Sunteți pe pagina 1din 111

Generator Protection

GRID
Technical Institute

This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.

Generator Protection

The extent and types of protection specified will depend on the following factors :-

Type of prime mover and generator construction


MW and voltage ratings Mode of operation Method of connection to the power system Method of earthing

Generator Protection - P 2

Generator Protection
Types of Prime Mover
Steam Turbines Gas Turbines Hydro Diesel

Construction

Mode of operation

Cylindrial Rotor Salient Pole (Hydro and small generators)

Ratings
Generator Protection - P 3

Base load Peak lopping Standby Power from 200kVA to 1000MVA Voltage from 440V to 24kV

Connection to the Power System


1. Direct :

2. Via Transformer :

Generator Protection - P 4

Generator Protection Requirements


To detect faults on the generator
To protection generator from the effects of abnormal power system operating conditions To isolate generator from system faults not cleared remotely Action required depends upon the nature of the fault. Usual to segregate protection functions into :
Urgent Non-urgent Alarm
Generator Protection - P 5

Generator Faults

Mixture of mechanical and electrical problems. Faults include : Insulation Failure


Stator Rotor

Excitation system failure Prime mover / governor failure Bearing Failure Excessive vibration Low steam pressure etc.

Generator Protection - P 6

System Conditions

Short circuits Overloads Loss of load Unbalanced load Loss of synchronism

Generator Protection - P 7

Generator Failure

Generator Protection - P 8

Generator Failure

Generator Protection - P 9

Generator Failure

Generator Protection - P 10

Generator Failure

Generator Protection - P 11

Stator Earth Fault Protection


Fault caused by failure of stator winding insulation
Leads to burning of machine core welding of laminations

Rebuilding of machine core can be a very expensive process Earth fault protection is therefore a principal feature of any generator protection package TYPE OF PROTECTION OF METHOD EARTHING OF METHOD CONNECTION

Generator Protection - P 12

Method of Earthing

Machine stator windings are surrounded by a mass of earthed metal Most probable result of stator winding insulation failure is a phase-earth fault Desirable to earth neutral point of generator to prevent dangerous transient overvoltages during arcing earth faults Several methods of earthing are in use Damage resulting from a stator earth fault will depend upon the earthing arrangement

Generator Protection - P 13

Method of Earthing
Solidly Earthed Machines : Fault current is high

Rapid damage occurs

burning of core iron welding of laminations

Used on LV machines only

Generator Protection - P 14

Method of Earthing
Generator - Transformer Units

IF ~ 10 15 A

IF ~ 200 300 A

Generator Protection - P 15

Method of Earthing
Desirable to limit earth fault current :
limits damage reduces possibility of developing into phase - phase fault

Degree to which fault current is limited must take into account :


detection of earth faults as near as possible to the neutral point ease of discrimination with system earth fault protection (directly connected machines)

Generator Protection - P 16

Method of Earthing : Fault Current

Limitation of Earth

Earth faults on the power system are not seen by the generator earth fault protection.

Discrimination not required can limit current to very low value. Sometimes down to 5A

Generator Protection - P 17

Method of Earthing : Fault Current


Limit To Generator Full Load Current

Limitation of Earth

Most popular.
Used for ease of fault detection and discrimination. Residual connection of CTs can be used Can result in serious core damage.

Generator Protection - P 18

Stator Earth Fault Protection


Directly Connected Generators :

51N

Earthed Generator : Earth fault relay must be time delayed for co-ordination with other earth fault protection on the power system.

Unearthed Generators : Other generators connected in parallel will generally be unearthed.

50N

51N

Protection is restricted to faults on the generator, grading with power system earth fault protection is not required. A high impedance instantaneous relay can be used (Balanced Earth Fault protection).
Generator Protection - P 19

Percentage Winding Protected


11.5kV; 75,000KVA

xV

250/1A

IS

xV R

For operation S(PRIMARY)

F xV R x.6600 x.200 33 1 x.200 x 0.8x 250

33
S(SECONDARY)

For protection of 90% of winding; x = 1-0.9 = 0.1


Relay setting = 0.8 x 0.1 = 0.08A = 8% of 1A

Generator Protection - P 20

Stator Earth Fault Protection


Generators connected via step-up transformer (resistance earthed) :

51N

50N

Instantaneous protection (50N) : System earth faults ARE not seen by generator earth fault protection instantaneous relay may be used. Set to 10% of resistor rating (avoids operation due to transient surges passed through generator transformer interwinding capacitance). Advantage : Fast

Generator Protection - P 21

Stator Earth Fault Protection

Time delayed protection (51N) : Time delay prevents operation on transient surges.

