TRANSFORMER OIL RELATED ASPECTS

OIL PLANT CAPACITY


60KL/Day(Now we are enhancing to 120KL/Day from existing 60KL capacity) A) TOBS storage capacity-1000KL (600KL tank-1no,100KL tanks-4nos) B) In process Oil storage capacity-125KL(20KL filters-3nos,10KL filters-6nos and 5KL filter-1no) C) Finished Oil storage capacity-390KL(240KL tank1no,100KLtank-1no and 25KLtanks-2nos.

FUNCTIONS OF TRANSFORMER OIL


To provide dielectric strength of the

transformer insulation system. To provide efficient cooling. To protect the transformer core and coil assembly from chemical attack. To prevent the build up of sludge in the transformer.
2

PRODUCTION OF TRANSFORMER OIL


Transformer oil is hydrocarbon product,mainly

oil contains napthanic,parrafinic and aromatics. To obtain the TOBS the crude oil which is burried from earth crust subjected in to the following sequence of operations . Distillation-Acid treatment-Neutralization-Water wash-Hot air blowing. Clay treatment process on TOBS will give us the finished transformer oil. After the hot filtration operation transformer oil is ready for filling the transformers. 3

DETORIORATION ASPECTS OF TRANSFORMER OIL


Deterioration due to the accidental leakage of

water . Deterioration due to the chemical decomposition. Deterioration due to the oxidation. Deterioration due to the contamination by gases. Deterioration due to the electrical stresses. Deterioration due to the thermal stresses. Deterioration due to the effect of oxidation products. Deterioration due to the physical contamination. 4

PRECAUTIONS INVOLVED IN TRANSFORMER OIL SAMPLING.


The utmost care should be taken to avoid

contamination of samples with external impurities such as dust and moisture. Attention is drawn to the danger of sampling in rainy or foggy weather. The hands of the sampler should not come into contact with the samples. Care should be taken when sampling oil colder than the surrounding air, to avoid contamination 5 by condensation.

PRECAUTIONS INVOLVED IN TRANSFORMER OIL SAMPLING.


Only glass sample containers,preferably fitted with

ground glass stopper,should be used. Cotton waste or other fibrous materials should not be used to wipe the containers or apparatus. Where practicable,if a bottom sample is required the contents of the tank or package,after movement,should be allowed for at least 8Hrs,preferably 24Hrs before sampling. Before the actual sample is taken,the entire sampling apparatus and containers should be rinsed with the oil,which should then discarded 6

PRECAUTIONS INVOLVED IN TRANSFORMER OIL SAMPLING.


To remove any moisture or dirt on the

surfaces over which the oil sample will flow a small amount of oil should be allowed to flow from the tank or package and run to waste before the sample is taken. Samples that are to be tested for sludge,corrosive sulphur or tan delta should be protected from light. 7

TRANSFORMER OIL
Specifications for Testing of transformer oil. IS-335 ASTM-D3487 IEC-60296 BS-148 JIS-2320
8

IS-335SPECIFICATION
APPEARANCE:Clear transparent and free from

suspended matter and or sediments. DENSITY:IS-1448 P(16) HYDROMETER/THERMOMETER DESIGN VALUE0.89 gms/ml @29.5C max KINEMATIC VISCOCITY:IS-1448 P(25) CONSTANT TEMPERATURE BATH THERMOMETERS/STOP WATCH DESIGN VALUE27cSt @ 27 C max
9

IS-335SPECIFICATION
INTERFACIAL TENSION:IS-6104

INTERFACIAL TENSIO METER DESIGN VALUE0.04N/M max FLASH POINT:IS-1448 P(21) PENSKY MARTINS CLOSED CUP FLASH POINT TESTER/THERMOMETERS. DESIGN VALUE140 C min POUR POINT:IS-1448 P(10) CLOUD POINT&POUR POINT APPARATUS/THERMOMETERS DESIGN VALUE-- -6 C max
10

IS-335SPECIFICATION
NEUTRALIZATION VALUE:IS-1448 P(2)

CONICALFLASKS/BURETTES/MEASURING CYLINDERS/BURETTE STANDS/ VOLUMETRIC FLASKS DESIGN VALUES-A. TOTAL ACIDITY : 0.03mgKOH/gm B. INORGANIC ACIDITY: NIL ELECTRIC STRENGTH(BDV): IS-6792 BDV TEST SET DESIGN VALUES A. UN FILTERD :30kv min 11 B. FILTERD : 60kv min

IS-335SPECIFICATION
DIELECTRIC DISSIPATION FACTOR (TAN

DELTA):IS-6262 TANDELTA TEST SET/OIL CELL HEATER/OIL CELL. DESIGN VALUE : 0.002 max RESISTIVITY : IS-6013 RESISTIVITY TEST SET/OIL CELL HEATER /OIL CELL DESIGN VALUES A. 1500*10E12 Ohm-cm @27 C min B. 35*10E12 Ohm-cm @90 C min

12

IS-335SPECIFICATION
PRESENCE OF ANTI OXIDATIVE

INHIBITOR :IS13631 MEASURING CYLINDERS/PIPPETES/ BURETTES/BURETTE STANDS DESIGN VALUE : NOT DETCTABLE WATER CONTENT : IS-13567 AUTO MATIC KARLE FISHER TITRATOR/WEIGHING BALANCE DESIGN VALUE : 50PPM max
13

