Sunteți pe pagina 1din 29

The New SafEye Xenon 800

IR Open-Path Gas Detector

MSA 2008

Open Path Gas Detection


Fast detection of a wide range of hydrocarbons
Measures gas cloud concentration over many meters Proven, reliable gas detection technology

MSA 2008

Applications
Indoor and outdoor installations for: Offshore oil & gas exploration and production Fence line emission monitoring at industrial sites Petrochemical storage areas LNG/LPG storage, pumping, and filling Pipelines Paint booths and paint production Bus terminals [natural gas powered vehicles]

MSA 2008

LEL Meter Concept


1 LEL meter = a cloud of 5% methane (100% LEL) gas that is one meter across.

MSA 2008

LEL Meter Concept


1 LEL meter = a cloud of 0.25% methane (5% LEL) gas that is twenty meters across.

MSA 2008

New Features
Advanced Xenon Flash source

Improved operation with up to 90% signal reduction

Improved, low-profile stainless steel housings w/swivel mounts Heated detector and source optics

MSA 2008

New Features
Explosion-proof enclosure Data port (I.S. approved)

Heated optics
Small (robust) footprint swivel mount

MSA 2008

Swivel Mount Unit

thumb screws for easy alignment

mounting plate
MSA 2008

Intrinsically Safe Hand-Held Kit


carrying case

General Purpose Hand-Held Kit

shoulder strap

intrinsically safe PDA

PDA charger

IR module general purpose PDA

MSA 2008

New Features
3mA: maintenance call early warning of preventative maintenance Programmable configuration and diagnostics via hand-held unit 3 year system warranty, 10-year lamp warranty

MSA 2008

Product Features
High sensitivity and fast response to hydrocarbon gases
Detection range up to 120 meters

Simple installation, alignment and functional check


One-person commissioning

MSA 2008

Product Features
Alignment Kit

filter to check functionality telescope

Allen wrenches

MSA 2008

Product Features
Gases detected: simultaneous detection of flammable gases C1-C8
Models

available specifically for LPG, methane, natural gas and ethylene

MSA 2008

Product Features
Dual-spectrum reference sensor, triple optics detector
Immune

to industrial environments including solar

radiation Continuous operation in extreme environmental conditions Operational integrity with up to 90% reduction in signal

No interconnecting cable between source and detector

MSA 2008

SafEye Xenon 800 Optical System

MSA 2008

Specification
Sensitivity Range: 0 - 5 LEL. m (optional 0-2 LEL. m)
Displacement/Misalignment tolerance to fault : 1

Response time < 3 seconds


Temperature Range: -40 C to + 55 C

MSA 2008

Specification
Warranty:
3 years for the complete system 10 years for Xenon Flash Lamp Explosion proof: Class I, Div. I, Groups A-D, Class I, Div. 2, Groups A-D

Approvals: U.S., Canada, Europe, Australia


IP Rating: IP66 and IP67 Environmental: meets MIL-STD-810C for humidity, salt, fog, vibration, mechanical shock, high/low temp

MSA 2008

Electrical Specification
Power supply: 24 VDC nominal (18 - 32 VDC)
Power consumption: Detector: 150mA @ 24 VDC Source: 100mA @ 24 VDC (detector/source 300mA peak includes heated optics) Electrical connection: 2 x M25 x 1.5mm or 2 x 14 NPT

MSA 2008

4- 20 mA Output Signals
4mA: Zero
3mA: Maintenance call: early warning of preventative maintenance

2mA: Obscuration/misalignment/beam block


1mA: Zero calibration mode

0mA: Fault

MSA 2008

Maintenance Call
Maintenance Call provides a 3mA output as a pre-warning maintenance signal. The SafEye Xenon 800 Detector continues to function in this mode.

3mA output indicates:


Low signal Dirty window Misalignment Detector parameter at limit value

MSA 2008

Communication Features
RS-485 Modbus RTU communication
Data communication with a host computer or universal controller

Central monitoring from a network of up to 247 addresses


Can network 32 SafEye 800 Detector units (without repeaters)

MSA 2008

SafEye Xenon 800 Detector


HAND-HELD DIAGNOSTIC KIT

MSA 2008

Hand-Held Unit Features


A diagnostic/calibration/interrogation tool that allows one-person commissioning and maintenance
Intrinsically safe connection provides easy and economical interface Quick and easy analysis of system status

MSA 2008

Hand-Held Unit Features


On-site configuration of SafEye 800 Detector parameters Verify detector parameters during installation

Recommended maintenance action to optimize the detectors performance.

MSA 2008

SafEye Xenon 800 Detector


HAND-HELD UNIT
Detector operation:

Detector status Change setup Current gas reading Detector serial number Address (if networked) Many other diagnostic features

MSA 2008

SafEye Xenon 800 Detector


HAND-HELD UNIT
Detector setup:
Select one of 4 standard gas calibrations Select full-scale range: 0-5 or 0-2 LEL.m Select accessory relay activation at warning alarm level Select alarm relay latching option Detector address setting

MSA 2008

SafEye Xenon 800 Detector


HAND-HELD UNIT
Detector maintenance:
Verify the detector installation range Recommended corrective actions Intensity of signal and gain Signal-to-noise ratio Signal-to-reference ratio LEL. M reading using an IR filter

MSA 2008

SafEye Xenon 800 Detector


HAND-HELD UNIT Specification
Intrinsically safe (general purpose version) certified: Class I, Div. I, Groups A-D
Extremely rugged: dust/waterproof rated to IP65

MSA 2008

The New SafEye Xenon 800 Open Path Gas Detection System
The IR open-path detector for all environments & applications

MSA 2008

S-ar putea să vă placă și