Overview
Reduced maintenance
Component availability
Staff reduction, loss of know how Simplified network structure
System reliability
[Schwan et al., 2003]
Failure models
Reliability calculation
Reliability indices
Evaluation / Prognosis
Comparison
Reliability
For analysis and planning purposes in all network levels with integrated data base and schematic or topological graphics
IEE RTDN 2005, London
Generation of a failure combination list Examination of a failure combination Network status analysis Identification of supply interruptions Measures for the rectifying of supply interruptions Statistical recording of results
Reliability Indices
PTD SE PT/Schi 02/05 6
Clear boundary of the system and components Network model which corresponds to operation
Failure sequence
Supply restoration models
Failure Models
Outage Models ME PM
0.013 804 0.0033 0.003 240 0.00077 60 0.009 60 0.009 9 0.005 60 0.009
UP
60 0.00013 60 0.00013 43 0.00016 60 0.00013
Cable Overhead line Transformer 110/20 kV Bus bar Outgoing Feeder Receiving Feeder Distribution substation
Independent single failure Multiple earth fault Protection malfunction Unnecessary protection operation
A: Expected value of failure frequency in yr-1 bzw. km-1yr-1 B: Expected value of outage duration in min. C: Expected value of conditional probability of failure
IEE RTDN 2005, London
Symbol Index
Unit
Fi
1/yr
Ti
Qi Pi Ei
h
1 or min/yr MVA/yr MVAh/yr
Ci
/ yr
10
11
Study Task
A German 110 kV subtransmission system feeding some 20 kV distribution networks should be analysed with special focus on:
The impact of the 110 kV network and the 20 kV structure on the reliability indices of the medium voltage customers
The comparison of the present reliability level of different distribution networks with benchmarks
The comparison of scenarios of network expansion with respect to investment costs and reliability
12
F J E K H C G B A D
13
EHV / HV
110 kV System
HV / MV
Distribution System
The infeed from transmission network is 100 % reliable The MV networks are modeled as bulk load on the 20 kV busbar
PTD SE PT/Schi 02/05 14
D K J
15
0.4
0,4
A1 A2 B1 Qi in min/yr 18
Unavailability
B2 B3 B4 C1 C2 C3 D1
E1
E2
F1
F2
G1
H1
H2
J1
J2
K1
16
16 14 12 10 8 6 4 2 0
Unavailability
A2 B1 Ei inA1 MVAh/yr
B2
B3
B4
C1
C2
C3
D1
E1
E2
F1
F2
G1
H1
H2
J1
J2
K1
16
E C
G B
17
HV / MV
20 kV System
The infeed from subtransmission network is 100 % reliable All MV backup connections are modeled The load is modeled on the MV side of the distribution transformer
PTD SE PT/Schi 02/05 18
Gau-Bischofsheim 1
Gau-Bischofsheim 4
Gau-Bischofsheim 2 Gau-Bischofsheim 3
Gau-Bischofsheim 6
Gau-Bischofsheim 7
Gau-Bischofsheim 9
HARXH5
E3960 300.0 MVA 100.0 p.u.
