7

36.9

108,000

126,000

9.73

11.36

P144TGMU
42.2
144,000
14.20

1.4

Indoor Temperature

1.3
Ratio of cooling capacity

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U1

1.2

24CWB
75.2FWB

1.1

22CWB
71.6FWB

1.0

20CWB
68FWB
18CWB
64.4FWB

0.9

15CWB
59FWB

1.3

Ratio of power input

1.2

24CWB
75.2FWB

1.1

22CWB
71.6FWB

1.0

20CWB
68FWB
18CWB
64.4FWB

0.9

16CWB
60.8FWB

0.8

15CWB
59FWB

0.7
0.6

-5
23

35.2

41.0

120,000

140,000

9.92

11.67

P144TGMU
46.9
160,000
13.67

5
41

10
15
20
25
30
50
59
68
77
86
Ratio of cooling capacity and power input

35
95

40
45 CDB
104
113 FDB
Outdoor temperature

1.3
1.2
Ratio of heating capacity

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

P108TGMU P126TGMU

15CDB
59FDB

1.1

21.1CDB
70FDB

1.0
0.9

25CDB
77FDB

0.8
27CDB
80FDB

0.7
0.6

Indoor Temperature

1.1
1.0
Ratio of power input

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

0
32

0.9

15CDB
59FDB

0.8
21.1CDB
70FDB

0.7
25CDB
77FDB

0.6

27CDB
80FDB

0.5
0.4
-20
-4

-15
5

-10
-5
0
5
14
23
32
41
Ratio of heating capacity and power input

10
15 CWB
50
59 FWB
Outdoor temperature
Ref:CbT_PURY-P108-144TGMU

OUTDOOR UNITS

R2-11

R2

16CWB
60.8FWB

0.8

6. CAPACITY TABLES

DATA U1

6-2. Correction by total indoor


CITY MULTITM system has different capacity and input at different total capacity of indoor unit connected. Using following tables,
the maximum capacity can be observed so as to ensure the system having enough capacity.

PURY-P72,96TGMU
50.0

Capacity(kW)

30.0

20.0

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PURY-P72-96TGMU

PURY-P108TGMU
PURY-P108,126TGMU
50.0

Capacity(kW)

40.0

30.0

20.0

10.0

10.0

Input(kW)

R2

40.0

5.0

P108

P126
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PURY-P108-126TGMU

OUTDOOR UNITS

R2-12

6. CAPACITY TABLES

DATA U1

170,000
160,000
150,000
140,000
130,000
120,000
110,000
100,000
90,000
80,000
70,000
60,000
50,000
40,000
30,000
20,000

R2

Capacity(BTU/h)

PURY-P72,96TGMU

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PURY-P72-96TGMU

Capacity(BTU/h)

PURY-P108TGMU
PURY-P108,126TGMU
170,000
160,000
150,000
140,000
130,000
120,000
110,000
100,000
90,000
80,000
70,000
60,000
50,000

Input(kW)

10.0

5.0

P108

P126
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PURY-P108-126TGMU

OUTDOOR UNITS

R2-13

6. CAPACITY TABLES

DATA U1

6-3. Correction by refrigerant piping length


CITY MULTITMsystem can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
2-3-1 and 2-3-2, the capacity can be observed. 2-3-3 shows how to obtain the equivalent length of piping.

6-3-1. Heating capacity correction


PURY-P-TGMU
Heating capacity correction factor

R2

1.00

0.95

0.90

20
66

40
131

60
80
100 120
197
263
328 394
Piping equivalent length

140
459

160
525

m
ft.

Ref.: CbRPL_PURY-P72-234TGMU_H

6-3-2. How to obtain the equivalent length of piping


1

PUHY, PURY-P72TGMU
Equivalent length = (Actual piping length to the farthest indoor unit)

PUHY, PURY-P96,108TGMU
Equivalent length = (Actual piping length to the farthest indoor unit)

+ (0.42 x number of bent on the piping) m


+ (1.38 x number of bent on the piping) ft.

PUHY, PURY-P126TGMU
Equivalent length = (Actual piping length to the farthest indoor unit)

+ (0.35 x number of bent on the piping) m


+ (1.15 x number of bent on the piping) ft.

+ (0.47 x number of bent on the piping) m


+ (1.54 x number of bent on the piping) ft.

PUHY, PURY-P144,168,192,204,216,234TGMU
Equivalent length = (Actual piping length to the farthest indoor unit)

+ (0.50 x number of bent on the piping) m


+ (1.64 x number of bent on the piping) ft.

OUTDOOR UNITS

Ref.: EPL_TGMU

R2-14

6. CAPACITY TABLES

DATA U1

6-4. Correction at frosting and defrosting


Due to frosting at the outdoor heat exchanger and the automatical defrosting operation, the heating capacity of the outdoor unit
should be considered by multiplying the correction factor which shown in the table below.
Table
Table of
of correction
correction factor
factor at
at frosting
frosting and
and defrosting
defrosting
Outdoor
CWB
Outdoor inlet
inlet air
air temp.
temp. CWB

