Sunteți pe pagina 1din 38

Describe the C200 Controller Architecture

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Introduction

Honeywell

This lesson introduces you to the Experion PKS C200 controller architecture At the conclusion of this lesson, you will be able to:
Identify the high-level components and connections Explain the basic purpose of the components and connections
Experion Server
FTE

ACE

ControlNet

Process C300 Controllers I/O Options

Rack I/O Series A

Rail I/O Series A


Fiber Optic Isolation

PM I/O

HART
GI/IS Rail I/O Series H

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Architecture Overview
Unlimited Secure Access
www eServer

Honeywell
State-of the Art Operation and Engineering Tools Advanced Applications and Integration

Casual Users

Application Control Environment

Experion Stations

Remote Engineering Tools

Wireless Devices (Operations and Maintenance)

PHD Historian

FTE Network C200

C300

PMD
ESV-LCN Connected

Redundant Servers

Safety Manager

NIM

Allen-Bradley ControlLogix PLC PM I/O Digital Video Manager SCADA Devices (OPC, Modbus DH+, and many more!)

TPS, TDC2000, TDC3000

Investment Protection Complete Integration

Ethernet

Comprehensive Support for Smart Field Devices

Video as a Process Input!

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

C200 Architecture
Experion Server ACE

Honeywell

FTE

Process Controllers
ControlNet

I/O Options Rack I/O Series A

Rail I/O Series A C300

PM I/O

Fiber Optic Isolation

HART

GI/IS Rail I/O Series H 4

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: C200 Control Strategy Components

Honeywell

Which of the following cannot be an integral part of a C200 control strategy?


A) Rack I/O
B) PM I/O C) Rail I/O
ControlNet

Experion Server
FTE

ACE

Process Controllers I/O Options

D) Fieldbus Valves E) PLC I/O using OPC communications


Rail I/O Series A
Fiber Optic Isolation

Rack I/O Series A

PM I/O

HART
GI/IS Rail I/O Series H

Incorrect. Correct! PLC PLCI/O I/Ois: using usingOPC OPCcommunications communications The Your correct answer: answer cannot be an integral part of a C200 control You must answer the question before You Incorrect Correct didYou not answered answer Click Clickanywhere anywhere this this question correctly! to to continue continue completely strategy. continuing Click anywhere to continue.

Submit

Clear

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 2: Redundant Components All of these can be redundant except:


A) C200 processors B) C200 Fieldbus interface modules
C) C200 PM I/O link modules D) C200 Rack I/O E) C200 PM I/O
Rail I/O Series A
Fiber Optic Isolation ControlNet

Honeywell
Experion Server
FTE

ACE

Process Controllers I/O Options

C300

Rack I/O Series A

PM I/O

HART
GI/IS Rail I/O Series H

The Your correct answer: answer is: Correct! Incorrect. C200 C200 Rack Rack I/O I/O cannot cannot be You You must did answer not answer the question this question before be redundant. redundant. Incorrect Correct You answered -Click Clickanywhere anywhere this correctly! to tocontinue continue continuing completely Click anywhere to continue.

Submit

Clear

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary Key concepts to take away from this lesson are:

Honeywell

The ACE communicates to the Experion Server over FTE The C200 communicates to the Experion Server over Ethernet, FTE or ControlNet C200s and ACE nodes on the same Experion Server can communicate Peer-to-Peer Three main types of I/O: PMIO, Rail I/O, and Chassis I/O

C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the C200 Controller Architecture

Completion Certificate

Proceed to the next lesson in your course material


C200 Controller Architecture Describe the C200 Controller Architecture

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe the C200 Controller Racks and Redundancy

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Introduction

Honeywell

In this lesson, you will learn how the C200 controller is networked to the server and remote I/O racks in non-redundant and redundant configurations

At the conclusion of this lesson, you will be able to:


Describe the C200 control processor, communication and redundancy modules Explain the C200 network connections and addressing

NET

OK

NET

Honeywell

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

10

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics

Honeywell

C200 Hardware C200 Network Connections and Addressing

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

11

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Control Processor (CP) 100MHz Power PC 603E processor with 8 MB RAM 4 MB Flash ROM for storing program

