Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com
1
GE Consumer & Industrial Multilin
Protection Fundamentals
By John Levine
2
GE Consumer & Industrial Multilin
Outline
Introductions Tools
Enervista Launchpad On Line Store Demo Relays at Levine
Objective
We are here to help make your job easier. This is very informal and designed around Applications. Please ask question. We are not here to preach to you. The knowledge base in the room varies greatly. If you have a question, there is a good chance there are 3 or 4 other people that have the same question. Please ask it.
4
GE Consumer & Industrial Multilin
Tools
5
GE Consumer & Industrial Multilin
6
GE Consumer & Industrial Multilin
7
GE Consumer & Industrial Multilin
Relays at L-3
8
GE Consumer & Industrial Multilin
9
GE Consumer & Industrial Multilin
10
GE Consumer & Industrial Multilin
ANSI Symbols
11
GE Consumer & Industrial Multilin
12
GE Consumer & Industrial Multilin
13
GE Consumer & Industrial Multilin
Protection Fundamentals
14
GE Consumer & Industrial Multilin
Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition Speed: Usually the faster the better in terms of minimizing equipment damage and maintaining system integrity Simplicity: KISS Economics: Dont break the bank
15
GE Consumer & Industrial Multilin
16
GE Consumer & Industrial Multilin
Types of Protection
Overcurrent Uses current to determine magnitude of fault
Simple May employ definite time or inverse time curves May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive May use various polarizing voltages or ground current for directionality Communication aided schemes make more selective
20
GE Consumer & Industrial Multilin
Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI (Clearing Time Interval)
CTI
5 5 +5 5 5 +5
Distribution Substation
21
GE Consumer & Industrial Multilin
(TOC) Coordination
t
Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI
CTI
Distribution Substation
22
GE Consumer & Industrial Multilin
23
GE Consumer & Industrial Multilin
Multiples of pickup
24
GE Consumer & Industrial Multilin
Bus Y a 5 E
a E
b c D C
d e B A
b d
c 5 C
25
GE Consumer & Industrial Multilin
Types of Protection
Differential
current in = current out Simple Very fast Very defined clearing area Expensive Practical distance limitations
Line differential systems overcome this using digital communications
26
GE Consumer & Industrial Multilin
5pu
IP
CT-X CT-Y
IP
Differential
Note CT polarity dots This is a through-current representation Perfect waveforms, no saturation
27
GE Consumer & Industrial Multilin
IS
IS
Relay
IR-X IR-Y
+5 5+ (-5 = 5 )
Current, pu
-5 DIFF CURRENT
5pu
IP
5pu
Fault
CT-X CT-Y
IP
Differential
Note CT polarity dots This is an internal fault representation Perfect waveforms, no saturation
28
GE Consumer & Industrial Multilin
X
IS IS
Relay
IR-X IR-Y
+5 5+ (+5 = 5 )
Current, pu
-5 DIFF CURRENT
Types of Protection
Voltage Uses voltage to infer fault or abnormal condition May employ definite time or inverse time curves May also be used for undervoltage load shedding
Simple May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive
29
GE Consumer & Industrial Multilin
Types of Protection
Frequency Uses frequency of voltage to detect power balance condition May employ definite time or inverse time curves Used for load shedding & machinery under/overspeed protection
Simple May be slow Selectivity at the cost of speed can be expensive
30
GE Consumer & Industrial Multilin
Types of Protection
Power Uses voltage and current to determine power flow magnitude and direction Typically definite time
Complex May be slow Accuracy important for many applications Can be expensive
31
GE Consumer & Industrial Multilin
Types of Protection
Distance (Impedance)
Uses voltage and current to determine impedance of fault Set on impedance [R-X] plane Uses definite time Impedance related to distance from relay Complicated Fast Somewhat defined clearing area with reasonable accuracy Expensive Communication aided schemes make more selective
