Sunteți pe pagina 1din 27

INTRODUCTION . .

The CAL 9000 temperature controller is based on proven temperature control techniques, but it incorporates substantial improvements due to the use of modern digital technology involving a microprocessor . Good functional design ensures that the versatile features of the 9000 have made it simple to use . For the majority of applications it is only necessary to key in the sensor type . It will then automatically operate with Default (factory) settings for the PID Control terms making it suitable for a wide range of applications which
require a single setpoint, slow cycle, proportional output controller .

To use the 9000 with Default settings see Sections Bt - BS. For more complex or difficult applications the Default settings can be overridden by more appropriate values, alternative control modes or enabling of the second set point . When the appropriate parameters are keyed in, they can be 'locked' to prevent unauthorised adjustment . Sec Section B6-8 9

INDEX SECTION A Installation and Connection Detail s

SECTION B Operating Instruction s

I
Section A --- Installation and Connection Detail s
I

k
The instrument is mounted in the panel through a 45mm square 1/16 DIN cut out using the special mounting clip provided . The mounting clip should be pressed home until the ratchet holds the unit firmly in place . it necessary the mounting

can be further tightened using the jacking screws .


To remove the unit from the panel, ores$ the legs of the Clips in opposite directions to release the ratchet .

PANEL CUT OUT

To unplug socket, press in lock buttons and pull apart I Supply Either 230V c 15% 50-60 Hz (612-934) or 115V x 159 . 50-60 HZ (612-928 ) IMPORTANT Check side label for supply voltage SPi 2

"J '

t.

N C) v

[R5

Imk3-5

Input Sensors - Key selectable from instrument front panel . Thermocouple types PTtOO RTD 2 wire

J,K,N,R,ST,E and FeCuNi DIN

Standard Output s SP1 Relay SA/250V ac Resistive load SPDT (energised to apply power to heating load) SP2 Relay 3A/250V ac Resistive load SPOT (Slaved to SPt - key selectable) refer to SP2 OPERATION table Section AS for relay coil status. IMPORTANT - WHEN SWITCHING INDUCTIVE LOADS
Oerate contacts and fit externa l

suppression to ensure long contact life and minimum interference .

Showing optional uses of second set point (SP2)


Mains Heater - with alarm s

7
ALARM)

ISI

Y NAI~

GSU PL

3A (max) LOW ALARM OR WITHIN LIMITS SIGNAL NIGH ALARM OR OUT OF LIMITS SIGNA L

Heating and Cooling

COOLING WATER
"Met Nis not ,Rc.1IIRMnded IDlt SP2 Output it used as S tafsty Circui t CONTROL MOOS (nINCTION 10) OPLRATh1G MOD! COMPAR191= 0
NIGH IASOVS SPI)

SP! RELAY IS WIRGISW BELOW Sh SITTING ABOVE SP2 SETTING


WITHIN SET BAND

SM LED IS ON
ABOVE

TYPICAL OIAMKLS OS USE


DEVIATION

ON'OEi IOPHON 0)

OPTION , LOW (SL OW OPT) OPTIONS


OUT OS LIMITS (ABOUT SPt) OPTIONS

SP2 SETTING Mass SP2 SETTING


OUTSIDE $ET SAND

ALARM NIG H DEVIATIO N ALARM LOW


DEVIATION ALAR M

NIGH (ALONE $91)


IWOPORTIONAL OPTION I

AROUND SPI SETTING ABOVE S S SITTING BELOW SM SETTING

AROUND SP1 SETTING ABOVE SPS SETTING BELOW SS SETTING

NIGH AND LOW SP4 COOLING I I COOLING


Sq NEAn5 0

(OPTIONS I-T) LOW (BELOW $H) OPTIONS

Section B Operating Instruction s


Digital Display
The four digit display normally shows process temperature to 1C or 1F and in high resolution 0 .1C or 0 .1F. It is also used to display setpoint value (flashing) and the FUNCTION and OPTION list .