A more sensitive current setting may be used.


Set to 5% of resistor rating. Advantage : Sensitive On large machines considered worthwhile to use both instantaneous and time delayed.

Generator Protection - P 22

Restricted Earth Fault Protection

RSTAB

64

Protects approx. 90 - 95% of generator winding.

Generator Protection - P 23

Connections for Biased REF


2000/1 ?

500/1 ?

P342/3 Relay Terminal CT Inputs

z
E/F CT Input

Smaller rating machines may have only one (neutral) tail CT brought out for connection
Generator Protection - P 24

Biased REF Protection Operating Characteristic


3

Differential current (x In) =I A +I B +I C +k.I


2

Operate

High sensitivity (5%)


Unit Protection FAST
0

Restrain K1 1 2 3 4

Effective bias (x In) = Max. phase current + k . I 2

Generator Protection - P 25

Neutral Displacement / Residual Overvoltage - Earth Fault Protection

1 3 2

P340 Relay

(1) Derived measurement from 5-limb or 3 x 1 phase VT

(2) Directly measured from a broken delta VT input


(3) Directly measured across an earthing resistor
Generator Protection - P 26

Stator Earth Fault Protection

100% Stator Earth Fault Protection : Standard relays only cover 95% of winding.

Probability of fault occurring in end 5% is low.


On large machines 100% stator earth fault protection may be required.

Two methods :
Low Frequency Injection Third Harmonic Voltage Measurement
Generator Protection - P 27

100% Stator Earth Fault Protection (27TN)

1 3 2

P340 Relay

(1) Derived measurement from 5-limb or 3 x 1 phase VT (2) 3rd harmonic overvoltage (3) 3rd harmonic undervoltage 3rd harmonic undervoltage supervised by 3 phase undervoltage and W/VA/Var at generator terminals
Generator Protection - P 28

100% Stator Earth Fault Protection

Distribution of 3rd harmonic voltage along the stator winding (a) normal operation (b) stator earth fault at star point (c) stator earth fault at the terminals
Generator Protection - P 29

100% Stator Earth Fault Low Frequency Injection


For Large Machines Only

Injection Transformer

Injection Frequency 12.5 20Hz


Alternative Injection Points

51

Provides protection during run up & Standstill


High cost due to injection equipment.

Generator Protection - P 30

Overcurrent Protection
For small generators this may be the only protection applied. With solid earthing it will provide some protection against earth faults. For a single generator, CTs must be connected to neutral end of stator winding.

51

Generator Protection - P 31

Overcurrent Protection
For parallel generators, CTs can be located on line side.

51

Generator Protection - P 32

Differential Protection
Provides high speed protection for all fault types May be : High impedance type : Biased (low impedance) type CTs required in neutral end of winding

Relay
Generator Protection - P 34

Differential Protection - Biased

BIAS

BIAS

OPERATE

Biased Differential Scheme


Generator Protection - P 35

Differential Protection

INTERPOSING C.T.

Overall Differential Scheme

Generator Protection - P 36

Interturn Protection (50DT)

IA2

IB2

IC2

Independent current settings per phase Single stage definite time delay
Generator Protection - P 37

Neutral Displacement / Residual Overvoltage - Interturn Protection (59N)

1 3 2

Gen Relay

(1) Interturn, derived measurement from 5-limb or 3 x 1 phase VT (2) Interturn, directly measured from a broken delta VT input (3) 95% stator earth fault protection across an earthing resistor

Generator Protection - P 38

Prime Mover Failure


Isolated Generators :
Machine slows down and stops. Other protection initiates shut down.

Parallel Sets :
System supplies power - generator operates as a motor. Seriousness depends on type of drive.

