maxDNA CONTROL SYSTEM

maxDNA is name of control system. maxDNA is developed by Metso Automation USA. maxDNA widely used for power plant automation. First maxDNA control supplied to RRVUNL Kota Unit-6. All the modules supplied to Kota unit were imported from USA. From then all the modules are being manufactured at our EDN Bangalore unit. maxDNA control system is customized for specific application.

maxDNA

THE REMOTE PROCESSING UNIT

(Control Cabinet)

The equipment includes

DPUs Field I/O modules Field terminations Communication networks Power supply unit

maxDNA RPU COMPONENTS


The Distributed Processing Unit (DPU4F) is the process controller. The Model 4F Distributed Processing Unit (DPU) is a multifunction controller and data acquisition processor that executes
control algorithms, sequence logic, sequence of events resolution data acquisition.

time

tagged

to

ms

maxDNA DPU4F (CONT.)


The heart of the DPU is a database called the Distributed Point Management System (DPMS). The DPMS is fully aware of the tag names, hierarchy, and other text attributes of its configured points. It is loaded with a configuration created by the Systems engineer and executes that configuration to provide the control and data acquisition functions required. The DPU 4F resides directly on the MAXNET communications network without the need for servers.

maxDNA RPU Cabinet


P S P S P S P S P S P S
System 24V

Schematic arrangement of RPU Cabinet

Switch

I/O Bus Connector Field 48V Field 24V

I/O Bus Connectors

Switch

I/O

I/O

I/O

I/O

I/O

I/O

D P U

IOP382 eight pack rack

I/O

I/O

I/O

I/O

I/O

I/O

D P U

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

maxDNA I/O Modules


TYPES OF I/O MODULES USED
Analog Input
Part Number IOP301 IOP302 IOP303 IOP304 IOP305 Description Isolated analog input; 16 channels 4-20mA common input; 16 channels 3-wire RTD input; 8 channels Thermocouple/emf input; 16 channels Voltage common input; 16 channels

Digital Input
Part Number IOP330 IOP334 IOP351 Description 24 Vdc common input; 16 channels 24 Vdc isolated input; 16 channels Form A/B relay; 16 channels

Analog Output
Part Number IOP320 Description 4-20 mA common output, 8 channels

Bus address 00 to FF (256) DI module address 0 to 31 AO & DO module address 32 to 252 DI Module one bus address DO module one bus address AI module two bus address AO module eight bus address

COMMISSIONING SEQUENCE A- PANEL POWER-UP


Check cabinet installation as per drawing( system O&M manuals). Check for any physical damage. Checking of hardwares as per configuration diagram. Verify I/O module addresses. Verify that modules are properly inserted in back plane. Ensure that DPU mode switch is kept at F. Verify that all backplanes are connected with ribbon cable and terminator is put to last backplane slot. Remove all P2/P3 connectors from the I/O modules to isolate field terminations. Ensure the panel electronic & power supply ground earthing. Ensure that no wirings are loose terminated. Check for power supply before power-up. Ensure that power supply connectors are properly connected to backplanes. Switch on power supply and check for 24VDC supply. Observe that DPUs boot-up and LED indications.

B-COMMUNICATION WITH EWS


Set the EWS and connect the peripherals including respective dongle card. Boot-up the EWS maxStartup program automatically start and minimizes. maxStartup software version is 4.2.1.SP-2 Without dongle card maxStartup program can not be started. Power on network switches Connect the network cable as per layout Establish the communication with EWS. Verify the DPU address at EWS. Load the application software and verify the ACTIVE LED of I/O module are green. ACTIVE indication should not blink. Unfreeze the outputs. All the outputs freezed when full application software is loaded to DPU. Connect P2/P3 connectors sequentially and proceed for loop checking.