66

44

22

11

00

-2
-2

-4
-4

-6
-6

-8
-8

-10
-10

39
39

36
36

34
34

32
32

28
28

25
25

21
21

18
18

14
14

1.00
1.00

0.95
0.95

0.84
0.84

0.83
0.83

0.83
0.83

0.87
0.87

0.90
0.90

0.95
0.95

0.95
0.95

0.95
0.95

PUHY,PURY-P108TGMU
PUHY,PURY-P108TGMU

1.00
1.00

0.93
0.93

0.82
0.82

0.80
0.80

0.82
0.82

0.86
0.86

0.90
0.90

0.90
0.90

0.95
0.95

0.95
0.95

PUHY,PURY-P126,144TGMU

1.00

0.95

0.90

0.87

0.88

0.89

0.90

0.95

0.95

PUHY,PURY-P168,192TGMU

1.00

0.98

0.89

0.86

0.89

0.90

0.92

0.95

0.95

0.95

PUHY,PURY-P204TGMU

1.00

0.94

0.87

0.86

0.87

0.88

0.90

0.90

0.93

0.93

PUHY,PURY-P216,234TGMU

1.00

0.94

0.84

0.86

0.87

0.88

0.90

0.90

0.93

0.95

Ref.: CaF_TGMU

0.93
Ref.: CaF_TGMU

6-5. Temp. range of running


Cooling

Indoor temperature

FWBCWB
86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

25
77

30
86

35
95

40
104

45
113

50
122

CDB
FDB

25
77

30
86

35
95

40
104

45
113

50
122

CWB
FWB

Outdoor temperature

Heating

Indoor temperature

FDB CDB
86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

Outdoor temperature
Ref.: tr-ygm-r2

OUTDOOR UNITS

R2-15

R2

43
43

PUHY,PURY-P72,96TGMU
PUHY,PURY-P72,96TGMU

Outdoor
FWB
Outdoor inlet
inlet air
air temp.
temp. FWB

R2

OUTDOOR UNITS

R2-16

Y SERIES
Y-SERIES

DATA U1

OUTDOOR UNITS
I.Y SERIES

1. SPECIFICATIONS.................................................................................................................................................. Y- 3
1. SPECIFICATIONS.....................................................................................................................................................Y-3
2. EXTERNAL DIMENSIONS ..................................................................................................................................... Y- 8
2. EXTERNAL DIMENSIONS........................................................................................................................................Y-5
3. ELECTRICAL WIRING DIAGRAMS ....................................................................................................................... Y-14
3. ELECTRICAL WIRING DIAGRAMS..........................................................................................................................Y-7
SOUNDLEVELS.......................................................................................................................................................Y-8
LEVELS .................................................................................................................................................... Y-16
4. 4. SOUND
5. 5. REFRIGERANT
DIAGRAMS
AND
THERMAL
SENSORS........................................................................Y-9
REFRIGERANTCIRCUIT
CIRCUIT
DIAGRAMS
AND
THERMAL
SENSORS..................................................................... Y-18
6. 6. CAPACITY
TABLES.................................................................................................................................................Y-10
CAPACITY TABLES ............................................................................................................................................... Y-21
6-1.
byby
temperature
...............................................................................................................................Y-10
6-1.Correction
Correction
temperature
.............................................................................................................................. Y-21
6-2.
Correction
by
total
indoor
.................................................................................................................................Y-12
6-2. Correction by total indoor................................................................................................................................ Y-24
6-3.
byby
refrigerant
piping
length
.............................................................................................................Y-14Y-30
6-3.Correction
Correction
refrigerant
piping
length............................................................................................................
6-4.Correction
Correction
frosting
and
defrosting...............................................................................................................
6-4.
at at
frosting
and
defrosting
................................................................................................................Y-15Y-32
6-5.Temp.
Temp.
range
of running
.................................................................................................................................. Y-32
6-5.
range
of running
....................................................................................................................................Y-15

OUTDOOR UNITS

Y-1

DATA U1
I.Y SERIES

CITY MULTI

Y- SERIES

OUTDOOR UNITS

Header
Joint
Indoor unit

Outdoor unit

Indoor unit

Indoor unit

Heat pump: PUHY-P-TGMU-A(-BS)

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P72

P96

P108

P126

P144

P168

P192

P204

P216

P234

8HP
72,000
80,000

10HP
96,000
108,000

12HP
108,000
120,000

14HP
126,000
140,000

16HP
144,000
160,000

18HP
168,000
188,000

20HP
192,000
216,000

22HP
204,000
228,000

24HP
216,000
248,000

26HP
234,000
268,000

Y Heat pump

* Nominal conditions *1, *2 are referable at the Specification sheet.

OUTDOOR UNITS

Y-2

1. SPECIFICATIONS

DATA U1

1. SPECIFICATIONS

Model

PUHY-P72TGMU-A(-BS)

PUHY-P96TGMU-A(-BS)

Power source

3-phase 3-wire 208-230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW

72,000
21.1

28.1

Power input

kW

6.48

8.67

Current input(208-230)

19.9-18.0

26.7-24.1

COP (kW / kW)


Temp. range of

Indoor

cooling

Outdoor

96,000

3.25

3.24
59 to 75 degFW.B. (15 to 24 degCW.B.)
23 to 109 degFD.B. (-5 to 43 degCD.B.)

32 to 109 degFD.B. ( 0 to 43degCD.B. ) Outdoor unit below Indoor unit


Heating capacity

*2 BTU / h

(Nominal)

*2 kW

80,000
23.4

31.7

Power input

kW

6.33

8.56

Current input(208-230)

19.5-17.6

26.4-23.8

COP (kW / kW)


Temp. range of

Indoor

heating

Outdoor

Indoor unit

Total capacity

connectable

Model / Quantity

3.70
-4 to 60 degFW.B. (-20 to 15.5 degCW.B.)

Liquid (High press.)


Gas (Low press.)

50-130% of outdoor unit capacity

50-130% of outdoor unit capacity

P06-P96 / 1-13

P06-P96 / 1-16

dB <A>
in. (mm)

56

57

3/8 (9.52) Flare

3/8 (9.52) Flare

refrigerant pipe
(O.D.)

3.69
59 to 81 degFD.B. (15 to 27 degCD.B.)

Noise level (measured in anechoic room)


Diameter of

108,000

(1/2 (12.7) total length>=295ft.(90m))

in. (mm)

3/4 (19.05) Brazed + Flare

External finish

7/8 (22.2) Brazed

Pre-coated galvanized sheets(+powder coating for -BS type)


<MUNSELL 5Y 8/1 or similar>

External dimension H x W x D

in.
mm

Net weight

72-15/32 x 39 x 33-3/32

72-15/32 x 39 x 33-3/32

1,840 x 990 x 840

1,840 x 990 x 840

lbs(kg)

Heat exchanger
Compressor

490 (222)

524 (237)

Salt-resistant cross fin & copper tube

Salt-resistant cross fin & copper tube

Inverter scroll hermetic comp.

Inverter scroll hermetic comp.

Type
Manufacturer

AC&R Works,MITSUBISHI ELECTRIC CORPORATION

Starting method

Inverter
kW

4.7

6.7

Case heater

kW

0.057(230V)

0.057(230V)

MEL32

MEL32

7,050

7,050

Lubricant
FAN

Inverter

Motor output

Airflow rate

cfm
m3 / min
L/s

External static press.

in.WG(Pa)

Control, Driving mechanism

200

3,333

3,333

0 (0)

0 (0)

Propeller fan x 1

Propeller fan x 1

Inverter-control , Direct-driven

Inverter-control , Direct-driven

0.38 x 1

0.38 x 1

Type x Quantity
Motor output

200

kW

HIC circuit (HIC: Heat Inter-Changer)


Protection

Copper pipe,pipe-in-pipe structure

High pressure protection

High pressure sensor, High pressure switch 601 psi (4.15 MPa)

Inverter circuit (COMP., FAN)

Over-current protection,Over-heat protection

Compressor

Over-heat protection

Fan motor

Thermal switch

Defrosting method
Refrigerant

Auto-defrost mode (Reversed refrigerant circle)