Steam Turbine Sets :


Steam acts as a coolant. Loss of steam causes overheating. Turbulence in trapped steam causes distortion of turbine blades. Motoring power 0.5% to 6% rated. Condensing turbines, rate of heating slow. Loss of steam instantly recognised.

Generator Protection - P 39

Prime Mover Failure


Diesel Driven Sets :
Prime mover failure due to mechanical fault. Serious mechanical damage if allowed to persist. Motoring power from 35% rated for stiff machine, to 5% rated for run in machine.

Gas Turbines :
Motoring power 100% rated for single shaft machine, 10% to 15% rated for double shaft.

Hydro Sets :
Mechanical precautions taken if water level drops. Low head types - erosion and cavitation of runner can occur. Additional protection may be required.

Generator Protection - P 40

Prime Mover Failure

Reverse Power Protection :


Reverse power measuring relays used where protection required.

Single phase relay is sufficient as prime mover failure results in balanced conditions.
Sensitive settings required - metering class CTs required for accuracy.

Generator Protection - P 41

Reverse Power
Operational limits

P Q
-P= P 0

a natural = 0.16 o

a stable = 0.5 o

Unstable area Trip area

Unstable area

Blinders at 0.5 degrees reduces operation area for low power settings where the power factor is low to improve reliability of reverse power element
Generator Protection - P 42

Low Forward Power


Operational limits
Trip area Unstable area Extended Trip area
a stable = 0.5 o
P= P 0

Trip area

To reduce the risk of overspeed damage to steam turbine generators a low forward power element is used for interlocking the generator CB and excitation for non urgent trips (eg thermal protection, stator earth fault for high impedance earthing). Turbine steam valves are tripped immediatelay and when power output has reduced the generator CB and excitation are tripped.
Generator Protection - P 43

Loss of Excitation
Effects Single Generator : Loses output volts and therefore load. Parallel Generators :

Operate as induction generator (> synch speed) Flux provided by reactive stator current drawn from system-leading pf Slip frequency current induced in rotor - abnormal heating
Situation does not require immediate tripping, however, large machines have short thermal time constants - should be unloaded in a few seconds.
Generator Protection - P 44

Loss of Excitation
Impedance seen by relay follows locus shown below :
X

Load Impedance R Offset Prevents operation on pole slips Diameter Typically : Offset 50-75%Xd Diameter 50-100% XS
Generator Protection - P 45

Impedance Locus

Relay Characteristic Time Delayed

Pole Slipping
Sudden changes or shocks in an electrical power system may lead to power system oscillations - regular variations of I and V and angular system separation In a recoverable situation these oscillations will die away a power swing In an unrecoverable situation the oscillations become so severe that synchronisation between the generator and the power system is lost - out of step/pole slipping

Causes
Transient system faults Failure of the generator governor Failure of the generators excitation control Reconnection of an islanded system without synchronisation Switching transients on a weak system
Generator Protection - P 47

Pole slipping
Recoverable Out-of-Step Power Swing (Power System)

Unrecoverable
Loss of Synchronism Pole-Slipping (Generator)
Generator Protection - P 48

Theory of pole slipping

Simplified Two Machine System:

Where: EG represents the generator terminal voltage; ZG represents the generator reactance; ZT is the reactance of step-up transform;

Zs represents the impedance of the power system connected to the generation unit
Es represents the system voltage.

Generator Protection - P 49

Loss of synchronisation Characteristics X EG/ES=1 S

EG/ES>1 L R

EG/ES<1

Generator Protection - P 51

Conventional Pole Slipping Protection


Blinder
X ZA ZC

Reactance Line

Zone 2 Zone 1

Lens
ZB

Generator Protection - P 53

Pole Slipping Protection - 78

Conventional lenticular (lens) characteristic


2 Zones defined by reactance line Zone 1 - pole slip in the generator Zone 2 - pole slip in the power system Separate counters per zone (1-20)

Setting to detect pole slipping when :


Generating Motoring Both (Pumped storage generator)