Harxheim 4
Harxheim 9
Harxheim 1
Harxheim 8
Harxheim 3
Harxheim 7
Bodenheim31
Mommenheim 15
Harxheim 6
Harxheim 2
Harxheim 10
Bodenheim 39
Nackenheim 7
Nackenheim 3
Mommenheim 13
Loerzweiler 6
Nackenheim 2
Nackenheim 18
Nackenheim 17
Nackenheim 20
Nackenheim 8
Nackenheim 9
Mommenheim 8
Mommenheim 7
Mommenheim 3
Mommenheim 4 Mommenheim 1
Loerzweiler 5
Mommenheim 12
Mommenheim 2
Mommenheim 6 Mommenheim 14
Loerzweiler 2 Mommenheim 6
Loerzweiler 3
Loerzweiler 7
Nackenheim 1
Nackenheim 22
Nackenheim 13
Mommenheim 5
Mommenheim 9
MT20201K/KA202020 MO01
Loerzweiler 1
NACKH12
Nackenheim 21
Nackenheim 14
Nackenheim 5
Schwabsburg 5
Schwabsburg 7
NACKH19
Schwabsburg 6
SWBSB3
Schwabsburg 1
Schwabsburg 2
Nierstein 22
Nierstein 11
NIERS14
Schwabsburg 4
Substation E
DEXHEIM S1
K3178
Nierstein 32 Nierstein 8
DEXHEIM S1/L87 DEX05
Nierstein 9
Nierstein 2
DEXHEIM S2
Nierstein 13
Nierstein 25
Nierstein 10
Nierstein 3
Nierstein 15
Nierstein 17 Nierstein 2
Nierstein 26
Nierstein 7
Nierstein 6
Nierstein 23
Nierstein 12 Nierstein 1
Nierstein 16
Nierstein 1/L432 NI04
Nierstein 33
Nierstein 18
Dexheim 9
Nierstein 19
Nierstein 20
Nierstein 29
Nierstein 5
Dexheim 6
Dexheim 8
Nierstein 24
Nierstein 4
Nierstein 21
Dalheim 4 Dalheim 1
Dexheim 7
Dienheim 1
Dienheim 4
Oppenheim 27
Oppenheim 21
Dienheim 2
Dienheim 3
Dienheim 8
Oppenheim 31
Oppenheim 18
Oppenheim 1
Oppenheim 4
Oppenheim 13
Oppenheim 20
Dalheim 3
Dalheim 2
Dalheim 5
Dienheim 7
Dienheim 5
Dienheim 6
Oppenheim 12
Oppenheim 7
Oppenheim 11
Oppenheim 5
Oppenheim 10
Oppenheim 26
Oppenheim 14
Oppenheim 6
Oppenheim 9
Oppenheim 34
Oppenheim 22
Guntersblum 25
Ludwigshoehe 1
Ludwigshoehe 2
Oppenheim 25
Oppenheim 8
Oppenheim 19
Oppenheim 23
Oppenheim 3
Ludwigshoehe 3
Ludwigshoehe 4
Oppenheim 24
Oppenheim 28
Oppenheim 29
Oppenheim 36
19
Unavailability Qi in min/yr
140 120 100 80 60 40 20 0
Distribution stations
20
OSTHOF 1b
OSTHOF 1a
OSTHOF 2
MU225K01
MU225K06
RHDUR10
Rheinduerkheim 22
Rheinduerkheim 4
Rheinduerkheim 37
Klaeranlage
Rheinduerkheim 39
HE54
Becker
Rheinduerkheim 28
Osthofen 21
Herrnsheim 5 Herrnsheim 4
Gottwein
Elbatainer
Mainzerstr. 1
Rheinduerkheim 21 Alcoa
MU3/6K17
Rheinduerkheim 27
Rheinduerkheim 6
Schaerf Herrnsheim 16 Herrnsheim 15 Herrnsheim 17 Herrnsheim 3 Rheinduerkheim 29 Rheinduerkheim 36 Rheinduerkheim 33 Rheinduerkheim 25 Rheinduerkheim 18 Rheinduerkheim 23
MT2/101K
Herrnsheim 7
Krankenhaus 2
Herrnsheim 13
Herrnsheim 14
Herrnsheim 2
Grace
Grace
Herrnsheim 26
Herrnsheim 22
Langgewann
Neu 2
Rheinduerkheim 24
MU1/K138
Paracelsusstr.
Herrnsheim 25
MU1/0K26
MU1/K139
Krankenhaus 3
Krankenhaus 1
MT465464
Hollerhecke
Hollerhecke
MU1/0K25
Virchowstr. Schuch
ELC
Horchheim 3
Luessen 4
Siwonit
Mueller
Zwischenpumpwerk
Procter&Gamble
Horchheim 4
Herrnsheim 21
Roehm 5
K3269
Rheingewannweg
MU1/0K49
Roehm 7
Luessen 3
Herrnsheim 24
Hornbach
Kaufland
ARAL
Worms-Nord
Hafenstr. 2
G
Roehm 3G
MU1/0K02 MU1/0K50
Trafoknoten HOLZTR12
MU1/0K01
UAHH_R2 HOLZHF B1
UAHH_R1
Substation B
HOLZHF B2
HOLZHF B3
HOLZHF A1
HOLZHF A2
MU1/0K05
Mc-Donalds
US-Lager
Hauptlager Luessen 1
Schaeferstr.