Type x Original charge

Drawing

lbs + oz (kg)

R410A x (15 lbs + 7 oz) (7.0kg)

R410A x (20 lbs + 16 oz) (9.5kg)

Control

indoor LEV and HIC circuit

External

W659658

Wiring

W274649

Refrigerant cycle

Standard

Document

Installation Manual

Installation Manual

attachment

Accessory

Details refer to External Drw W659658

Details refer to External Drw W659658

High static pressure motor : PAC-KBU04MT-U-F

High static pressure motor : PAC-KBU04MT-U-F

Joint : CMY-Y102S-G

Joint : CMY-Y102S-G,CMY-Y102L-G1

Header:CMY-Y104/108/1010-G

Header:CMY-Y104/108/1010-G

Optional parts

Remark

Note :

Details on foundation work,duct work,insulation work,electrical wiring,power source switch,and other items shall be referred to the Installation Manual.

*1 Nominal cooling conditions


Indoor : 80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PUHY-P72-96TGMU

OUTDOOR UNITS

Y-3

1. SPECIFICATIONS

DATA U1

Model

PUHY-P108TGMU-A(-BS)

Power source

PUHY-P126TGMU-A(-BS)
3-phase 3-wire 208-230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW

108,000
31.7

36.9

Power input

kW

9.73

11.36

Current input(208-230)

30.0-27.1

35.0-31.6

COP (kW / kW)


Temp. range of

Indoor

cooling

Outdoor

126,000

3.25

3.24
59 to 75 degFW.B. (15 to 24 degCW.B.)
23 to 109 degFD.B. (-5 to 43 degCD.B.)

32 to 109 degFD.B. ( 0 to 43degCD.B. ) Outdoor unit below Indoor unit


Heating capacity

*2 BTU / h

(Nominal)

*2 kW

120,000
35.2

41.0

Power input

kW

9.92

11.67

Current input(208-230)

30.6-27.6

36.0-32.5

COP (kW / kW)


Temp. range of

Indoor

heating

Outdoor

Indoor unit

Total capacity

connectable

Model / Quantity

3.51
-4 to 60 degFW.B. (-20 to 15.5 degCW.B.)

Liquid (High press.)

refrigerant pipe
(O.D.)

3.54
59 to 81 degFD.B. (15 to 27 degCD.B.)

Noise level (measured in anechoic room)


Diameter of

140,000

Gas (Low press.)

50-130% of outdoor unit capacity

50-130% of outdoor unit capacity

P06-P96 / 1-19

P06-P96 / 1-20

dB <A>
in. (mm)

60

61

3/8 (9.52) Flare

1/2 (12.7) Flare

(1/2 (12.7) total length>=131ft.(40m))

in. (mm)

7/8 (22.2) Brazed

External finish

1-1/8 (28.58) Brazed

Pre-coated galvanized sheets(+powder coating for -BS type)


<MUNSELL 5Y 8/1 or similar>

External dimension H x W x D
Net weight

in.

72-15/32 x 39 x 33-3/32

72-15/32 x 50-13/16 x 33-3/32

mm

1,840 x 990 x 840

1,840 x 1,290 x 840

lbs(kg)

Heat exchanger
Compressor

524 (237)

616 (279)

Salt-resistant cross fin & copper tube

Salt-resistant cross fin & copper tube

Inverter scroll hermetic comp.

Inverter scroll hermetic comp.

Type
Manufacturer

AC&R Works,MITSUBISHI ELECTRIC CORPORATION

Starting method

Inverter
kW

8.0

8.5

Case heater

kW

0.057(230V)

0.057(230V)

MEL32

MEL32

7,050

8,450

Lubricant
FAN

Inverter

Motor output

Airflow rate

cfm
m3 / min
L/s

External static press.

in.WG(Pa)

Motor output

240

3,333

4,000

0 (0)

0 (0)

Propeller fan x 1

Propeller fan x 1

Inverter-control , Direct-driven

Inverter-control , Direct-driven

0.38 x 1

0.64 x 1

Type x Quantity
Control, Driving mechanism

200

kW

HIC circuit (HIC: Heat Inter-Changer)


Protection

Copper pipe,pipe-in-pipe structure

High pressure protection

High pressure sensor, High pressure switch 601 psi (4.15 MPa)

Inverter circuit (COMP. , FAN)

Over-current protection,Over-heat protection

Compressor

Over-heat protection

Fan motor

Thermal switch

Defrosting method
Refrigerant

Auto-defrost mode (Reversed refrigerant circle)


Type x Original charge

lbs + oz (kg)

R410A x (20 lbs + 16 oz) (9.5kg)

Control
Drawing

R410A x (28 lbs + 11 oz) (13.0kg)


indoor LEV and HIC circuit

External

W659658

W659659

Wiring

W274649

W274649

Standard

Document

Refrigerant cycle

Installation Manual

Installation Manual

attachment

Accessory

Details refer to External Drw W659658

Details refer to External Drw W659659

Optional parts

High static pressure motor : PAC-KBU04MT-U-F


Joint : CMY-Y102S-G,CMY-Y102L-G1
Header:CMY-Y104/108/1010-G

Remark

Note :

Details on foundation work,duct work,insulation work,electrical wiring,power source switch,and other items shall be referred to the Installation Manual.

*1 Nominal cooling conditions


Indoor : 80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PUHY-P108-126TGMU

OUTDOOR UNITS

Y-4

(3-5/32)
80

(2-1/4)
57

768 (30-1/4)

(6-9/16)

(3-5/32)

80

5(7/32)

Cross section Y-Y

(1/2)12

Cross section X-X

Knockout hole
<Bottom piping hole>

166

Note1.Use the opening at the bottom of the unit


when running the power supply line from
the front or from the side of the unit.
Note2.Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.