32
GE Consumer & Industrial Multilin
ZL
Impedance
Relay in Zone 1 operates first Time between Zones is called CTI
R
T2 T1 ZA
ZB
21
21
A
Source
B
33
GE Consumer & Industrial Multilin
POTT will trip only faulted line section RO elements are 21; 21G or 67N
34
GE Consumer & Industrial Multilin
r Powe More
SS SS
More
r Powe
-P
+P
-Q
180 Opposites!
35
GE Consumer & Industrial Multilin
Generation-typically at 420kV
Transmission-typically at 230765kV Receives power from transmission system and transforms into subtransmission level
Subtransmission-typically at 69-161kV Receives power from subtransmission system and transforms into primary feeder voltage Distribution network-typically 2.469kV Low voltage (service)-typically 120-600V
36
Protection Zones
1. Generator or Generator-Transformer Units 2. Transformers 3. Buses 4. Lines (transmission and distribution) 5. Utilization equipment (motors, static loads, etc.) 6. Capacitor or reactor (when separately protected)
Bus zone Unit Generator-Tx zone Transformer zone Line zone Bus zone Transformer zone Bus zone Motor zone
~
Generator XFMR Bus Line Bus XFMR Bus Motor
37
GE Consumer & Industrial Multilin
Relay Zone A
Zone A
Relay Zone B
Zone B
Zone A
Relay Zone B
Zone B
CTs are located at both sides of CB-fault between CTs is cleared from
both remote sides
39
GE Consumer & Industrial Multilin
42
GE Consumer & Industrial Multilin
What Info is Required to Apply Protection What Info is Required to Apply Protection
1. One-line diagram of the system or area involved 2. Impedances and connections of power equipment, system frequency, voltage level and phase sequence 3. Existing schemes 4. Operating procedures and practices affecting protection 5. Importance of protection required and maximum allowed clearance times 6. System fault studies 7. Maximum load and system swing limits 8. CTs and VTs locations, connections and ratios 9. Future expansion expectance 10.Any special considerations for application.
43
GE Consumer & Industrial Multilin
44
GE Consumer & Industrial Multilin
46
GE Consumer & Industrial Multilin
47
GE Consumer & Industrial Multilin
48
GE Consumer & Industrial Multilin
49
GE Consumer & Industrial Multilin
1-Line [1]
50
GE Consumer & Industrial Multilin
1-Line [2]
3-Line
52
GE Consumer & Industrial Multilin
Diagram Comparison
53
GE Consumer & Industrial Multilin
55
GE Consumer & Industrial Multilin
56
GE Consumer & Industrial Multilin
Better practice, do not change the contact style, but rather use marks like these to indicate nonstandard reference position
57
GE Consumer & Industrial Multilin
5b 5 5 5 TC 5b 5 5a 5
58
GE Consumer & Industrial Multilin
5 /a 5 or 5 /b 5
Relay
T/C Coil
59
GE Consumer & Industrial Multilin
Relay
Relay
Breaker
Breaker
60
GE Consumer & Industrial Multilin
Current Transformers
Current transformers are used to step primary system currents to values usable by relays, meters, SCADA, transducers, etc. CT ratios are expressed as primary to secondary; 2000:5, 1200:5, 600:5, 300:5 A 2000:5 CT has a CTR of 400
61
GE Consumer & Industrial Multilin
Excitation Curve
63
GE Consumer & Industrial Multilin
Relaying
64
GE Consumer & Industrial Multilin
Current into the Dot, Out of the Dot Current out of the dot, in to the dot
Forward Power
IP
IS
Relay or Meter
IR
Forward Power
IP
IS
Relay or Meter
IR
65
GE Consumer & Industrial Multilin
Voltage Transformers
Voltage (potential) transformers are used to isolate and step down and accurately reproduce the scaled voltage for the protective device or relay VT ratios are typically expressed as primary to secondary; 14400:120, 7200:120 A 4160:120 VT has a VTR of 34.66
VP VS
Relay
66
GE Consumer & Industrial Multilin
67
GE Consumer & Industrial Multilin
Secondary Circuit
Case ground made at IT location Secondary circuit ground made at first point of use
68
Equipment Grounding
Prevents shock exposure of personnel Provides current carrying capability for the ground-fault current Grounding includes design and construction of substation ground mat and CT and VT safety grounding
69
GE Consumer & Industrial Multilin
System Grounding
Limits overvoltages Limits difference in electric potential through local area conducting objects Several methods
Ungrounded Reactance Coil Grounded High Z Grounded Low Z Grounded Solidly Grounded
70
GE Consumer & Industrial Multilin
System Grounding
1. Ungrounded: There is no intentional ground applied to the system-however its grounded through natural capacitance. Found in 2.415kV systems. 2. Reactance Grounded: Total system capacitance is cancelled by equal inductance. This decreases the current at the fault and limits voltage across the arc at the fault to decrease damage.
71
GE Consumer & Industrial Multilin
System Grounding
3. High Resistance Grounded: Limits ground fault current to 10A-20A. Used to limit transient overvoltages due to arcing ground faults. R0 <= X0C/3, X0C is capacitive zero sequence reactance 4. Low Resistance Grounded: To limit current to 25-400A R0 >= 2X0
72
GE Consumer & Industrial Multilin
System Grounding
5. Solidly Grounded: There is a connection of transformer or generator neutral directly to station ground. Effectively Grounded: R0 <= X1, X0 <= 3X1, where R is the system fault resistance
73
GE Consumer & Industrial Multilin
Grounding Differences.Why?
Solidly Grounded
Much ground current (damage) No neutral voltage shift
Line-ground insulation
Limits step potential issues Faulted area will clear Inexpensive relaying
74
GE Consumer & Industrial Multilin
Grounding Differences.Why?
Somewhat Grounded
Manage ground current (manage damage) Some neutral voltage shift Faulted area will clear More expensive than solid, less expensive then ungrounded
75
GE Consumer & Industrial Multilin
Grounding Differences.Why?