Honeywell

Lithium battery (or optional rechargeable battery extension module) Can support up to 8 I/O chassis and 64 IOMs Controller can be redundant or non-redundant Double-wide module -- occupies 2 slots on CP rack
OK

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

12

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

ControlNet Interface (CNI)

Honeywell

Provides the interface to the supervisory network (supervisory CNI) Peer-to-peer communication I/O communication (downlink CNI) One CNI can support up to 24 IOMs
NET

4 downlink CNIs can be connected to one controller

Each CNI must have a unique MAC ID on the same network

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

13

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Fault Tolerant Ethernet Bridge (FTEB)

Honeywell

Last two digits of the Ethernet address are set here

FTEB

FTE

CNI

ControlNet

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

14

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Redundancy Module (RM) Placed in controller chassis to support redundant controllers


RM must be in the same position in both racks Both RMs are connected by an optical cable Switchover between redundant controllers is bumpless Note: If controller is redundant, then all IOMs must be remote

Honeywell

Redundancy Cable (Fiber Optic)

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

15

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: C200 Control Processor

Honeywell

Which of these statements, about the control processor (CP), is false?


A) It can support up to 8 I/O chassis and 64 IOMs
B) It is a double-wide module that occupies 2 rack slots
OK

C) It can be redundant
2

D) It provides an interface to the supervisory network

Yourcorrect The answer: answer is: You You Incorrect Correct did must You not answer answer answered -Click Click the anywhere anywhere this question this question correctly! to to before continue continue completely continuing Good Incorrect. job! The false statement is "It provides an interface to the supervisory network." The interface to the supervisory network is provided by either the CNI CNI card card or or the the Fault Fault Tolerant Tolerant Ethernet Ethernet Bridge Bridge (FTEB). (FTEB) Click anywhere to continue.

Submit

Clear

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

16

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Topics C200 Hardware C200 Network Connections and Addressing

Honeywell

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

17

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Non-redundant Controller
TC-CCR013 -ControlNet Interface (CNI), Redundant Media
TC-PRS021-- C200 Control Processor (Optional) TC -CCR013 -CNI to connect to other I/O racks TC-FXX102 -- 10-slot rack

Honeywell

TC-FPCXX2 -120/240 VAC Power Supply

Controller Chassis
LAN Connection Ethernet, TCPIP, etc.

I/O modules and terminal blocks Taps -- 9904-TPS, R, YS, and YR (4 kinds) ControlNet Cable (TC - KCCxxx) -- Supervisory C o n t r o l N e t

Terminators-TC-TCXBNC

TC-CCR013 -- CNI, Redundant Media

TC-PCIC01 -- ControlNet Communication Interface Module for PC (redundant media) (in server) Server (stations not shown)

Additional Remote I/O

I/O modules and terminal blocks

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

18

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Redundant Controller
TC-PRS021 -- C200 Control Processor TC-CCR013 -- CNI, Redundant Media TC-CCR013 -- CNI to connect to I/O racks TC-FXX072 7-slot rack TC-PRR021 -Redundancy Module Redundant Chassis Identical Configuration Module for module

Honeywell

TC- FXX072 7 SLOT RACK

TC-FPCXX2 -120/240 VAC Power Supply

-GN KRRxx1 Redundancy Cable (Fiber Optic)

ControlNet Cable

-- I/O Comm

ControlNet Cable (TC -KCCxxx ) -- Supervisory Terminators -TC-TCXBNC NO IOMs PERMITTED IN CONTROLLER NO IOMs PERMITTED IN CONTROLLER CHASSIS FOR REDUNDANT CHASSIS FOR REDUNDANT CONFIGURATION!! CONFIGURATION!! (IOLIM and FIM are exceptions)
Chassis

to Server

to IO

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

19

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Non-redundant Address Settings