(P72type:Not attached)
(P96,P108type:Attached near the ball valve)

(P72type:Packaged in the accessory kit)


(P96,P108type:Already installed on the unit)

<Accessories>

Model
A
72 132(5-7/32)
96 136(5-3/8)
108 136(5-3/8)

Conn. pipe(Liquid)

160
(6-5/16)

53

65
(2-9/16)

(2-3/32)

20 (13/16)

117

(1-15/32) (4-5/8)

37

Air
inlet

(2-25/32)70

(13/32)(3-9/16)
10 90

553 (21-25/32)

37

Left side view

Refrig. service
valve (Liquid)
(2-21/32)
<Flare>

Front view

67 160 (6-5/16)

Top view

990 (39)

(35-7/16)
900(mounting pitch)

45
(1-25/32)

840 (33-3/32)

Knockout hole
Refrig. service 100
83
<Front piping
valve(Gas) (3-15/16) (3-9/32) hole>
<Flange>
67 207
207 67
Knockout hole
(2-21/32)(8-5/32)
(8-5/32) (2-21/32)
<Left piping hole>

(1-19/32)
40

Knockout hole
Service panel

(1-25/32)

2X2-14(9/16)X20(13/16) 0val hole


(Mounting hole)
45

<Left side hole for


control wiring>

Air
inlet

(4-5/8) (1-15/32)

117

(5-11/32)
135
(3-5/32)80

Air outlet

<Bottom hole for control wiring>

134

100
(3-15/16)
(5-9/32)

Conn. pipe(Gas)

1575 (62-1/32)

attached conduit mounting plate <Accessory>

280
(11-1/32)

(10-7/16)
265
78 (3-3/32)

(9-9/32)
235

(21/32)
16
(33-9/32)
845(mounting pitch)
(21/32)
16
1840 (72-15/32)

<Hole for power supply>

(5-29/32) (1-3/4)
150
44

OUTDOOR UNITS

(7/16)11

PUHY-P72,96,108TGMU-A(-BS)

494(19-15/32)

2. EXTERNAL DIMENSIONS

2. EXTERNAL DIMENSIONS

DATA U1

Drw. : PUHY-TGMU_W659658 1/2


Unit : mm(in)

Y-5

877 (34-17/32)

Front
<Top view>

OUTDOOR UNITS

450
100
(17-23/32) (3-15/16)

2.Foundation work

No restrictions on wall height


<left and right>

<Side view>

h= wall height <H'> - total height of unit.


(17-23/32) (3-15/16)
450
100

[When inlet air enters from right


and left sides of unit]

450
100
(17-23/32) (3-15/16)

In case of single installation


[Basic rules for spacing the unit]

H
H'

Wall height<H>

1000
(39-3/8)

450
450
(17-23/32) (17-23/32)

Wall height<H>

Wall height <H>

Wall height <H>

Wall height <H>

1000
(39-3/8)

B Must be open

A Front

450
450
450
450 * 250
* 450
(17-23/32) (17-23/32) (17-23/32)(17-23/32)(17-23/32) (9-27/32)

1000
(39-3/8)

Wall height <H>

Spacing PUHY-P72,96,108TGMU-A(-BS)

M10 Anchor Bolt


<Local supply>

Corner

1000
(39-3/8)
No restrictions on wall height

Wall height<H>

In case of collective installation and continuous installation

450
250
(17-23/32)(9-27/32)
250
250
900
(9-27/32) (35-7/16) (9-27/32)

1.Space required around unit

h
H

250
(9-27/32)
(35-7/16) 900

2. EXTERNAL DIMENSIONS
DATA U1

Drw. : PUHY-TGMU_W659658 2/2


Unit : mm(in)

Y-6

L1
L2
L3

Ground

Power source
3~
208/230V 60Hz

Indoor/outdoor
transmission line

Central control
transmission line

*1

*4

21S
4a

SV
5b

CH11

*4

Shield

M1
M2

TB3

M1
M2
S

TB7

red

white

black

L1

L2

L3

TB1
(Terminal Block)

Shield

21S
4b

CN21
blue

F02
250VAC
6.3A T

G
L1

black

red

321
CNH

21
CNTYP4

R22

LD1

10

R23

321
CNTYP5

SWU2 SWU1

C5

FN1

CNS2
blue
123

R1

52C

NF
(Noise Filter)

CNS1
blue
12

Unit address setting

2
1
0
SWU3

123 456
CNLVB
red

LEV1

FN5

FN4

CN41
1 2 3 4

FN3

CN40
1 2 3 4

LD2

FN2

10
10
10
10
SW5 SW4 SW3 SW2 SW1
*2

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

Function setting

ZNR4

1 2 3 4 5 CN20

F01
250VAC
6.3A T

321
CNL
black

1 2 3

63HS

1 2 3

red
white
black

63LS

red
white
black

Control circuit board

21
CN01

TH11

ZNR1~4

DS
(Diode stack)

DSA

X01

X02

X03

X08

X09

87654321
CN02

TH8 TH7 TH6 TH5

detection
circuit

detection
circuit

L3 L2

12 3

1 CN32
2
3

1 CN33
2
3
4
5
6

1 CN36

1
2 CN35
3 red

1
2 CN38
3 green

white

SV1

CN52C

red

1 yellow
2
X52
3

21
CNTYP1
red

black

63H1

52C

black

Z20

green

OUTDOOR UNITS
red

Inverter controller box

DCL

black

C1

CNVCC1

CNRS3B

SNOW

red
C4
N

T
(Transformer)

F01
250VAC 3.15A T

Gate amp board

CNDC2
4

IPM

ACCT-U

1 2

green
CNTH

CN15V1

CNDR1

14

W CNDC1
yellow
1
3

ACCT-W

black

white

red

THHS5

1 2 3 CNVDC

F01
250VAC
15A T

LED1 operation
LED2 error
1

4
SW 2

14

CNAC2

CN15V2

CNDR2

1
CNDC2
3 yellow

4
3 CNCT2
2 blue
1

Function
setting

ON
OFF

CNINV

FAN control board

*2

or STEP DEMAND

ACCT

CNRS2

CNTR
1
2
3

Compressor ON/OFF
NIGHT MODE

Compressor ON/OFF
Trouble

*1

black
DCCT
1234

1
black
2
CNAC3 3

CN51
1
2
3
4
5

CNRS3A

12V

CN3S 23
red
1

CN3D 2

SW1

G L3 L1

ON
OFF

THHS1

L2

green
CNTH
12

CNL2
12

SW2

Function setting

F01
250VAC
2A T CNCT
1234
1 2345

ON
OFF

LED1 operation
LED2 error
LED3 charge

L1

Power circuit board

1 2 34 5 6 78
CNVCC1

3
2
1

R2

CNFAN
red
CNL1 CN30V red
12
12

X01

CNFG 1
blue
2

1234 5 67
CNRS1

*3

MF1

1
2
3
CN04

V
W

MF

MC

Motor
(Compressor)

Fan motor
(Heat
exchanger)

