ZonePRO Modulating Thermostats

Technical Training July 10, 2006

Models and Features


Models with 1 output - TB6980A1007 (Floating) - TB7980A1006 (Analog 0-10V or 2-10V) Models with 3 outputs - TB6980B1006 (1st output is floating) - TB7980B1005 (1st output is analog 0-10V or 2-10V) - 2nd output can be configured for:
Analog 0-10V Analog 2-10V 24V

- 3rd output is 24V only Features for all models - Automatic changeover (duct sensor required) - Manual changeover (remote switch or relay required) - Night setback - Min and Max temperature setpoint stops
2

Applications and Accessories


Hydronic and pressure dependent VAV with or without reheat Non-programmable Up to three outputs depending on model Can be used for: - Floating or Analog damper/valve actuator control - Damper/valve actuator with duct reheat and aux heat (B models) - Hydronic systems (room control, perimeter heating and cooling) Compatible accessories - R841 family of electromechanical relays - 50014156-002 remote room sensor - 50014157-001 duct temperature sensor - 32004800-001 bare thermistor

Terminal Connections
Terminal 1 2 3 4 3 4 5 6 7 8 9 10 9 11 9 12 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB Description Power supply

TB7980 models Output 1 TB6980 models

Output 2 (TB6980B and TB7980B models) WARNING: Make sure SW6 is set to the proper setting (Triac or Analog) Output 3 (TB6980B and TB7980B models)

External sensor input. (For applications requiring an external sensor)

Mode Changeover input (N.O contact).

Night Setback activation input (N.O. contact)

Typical Applications

Relay

TB6980B

24 VAC not COM

Damper control with electric reheat and auxiliary hot-water heating


5

Typical Applications

Relay

TB7980B

Relay

Damper control with electric reheat and auxiliary baseboard heating


6

Typical Applications

50014157001

Relay

TB7980B

Damper control with automatic changeover, electric reheat and central cooling
7

Typical Applications

50014157-001 Relay

TB6980B

Temperature control of fresh air supply


8

Typical Applications

TB7980B

TB7980B

TB7980B

Changeover and NSB inputs sharing the same 24-Vac transformer


9

Configuration TB7980B1005

Modle 1A2T

Application

Default mode & output 1 type

Output 2 type

Output 3 type

Output 3 activation

NSB value

Output 1 min. opening 0 1 0% 10%

Maximum setpoint

Minimum setpoint

0 1

Internal sensor Room

0 1

Cool / 0-10V Heat / 0-10V

0 1

Not used SSR 24 VAC N.C. Valve N.O. Valve Mech. relay SSR 3-32V SCR 0-10V Act. 0-10V

0 1

Not used SSR 24 VAC

0 1

100% 10%

1 2

1C (2F) 2C (4F)

2 3 4 5

Return Supply Auto changeover Limited cooling

2 3

Cool / 2-10V Heat / 2-10 V

2 3 4 5 6 7

2 3 4 5

N.C. Valve N.O. Valve Mech. Relay Contact

2 3 4 5 6 7

20% 30% 40% 50% 60% 70%

3 4 5 6 7 8

3C (6F) 4C (8F) 5C (10F) 6C (12F) 7C (14F) 8C (16F)

2 3 4 5

20% 30% 40% 50%

Can be set between 35C (95F) and "minimum setpoint + 1 Default value is 35C (95F)

Can be set between 10C (50F) and maximum setpoint -1

Default value is 10C (50F)

Act. / 210V

8
9

80%
90%

9C (18F)

Default configuration

10

Configuration TB6980B1006

Modle 1F2T

Application

Default Mode

Output 2 type

Output 3 type

Output 3 activation

NSB value

Output 1 min. opening


0 1 2 3 4 5 0% 10% 20% 30% 40% 50%

Output 1 opening time


0 1 2 3 4 5 6 7 8 80 90 100 110 120 130 140 150 160

Maximu m setpoint

Minimu m setpoint

0 1 2 3 4 5

Internal sensor Room Return Supply Auto changeover Limited cooling

0 1

Cool Heat

0 1 2 3 4 5 6 7 8

Not used SSR 24 VAC N.C. Valve N.O. Valve Mech. relay SSR 3-32V SCR 0-10V Act. 0-10V Act. / 2-10V

