Documente Academic
Documente Profesional
Documente Cultură
3-phase voltages are produced with a 3-phase ac generator( alternator) as shown in Fig Generator consists of a rotating magnet (rotor) surrounded by a stationary winding (stator) 3 coils with terminals a-a,b-b,c-c are placed 120 apart around stator As rotor rotates, its magnetic field cuts flux from 3 coils and induces voltages in coils. As coils are placed 120 apart, induced voltages in coils are equal in magnitude but out of phase by 120 As each coil can be regarded as a single-phase generator by itself, 3phase generator can supply power to single-phase and 3-phase loads A typical 3-phase system consists of 3 voltage sources connected to loads by 3 or 4 wires. A 3-phase system is equivalent to three singlephase circuits. Voltage sources can be either wye or delta connected as shown in Fig.
BALANCED VOLTAGES
For wye NW V an , V bn, V cn are Voltages between lines a, b, and c, and neutral line n.These voltages are called phase voltages. If voltage sources have same amplitude and freq and are out of phase with each other by 120, voltages are said to be balanced and implies that V an +V bn+V cn =0 so balanced phase voltages are equal in magnitude & are out of phase with each other by 120. Mathematically
Where Vp is effective or rms value of phase voltages. This is known as abc sequence or + sequence in which V an leads V bn, which in turn leads V cn rotor in rotates counterclockwise. For delta NW, in acb or sequence V an leads V cn which in turn leads V bn and rotor rotates clockwise
LOAD CONNECTIONS
Like generator connections, a 3-phase load can be either wye- or delta-connected depending on end application. Neutral line in Y may or may not be there but in delta it is impossible. A wye- or delta-connected load is said to be unbalanced if phase impedances are not equal in magnitude or phase. But A balanced load is one in which phase impedances are equal in magnitude and in phase. i.e. for Y load Z1 = Z2 = Z3 = ZY , for Delta Za = Zb = Zc = Zdelta Zdelta = 3ZY , ZY = 1/3 Zdelta and there are 4 possible connections: Y-Y connection (i.e., Y-connected source with a Y-connected load), YDelta, Delta-Delta, Delta-Y Balanced delta-load is more common than balanced wye- load. This is due to ease with which loads may be added/removed from each phase of delta- load. This is very difficult with a wye-load because neutral may not be accessible. Whereas Delta-sources are not common as circulating current will result in delta-mesh if 3 phase voltages are slightly unbalanced
EXAMPLE
Van = 200 cos(wt+10) Vbn = 200 cos(wt-230) Vcn = 200 cos(wt-110) Solution: voltages can be expressed in phasor form as
We notice that Van leads Vcn by 120 which in turn leads Vbn by 120 so an acb sequence.
Voltage across neutral wire is zero. Neutral line can be removed without affecting system. In Y-Y line current is same phase current In long distance power Xmsn, conductors in multiples of 3 are used with earth itself acting as neutral conductor
EXAMPLE
Calculate line currents in 3-wire Y-Y system of Fig. Solution: 3-phase circuit in Fig. is balanced; we may replace it with its single-phase equivalent circuit such as in Fig Ia from single-phase analysis as where
So
Y-
Example: A balanced D- load having an impedance is 20- j15 ohm connected to a D +sequence generator having Calculate phase currents of load and line currents Solution: load impedance per phase is
But I b lags I a by since we assumed abc sequence; that is, Putting Ia-Ib implies Another way to obtain line currents is to replace D source with its equivalent Y source, as shown in Fig
Example
Unbalanced Y-load has balanced voltages of 100 V and acb sequence. Calculate line currents and neutral current. Solution: Line currents are