1
2

Name
Terminal block
AC Current Sensor
DC Current Sensor
DC reactor
(Power factor improvement)
Relay(Inverter main circuit)
Motor Fan Radiator panel
Crank case heater(Compressor)
4-way valve
Solenoid valve
(Discharge-suction bypass)
Solenoid valve
(Heat exchanger capacity control)
Electronic expansion value
(SC coil)
Thermistor Discharge pipe temp. detect
Pipe temp.detect(Hex outlet)
OA temp. detect
liquid outlet temp.detect
at Sub-cool coil
bypass outlet temp.detect
at Sub-cool coil
Radiator panel temp. detect
High pressure switch
High pressure sensor
Low pressure sensor
Choke coil(Transmission)
Function device

OFF

ON

Compressor
ON/OFF

CN3D
1-2P

SHORT

OPEN

CN3D 1-2P

100%
0%

OPEN

Model
P72/96/108
P126/144

*3

<Difference of appliance>
:exist X:not exist

CN3D 1-3P

*4

SHORT

OPEN

SW4-7:ON (STEP DEMAND)

SHORT

OPEN

CN3D
1-3P

75%
50%

SHORT

ON

OFF

NIGHT
MODE

SW4-7:OFF (Compressor ON/OFF and NIGHT MODE)

*2 Function according to switch operation.


(SW4-7,CN3D 1-2P,and CN3D 1-3P)

*1 The broken lines indicate field wiring.

, G Ground terminal

THHS1,5
63H1
63HS
63LS
L1,L2
Z20

TH8

TH7

TH11
TH5
TH6

LEV1

SV5b

SV1

52C
MF1
CH11
21S4a,b

DCL

Symbol
TB1,3,7
ACCT
DCCT

PUHY-P72,96,108TGMU-A(-BS)
PUHY-P72,96,108,126,144TGMU-A(-BS)

red

<Symbol explanation>

3. ELECTRICAL WIRING DIAGRAMS

3. ELECTRICAL WIRING DIAGRAMS

DATA U1

Drw. :PUHY-TGMU_W274649

Y-7

4. SOUND LEVELS

DATA U1

4. SOUND LEVELS

Measurement condition
PUHY-P72,96,108,126,144TGMU-A(-BS)
PUHY-P72,96,108TGMU-A(-BS)

Sound level of PUHY-P108TGMU-A(-BS)

Ref.:NC_PUHY-P108TGMU_WYNB0-4263

90
Stand 60Hz
Night 60Hz

Octave band sound level (dB)

80

3-1/4ft.
(1m)

3-1/4ft.
(1m)

Measurement
location

70

NC-70

60

NC-60

50

NC-50

40

NC-40

30

NC-30
Approximate minimum
audible limit on
continuous noise

20

NC-20

10
63

125

250

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Night Mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
63.0 64.0 57.5 55.0 50.5 50.5 54.0 50.0 60.0
64.0 55.0 48.5 46.5 42.5 43.0 41.5 40.0 51.0

When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P72TGMU-A(-BS)

Ref.:NC_PUHY-P72TGMU_WYNB0-4261

Sound
Soundlevel
levelof
ofPUHY-P96TGMU-A(-BS)
PUHY-P126TGMU-A(-BS)
90
90

90
Stand 60Hz
Night 60Hz

80
80

70

NC-70

60
NC-60
50

NC-50

40

NC-40

30
NC-30

10
63

125

250

70
70

1k

2k

4k

NC-60
NC-60

50
50

NC-50
NC-50

40
40

NC-40
NC-40

30
30

NC-20
500

NC-70
NC-70

60
60

20
20

Approximate minimum
audible limit on
continuous noise

20

Octaveband
bandsound
soundlevel
level(dB)
(dB)
Octave

Octave band sound level (dB)

80

NC-30
NC-30
Approximate
Approximateminimum
minimum
audible
audiblelimit
limiton
on
continuous
noise
continuous noise

10
10
63
63

8k

125
125

250
250

NC-20
NC-20
500
500

1k
1k

2k
2k

4k
4k

8k
8k

Octave
Octaveband
bandcentral
centralfrequency
frequency(Hz)
(Hz)

Octave band central frequency (Hz)

Standard
60Hz
Night Mode 60Hz

Ref.:NC_PUHY-P96TGMU_WYNB0-4262
Ref.:NC_PUHY-P126TGMU_WYNB0-4264

Stand
Stand 60Hz
60Hz
Night
Night 60Hz
60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
61.5 57.5 54.5 52.5 49.0 48.0 48.0 42.5 56.0
61.0 54.5 50.0 46.0 41.5 39.5 37.0 38.0 49.0

When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Standard
Standard 60Hz
60Hz
Night
NightMode
Mode 60Hz
60Hz

63
63
62.5
67.5
60.0
64.0

125
125
58.5
68.5
56.5
55.0

250
250
55.5
60.5
50.0
48.5

500
2k
4k
8k
500 1k
1k
2k
4k
8k
53.0
58.5 49.5
54.5 49.0
50.5 49.0
48.0 43.0
42.5
45.5
46.5 41.0
44.5 38.5
45.0 38.0
43.5 39.0
42.0

dB(A)
dB(A)
57.0
61.0
49.0
52.0

When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from
When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.
Night Mode automatically in the case that the operation condition is severe.

OUTDOOR UNITS

Y-8

5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

DATA U1

5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

ST2 BV2

Drw. : RC_PUHY-P72-108TGMU

ST7

ST6

ACC

63LS

CJ2

Fusible
Plug

ST1 BV1

PUHY-P72,96,108TGMU-A(-BS)

TH7

Comp

TH5
TH6

HEX F

HEX B

TH8

SCC

LEV1

ST4

TH1

CJ1

63H

21S4a

O/ S

63HS

ST3

SV1

CP1

OUTDOOR UNITS

Y-9

6. CAPACITY TABLES

DATA U1

6-1. Correction by temperature

6. CAPACITY TABLES

CITY MULTITM could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value
and the ratio below , the capacity can be observed at various temperature.