Generator Protection - P 54

Pole Slipping Protection - 78

Pole slip when generating


Impedance position on RHS of lens characteristic Impedance crosses lens on RHS Impedance spends >T1 (15ms) in RHS of lens Impedance spends >T2 (15ms) in LHS of lens Impedance leaves lens on LHS Zone 1 and 2 counter is incremented if in Z1 Zone 2 counter is incremented if in Z2 Trip when zone counter value exceeded

Pole slipping when motoring is the opposite

Generator Protection - P 55

State Transition Diagram


(Reset_Timer Time Out)
Actions are the same as State Machine Entry

State Machine Entry


Reset Trip_ Signals; Reset Start_ Signals; Reset Flag_Zone1; Reset All Counters; Reset All Timers; Zm = R1 or R3 Zm = R4 IF(Mode_Both) Flag_Mode=!Flag_Mode;

No Signal Condition*
Actions are the same as State Machine Entry

VTS-FAST-BLOCK
Actions are the same as State Machine Entry

IDLE
Zm = R1 . Reset Start_Signals; Reset Flag_Zone1; IF(Any Trip_Signal) Reset Counters; Reset Trip_Signals;

Zm = R2 Start Timer1 Zm = R1 or R4 Reset Timer1 Zm = R3 but Timer1<T1 Reset Timer1

Zm = R4 or R2 or R3

DETECTED

Zm = R4 but Timer2 < T2 Reset Flag_Zone1; Reset Timer2;

Zm = R1 or R2 Reset Flag_Zone1; Reset Timer2;

Zm = R2

START

(Zm = R4) & Timer2 > T2) If (C2==0) Start Reset_Timer; C2++; Set Zone2_Start; if(C2>=Count2) Set Zone2_Trip ; If (Flag_Zone1) C1++; Set Zone1_Start; if(C1>=Count1) Set Zone1_Trip; Reset Timer2;

(Zm = R3) & Timer1 > T1) Flag_Zone1=Zone1Pu(); Reset Timer1; Start Timer2;

CONFIRM

*No Signal Condition (VA<1V or I <0.02A)


Zm = R3

Generator Protection - P 56

RTDS Pole Slip Simulation

Local Load 132 kV BUS T/line 140 km 132/13.5 kV 11 kV BUS

Yd1 Grid System Generator with AVR and Governor control

Generator Protection - P 57

Pole Slipping - 80% Load, Local 3 ph fault

Generator Protection - P 58

Loss of excitation at 100% machine loading

Generator Protection - P 59

Rotor Thermal Protection

Unbalanced loading leads to negative sequence current Double frequency slip Rapid overheating of rotor
Generator Protection - P 60

Unbalanced Loading

Gives rise to negative phase sequence (NPS) currents results in contra-rotating magnetic field

Stator flux cuts rotor at twice synchronous speed


Induces double frequency current in field system and rotor body Resulting eddy currents cause severe over heating
Use negative sequence overcurrent relay Relay should have inverse time characteristic to match generator I22t withstand

Generator Protection - P 61

Unbalanced Loading

Machines are assigned NPS current withstand values :


Continuous NPS rating, I2R (PU CMR) Short time NPS rating, I22t (K)

If possible level of system unbalance approaches machine continuous withstand, protection is required.

Generator Protection - P 62

Overload Protection
high load current heating of stator and rotor insulation failure Governor Setting Should prevent serious overload automatically. Generator may lose speed if required load can not be met by other sources.
Generator Protection - P 63

Stator Thermal Protection


Current operated

Over power protection Overcurrent element Thermal replica


RTD Thermal Probes

PT100 Platinum probes Embedded in machine Alarm and trip thresholds for each RTD

Generator Protection - P 64

Overload Protection (1)

Thermal replica for stator overload protection


Current based on I1 and I2 Heating and cooling time constants Non-volatile memory thermal state Alarm output

Time

Current
Generator Protection - P 65

Rotor Earth Fault Protection

Field circuit is an isolated DC system. Insulation failure at a single point :


No fault current, therefore no danger Increase chance of second fault occurring

Insulation failure at a second point :


Shorts out part of field winding Heating (burning of conductor) Flux distortion causing violent vibration of rotor

Desirable to detect presence of first earth fault and give an alarm.