Luessen 2
Pfortenring
Birkenweg
Walter
US-Kaserne
Hafenstr. 1
Duerer Str.
Nicolaus-Reuss-Str.
Triebwagenladung
Luetzowstr.
Raiffeisen
Heidenhainstr.
Fahrzeug Schaefer
Erich-Ollenhauer-Str. 2
Theodor-Heuss-Str.
Post 2
Deuka
Wehrzollhaus-Rosengarten1
DRK
Eckenbertstr.
Eulenburgstr.
Horn
GEN_ROS
Heppenheimer Str.
ROSENG S1
Kurfuerstenstr.
Pfalzneuburgstr.
Mainzerstr. 2
Lokschuppen
ROSENG S2 Pfrimmanlage
MU021K01
Weinsheimer Str. 2
Mersch
Engelmannstr.
Hermannstr.
Rhenania
Weinsheimer Str. 3
Zwinglistr.
Herrngasse
Gaustr.
Kaibel&Sieber
Massa 2
EMF
Adelheidtstr.
Rudolph-Heilgers-Str.
BIZ
Worms 188
Nutzkauf
Nievergoltstr.
Konventstr.
Dreihornmuehlgasse
Gueterhallenstr.
Martinsplatz
Martinsplatz
Berliner Ring
Heinrich-Heine-Str
Alzeyer Str.
Frauenstr.
Hochheim 2
Hochheim 1
Bebelstr.
Liebenauerfeld
Gymnasiumstr.
Messeplatz
CEWE-Color
Pfiffligheim 2
Monsheimerstr.
Pipinweg
Knode Str.
Bahnhof 2
Bahnhof
Rheinstr. 2
Droste-Huelshoff-Str.
Hallenbad
P.H.
Polizeikaserne
Wasserturm
Karolingerstr.
C&A
Kyffhaeusserstr.
Vangionenstr.
Langenbach
Renolit Kirschgartenweg Schildweg Bobenheimer Str. Rohrlache 1 Rohrlache 1 Laubscher Kaiserpassage Sparkasse 1
Weinsheimer Str. 1
Martinsgasse
Lutherplatz
Maria-Muenster-Bach
Cornelius-Heyl-Str.
Im Winkel
Sophienplatz
Mang
Sparkasse 2
Woolworth
Kieskran
Flugplatz
Rohrlache 2
Stamm
Knappenstr.
Festhaus
Ludwigsplatz
Rheinbeton
Speyerer Str.
Hochstr.
Rmerstr.
Rmerstr.
Schoepfwerk
Landgraben
Aulweg
Esbella
REA 2
Kiefel
Gutenbergstr.
Verwaltung
Kaufhof
Rheinstr. 1
Rhenania 2
Delta 1
Zoo
Kani
Rosengasse
Cornelianum
Buergerturm DELTA1.B
Altbach
Katterloch
Bundeswehr
Andreasring
Andreasstr.
Neu
Sophienstift
Delta 2
Forestone
Hochstift
Valckenberg
Volksbank
Philosophenstr.
MU1/0K06
Werk II_1B
Werk II_1A
21
Unavailability Qi in min/yr
80 70 60 50 40 30 20 10 0
Distribution stations
22
Improvement of Substation B
Substation B
110 kV
Substation A
20 kV
City
Industry
Existing Substation B
Substation B
110 kV
T4
Substation A
Variant Switchgear
Substation B
110 kV
T4
Substation A
20 kV
City
Industry
Industry
Substation B
110 kV
T4
Substation A
20 kV
City
Industry
Industry
PTD SE PT/Schi 02/05 24
120%
Frequency
100%
Unavailability
Costs
80%
60%
40%
20%
25
Additional tool for planning and operation Support and addition to (n-1) criterion Important tool in deregulated networks
Comparison of equal (n-1) variants (e. g. switchgear concept) Support for network restructuring Quality level for customer Basis for risk assessment Maintenance management
26