P72TGMU P96TGMU
21.1

28.1

72,000

96,000

6.48

8.67

1.3

Indoor Temperature

1.2
Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

1.1

24CWB
75.2FWB

1.0

22CWB
71.6FWB

0.9

20CWB
68FWB
18CWB
64.4FWB

0.8

16CWB
60.8FWB

0.7

15CWB
59FWB

0.6

Ratio of power input

1.3

24CWB
75.2FWB

1.2

22CWB
71.6FWB

1.1

20CWB
68FWB
18CWB
64.4FWB

1.0

16CWB
60.8FWB

0.9

15CWB
59FWB

0.8
0.7

-5
23

P72TGMU P96TGMU
31.7

80,000

108,000

6.33

8.56

5
41

10
15
20
25
30
50
59
68
77
86
Ratio of cooling capacity and power input

35
95

40
45 CDB
104
113 FDB
Outdoor temperature

1.4
1.3
Ratio of heating capacity

23.4

15CDB
59FDB

1.2
1.1
21.1CDB
70FDB

1.0
0.9

25CDB
77FDB

0.8
27CDB
80FDB

0.7
0.6

Indoor Temperature

1.1
Ratio of power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

0
32

1.0

15CDB
59FDB

0.9
0.8

21.1CDB
70FDB

0.7

25CDB
77FDB

0.6
27CDB
80FDB

0.5
-20
-4

-15
5

-10
-5
0
5
14
23
32
41
Ratio of heating capacity and power input

10
15 CWB
50
59 FWB
Outdoor temperature
Ref:CbT_PUHY-P72-96TGMU

OUTDOOR UNITS

Y-10

6. CAPACITY TABLES

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

P108TGMU P126TGMU
31.7

36.9

108,000

126,000

9.73

11.36

P144TGMU
42.2
144,000
14.20

1.4

Indoor Temperature

1.3
Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U1

1.2

24CWB
75.2FWB

1.1

22CWB
71.6FWB

1.0

20CWB
68FWB
18CWB
64.4FWB

0.9

16CWB
60.8FWB

0.8

15CWB
59FWB

1.3

24CWB
75.2FWB

Ratio of power input

1.2
1.1

22CWB
71.6FWB

1.0

20CWB
68FWB
18CWB
64.4FWB

0.9

16CWB
60.8FWB

0.8

15CWB
59FWB

0.7
0.6

-5
23

41.0

120,000

140,000

9.92

11.67

P144TGMU
46.9
160,000
13.67

10
15
20
25
30
50
59
68
77
86
Ratio of cooling capacity and power input

35
95

40
45 CDB
104
113 FDB
Outdoor temperature

1.2
Ratio of heating capacity

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

35.2

5
41

1.3

P108TGMU P126TGMU

15CDB
59FDB

1.1

21.1CDB
70FDB

1.0
0.9

25CDB
77FDB

0.8

27CDB
80FDB

0.7
0.6

Indoor Temperature

1.1
1.0
Ratio of power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

0
32

0.9

15CDB
59FDB

0.8
21.1CDB
70FDB

0.7
0.6

25CDB
77FDB

0.5
0.4
-20
-4

27CDB
80FDB

-15
5

-10
-5
0
5
14
23
32
41
Ratio of heating capacity and power input

10
15 CWB
50
59 FWB
Outdoor temperature
Ref:CbT_PUHY-P108-144TGMU

OUTDOOR UNITS

Y-11

6. CAPACITY TABLES

DATA U1

6-2. Correction by total indoor


CITY MULTITM system has different capacity and input at different total capacity of indoor unit connected. Using following tables,
the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY-P72,96TGMU
50.0

Capacity(kW)

40.0

30.0

20.0

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PUHY-P72-96TGMU

PUHY-P108TGMU
PUHY-P108,126TGMU
50.0

Capacity(kW)

40.0

30.0

20.0

10.0

Input(kW)

10.0

5.0

P108

P126
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PUHY-P108-126TGMU

OUTDOOR UNITS

Y-12

6. CAPACITY TABLES

DATA U1

Capacity(BTU/h)

PUHY-P72,96TGMU
170,000
160,000
150,000
140,000
130,000
120,000
110,000
100,000
90,000
80,000
70,000
60,000
50,000
40,000
30,000
20,000
10.0

Input(kW)

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PUHY-P72-96TGMU

Capacity(BTU/h)

PUHY-P108TGMU
PUHY-P108,126TGMU
170,000
160,000
150,000
140,000
130,000
120,000
110,000
100,000
90,000
80,000
70,000
60,000
50,000

Input(kW)

10.0

5.0

P108

P126
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: CbTI_PUHY-P108-126TGMU

OUTDOOR UNITS

Y-13

6. CAPACITY TABLES

DATA U1

6-3. Correction by refrigerant piping length


CITY MULTITMsystem can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
2-3-1 and 2-3-2, the capacity can be observed. 2-3-3 shows how to obtain the equivalent length of piping.

6-3-1. Cooling capacity correction


PUHY-P108TGMU
PUHY-P144TGMU

PUHY-P72TGMU

Tot
al c
apa
city
of i
ndo
or u
nit

0.9
0.85
0.8

36

0.75

54

0.7

72
93

0.65
20
66

40
131

60
80
100 120
197 263
328 394
Piping equivalent length

140
459

160
525

Cooling capacity correction factor

Cooling capacity correction factor

0.95

72
108
144
54
187

0.75

81

0.7

108
140

0.65
20
66

40
131

60
80
100 120
197 263
328 394
Piping equivalent length

140
459

160
525

m
ft.

CbRPL_PUHY-P108TGMU_C
Ref.: CbRPL_PUHY-P144TGMU_C

PUHY-P168TGMU

0.95

Tota
l ca
pac
ity o
f ind
oor
unit

0.9
0.85
0.8

48
72
96
124

0.75
0.7
0.65
20
66

40
131

60
80
100 120
197 263
328 394
Piping equivalent length

140
459

160
525

Cooling capacity correction factor

Cooling capacity correction factor

0.8

Ref.: CbRPL_PUHY-P72TGMU_C

of i
ndo
or u
nit
54

0.75
0.95
0.7

81
108
140

0.65
40
131

60
80
100 120
197 263
328 394
Piping equivalent length

20
40
PUHY-P126TGMU
66 131
1

60
80
100 120
197
263
328 394
Piping equivalent length

0.90

20
66

140
459

160
525

Tota
l

6-3-3. How to obtain the


0.85

140
459

m
ft.

160
525

cap

acit

y of

indo length
equivalent
or u
nit

20
66

40
131

60
80
100 120
197 263
328 394
Piping equivalent length

140
459

160
525

m
ft.

Ref.: CbRPL_PUHY-P168TGMU_C

163

PUHY, PURY-P96,108TGMU

0.7

Equivalent length = (Actual piping length to the farthest indoor unit)

0.65

60
80
100 120
197 263
328 394
Piping equivalent length

0.95

Tota
l ca
pac
ity o
f ind
oor
unit

0.9
0.85
0.8

96
144
192
249

0.75
0.7
0.65
0

20
66

40
131

60
80
100 120
197 263
328 394
Piping equivalent length

140
459

160
525

m
ft.