Generator Protection - P 66

Rotor Earth Fault Protection


Potentiometer Method

Exciter

Required sensitivity approximately 5% exciter voltage. No auxiliary supply required. Blind spot - require manually operated push button to vary tapping point.
Generator Protection - P 67

Rotor Earth Fault Protection


AC Injection Method

Brushless Machines No access to rotor circuit

AC Auxiliary Supply
R

Require special slip rings for measurement If slip rings not present, must use telemetering techniques (expensive)
Generator Protection - P 68

Rotor Earth Fault Protection


Brushless Machine
A brushless generator has an excitation system consisting of: A main excitor with rotating armature and stationary field windings A rotating rectifier assembly, carried on the main shaft line out A controlled rectifier producing the d.c. field voltage for the main exciter field from the a.c. source (often a small `pilot` exciter) Hence: No brushes are required in the field circuit All control is carried out in the field circuit of the main exciter Detection of rotor circuit earth fault is still necessary Based on dedicated rotor-mounted system that has a telemetry link to provide an alarm/data

Generator Protection - P 69

Generator Back-Up Protection


Overcurrent Protection
Typical use : Very or extremely inverse for LV machines Normal inverse for HV machines

Must consider generator voltage decrement characteristic for close-in faults. With reliable AVR system, conventional overcurrent relays may be used. Otherwise, voltage controlled / restrained relays are required.
10 x FL

with AVR Full Load

no AVR Cycles

Generator Protection - P 70

Generator Back-Up Protection


Overcurrent Protection
Voltage Restrained
Operating characteristic is continuously varied depending on measured volts. Alternatively, use impedance relay.

Voltage Controlled
Relay switches between fault characteristic and load characteristic depending on measured volts.

Generator Protection - P 71

Generator Back-Up Protection (2)


10 O/L CHARAC

1.0

t sec

FAULT CHARAC LARGEST OUTGOING FEEDER

6.6kV 5MVA 115% XS 500/5 200/5

0.1

GENERATOR DECREMENT CURVE

0.01 100

240 600 1000 3000

10,000 AMPS

Generator Protection - P 72

Voltage Dependent Overcurrent Protection (51V)

I> Fault k.I> Terminal Volts Voltage control Load

I> Fault k.I> Terminal Volts Voltage restraint Load

Generator Protection - P 73

Impedance Relay
X Load Fault R Underimpedance

2 Zones of protection
Zone 1 - Set to operate at 70% rated load impedance. Back-up protection for generator-transformer, busbar and outgoing feeders. Time delayed for co-ordination with external feeder phase fault protection. Zone 2 Set to 50% transformer impedance. Back-up protection for generator phase faults. Faster time delay to coordinate with generator phase fault protection
Generator Protection - P 74

Under & Over Frequency Conditions

Over Frequency

Results from generator over speed caused by sudden loss of load.


In isolated generators may be due to failure of speed governing system.

Over speed protection may be provided by mechanical means.


Desirable to have over frequency relay with more sensitive settings.

Generator Protection - P 75

Under & Over Frequency Conditions


Under Frequency Results from loss of synchronous speed due to excessive overload. In isolated generators may be due to failure of speed governing system. Under frequency condition gives rise to:
Overfluxing of stator core at nominal volts Plant drives operating at lower speeds - can affect generator output Mechanical resonant condition in turbines

Desirable to supply an under frequency relay. Protection may be arranged to initiate load shedding as a first step.
Generator Protection - P 76

df/dt (81R) Loadshedding


df/dt+t: Time Delayed ROCOF

Df/dt can operate quicker than underfrequency for large changes in frequency Rolling window is better than fixed window as gives faster operation Averaging cycles is typically 5 to provide some stability for power system oscillations Stages can be used for load shedding or alarm/tripping of the generator

Generator Protection - P 77

Under & Over Voltage Conditions

Protection

Under & over voltage protection usually provided as part of excitation system.
For most applications an additional high set over voltage relay is sufficient.

Time delayed under and over voltage protection may be provided.

Generator Protection - P 78

Under & Over Voltage Conditions


Over Voltage

Results from generator over speed caused by sudden loss of load.