B
O u
0

L< I W I t; CAL 9000 Front Panel

Functions are the available controller facilities eg . Derivative time/Rat e

Function 6
Options are the available values for each Function eg . Derivative value - 50 seconds

Function numbers are on the Right,

OW Lion 4

Option numbers are on the Left of the floating decimal point . Parameters : are the selected Options from the Function list .

Error Indicato r
This is situated to the left of the digital display and the three LED's display the difference between setpoint and process temperatures in five steps, each one representing 290 of full scale value .
The error indicator can also be used in high resolution, t 1% steps or low resolution, s 4% steps
or mote Item sP

1ss
1 . to 3 . 450.0 SP 174 SP jf

set ro nt 144 .

Wtt~tn

: of SP

1% to 9 : ss o- S P 144 7 : of mote CC'O~ SP tsumaie tn 904 iwt .4.101

Output Indicator s
The two separate LEDs beneath the digital display indicate : Illuminated SP1 Output ON (green )
O Illuminated SP2 output (amber). On or Off depending on mode of OOeratio n

selected - see Table A S

User Mode

0
tt

0
Is

* Displays Setpomt (flashing) 7k Keyed together increases setpo;nt * VKeyed together decreases setpoint

i-digit rollover rate increase s

Setter Mod e
p Entry to Function and Option List and Exit to normal display and process temperature V Indexes FUNCTION/OPTION number up or down in single digit s s# Changes adjustment from Functions to Options and vice-versa (1e . toggling)

For ease of use in normal applications, the CAL 9000 has been preset with factory or DEFAULT settings in place of customers OPTIONS . These preset parameters enable the instrument to operate in PID Control mode with single setpoint . slow cycle, prooortional output .
This configuration should give good results where the heater is adequatel y

Default Range Table be keyed into the instrument . The Default Range will limit the setpo nt values only. The instrument will indicate process temperatures over the full linearised range shown in the table in Section 89 . It is important to ensure that the range maximum is compatible with safety. Proceed as follows :
Apply power . All LED segments will be briefly illuminated during the self check routine, then the display will request sensor selection, ie . The Option number for Function 16, and will not respond to any further instructions until this is made.

rated and the control sensor is sited reasonably close to it . Default settings (for SP1 only) are : Prooortiona, Time .' 30 secs Cycle rate Proportional Band/ =2,5% of Default Gain full scale Derivative Time/Rate =25 secs Integral Time/Auto Reset =350 sec s To use the controller with Default settings requires only that the Option number of the sensor, selected from the Sensor

Optictt

Wpa

Mitt/MaxC

1. 2. 3.
4.

J N N
R

Iron Constantan Thermocouple Chromel Constantin Thermocouple NiCrosil Nisil


Pt13% Rh-Pt Thermocouple

0- 400 0- 400 0- 400


0-1600

32-800 32-800 32-80 0


32-1999

5. 6. 7.
8.

S T E

Pt 10% Rh-Pt Thermocouple Copper Constantin Thermocouple Chromel Constantan Thermocouple

0-1600 0- 250 0- 500

32-1999 32-500 32-1000


32-800

Fe-CuNI DIN Thermocouple 0- 400

9.

PT100 RT0 Platinum Resistance Thermometer 0- 200

32-400

Ranging If the Default range maximum is not suitable it can be increased or decreased to any desired value within the linearised band . Refer to Section 86 Parameter Adjustments.

STEP
1 Install Unit . Power on . Check that display reads :

5CTIQII D/SPG95l
Note : digits shown green are flashing
Q

2 To key in the selected sensor type . Example : OPTION 4 . Type-K thermocouple: Check that display reads :

PRESS TWICE

3 To enter the selected thermocouple type into memory : The display now reads sensor Temperature*, eg. Ambient (18C). 4 To key in the set point value: To Increase the set point : To decrease the set point:
It should be noted that the digit rollover rate increases (ie . accelerates). eg . Set Point 450C .