IS-335SPECIFICATION
CORROSIVE SULPHUR : IS-335 ANNEX-B

TEMPERATURE CONTROLLED OVEN/CONOCAL FLASKS/FORECEPS DESIGN VALUE : NON CORROSIVE OXIDATION STABILITY :IS-335 ANNEX-C OXIDATION STABILITY BLOCK/ VACUUM PUMP/OXIDATION TUBES/G-4 FILTERS/BURETTES/BURETTE STANDS/ CONICAL FLASKS/WEIGHING BALANCE. DESIGN VALUES A.NEUTRALIZATION VALUE:0.4mgKOH/gm B. SLUDGE % BY MASS :0.1max
14

IS-335 SPECIFICATION
AGEING CHARACTERISTICS: IS-12177

AGEING OVEN /WEIGHING BALANCE/ VACCUME PUMP/ G-4 FILTERS/ BURETTES/BURETTE STANDS/ CONICAL FLASKS. DESIGN VALUES A.RESISTIVITY@27DegC-2.5Ohm-cm min B.RESISTIVITY@90DegC-0.2Ohm-cm min C.TANDELTA@90DegC-0.2 max D.TOTAL ACIDITY -0.05mgKOH/gm E. TOTAL SLUDGE 0.05%
15

NABL RECUREMENTS IN OIL LAB


Equipment history cards Measurement uncertainty calculations. Regular calibrations of instruments from NABL

accredited laboratories.

Interlab comparison

Replicate testing

16

APPEARANCE TEST
APPEARANCE Measurement uncertainty calculation for

transformer oil appearance test

Sources of uncertainty a) Improper sampling

b) Presence of sediments and suspended matter in the bottles used for sampling c) Persons skills
17

APPEARANCE TEST
a) Improper sampling :

To avoid the uncertainty due to improper sampling the following care should be taken 1) Dont use the cotton waste while sampling 2) Dont pickup the sampling in dust and foggy weather 3) Clean the sampling point (pipe end) before sampling

18

APPEARANCE TEST
b) Presence of sediments and suspended matter in

the bottles used for sampling : The test results may be effect due to the contamination of sediments and suspended matter, if any present in the sampling bottles. Bottles should be thoroughly clean before sampling by using the following cleaning agents as per the sequence 1) Tap water 2) Soap solution 3) Tap water 4) Hot distilled water 5) Acetone and allow for oven drying at 110C for 1hr. And then vacuum with the vacuum pump.
19

APPEARANCE TEST
Persons skills :

Person skills may also be the one of the reason for effecting the test results. To avoid this problem . The following persons will take care in the bottles cleaning and reporting the results 01) P.SRINIVAS RAO

20

BRAKE DOWN VOLTAGE TEST


Measurement uncertainty calculation for

BDV test on transformer oil Sources of uncertainty 1) Test results obtained 2) BDV test set resolution 3) BDV test set calibration 4) Atmospheric condition
21

BRAKE DOWN VOLTAGE TEST


Results obtained .

Repeated measurements on sample transformer oil sample a) ( 68,74,72,60,68,64) = 67.6kv b) (66,72,80,64,68,62) = 68.6kv c) (68,70,70,68,80,76) = 72.0kv d) (72,62,76,68,82,68) = 71.3kv e) (64,66,78,72,68,70) = 69.6kv Average value = 69.82kv St. Deviation = (-2.22)2+(-1.22)2+(2.18)2+(1.48)2+(-0.22)2 / 4 = (4.9284+1.4884+4.7524+2.1904+0.0484) / 4 = 1.8308 22 Type A uncertainty = 0.818kv

BRAKE DOWN VOLTAGE TEST


2)BDV test set resolution :

(B1)uncertainty due to BDV test set resolution = 2 / 2 3 = 0.577kv 3) BDV test set calibration :
(B2)uncertainty due to BDV test set calibration. = 1.9 / 2 = 0.95kv Type B uncertainty = (B1)2+(B2)2

= (0.572)2+(0.95)2 = 1.1115kv combined uncertainty = (Type A)2+(Type B)2

23

BRAKE DOWN VOLTAGE TEST


combined uncertainty = (Type A)2+(Type B)2 = (0.818)2+ 1.1115)2
= 1.38kv Note :4 Room temperature and relative Humidity maintained at 27C and 44% RH respectively so uncertainty due to Atmospheric Conditions is not Considered Expended uncertainty = 2 x 1.38 = 2.76kv At 95% confidence level with respeet to 69.82kv 69.82 2.76
24

INTERLAB COMPARISION

Brake down voltage Inter lab comparison 1) PGCL values = 73.1kv Vijai electrical value = 69.3kv Difference

= 3.8kv Uncertainty = 3.01kv Z = Difference / uncertainty = 3.8 / 3.01 = 1.26 Z Value is less than 2 OK
25

INTERLAB COMPARISION

ERDA VALUE = 64.0kv Vijai electrical value = 69.3kv Difference

= 5.3kv Uncertainty = 3.01kv Z = Difference / uncertainty = 5.3 / 3.01 = 1.76 Z Value is less than 2 OK

26

INTERLAB COMPARISION

CPRI VALUE = 87.0kv Vijai electrical value = 69.3kv Difference = 17.7kv Uncertainty = 3.01kv Z = Difference / uncertainty = 17.7 / 3.01 = 5.88 Z Value is higher than 2 (Not OK) The value of BDV reported By CPRI Bangolure

appears to be very high . Requested CPRI to examine the same


27