May be due to failure of the voltage regulator. An over voltage condition :
Causes overfluxing at nominal frequency Endangers integrity of insulation

Under Voltage
No danger to generator. May cause stalling of motors. Prolonged under voltage indicates abnormal conditions.
Generator Protection - P 79

Generator Abnormal Frequency Protection (81AB)


6 independent bands of abnormal frequency protection Accumulation of time up to 1000 hours in each band Band data provided by generator manufacturer Bands match resonance, blade stress frequencies Dead band timer before accumulation starts allows time for resonance to established

When generator is off-line bands can be blocked


Generator Protection - P 80

Generator Abnormal Frequency Protection (81AB)


Band 1
f nom Band 2

Band 3
Band 4

Timer 1 Timer 2 Timer 3 Timer 4


Generator Protection - P 81

Application Negative Sequence Overvoltage (47)


Swapping of 2 phases to motor (pump water) CB a b c Block CB Close Generator/Motor

Busbar

b a c

Generator/Motor
47 Negative Sequence Overvoltage

Hydro machines can operate as motors/pumps by swapping 2 phases (phase rotation is reversed)
Generator Protection - P 82

Use of Alternative Setting Groups Example : Pumped Storage Unit


When the units are being used to generate power the protection could be as below:

87G 27 & 59 81U & 81O 32R 51N 40 51V 46

Generator differential Under & over voltage Under & over frequency Reverse power Stator earth fault Loss of excitation Voltage dependent overcurrent Negative phase sequence

1 2 3 4
When the units pump water the protection applied will change

Four groups available

Generator Protection - P 83

Phase Rotation
Phase rotation for hydro generator/motor applications where 2 phases are swapped to make the machine operate as a pump (motor)
CT1 CT2

G
Phase Reversal Switches

P340 Case 1 : Phase Reversal Switches affecting all CTs and VTs

CT1

CT2

G
Phase Reversal Switches

P343/4/5

Case 2 : Phase Reversal Switches affecting CT1 only


Generator Protection - P 84

Phase Rotation
Phase rotation settings can be changed for generator/motor operation using 2 setting groups
Setting SYSTEM CONFIG Phase Sequence VT Reversal Range Standard ABC / Reverse ACB No Swap / A-B Swapped / B-C Swapped / C-A Swapped No Swap / A-B Swapped / B-C Swapped / C-A Swapped No Swap / A-B Swapped / B-C Swapped / C-A Swapped Default Standard ABC No Swap

CT1 Reversal

No Swap

CT2 Reversal (P343/4/5 only)

No Swap

Generator Protection - P 85

Unintentional Energisation at Standstill

50

27
& VTS
tPU tDO

&

Trip

Overcurrent element detects breaker flashover or starting current (as motor) Three phase undervoltage detection VTS function checks no VT anomalies
Generator Protection - P 86

Check Synch (25)

Check is used when closing generator CB to ensure synchronism with system voltage.
Check synch relay usually checks 3 things: Phase angle difference Voltage Frequency difference

Generator Protection - P 87

Check Synchronising (25)


Phase angle difference
Single phase comparison Typical setting is 20 to reduce mechanical stresses on generators.
Can select either A-N, B-N, C-N, A-B, B-C, C-A is settings

Voltage
Check synch relay inoperative if : Generator/busbar voltage is below or above preset limit (independent settings for generator and busbar under/overvoltages) voltage difference exceeds preset limit

Typical settings for undervoltage: 80 - 85% Vn Typical settings for difference voltage: 6 - 10% Vn

Frequency difference
Usually measured by time to traverse phase angle limits or direct slip frequency measurement (Fgen Fbus)
Eg Timer setting of 2 secs over 20 : Slip frequency = 2 x (20 x ) / 360 = 0.055Hz = 0.11% (50Hz) Timer usually set to 2 secs or 10 x C.B. closing time whichever is greater).
Generator Protection - P 88

Check Synchronising (25)


Check synch has 2 stages Check Sync 1/2
Usually only 1 stage is required for generator applications Check Sync 2 has CB closing time compensation Check Sync2 only permits closure for decreasing angles of slip

Check synch has vector compensation to account for phase shift across transformer with Main VT Vect Grp setting 0-11 Check synch has ratio correction to correct ratio errors of VTs Voltage monitors for dead/live generator/busbar System Split output operates for phase angle > setting adjustable from 90 to 175 degrees

Generator Protection - P 89

Check Synch (25)

Check synch stages 1 and 2


Generator Protection - P 90

Typical Schemes

GRID
Technical Institute

This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.

