REYROLLE
TRANSMISSION NETWORK
DISTRIBUTION NETWORK
Busbars Interconnectors Double Wound Transformers Radial Feeders Ring Mains Embedded Generation Motors
Created:
REYROLLE
Power system should be planned, constructed & operated such that there is sufficient generation to meet predicted demand as economically as possible.
Designed to avoid loss of synchronism, voltage collapse, load shedding or unacceptable frequency/voltage variations when faults occur and/or plant is switched out of service.
All under varying conditions of production and consumption of power. Provision must also be made for necessary maintenance to be carried out
Created:
REYROLLE
Back-up (Redundancy)
Cost Effective
Created:
REYROLLE
For Transmission Systems: Technical Considerations are more Important than Cost!
Created:
REYROLLE
Back-Up Protection
Different Operating Principle Slower (Often time delayed)
REYROLLE
Created:
REYROLLE
CTs on busbar side of line Circuit Breakers & near side of Bus Section Breaker
CTs on Line side of Line Circuit Breakers & far side of Bus Section Breaker
Overlapped Zones of Protection provide cover for Circuit Breakers and connections.
Created:
REYROLLE
Feeder Protection
Main Protection 2 Independent Feeder Protection systems using separate CTs Preferably utilising different principles of operation Different relay or hardware platform to avoid common mode failure Any signalling or communications channels should be diversely routed
Back-up Protection Inherent back-up Protection Zones 2 & 3 of distance protection Back-up IDMTL Overcurrent device at each feeder end Where distance protection is not used and additional 2-phase IDMTL IDMTL device is also applied
Created:
REYROLLE
Feeder Protection-1
1ST Main (Current Diff) 2ND Main (Distance)* Back-up O/C (IDMTL)* Circuit Breaker Fail
OHL
Channel 2
Circuit Breaker Fail Back-up O/C (IDMTL) 2ND Main (Distance) 1ST Main (Current Diff)
Created:
REYROLLE
Feeder Protection-2
1ST Main (Current Diff) 2ND Main (Current Diff) IDMTL Overcurrent 2-phase Overcurrent Circuit Breaker Fail
OHL
Intertrip Channel 2
Intertrip Channel 1
Circuit Breaker Fail 2-phase Overcurrent IDMTL Overcurrent 2ND Main (Current Diff) 1ST Main (Current Diff)
Created:
REYROLLE
2 Independent Systems of overall differential protection Both systems will use common set of CTs These Systems will operate 2 separately energised trip circuits
Back-up Protection
2-Stage HV O/C Protection Stage 1 - Faults beyond LV circuit breaker Stage 2 - Time Delayed - Trips all circuit breaker capable of supplying fault current HV Three phase overcurrent from the same CTS LV 3-phase overcurrent protection LV E/F from residually connected IDML relay
Created:
REYROLLE
To Trip Circuit 1
Transformer Overall 1
SGT1
Winding Temperature
HV Overcurrent
Transformer Overall 2
To Trip Circuit 2
Created:
REYROLLE
2 Independent Systems of overall protection (common set of CTs) Restricted Earth Fault for HV and LV winding respectively (Earth Faults only) 1 Overall biased differential Protection (Slower, but reacts for all faults ) Back-up Protection
2-Stage HV O/C Protection Stage 1 - Faults beyond LV circuit breaker Stage 2 - Time Delayed HV Three phase overcurrent from the same CTS LV 2-stage LV unrestricted earth fault Stage 1 - Faults beyond LV circuit breaker Stage 2-Time Delayed - All circuit breakers supplying fault current
Created:
REYROLLE
Transformer Protection
2-Stage HV OC Guard
2-Stage HV OC
Biased Differential Tapchanger Selector Buchholtz Tapchanger Diverter Oil Surge Main Buchholtz Surge SGT1 Aux Buchholtz Surge LV Unrestricted EF St 1 CT/VT Gas Detection
To Trip Circuit 1
* HV & LV connections protection may also be included (using CTs mounted on Transformer HV & LV Bushings)
Winding Temperature
HV Overcurrent HV REF LV Unrestricted EF St 2 LV REF
To Trip Circuit 2
Created:
REYROLLE
Back-up Protection Afforded by IDMT Overcurrent protection on Bus Sections & Bus Couplers where appropriate Further back-up protection provided by Zones 2 & 3 of any remote Feeder distance protection
Created:
REYROLLE
RESERVE 2
206 286
MAIN 1
184 104 204 284
MAIN 2
180
105
205
280
Main 1
Main 2
186 184 106 104 206 204 286 284
Res. 1
Res. 2
166
169
Check
Any one of the Discriminating Zones AND the check zone must operate to trip the breakers
Created:
REYROLLE
Mesh Corner 1
Mesh Corner 4
Mesh Corner 2
Mesh Corner 3
Created:
REYROLLE
Feeder End
Transformer End
Created:
REYROLLE
CBTC
TD 0.15s
CB 'E'
+
CB 'D' CB 'F' BTRTR
Prot. BF C CK +
m
Backtrip
r
Intertrip
BTRTR - Back trip receive trip relay BTD - Back trip discriminating relay TD - Time delay relay T - Trip relay CBTC - Circuit breaker trip coil
Created:
REYROLLE
System Fault
Time (ms)
BF C
Tr
ip
i rc C
t ui
Created:
REYROLLE
80
60
40
28 0 14 0 20 26 0 22 0 20 0 18 0 16 0 12 0 10 0 24 0
Created:
REYROLLE
For Transmission Systems: Technical Considerations are more Important than Cost!
Created:
REYROLLE
Back-Up Protection
Different Operating Principle Slower (Often time delayed)
REYROLLE