PRESS P ONCE

PRESS *and HOLD PRESS PRESS

When the keys in (4) above are released the unit will operate as a normal temperature controller. The square LED, is illuminated, showing that SP1 output is energised . To view the set point temperature :

PRESS *

To adjust the set point value at any time: REPEAT STEP 4

Should a particular application require the use of additional features, for example : second setpoint output or High Resolution, refer to Section 86 : PARAMETER ADJUSTMENTS .
This also applies where the Default settings prove to be unsuitable. The 9000 can be tuned for optimum performance by the adjustment of control parameters . If guidance is needed to establish the appropriate settings, refer to Section C : TUNING .

NOTE : Because the following selections nfluence the values of other settings and can have a fundamental effect on control Charactanstics, it is important that when required, they should be made during initial setting and in the following order, to avoid the need for retuning. 1 . High Resolution (Function 18 Option 1) 2. C/F selection (Function 22 )

3 . Range adjustment s
Selection C' or F (Function 5 ) If the temperature scale is changed it is essential to replace the upper fascia . Range Adjustments The Default full scale (automatically selected by the choice of sensor) may be altered g to any value within the Irnearised band shown in table (Section 89) . Use the followin procedure : 1, Press P once and release . 2 Press P again and hold . 3 . Press* and hold . 4. Release P (hold*). Default full scale flashes S . Either press or to adjust full scale value 0 . 0 0 " O 6. Release or

7 . Release 1k
Repeat steps 1-4 to view new full scale value. Parameter Adjustments

STEP
1 Ensure that the link behind the lower front bezel is in the Parameter Setting position (see Parameter Lock Section 811) . 2 To convert main display from temperature reed-out into FUNCTION and OPTION listing mode: FUNCTION numbers appear to the right of, and OPTION numbers to the left of, the floating decimal point, starting with FUNCTION 3. The FUNCTION listing has been arranged to give easiest access to those which are most frequently used. When indexing in a positive (A) direction, FUNCTION 23 is followed by FUNCTION 3. FUNCTIONS 2 and 1 can be accessed from FUNCTION 3 by indexing in a negative (y) direction. FUNCTION 1 is followed by FUNCTION 12.

Rcnvn

0/SPLAy

PRESS P

OPTION 0

FUNCTION 3 (FLASHING)

STEP
3 1b index sequentially. The FUNCTION digit(s) will flash indicating that the FUNCTIONS can be indexed sequentially from 3 to 23 enabling previously entered or Default OPTIONS to be viewed: C9 . FUNCTION 12 OPTION 2 .

ROW 015%RY

PRESS O R

4 To alter an OPTION : To cause the flashin g of the display to shift from the FUNCTION column to the OPTION column to the left of the decimal point . Note that it is the flashing digit(s) that can be altered . To Change OPTION number :

PRESS 11r

2./ 2

PRES S OR PRESS V

To return to FUNCTION indexing : When all required OPTIONS have been selected for each FUNCTION, to place in memory and commence control under the new instructions :

PRESS

PRESS

STEP
Changing SP1 Proportional Time/Cycle Rate

8(711]1 1

Q/SPLRy

to change SP1 proportional time from 30 secs (Default setting) to 20 secs . FUNCTION 4 : Change OPTION 0 to OPTION 4 1 TodisplayOPTION/FUNCTION List : Ensure that link behind lower bezel is in 'unlocked' position . 2 To index the FUNCTION number to 4 : PRESS P

PRESS A

3 Change to OPTION numbers :

PRESS *

4 To alter OPTION number 0 to OPTION number 410

PRESS

STEP 8C71Qn OWN


5 To place in memory : PRESS P

STEP
Use of Manual Rese t

IT71011 Dl5Hy

m
5

P. PD and ON/OFF mode . When the system has settled, if a discrepancy exists between Set Point and Process Temperature, the 'offset' can be removed by the use of Manual Reset . For example, if the process temperature is 252C and the set point is 250C .

Process temperature is - 0190

to view the set point temperature : PRESS

, 2 To correc hsh 'onset' of tplays Display ows FUNCTIO N ON 3 : PRESS P OPTION 0 7, 0105

4 change to OPTION number s PRESS flashing :

sIN G
P 1909

5 key the 'onset ' temperature Om8 (-4C) : PRESS

6 To place in memory : PRESS The Process temperature readin g

will settle from 252C to 250C.