Protection Package for Diesel Generator

87 G

64 R 32 51 V

32 64R 64S 51V

Reverse Power Rotor Earth Fault Stator Earth Fault Voltage Dependent Overcurrent 87G Generator Differential
Protection P343

64 R

Generator Protection - P 93

Overall Protection of Generator Installation


Generator Feeder Protn. Overcurrent Voltage Restraint

51 V

Restricted E/F

Buchholz Winding Temp.

Reverse Power Field Failure

32 40 87

Generator Differential Rotor E/F Prime Mover Protection Negative Phase Sequence

64R

46

Overall Gen/Trans Diffl Protn.

Stator E/F

64S

Generator Protection - P 94

Overall Protection of Generator Installation


Generator Feeder Protection
O/C

Circuit Breaker Fail

Busbar Protection

Restricted E/F

O/C + E/F

Buchholz Winding Temperature


O/C

Buchholz

V.T.s
Transformer Overfluxing

Standby E/F
Restricted E/F

Permissive (Low Power) Interlock Field Failure

Pole Slipping

Generator Differential

Unit Transformer Differential Protn.

Rotor E/F

Overall Generator Transformer Differential Protn.

Low Steam Pressure, Loss of Vacuum Loss of Lubricating Oil Loss of Boiler Water Governor Failure Vibration, Rotor Distortion
Negative Phase Sequence

Stator E/F Protection

Generator Protection - P 95

Embedded Generation

GRID
Technical Institute

This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.

Co-generation/Embedded Machines

AR?

PES system

81U/O 27/59 59N

Frequency Voltage Residual Voltage ROCOF

50/51N 47/46 25

O/C & E/F NPS Voltage


NPS O/C Check Synch Islanded load fed unearthed

df/dt
dV

Voltage Vector Shift

Generator Protection - P 97

Embedded Generation

USED TO PROVIDE:

Emergency Power Upon Loss Of Main Supply Operate In Parallel To Reduce Site Demand Excess Generation May Be Exported Or Sold

Generator Protection - P 98

Engineering Recommendation G59

ER G59 relates to the connection of generating plant to the distribution systems of licensed distribution network operators (DNOs) ER G83/1 covers connection of generating units rated < 16A / phase in parallel with LV distribution system ER G59 COVERS:
Safety Aspects Legal Requirements Operation Protection

Generator Protection - P 99

Engineering Recommendation G59


General Requirements Protective Equipment The main function of the protection systems and settings is to prevent Generating Plant supporting an islanded section of the Distribution System when it would or could pose a hazard to the Distribution System or customers connected to it.

Generator Protection - P 100

Engineering Recommendation G59


LoM (Loss of Mains = Islanding) Protection Requirements To disconnect the Generating Plant from the Distribution System in the event of loss of one or more phases of the DNOs supply.
LoM is required to ensure requirements for earthing and out of synch closure are complied with and customers are not supplied with voltage and frequency outside statutory limits

Generator Protection - P 101

Loss of Mains Problem


Loss of mains is where a generator is inadvertently isolated from the grid and continues to supply local load
BUS-BAR FAULT

33kV DISTRIBUTION

33/11kV

CIRCUIT BREAKER

Loss of mains can be caused by:


Protection tripping Accidentally due to network reconfiguration

SECTIONALISING SWITCH

400V DG

Generator Protection - P 102

Loss of Mains Problem

Islanding is unacceptable for a number of reasons:


Safety risk - for example, through personnel working on the network under the assumption that no parts of the network are energised
Stresses from out of synchronism re-closure

Loss of system earth where the earth is on the star winding of a network transformer. This can cause problems for existing earth fault protection to detect earth faults if the system is unearthed.
Utility is legally bound to maintaining quality of supply (frequency and voltage ) to local demand.