Ref.: CbRPL_PUHY-P192TGMU_C

PUHY-P204TGMU
1

of piping
63
95

0.75

40
131

0.65

Ref.: CbRPL_PUHY-P72-234TGMU_H

Equivalent length = (Actual piping length to the farthest indoor


126 unit)

20
66

0.7

Ref.: CbRPL_PUHY-P108TGMU_C

PUHY, PURY-P72TGMU
0.8

0.75

m
ft.

0.95
0.9

84
126
168
218

Cooling capacity correction factor

0.8

indo
or u
nit

0.8

140
459

160
525

Cooling capacity correction factor

Tot
al c
apa
city

0.85

0.85

PUHY-P192TGMU

0.95

1.00
0.9

Tota
l ca
pac
ity o
f

0.9

Ref.: CbRPL_PUHY-P96TGMU_C

PUHY-P108TGMU

PUHY-P-TGMU

0.95

m
ft.

6-3-2.1 Heating capacity correction


Heating capacity
correctioncorrection
factor factor
Cooling capacity

0.85

Tota
Tot l capac
al c
apa ity of in
doo
city
r un
of i
it
ndo
or u
nit

0.9

0.95

m
ft.

PUHY-P96TGMU

Cooling capacity correction factor

m
ft.

0.95

Tota
l

0.9

cap

acit

y of

0.85

indo

or u

nit
102
153
204
265

0.8

+ (0.35 x number of bent on the piping) m


0.75 x number of bent on the piping) ft.
+ (1.15
0.7

+ (0.42 x number of bent on the piping) m


+ (1.38
0.65 x number of bent on the piping) ft.
0

Ref.: CbRPL_PUHY-P126TGMU_C

OUTDOOR UNITS

20
66

40
131

60
80
100 120
Ref.: EPL_TGMU
197 263
328 394
Piping equivalent length

140
459

160
525

m
ft.

Ref.: CbRPL_PUHY-P204TGMU_C

Y-14

6. CAPACITY TABLES

DATA U1

6-4. Correction at frosting and defrosting


Due to frosting at the outdoor heat exchanger and the automatical defrosting operation, the heating capacity of the outdoor unit
should be considered by multiplying the correction factor which shown in the table below.
Table of correction factor at frosting and defrosting
Outdoor inlet air temp. CWB

-2

-4

-6

-8

Outdoor inlet air temp. FWB

43

39

36

34

32

28

25

21

18

14

PUHY,PURY-P72,96TGMU

1.00

0.95

0.84

0.83

0.83

0.87

0.90

0.95

0.95

0.95

PUHY,PURY-P108TGMU

1.00

0.93

0.82

0.80

0.82

0.86

0.90

0.90

0.95

-10

0.95
Ref.: CaF_TGMU

PUHY,PURY-P126,144TGMU

1.00

0.95

0.90

0.87

0.88

0.89

0.90

0.95

0.95

PUHY,PURY-P168,192TGMU

1.00

0.98

0.89

0.86

0.89

0.90

0.92

0.95

0.95

0.95

PUHY,PURY-P204TGMU

1.00

0.94

0.87

0.86

0.87

0.88

0.90

0.90

0.93

0.93

PUHY,PURY-P216,234TGMU

1.00

0.94

0.84

0.86

0.87

0.88

0.90

0.90

0.93

0.95

0.93
Ref.: CaF_TGMU

6-5. Temp. range of running


Cooling

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

25
77

30
86

35
95

40
104

45
113

50
122

25
77

30
86

35
95

40
104

45
113

50
122

Outdoor temperature

Heating

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

Outdoor temperature
Ref.: tr-ygm-y

OUTDOOR UNITS

Y-15

OUTDOOR UNITS

Y-16

Optional parts for PUHY,PURY-P-TGMU

DATA U1

OUTDOOR UNITS
I.Optional parts for PUHY,PURY-P-TGMU

1. JOINT ................................................................................................................................................................... Op- 2


1. JOINT ....................................................................................................................................................................... OP-2
2. HEADER............................................................................................................................................................... Op- 3
2. 3.
HEADER...................................................................................................................................................................
OP-3
JOINT KIT "CMY-R160-J" FOR BC CONTROLLER ............................................................................................
Op- 4
3. 4.
JOINT
KITSTATIC
CMY-R160-J
FOR BC
CONTROLLER
.................................................................................................
OP-4
HIGH
PRESSURE
MOTOR
PAC-KBU04MT-U-F
..................................................................................
Op- 5
4. HIGH STATIC PRESSURE MOTOR PAC-KBU04MT-U-F......................................................................................... OP-5

OPTIONS

OUTDOOR UNITS

OP-1

1. JOINT

DATA U1

MULTITM

Piping for CITY


can be easily done with Joints and headers provided by MITSUBISHI ELECTRIC CORP..
For PUHY-P-TGMU and PURY-P-TGMU, 4 sets of Joints are available. Details for applying the Joint sets are referable to System
Design 5-1. or their own Installation Manual.
I.Optional
1.
JOINT parts for PUHY,PURY-P-TGMU

Ref.: W901632
in.

CMY-Y102S-G
For gas pipe:

For liquid pipe:


<Deformed pipe(Accessory)>
5/8"

1/2"
3-5/32"

5/8"

1/4"

3/8"

3/8"

3-5/32"

3-5/32"
5-15/16"

3/8"

3/8"

5/8"

29/32"

1-3/16"

3/4"
3/4"

3/4"

<Deformed pipe(Accessory)>

3-31/32"

3/4"

1/2"
3-5/32"

ID: Inner Diameter

OD: Outer Diameter

Ref.: W901633
in.

CMY-Y102L-G1
<Deformed pipe(Accessory)>

For liquid pipe:

<Deformed pipe(Accessory)>

OPTIONS

For gas pipe:

ID: Inner Diameter

OD: Outer Diameter


Ref.: W901634
in.

CMY-Y202-G1
For gas pipe:

For liquid pipe:


<Deformed pipe(Accessory)>

ID: Inner Diameter

<Deformed pipe(Accessory)>

OD: Outer Diameter

Ref.: W901635
in.

CMY-Y302-G1
For gas pipe:

ID: Inner Diameter

<Deformed pipe(Accessory)>

For liquid pipe:

<Deformed pipe(Accessory)>

OD: Outer Diameter

OUTDOOR UNITS

OP-2

2. HEADER

DATA U1

MULTITM

Piping for CITY


can be easily done with Joints and headers provided by MITSUBISHI ELECTRIC CORP..
For PUHY-P-TGMU and PURY-P-TGMU, 3 sets of Headers are available. Details for applying the Header sets are referable to
System Design 5-2. or their own Installation Manual.
2. HEADER

Ref.: W901636
in.