I250
11

All adjustable Parameters are held in memory and are shown in the Functions and Options Table below. For each Function, Option 0 is the Default (factory) Setting .

FYect3om Option Parameter Function Option Paratpeter Number Number Number Numb s
1 Manual Reset 7 Sri Derivative Adjusting +/- 10 steps Approach Contro l

Driset. Key in Range : 0 1 .5 x Proportional Correction Prop Bond + 2 Band (in degrees) (max 99) ,. 1 0. 5 2 1 .0 SP2 Adjust 3 2 .0 Key in 1 steps 4 2 .5 setting Range : 5 3 .0 (from SP1) 0 to 99 6 4 .0 in degrees (inoperative until 7 5 .0
Option selected at

Function 19) a S1 Integral Time 1 Lock 0 350 sec S 1 OUT 0 Unlocked 2 25s 1 Locked 3 SOs 4 100$ 4 SPI Proportional S 2005 Time 6 600s
0 1 30 is sec 7 100011

-a
% of span

2 Ss 9 Display Bias 3 101 1 4 205 10 SP2 Proportional 5 605 Time 6 0.055 0 ON/OFF ssa 7 ON/OFF 1 t cc s 2 5s SP1 Prop Hysterisis 3 los Band 4 20 5 0 2.5% 1 .25% 5 60 5 er 1 0.5% 0,25% 6 0 .051 2 1% 0 .5% 7 3D s 3 2% 1 .0% 4 3% 1 .5% 11 SP2 Prop Nysterisis S 5% 9 .5% Band 6 10% 5 .0% 0 2.5% 1 .25% 7 20% 10 .0% 1 0.5% 0 .25% 2 1% 0 .5% % of Msumam Proo Bond 3 2% 1 .0% span Po,P mode : 255 (25 .5m Hrfes) 4 3% 1 .5% PID mode 127 (127' in Mi Scs I 5 5% 2 .5% 6 10% 3 .0% SP1 Derivative Time 7 20% 10.0 % 0 25 sec .01 OUT Maximum Prop Ban d 2 55 PD.P mode 255 (25 Vim Mi-PetI PID inocc 127 (12 7 in H.-Af t 3 103 4 50$ S 1005 Note : Functions 9, 14 and 23 art factory settings 6 200s

12

wheel"
19

anion

ft Sawa
Grow Indication Resolution

False wt
17

lt+t.we (rum..
0 I 1R 0
1

t]ptwu

Nfa~aety
Nesatite Temperawre ranging Disabled Enabled Nigh Resolutio n Normal
Hues (-99.9 to 199.9) Settings in 1

I)

I 2

Normal (4% x F5 pe r segment ) High (19 x FS per

segment)
to. (417. x FS Pe r segment)

13
14 0 1 4 3 15 0 I 14 0
1

Spare perivative Polling Ratio 0.5x Derivative Time 0.4 0.7 1 .0 Reset an functions to Default Normal
Reset

increments becom e 0 .1 increments in


High Resolution. 14

0 1 2

SP2 Opera" Mode OUT Hgh (above SP1 ) Low (below SPI )

3
20 0

out of Limits

Sensor

Select
91

None-Controller Inoperable 1

SPt Sensor Wmou t Protection SPl output OF F (UPSCALE) 21 output ON (DOWNSCALE) 3P2 Sensor Burnout Protectio n SP2 output OFF (UPSCALE ) SP2 output ON (DCTNN5CALE) C/ f C
of Version N o

2 3 4 5 6 7
8

K N R S 1 E
Fe.CuNI

0 1 42 0
1

PT100#RTD 23

Nele: The use 01 Option 1 at Function 15 will return an settings to Default except for Function 22 (*C .,*F) and factory set 'unctions 9 . 14. 2 3