Generator Protection - P 103

Existing LoM Methods Performance Assessment

Loss of mains performance can be assessed in terms of sensitivity and stability


Sensitivity
Smallest possible mismatch between local generation and the demand at the instant of islanding. Also referred to as non-detection zone

Stability
Stability for different fault types with varying duration and retained voltage at the point of measurement

When designing LoM method objective is to have a small non detection zone and be stable for as many fault characteristics as possible STABILITY
Network faults

SENSITIVITY
Generator/demand Imbalance
Generator Protection - P 104

Existing Loss of Mains Methods


Passive Methods
Under/over frequency and voltage Requires large change in load, time delayed
Df/dt rate of change of frequency Sensitive, fast operating Voltage vector shift Not as sensitive as df/dt, fast operating Direct inter-tripping
Not load dependent, fast, expensive, signalling can be complex

Active Methods
Active frequency drift
Reactive Error export

There is an abundance of active methods proposed in the technical literature, however, their application in practice has been limited to date. The traditional protection philosophy of independence from other systems makes the introduction of these methods difficult.
Generator Protection - P 105

Loss of Mains Methods Voltage Vector Shift

Single phase line diagram showing generator parameters

R
E

jX
IL VT

Generator Protection - P 107

Loss of Mains Methods Voltage Vector Shift

Vector Diagram Representing Steady State Condition

IL

VT

IL X ILR

Generator Protection - P 108

Loss of Mains Methods Voltage Vector Shift


Transient voltage vector change q due to change in load current IL

E VT VT

ILX ILR

IL

IL
Generator Protection - P 109

ILX

Loss of Mains Methods - ROCOF df/dt


The rate of change of speed, or frequency, following a power disturbance can be approximated by: P.f df/dt =

2GH

where

P = Change in power output between synchronised and islanded operation f = Rated frequency G = Machine rate MVA H = Inertia constant

Generator Protection - P 110

Loss of Mains Methods - ROCOF


P341 df/dt calculation

df/dt =

Fn - fn - 3 cycle

3 cycle
Two consecutive calculations must give a result above the setting threshold before a trip decision can be initiated

Generator Protection - P 111

Loss of Mains Methods - ROCOF


df/dt+t: Time Delayed ROCOF t Start

Pick up cycles

Trip f Time delay df/dt Setting


Generator Protection - P 112

G59 Other Protection


Neutral voltage Overcurrent Earth fault Phase unbalance Reverse power
Used when generator does not export power during normal operation

Generator Protection - P 113

G59 Protection Settings


Protection Settings for Long-Term Parallel Operation
Prot Function Small Power Station LV Connected HV Connected Medium Power Station

Setting
U/V st 1 U/V st 2 O/V st 1 O/V st 2 Vph-n -13% Vph-n -20% Vph-n +10% Vph-n +15%

Time
2.5s* 0.5s 1.0s 0.5s

Setting
Vph-ph -13% Vph-ph -20% Vph-ph +10% Vph-ph +13%

Time
2.5s 0.5s 1.0s 0.5s

Setting
Vph-ph -20%

Time
2.5s*

Vph-ph +10%

1.0s

U/F st 1
U/F st 2 O/F st 1 O/F st 2 LoM (Vector Shift) LoM (RoCoF)

47.5Hz
47Hz 51.5Hz 52Hz K1 x 6 degrees K1 x 0.125 Hz/s

20s
0.5s 90s 0.5s

47.5Hz
47Hz 51.5Hz 52Hz K1 x 6 degrees K2 x 0.125Hz/s

20s
0.5s 90s 0.5s

47.5Hz
47Hz 51.5Hz

20s
0.5s 90s

Intertripping expected Intertripping expected

Notes: K1 = 1.0 (low impedance networks or 1.66-2 (high impedance networks) K2 = 1.0 (low impedance networks or 1.6 (high impedance networks) A fault level of < 10% system design max fault level is high impedance * Might need to be reduced if auto-reclose time <3s
Generator Protection - P 114

G59 Protection for HV Generator connected to DNO HV System for Parallel Operation Only

Generator Protection - P 115

G59 Protection for HV Generator connected to DNO HV System for Standby and Parallel Operation

Generator Protection - P 116

www.alstom.com

GRID
Technical Institute

This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.

S-ar putea să vă placă și