CMY-Y104-G
For gas pipe:
<Deformed pipe(Accessory)>

For liquid pipe:


<Deformed pipe(Accessory)>

For gas pipe:


<Deformed pipe(Accessory)>

For liquid pipe:


<Deformed pipe(Accessory)>

Ref.: W901638
in.

CMY-Y1010-G
For gas pipe:
<Deformed pipe(Accessory)>

For liquid pipe:


<Deformed pipe(Accessory)>

OUTDOOR UNITS

OP-3

OPTIONS

Ref.: W901637
in.

CMY-Y108-G

3. JOINT KIT "CMY-R160-J" FOR BC CONTROLLER

DATA U1

Joint kit "CMY-R160-J" for BC controller is used to combine 2 ports of the BC controller at a PURY-P-TGMU system so as to enable
down-stream Indoor capacity above P55 as shown in Fig. 1.
3. JOINT KIT "CMY-R160-J" FOR BC CONTROLLER

The Joint kit include following items:


1 Instruction

2 Joint pipe
(for liquid side)

This sheet

1pc

3 Joint pipe

4 Cover 1

(for gas side)

1pc

5 Cover 2
(for gas side)

1pc

2pcs

6 Cover 3

7 Band

8 Reducer

(for liquid side)

1pc

1pc

8pcs

1pc
Ref.: WT04350X01_01

2 Joint pipe (for liquid side)

3 Joint pipe (for gas side)

mm(in.)

OPTIONS

Ref.: W901616

1. Designing CMY-R160-J to a PURY-P-TGMU system


The maximum down-stream Indoor capacity for 1 port of BC
controller is P54. When the down-stream Indoor capacity is
above P54, Joint kit CMY-R160-J is needed to combined 2
ports of BC controller to enlarge the capacity, like Group 2 and
3 in Fig. 1.
Maximum 3 Indoor units are allowed to connect to 1 port of BC
controller or 2 combined ports of BC controller using CMYR160-J.
When connecting Indoor units to 1 port of BC controller or 2
combined ports of BC controller using CMY-R160-J, CMYY102S-G or CMY-Y104-G is applicable, like Group 1 and 2 in
Fig. 1

PURY-P-TGMU
BC controller
CMY-Y102S-G

IU
IU
Group1
Total Indoor Capacity
<=P54

IU

Joint kit
CMY-R160-J

IU
IU
Group2
Total Indoor Capacity
P55 to P96

Caution: Mixed cooling and heating mode at the same time for
Indoor units connecting to 1 port or 2 combined ports is not
available.

Fig.1. CMY-R160-J applying scheme

IU

IU
Group3
Total Indoor Capacity
P72 or P96
Ref.: WT04350X01_02

2. Piping at the installation site


The connection of CMY-R160-J to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing is
necessary. All piping must be careful to avoid foreign material getting inside.
After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.

2 Joint pipe (for liquid side)

Piping to indoor unit


(Non-oxidized brazing)

Flare nut 9.52 (3/8")


Clamping torque 35Nm
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
Flare nut 15.88 (5/8")
Clamping torque 80Nm
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
3 Joint pipe(for gas side)

Fig.2. Connecting CMY-R160-J

Ref.: WT04350X01_03

OUTDOOR UNITS

OP-4

4. HIGH STATIC PRESSURE MOTOR PAC-KBU04MT-U-F

DATA U1

4. HIGH STATIC PRESSURE MOTOR PAC-KBU04MT-U-F

With PAC-KBU04MT-U-F, the PUHY-P-TGMU,PURY-P-TGMU outdoor unit will gain external 30Pa or 60Pa static
pressure, which makes the outdoor unit exhausting design much easier to coordinate with the building situation.
1. Inside the package of PAC-KBU04MT-U-F, following items are enclosed together with the installation manual.
1 Instruction

2 Motor

3 Reinforcing plates

4 Label

5 Binder

2.1 You may order outdoor unit installed the optional PAC-KBU04MT-U-F
instead of non-static pressure motor, and set the expected external
static pressure at shipment, or change the motor by yourself at the
field. For the details you need to talk to your provider.

Fan guard
Panel
(back)
Panel 1
(front)
Label

Screw2
Panel 2
(front)
Fig.1
Propeller fan

DIPSW3-9

DIPSW5-1

ON
ON

ON
OFF

Nut

Connector
Motor

2.2b. Switching for 30Pa or 60Pa static pressure


1 Remove the Panel 2, referring to Fig.1.
2 Remove the control box cover.
3 Set the DIPSW, which is on the front board in the control box,
referring to the figure below.
(For the DIPSW location, refer to the wiring nameplate on the
back of the control box cover).

PUHY-P-TGMU
PURY-P-TGMU
30Pa
60Pa

Side
panel

OPTIONS

2.2 In the case you change the motor, and set the expected static
pressure at the field. Instruction 2.2a, 2.2b and 2.2c should be
followed.
2.2a. Mounting the motor
A. Remove the screw1, and remove the fan guard, referring to Fig.1.
B. Remove the screw2, and remove the panel 1, referring to Fig.1.
C. Remove the nut, and remove the propeller fan, referring to Fig.2.
D. Remove the connector of the motor, referring to Fig.3.
E. Remove the screw3 of the motor, and exchange the motor,
referring to Fig.4.
F. Connect the motor connectors.
Secure the connectors with a clamp below the motor base not
directly exposed to rainwater, referring to Fig.5.
G. Remove the screw4 from both sides of the side panel and replace
the side panel with the supplied reinforcing plates. referring to
Fig.6.
H. Put back the propeller fan, fan guard and panel in the reverse
order from A-C.
(Bind the nut tight with the torque of 20 2 Nm.)
I. Attach the supplied label on the unit, referring to Fig.1.

Screw1

Screw2

2. Installing the high static pressure motor PAC-KBU04MT-U-F


onto the outdoor unit.

Fig.2

Fig.3

Screw4

Screw3

2.2c. Field work of 2.2a and 2.2b needs working space at the front
and back of the outdoor unit. Enough working space should be
considered for the field work of 2.2a and 2.2b. For example,
upon corrective installation 20mm(3/4") or the like interval is
helpful.

Screw3

Fix the wire


by the binder

Establish a trap
below the connector.

Screw4
Fig.4

Top View

Secure the motor connector.


The motor connector
must be below the motor base.
Fig.5

Screw4

Fig.6

Front View

Ref.: WT04579X01

OUTDOOR UNITS

OP-5

OPTIONS

OUTDOOR UNITS

OP-6