0 1 2 3 4 5

Not used SSR 24 VAC N.C. Valve N.O. Valve Mech. Relay Contact

0 1 2 3 4 5 6 7 8 9

100% 10% 20% 30% 40% 50% 60% 70% 80% 90%

1 2 3 4 5 6 7 8 9

1C (2F) 2C (4F) 3C (6F) 4C (8F) 5C (10F) 6C (12F) 7C (14F) 8C (16F) 9C (18F)

Can be set betwee n 35C (95F) and min setpoint + 1 Default value is 35C (95F)

Can be set between 10C (50F) and max setpoint -1 Default value is 10C (50F)

Default configuration

11

Configuration menu TB6980B Output 1 Activation


output 1 default mode

12

Configuration menu TB6980B Output 1 Modes

Menu setting 0
1 2

TB7980 models Cool / 0-10 V analog (max. of 10 min. refresh)


Heat / 0-10 V analog (max. of 10 min. refresh) Cool / 2-10V analog (max. of 10 min. refresh)

TB6980 models
Cool (24 V tri-state floating) Heat (24 V tri-state floating)

Heat / 2-10 V analog (max. of 10 min. refresh)

13

Configuration menu TB6980B Output 2 Activation


output 1 default mode
Output 1 jumps at 100% if there is an instant 5F difference

14

Configuration menu TB6980B Output 2 Modes


Menu setting
0 Not used

Description
24 VAC pulsed (triac) 1 sec. Cycle
24 VAC pulsed (triac) / 10 min. cycle / direct action (e.g., N.C. thermal valve) 24 VAC pulsed (triac) / 10 min. cycle / reverse action (e.g., N.O. thermal valve) 24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical relay such as R841) 0-10 V pulsed / 1 sec. Cycle 0-10 V analog / 1 sec. Refresh (e.g., SCR controlled device such as re-heater)

1
2

5 6

7
8

0-10 V analog / max. of 10 min. refresh (e.g., valve)


2-10 V analog / max. of 10 min. refresh (e.g., damper)

15

Configuration menu TB6980B Output 3 Activation


output 1 default mode
Output 1 jumps at 100% if there is an instant 5F difference Output 2 jumps at 100% if there is an instant 11F difference

16

Configuration menu TB6980B Output 3 Modes


Menu setting
0 1 2 Not used 24 VAC pulsed (triac) 1 sec. Cycle 24 VAC pulsed (triac) / 10 min. cycle / direct action (e.g., N.C. thermal valve) 24 VAC pulsed (triac) / 10 min. cycle / reverse action (e.g., N.O. thermal valve) 24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical relay such as R841) N.O. contact (The contact closes when output 1 reaches or exceeds set percentage)

Description

17

Configuration menu TB6980B Mode Output 3 Activation Contact


output 1 default mode

18

Configuration and Operation


Configuration - Dip switches
Temperature display, F or C (SW1)
Access mode (SW2) Output 2 type (SW6) This sets output 2 type (analog or triac)

Operation - Backlight (on for 12 seconds) - Temperature setting by 1 increments


(2F in changeover) - Output display (Hold Override for 4 seconds)

19

Operation (continued)
Operation - Changeover
Manual changeover (contact)
Automatic changeover (9F differential between duct and room) Night setback

Override (2 hours)

Error codes - E1 (internal sensor defective) - E2 (internal sensor shorted) - E3 (external temperature sensor defective or not connected) - E4 (external temperature sensor shorted)
20

System Components
OS # TB6980A100 7 TB6980B100 6 TB7980A100 6 TB7980B100 5 2.7 x 4.6 x 1.0 in. (69 x 118 x 27 mm) VC7930, VC7934, VC7936, ML7984A4009, ML7420, ML7161A2008, MN7505A2001 Dimensions Compatible Valves and Actuators Sensors and Accessories Replaces T6984A1059 R841 Series of electromechanical relays, 50014157-001 air duct sensor, 50014156-002 space sensor, ST6008A1003 and ST7009A1003 time clocks, 209651A wall plate T6984D1046, T6984E1043 T7984A1057, T7984A1065 T7984B1055, T7984C1053

VC6930, VC6934, VC6936, ML6984A1006, ML6420, ML6161B2024, MN6105A1011

ML6984 ZonePRO

MN7505

ST7009
21

VC7930

Literature and Point of Purchase Materials


TECHNICAL LITERATURE 62-0238 63-4370 63-8563 Installation Instructions Guide Specification Actuator Cross Reference SALES LITERATURE 63-9555 n/a Brochure Flyer

All ZonePRO sales, technical and PowerPoint materials can be downloaded at customer.honeywell.com/buildings
22

www.honeywell.com