The Solution
Eaton 9390, 9395 & BladeUPS UPS
Industry-leading efficiency in double conversion mode
Source: CEMEP UPS
Transformer-free technology
Low frequency & analogue control designs require transformers
Transformer-free topology
Transformer-free benefits
High Efficiency over range Input Power Performance Output Power Performance NEW GREEN TECHNOLOGY: Next Generation Green Technology. Lowest Pollution to Electrical GRID
TRANSFORMER-FREE UPS
EATON EXPERIENCE: First to Introduce Transformer-free Technology. Over 15 years of experience Proven Reliability
EATON
Advantages
Transformer-Free resources
11
11
12
12
On Line UPS provide constant voltage regulation, but may unnecessarily waste energy
On Line UPS with Energy Saver or ECO modes work in bypass mode when mains is suitable, and in Double Conversion mode when line voltage is close to the limits of ITIC Curve Transition time between Normal and Double Conversion mode should be ~2-4 ms under all line/load conditions up to 2x faster than any Mission Critical STS
2011 Eaton Corporation. All rights reserved.
13
13
14
14
15
15
ESS solves both issues; it provides best possible efficiency, and instantaneous transfer to double conversion when needed.
16
16
In short, we can detect and transition faster and more reliably than traditional ECO mode or high efficiency schemes.
17
17
Source Outage
18
18
Test Description
1/2 cycle 0% dropout sequence (All Phases) (0% is a low impedance (short) source fault)
Source
Test Result
1.2ms Transfer Time (600us detection time plus 600us SCR clearing time).
Output
19
19
Test Description
40 cycle 40% dropout sequence (All Phases)
Output
20
20
Test Description
1 cycle 0% dropout sequence (phase L1) (0% is a low impedance (short) source fault)
Source
Test Result
1ms Transfer Time
Output
21
21
Test Description
12 cycle 40% dropout sequence (phase L2)
Test Result
1.2ms Transfer Time
Source
Output
22
22
Test Description
1 cycle 0% dropout sequence (Phase L2)
Output
23
23
All modes are selectable from the front panel or through serial communications (XCP).
24
24
25
25
EMI is dramatically reduced, since the power converters are idling 99.xx% of the time
Load inrush handling is enhanced, due to lower impedance of utility source vs. inverter. This is good for motor loads and medical imaging applications ESS allows "seasonal scheduling" that is, run in non-ESS during the Summer thunderstorm season, then run in ESS rest of the year
26
26
In Load Fault Mode, ESS Stays on Bypass and supplies inverter current to provide maximum fault current!
27
27
Eatons Energy Saver System drives these losses down to nearly zero. The energy savings recovers the cost of the UPS in less than 5 years.
* Underlying figures from The Invisible Crisis in the Data Center: The Economic Meltdown of Moores Law, Uptime Institute, 2007
2011 Eaton Corporation. All rights reserved.
28
28
The Solution:
Eaton 9395 UPS and VMMS
C H A L L E N G E
30
30
VMMS Principle
Example With Same Load Applied To Different Multi-UPS Configurations
* In ready state, the UPM rectifies DClink, generates logic level PWM signals, and filters EMI and lightning spikes.
32
32
In Ready State:
UPM Output Contactor is closed; Output Filter is connected and DC Bus is energised via the inverter; logic level PWM signals are generated, but IGBT gate pulses are held off In VMMS mode, UPMs can pick up load in <1ms In ESS mode, the output filter capacitors also provide surge protection the more UPMs, the more protection!
2011 Eaton Corporation. All rights reserved.
33
33
UPM cycling
At the beginning of each ABM cycle, all UPMs are turned on All UPMs are on during charge cycle At the end of the ABM cycle, UPS reverts to VMMS mode different UPMs are turned off after each ABM cycle, to ensure the workload is shared equally amongst UPMs over the systems life
34
34
VMMS In A Nutshell
9395 UPS Efficiency
96 94
92
9395 9395 1100kVA 825kVA 550kVA with withVMMS VMMSand andN+0 N+0configuration* configuration*
Efficiency %
90
Eaton 9395 550kVA UPS Eaton 9395 275kVA UPS Typical Operating Range
84 82
80
78
Load kVA 9395 275kVA 9395 550kVA 9395 825kVA 9395 1100kVA 9395 VMMS N+0
Notes: - Scaled drawing - VMMS and N+0 curves using VMMS default max UPM % load level @ 80% (*)
35
35
VMMS Applications
VMMS can be used in all multi-module (multiple-UPM) 9395 systems
Single 9395 units from 550kVA to 1100kVA Distributed parallel systems Centralised SBM Systems
Data Centres, especially when UPS system feeds dual corded servers Any applications when load is not constant
2011 Eaton Corporation. All rights reserved.
36
36
VMMS Example:
9395 / 825kVA Units in Dual Corded Load with A and B feeds Example with 440kVA load
(A 220kVA + B 220kVA)
Single or Dual Source Data Centre with Dual Corded Servers
Without VMMS
91.2% Used as reference for savings calculation Industry-leading UPS efficiency in double conversion
56 MWh / year
Additional energy savings from reduced cooling in VMMS (typically +30-40% to UPS energy savings) UPMs in VMMS idle mode available for redundancy
A Feed 220kVA
A Feed 220kVA
A Feed 220kVA
B Feed 220kVA
B Feed 220kVA
B Feed 220kVA
37
37
95%
System Efficiency %
90%
85%
80%
75%
70% 0 10 20 30 40 50
System Load %
60
70
80
90
100
Eaton Confidential
2011 Eaton Corporation. All rights reserved.
38
38
X
VMMS on B
Double Conversion backup for 100% of system load For dual source no need for down stream static switch
39
39
Energy Saver System is available on all Eaton BladeUPS, 9390 and 9395 UPS
Also all earlier installations can be upgraded with the ESS capability
2011 Eaton Corporation. All rights reserved.
40
40
41
41
42
42
44
44
45
45
Energy is fed back to mains through static bypass All power paths including bypass tested with load Energy consumption is limited to losses