Honeywell
03

C200

CNI

PCIC

CNI CNI

Server

CNI

01

01 02

04

03

CNI

05 23
C200
CNI

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

20

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

CNI

Address Settings Redundant C200


23 01 01 05
C200 CNI CNI CNI RM

Honeywell
03

ServerA
PCIC

CNI

01

04
01 05
CNI CNI RM CNI

PCIC

C200

CNI

ServerB

03
C200

07

CNI

24

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

21

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

CNI

FTEB
01 01 05
FTEB C200 CNI CNI RM

Honeywell
03

ServerA

CNI

Switch

02

04 01 05
CNI CNI RM CNI

FTEB

Switch

C200

ServerB

03 07
FTEB

C200

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

22

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

CNI

Question 2: MAC Addresses

Honeywell

While configuring a ControlNet-connected Control Processor (CP), which MAC address is entered as the supervisory MAC address?
A) MAC address of the PCIC card B) Device index of the FTEB card C) MAC address of the CNI card connected to the server D) MAC address of the CNI card connected to the I/O card

ServerB
PCIC

03 24
C200 CNI

The correct answer is: Your answer: Correct! Incorrect. The The address MAC of the of CNI the card CNI connected card You must MAC answer theaddress question before Correct anywhere to continue You didserver not answer this question completely Youanswered this correctly! Incorrect -Click Click anywhere to continue to connected the to should the server be entered should as be the entered supervisory as the continuing supervisory MAC address. MAC address. Click anywhere to continue.

Submit

Clear

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

23

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary

Honeywell

When you connect the C200 controller to the server and to remote I/O racks in non-redundant and redundant configurations, remember:
The double-wide control processor (CP) supports up to 8 I/O chassis and 64 IOMs ControlNet Interface (CNI) modules provide interfaces to the I/O ControlNet and the Supervisory ControlNet Redundant controllers require all IOMs be configured remotely All devices on the same network must have unique MAC addresses Redundant supervisory CNI cards must be addressed with the same odd number Redundant FTEBs must be addressed differently with the primary having an odd number and the secondary having the next highest even number

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

24

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the C200 Controller Racks and Redundancy

Completion Certificate

Proceed to the next lesson in your course material


C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

25

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell

This page intentionally left blank

C200 Controller Architecture Describe the C200 Controller Racks and Redundancy

26

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Describe the C200 I/O Modules

C200 Controller Architecture Describe the C200 I/O Modules

27

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Introduction

Honeywell

In this lesson you will learn about the standard C200 input/output (I/O) modules and their applications At the conclusion of this lesson, you will be able to:
List the standard I/O types that are compatible with the Experion system
Identify the application for each type of I/O module

Rail I/O Series A

GI/IS Rail I/O Series H

PM I/O

C200 Controller Architecture Describe the C200 I/O Modules

28

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Chassis Series A Input/Output Modules

Honeywell

Compact size may reside in either the controller rack or remote I/O rack
Diagnostic and non-diagnostic modules available

IOM configurable through Control Builder


Removable wiring hood Can be removed and replaced under power All modules have a form factor of 5 X 5 Redundancy not supported

C200 Controller Architecture Describe the C200 I/O Modules

29

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series A Rail I/O Modular connections slide rail 8 terminal bases can be connected to a single gateway
Gateway

Honeywell

Gateway provides link to the ControlNet


-1 2 + +

Terminal Base
8 7 2 3

DIN Rail

Analog I/O, digital I/O, thermocouple and RTD

IOM types:
AI- Analog Input AO- Analog Output DI- Digital Input DO- Digital Output

C200 Controller Architecture Describe the C200 I/O Modules

30

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Series H Rail I/O Galvanically isolated Intrinsically safe


Server

Honeywell

Supervisory ControlNet
Controller CNI Module

I/O ControlNet
Repeater/ Adapter
C O M M O D

Fiber Modules
E x C ont r ol N et Fi ber M od ul e TC PM FO 01 E x C ont r ol N et Fi ber M od ul e TC PM FO 01 PWR C ha n1 C ha n2 C ha n1 C ha n2

E C ont r ol N et R epea A te r dapt er x TC PB FO 01

Repeater/ Adapter
C O M M O D 1 2 3 4

Fiber Modules
E xC ont r ol N et Fi ber M od ul e TC PM FO 01 E xC ont r ol N Fi et ber M od ul e TC PM FO 01 PWR C ha n1C ha n2 C ha n1 C ha n2