SENSOR OPTION F4 TYPE 1 1 X, . _ 2 3 N 4 R 5 S 6 T


7 9 E PT1001s.TD

oC
MR4

DEFAULT RANGE OF
MAX MIN

MAX 800 B00 1999 1999 500


1000

0 a
0 0 0
0

400

400
1600 1600 250
500

32 32
32 34 32 32 32
32

UNEAR<SEO RAMC C of MIN MAX MAX MIN 147 0 0 80 0 32 1200 _M 1 1994 0 1400 32 1600 32 1999 0 1999 0 1600 32 -90 250 -130 480
0 600 32 111 0

B Fe-CuNi

0
0

400
200

800
400

0
-90

800
400

32
-130

1470
750

Range adjustments (including Default) only limit setpoint values . Process temperatures will
be displayed over the full linearised range . To clear SP2 to Default 'out use F19 or F15, then briefly de-power. 13

The following sensor types can be used for negative temperatures. The negative value shown against each type is automatically set by the choice of sensor (Function 16) and requires enablin g

with Function 17, Option 1 . Type T thermocouple -90C, - 130F PT100IRTD -100C, - 150F Type N thermocouple -50- 58F Type K thermocouple + non linearised

The chosen parameters may be permanently locked into memory by removing or altering the position of the link behind the lower front fascia as shown below.

When the Parameter lock has been applied, only the setter adjustments are possible (see Section 812) .
Note that locked positions (2) and (3) are alternatives and that the link socket is in the 'inactive' position in (2).

Parameter Setting Position (1) Locked Position (2) Locked Postion (3) Note: It is Important to switch off briefly after changing link positio n

The sette' can perform the following 2 . Adjust the second set point - SP2. operatiors by depressing the recessed (assuming Function 19 either Options key P. 1, 2 or 3 have been selected). 1 . Adjust manual reset 3 . Lock the main set point - SP1 to (PD, P and ON/OFF modes only) - prevent adjustment b y

see Section 87 for key sequences. the operator.


EE1 - Sensor burnou t
Depending on the selection made a t

Functions 20 and 21, the SP1 and SP2 outputs ire turned ON or OFF. The main temperature display, on a fault indication, is replaced by 'EE' Flashing, followed by a digit . This indicates that an error has been detected in the system. Action should be taken as follows ; Note : Itttpair and Ilecalibration

Check sensor and/or connections then Rey *


EE2 - Temporary System Error

Self clearing
EEO - loss of calibration EE9 - NVM data fault (non volatile memory)

Consult

Due to the nature of Its design, the 9000 can only be repaired and recalibrated by using special equipment and should be returned to a if found to be faulty.

14

SECTION C I Tunin g
If the preset PID DEFAULT values prove to be unsuitable for a particular application, the following method can be used to establish new settings which should be acceptable and which can be adjusted to give optimum control . This method of tuning may differ from that used on other controllers. The first step is to control the system with the instrument in ON/OFF mode and use these results to calculate the new Parameter values for SP1 . Check that all settings are in DEFAULT . If required, range adjustments should be made first . Refer to Section 36. Check that Parameter Lock is in the Parameter Setting position (Section 811) and proceed as follows : i . Adjust Proportioning Time to ON/OFF (This switches off all other control terms and sets Hystersis to 1 .25% of full scale) . ii . Key in Set-point temperature. iii . Switch on and allow the process to stabilise . Then monitor process temperature, ideally using t . chart recorder, or alternatively by taking readings from the display at regular interv ls, as frequently as possible . The results should look similar to the example .

iv . Using the figires obtained for the oscillation period (T) seconds and amplitude (A) degrees, the following Parameter values can be calculated . a. Proportonal Time/Cycle Rate = T If 10 seconds or less use SSR . 20 b . Proportional Bend %/ = A x 1,5 x 100 Set to next LARGER % setting. Gain % full scale c . Derivative Time/ Rate = T Set to next SHORTER time setting . 10 d . Integral Time/Auto Reset = T Set to next LONGER time setting . ' (Approach control will be activated in DEFAULT setting = 1 .5 x prop band . If the warm up characteristic is unacceptable, refer to Section C6) .
v. Enter these new values and restart the process from cold .

