Documente Academic
Documente Profesional
Documente Cultură
The insulation strength and characteristics of various components of a system (including those of voltage limiting devices) must be selected relating to those stresses.
i. To reduce frequency of supply interruptions ii. To reduce component failures
The selected level of voltage shall be low enough to be operationally and economically acceptable
Load rejection (supplying capacitive current through a large inductive reactance ex. A smaller generator connected to a long cable or over head line) Ferro resonance ( inter change of stored energy for series or parallel combination of inductive and capacitive reactance)
Switching surges
They are of short duration and irregular form Typical switching impulse standard form is the 250/2500 sec. ( time to crest/ time to half value wave) The magnitude of internally operated switching surges is related to the system operating voltage In a system where CBS are not subjected to multi re striking the switching surges will rarely exceed 3 pu 2.5 pu would be typical maximum based on which the discharge duty of LA is assessed However in systems above 300 kV, it may be necessary to suppress maximum switching surges to 2 pu or less by the installation of a shunt reactor and/or closing resistors on the circuit breakers
Resonance effects
For voltage level below 300 kV. Resonance effects occur
i. When switching transformer ii. When switching cable and overhead line combination iii. Between lumped capacitive and reactive elements and over head lines iv. Charging long lines without shunt reactor compensation
Direct stroke
A direct stroke can be to the earthed tower top or on phase conductor Stroke on earthed lower top, for transmission of shielded design, is innocuous Raise in potential caused by passage of current through tower impedance to earth will be less than with stand strength of line
Direct strokecontd.
However the rise in potential can be severe and exceed with stand capability, if
Tower footing resistance is high Rate of rise of current exceeds a certain level
Flashover may occur Through the system voltage, losses is the frequency of flash over
Direct strokecontd.
Direct stroke on phase conductor May occur if there is a shielding failure i.e. stroke avoids earth wire and lands on line conductor. Discharge current flows equally in both directions. Impedance to earth is half the surge impedance (Z0) of the conductor. IN a 400 kV line Z0 = 175 ohms Voltage rise is sufficient to cause failure of line insulation Minimum critical current for flash over Ic = 2 V I0 Z0
VI0 = minimum flash over voltage for 1/50 Wave
At flash over the impedance through which the discharge current flows drops abruptly from Z0/2 to impedance of tower, x -arm, tower footing
Surge propagation:
Surge waves are propagated at the velocity of light along the conductor On arrival at substation, equipment there in get stressed. Rod gaps and surge arrestors provide necessary protection Waves are subjected to considerable attenuations due to losses both in the conductor (ohmic losses) and corona losses
Lightning discharges
Clarification of lightning discharges stroke (A) stroke (B) Stroke (A) : produced by the charged cloud which induces a charge on the stationery objects such as high buildings etc. Charge distribution causes concentration of potential at the top most point Electro static stress being great at that point ionization of surrounding atmosphere takes place Dielectric strength of surrounding air decreases giving an easy path to lightning stroke. Decrease in dielectric strength of surrounding air takes considerable time
Lightning discharges
Stroke B: A, B & C are three clouds with A and C positively charged and B negatively charged When there is a stroke between (A) and (B) the charge on (C) becomes free and immediately and indiscriminately strikes on any object on the ground For stroke (B) there is no time lag Stroke (B) may completely ignore highest building and strike bare ground. No protection can be arranged against stroke `B` Stroke `A` can be made safe by channelising the charge through a lightning conductor placed on the top of the building
Lightning strokes
Over voltage due to lightning strokes surge impedance of the line = Zs Discharge current = Id Over voltage due to direct stroke = Vd = Id x Zs However current travels in both directions over voltage = Vd = Id x Zs 2 when lightning strikes over earth wire or a tower Over voltage = Id x Ze + Lc di dt Ze = impedance of earth wire Lc is the inductance of the line conductor
Protection against lightning 1. Protection of transmission lines from direct strokes 2. Protection of power stations and substations from direct strokes 3. Protection of electrical equipment from traveling waves
When ground wire is present it increases capacitance between conductor and earth i.e. C1 Decreases induced voltage on the line. It is observed that presence of a ground wire reduces induced voltage on line to half. For two ground wires the induced voltage comes down to one third Presence of two ground wires also provides better shielding
Earth wires
Disadvantages with ground wire: (a) higher line cost (b) Probable direct shorting between line conductor and ground wire when the later gets cut In 400kV system transmission line towers will have twu earth wires.
Protective equipment : LAs and Surge diverters They are connected between line and earth
EHV lines * Closing unloaded lines * Closing charged lines * Auto re closing of C.B.
Opening resistors ( Resistance switching with CB) used only with ABCB
Switching surges
Breaking inductive circuit, the energy stored inductance gives rise a voltage rise across capacitor. Switching of capacitive, line charging currents give rise to a over voltage due to restrike. Closing of EHV lines
-Use of opening resistors with C.B. - Use of restrike free C.B. -Use pre-insertion resistors with C.B.
Resonance The fault causing resonance between inductance and capacitance in a part of the circuit
Traveling waves
High voltage waves get Reflected waves -Proper reflected on reaching gets superimposed switching a junction or end. for initial wave. sequence. Voltage may rise to several time the normal voltage. Poor voltage control Failure of -Proper Voltage transformers and control Rotating Machines
-- in sub stations
Surge Absorbers
Types of Earthing
For purpose of selection of voltage rating of a LA three types of earthing are considered (I) Effective earthed system: a system is effectively earthed if under any fault condition the line to earth voltages of healthy phases do not exceed 80 % of the system line to line voltage If in a system all transformers have star connected winding with neutrally solidly earthed then the system is effectively earthed However if only few transformers are earthed like that, it is not effectively earthed system
By going for a higher voltage rating for a surge arrestor, the degree of protection for equipment gets reduced.
Protective margin of LA
Protective margin of LA = BIL of the equipment--maximum discharge voltage of LA While determining protection level offered by a LA 10% allowances towards drop in lead length and manufacturing tolerance shall be allowed. Protective margin shall be 20% of the BIL of the equipment when closely located In a 220 kV system Discharge voltage of LA = 649 kV Allowing 10 % margin protection level = 713 kV BIL of equipment = 900 kVp Protection margin = 900-713 = 187 kVp There is more than 20 % of the BIL of 180 kV
The electrical circuit length between L.A. and the transformer bushing terminal (inclusive of lead length in metes for effectively earthed) should not exceed the limits given below:
220kV 400kV
LINE INSULATION
Extra high voltage line can be made lightning proof by 1 Efficient shielding 2 Low tower footing resistance equal to or less than 10 ohms shielding angle Transmission lines up to 220kV 30 400 kV at and above 20
132kV
220kV 400kV
76
127 231
76x3=228
127x3=381 231x3=762
6
10 20
7
11 22
9/10
13/14 23/24
Tower forting resistance 10ohms severest lightning discharge 50kA (rms) Impulse strength of Insulation=2x50x10x10=700kV As per the table for 7 discs, the impulse FOV ( kVp =695kVp) For better performance tower forting resistance shall be brought down. For 132kV best is 7 ohms
1 2