Ungrounded
Very little ground current (less damage) Big neutral voltage shift
Must insulate line-to-line voltage
May run system while trying to find ground fault Relay more difficult/costly to detect and locate ground faults If you get a second ground fault on adjacent phase, watch out!
76
GE Consumer & Industrial Multilin
Low/No Z
5 5 0 0
5N 5 5N 5
5 5 5 5
5N 5 5N 5
5 5 5 5
5N 5 5N 5
77
GE Consumer & Industrial Multilin
Med/High Z
5 5 0 0 5G 5 5G 5
5 5 5 5 5G 5 5G 5
5 5 5 5 5G 5 5G 5
78
GE Consumer & Industrial Multilin
79
Substation Types
Single Supply Multiple Supply Mobile Substations for emergencies Types are defined by number of transformers, buses, breakers to provide adequate service for application
80
GE Consumer & Industrial Multilin
81
GE Consumer & Industrial Multilin
82
GE Consumer & Industrial Multilin
Bus 2
Breaker-and-a-half allows reduction of equipment cost by using 3 breakers for each 2 circuits. For load transfer and operation is simple, but relaying is complex as middle breaker is responsible to both circuits
Ring bus advantage that one breaker per circuit. Also each outgoing circuit (Tx) has 2 sources of supply. Any breaker can be taken from service without disrupting others.
84
GE Consumer & Industrial Multilin
Bus 2
Double Bus: Upper Main and Transfer, bottom Double Main bus
Main-Reserved and Transfer Bus: Allows maintenance of any bus and any breaker
85
Switchgear Defined
Assemblies containing electrical switching, protection, metering and management devices Used in three-phase, high-power industrial, commercial and utility applications Covers a variety of actual uses, including motor control, distribution panels and outdoor switchyards The term "switchgear" is plural, even when referring to a single switchgear assembly (never say, "switchgears") May be a described in terms of use:
"the generator switchgear" "the stamping line switchgear"
86
GE Consumer & Industrial Multilin
Switchgear Examples
Metal-enclosed switchgear
Bus not insulated Breakers or switches not required to be draw-out No compartment barriering required
88
GE Consumer & Industrial Multilin
89
GE Consumer & Industrial Multilin
91
GE Consumer & Industrial Multilin
92
GE Consumer & Industrial Multilin
93
GE Consumer & Industrial Multilin
96
GE Consumer & Industrial Multilin
Contribution to Faults
97
GE Consumer & Industrial Multilin
98
GE Consumer & Industrial Multilin
A C G B
99
GE Consumer & Industrial Multilin
Z X
100
GE Consumer & Industrial Multilin
101
GE Consumer & Industrial Multilin
102
GE Consumer & Industrial Multilin
103
GE Consumer & Industrial Multilin
104
GE Consumer & Industrial Multilin
Useful Conversions
105
GE Consumer & Industrial Multilin
Standard practice is to define Base power 3 phase Base voltage line to line Other quantities derived with basic power equations
106
GE Consumer & Industrial Multilin
107
GE Consumer & Industrial Multilin
108
GE Consumer & Industrial Multilin
base
base
109
GE Consumer & Industrial Multilin
Zactual
0 Zpu2 =Zpu1 x kV
111
GE Consumer & Industrial Multilin
112
GE Consumer & Industrial Multilin
Utility Information
kV MVA short circuit Voltage and voltage variation Harmonic and flicker requirements
113
GE Consumer & Industrial Multilin
Generator Information
Rated kV Rate MVA, MW Xs; synchronous reactance Xd; transient reactance Xd; subtransient reactance
114
GE Consumer & Industrial Multilin
Motor
kV Rated HP or KW Type
Sync or Induction
Drive
Is it regenerative Harmonic spectrum
115
GE Consumer & Industrial Multilin
Transformers
Rated primary and secondary kV Rated MVA (OA, FA, FOA) Winding connections (Wye, Delta) Impedance and MVA base of impedance
Reactors
Rated kV Ohms
116
GE Consumer & Industrial Multilin
ANSI 1-Line
118
GE Consumer & Industrial Multilin
IEC 1-Line
119
GE Consumer & Industrial Multilin
120
GE Consumer & Industrial Multilin
121
GE Consumer & Industrial Multilin
122
GE Consumer & Industrial Multilin
A Study of a Fault.
123
GE Consumer & Industrial Multilin
124
GE Consumer & Industrial Multilin
125
GE Consumer & Industrial Multilin
Current limiting fuses (provides partial protection only for a limited current range)
FlexCurve for improved coordination opportunities Employ 51VC/VR on feeders fed from small generation to improve sensitivity and coordination Employ UV light detectors with current disturbance detectors for selective gear tripping
129
GE Consumer & Industrial Multilin
130
GE Consumer & Industrial Multilin
131
GE Consumer & Industrial Multilin
132
GE Consumer & Industrial Multilin
133
GE Consumer & Industrial Multilin
134
GE Consumer & Industrial Multilin
135
GE Consumer & Industrial Multilin
136
GE Consumer & Industrial Multilin
Protection Fundamentals
QUESTIONS?
137