The above settings can be further adjusted to give optimum performance . The following curves and notes will provide guidance for tuning the individual contro l

terms. _

~~

-'15

Setting cetermnes the Cycle rate of the output device . In the interest of long contact life this shoLId be the slowest lOnge$t setting) possible if relay output is being used . Otherwise there is no disadvantage in using faster settngs.

Ideal Setting Setting Too Lon g This term is employed to smooth out the Oscillating control characteristic typical of ON/OFF control . A feature: of proportional control is that the system may run at a slightly different temperature to the set-point (Offset), and have a slower reaction to disturbances .

1(
Setting too narrow Settin Idea l 9 Setting too wide slow
system oscillates warm up and poor control The purpose of the integral term is to automatically correct for offset errors Caused by the introduction Of PROPORTIONAL control . If incorrectly set this can cause instability or increase warm up time .

Setting too short Ideal setting Setting too lon g

16

The derivative term is added to PROPORTIONAL control action to speed up response to disturbances aid to suppress overshoot . In applications where these two requirements would need different settings, the use of Derivative Approach Control for adjusting warm up characteristics allows the Derivative setting to be biased in favour of disturbance behaviour.

I disturbance

f I
disturbance

I disturbanc e

Setting too long Ideal setting Setting too short

This feature allows the warm up characteristics to be tuned separately from normal running conditions and is particularly useful for applications where the sensor is some distance from the heater . The setting determines where the derivative action starts with respect to set-aoint . The smaller the setting, the closer to set-point .

Setting too small Setting ideal Setting too large Where a given application cannot be tuned to give acceptable results over the required range of process temperatures and conditions, it is possible that better results may be obtained with Proportional, Derivative and Approach Control terms only . 'Cann . Ideal settings for these systems are very dependant on the application, and are often best determined by experiment.

The following general points may prove useful for initial consideration .
A common characteristic is that there is a considerable difference between the syste m

response to the input of heating and of cooling energy .

In general, bosh channels can be set independantly using the Tuning guidelines for settings for Proportional Time and Proportional Band, and where it is known that one channel has a dominating and rapid effect on system temperature, the employment of narrow hysteresis ON/OFF settings for this may give excellent results . Where both sirtpoints are required to be set close together (small deadband), wide proportional or hysteresis band settings will overlap allowing simultaneous operation of outputs, which may give the best overall control .

17

S BleclrlCJI

Suppy volt ge 940V :157. 5060Hz Oct StNO 612-934


110V :15% 506OH2 Stock NO 612-928 consumption 5VA

Sensors Thermocouples J/K/R/5/T/E IPIS 1966 N NicrosibNisil Fe-Cut4i DIN 43710 External resistance Max 100 ohms Cold junction compensation Rejection typicall y

Output modules Standrd - dual outpu t


SP/ Relay SA 2SOV IC . Resistive load SPOT (contacts de-rated from 16A to give extended lit )

201 (0.OSC/q
Resistance thermometers Pt100/RTO 100 ohms at 0C, plat. DIN 43760/851904 Standard 2 wire Bias current <0,2mA Sensor burnout Automatic protection Fault displayed ' SP1 and 5P2 Default upscale (output of, key dOwnscale Common mode Negligible effect up to 264V rms

SP2 Relay 3A'250V ac . Resistive load SPOT

Accuracy Calibration as uracy mO .25% of range =1 C (o0 .5C In Niles) Control stabilit y
Typically -01!% of full scale, dependent on application

50/60Hz (140 dB) Series mode >1000 :1 negligible effect up to SOmv 50Hz (60 dB)
General Ambient temperature 0 .50C (32 .130F) Noise immunit y Testeo for mains interference on Schaffner 200/222 Interference Simulator . No effect on storeo catd Normal control resumed immediately loliow :ng interference or 'brown out s

Samphng timit 3 samples per secon d


Re-zero of CJt: and auto calibrate every 5 seconds

Temperature coefficien t
<15opprn/C of may Imearised range typical Reference conditions

220C x200, 230/11SV =5%, after 30 minutes settling time

Data retention 10 years with instrument unpowered Safety standards Designed in accordance with.
UI. 873 - Industnal Temperature Controllers, CSA 022.2/244981, VDE 0411 Class I Mouldings in flame retarcent polycarbonate.