EC ont r ol N et R epea t A r e dapt er x TC PB FO 01

1 2 3 4

+V-V+V-V

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

+V-V+V-V

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

NonHazardous Area Hazardous Area

C ont r ol N et R epea A te r dapt er TC PB FO 01

Ex C ont r ol N et Fi ber M od ul e TC PM FO 01

ExC ont r ol N et Fi ber M od ul e TC PM FO 01

C O M

M O D

PWR

C ha n1 C ha n2 1 2 3 4

C ha n1C ha n2

+V-V+V-V

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

Fiber Optic Cable

C ont r ol N et R epea t A r e dapt er TC PB FO 01

ExC ont r ol N et Fi ber M od ul e TC PM FO 01

ExC ont r ol N et Fi ber M od ul e TC PM FO 01

C O M

M O D

PWR

C ha n1C ha n2 1 2 3 4

C ha n1 C ha n2

+V-V+V-V

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

R ec v

Xm t i

Rail I/O Modules - Series H


Ex TC PG C N 11

I/O ControlNet

Gateway
A B

--

12 ++

1 2

V+ V- V+ V-

C200 Controller Architecture Describe the C200 I/O Modules

31

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Process Manager I/O (PM I/O) PM I/O Link Interface Module in C200 controller chassis Redundancy of PM IOLIM as part of C200 redundancy PM I/O can be redundant PM I/O includes AI, AO, DI, DO, RTD, T/C, DI SOE FTA for I/O Remote I/O using fiber optic

Honeywell

PM I/O

C200 Controller Architecture Describe the C200 I/O Modules

32

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Serial Interface Module

Honeywell

NET

OK

NET

Serial Interface Processor

Honeywel l

SIM FTA Power Adapter ADAPTER SERIAL INTERFACE FTA MODBUS (16 Array Channels) SERIAL INTERFACE FTA A/B (16 Array Channels)

Modbus Compatible Subsystem

Allen-Bradley Compatible Subsystem

C200 Controller Architecture Describe the C200 I/O Modules

33

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 1: I/O Application Which I/O module can be used in a hazardous environment?
A) Chassis I/O
NET OK NET

Honeywell

B) Serial Interface C) Series H I/O


Honeywell

Rail I/O Modules - Series H


E x TC-PGCN11

Gateway
A B

-+ 1 2 +

V+V- V+V-

The correct Your answer: answer is: Incorrect. Correct! Series Series H HI/O I/O modules modules are are specifically specifically You must answer the question before Correct -Click anywhere to continue You Incorrect did You not answer answered Click this anywhere this question correctly! to completely continue designed for unsafe environments. continuing Click anywhere to continue.

Submit

Clear

C200 Controller Architecture Describe the C200 I/O Modules

34

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Question 2: I/O Redundancy Which I/O module will support redundancy?


A) Chassis I/O B) PM I/O
Honeywell
NET OK NET

Honeywell

C) Series H I/O
Rail I/O Modules - Series H
E x TC-PGCN11

Gateway
A B

-+ 1 2 +

V+V- V+V-

Yourcorrect The answer: answer is: You must answer the question before Correct Click to continue You Incorrect did You not answer answered Clickanywhere anywhere this this question correctly! to continue completely Yes! PM I/O modules are the only standard PM are only standard No. I/O modules the continuing I/O modules that are available in a redundant configuration. Click anywhere to continue.

PM I/O

Submit

Clear

C200 Controller Architecture Describe the C200 I/O Modules

35

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Summary

Honeywell

The standard I/O types compatible with the Experion system are:

Chassis Series A I/O modules that can be installed in the same chassis as the C200 or a remote I/O chassis

Series A Rail I/O modules, which include analog I/O, digital I/O, thermocouple, and RTD
Rail I/O gateway provides a link to the ControlNet Series H Rail I/O modules, which are intrinsically safe for use in hazardous environments PM I/O modules which include AI, AO, DI, DO, RTD, T/C, and DI SOE

Serial Interface modules which interface to Allen-Bradley and Modbus subsystems


C200 Controller Architecture Describe the C200 I/O Modules

36

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Conclusion

Honeywell

Describe the C200 I/O Modules

Completion Certificate

Proceed to the next lesson in your course material


C200 Controller Architecture Describe the C200 I/O Modules

37

EXP20R300 - EPKS CEE C200/C300/ACE 11/28/2013

Honeywell

This page intentionally left blank