Degree of protection Designed in accordance with: IEC 5291976 BS 54901977


Bezel assembly IP-54 'Protected against splashing water and dust '

Case inside panel IP-30 'Protected against >2 .5mm die objects' Dimensions Bezel 48x4803mm/1 .89"xl .89"05" Depth behind panel 115mm/4.4" overall Weight 380g/13oz

18

. . . vn .

0 Control Modes
Default mode (factory) settings SP1 PID P-oporhonal . Integral Derivative Proportional Time/Cycle Rate - 30 sec Proportional Band/Gain 25 %

of Spa n Derivative Time./Rate - 25 sec . integral Time/Auto Reset - 350 sec . SP2 Off Inactive
Key selectable mode s SP1 PID or PD with Approach Control 5P2 C-evlahon Alar m High Low or Out of Limits wolustaole Q0-99oC/F about SP1 setting Control modes - on/off, or Froportlona l

Key selsctabk poirwro ees-SPI Defile ti t Tpt Prop Tlme'Oae Rate .Soms, 1, 5, 10, 20, 30, 60 secs Fast cycle <losec, SSR recommended
Prop Trn'e' Circle rate >1 sec, min on/off times 0.5% x Tpl Linear or: . mternol/exterrlal, key 50ms Cycle rate Xpt Prop Band 'Gai n b1 Derivative Time Rate AC Approach contro l 0 .5,1,2,9 .5.3,5,10.20'. span 2.5: off, 5, 10, 25, 50, 100, 200 sec 25 sec off, 0.5, 1, 15, 2, 25, 3, 4, 5xtPI 1 .5 Derivative, activated-about SP 1

30 sec

Tv Integral Time Auto Rese t MR Manual reset

off . 25, 50 . 100, 200. 350, 600, 100 0 W


PD, P a onioff modes, x9900!F about SP1

350 sec Do

xsol Hysteresis

025, 0 .5, 1 . 1 .25, 1 .5, 25, 5, 10%x span None On/off mope onl y

Key aketbk partltnetevs-$Pt Daefauft


Tot xo2'xfa2 Prop -,me Prop Bana and 'lysteresn as SP1 None

19

C C

Displays
Main digital display 4 High brightness 7 segment LEDs, 10mm (0.4) high displaying Normally - Process temperature or main set point - SP1 or Option/Function No, display or setting or Fault conditions Range Norma -199 to 1999C/F High resolution -99 .9 to 199 .9C/ F Negative temp Defaults to set point minimum of 0C/32F, key to enable negative temperatures, ;Sensors T/Pt100 RTD) Linearisec to -90 C

K&N non Linearised to -50C .


Error indicato r

5 state/3 LUDs Default <x1%, 1 .3%, >3% xFS High resolution <x0 .5%, 0.5-1 .5%, >1 .5% Low resolution <=2%, 2-6%, >6% Output Indicator s SP7 Square, green LED 5a2 Round, amber LE D
Setting 3 operator keys, I flush key

Sr OfIR4p -liaeartq and da/sutM aaetiap' C


Sensor type unearise0 range Tolerance Default FS

J K N R S

0-800C 0-1200C 0-1200C 0-300C 300-1600C 0-400C 400-600C 600-1600C -90 to 250C 0-600C 0-800C -90 to 250C 250-400C

C tC tC 4C 2C 4C 2C 1.C 1.C !C !C 0.25C 0.5C

400 C 400 C 400 C 1600 C 1600 C Range adjustments (including Default) only limit setpoint values. Process temperatures will be displayed over the full linearised range .

T E Fe-Cum Ff100/ RTD

250 C 500 C 400 C 200 C

20

USERS NOTES :-

Its Components Un t.d March 1987

S-ar putea să vă placă și