Electrical Theory

Howard W Penrose, Ph.D., CMRP Instructor

(c)2005 Penrose

Overview of Electrical Theory


Atomic Structure and Electron Movement Conductors, Semi-Conductors, Insulators Basic Electricity: Current, Voltage and Resistance Electrical and Magnetic Fields Alternating Current Electricity: L, C, XL, XC, Z
(c)2005 Penrose

Atomic Structure and Electron Movement

(c)2005 Penrose

Classic Atom

(c)2005 Penrose

Electron Movement
Photon

Photon + N

(c)2005 Penrose

Conductors, SemiConductors and Insulators

(c)2005 Penrose

Conductors
Free Electrons (e) Easily Directed Usually metals Copper Aluminum Gold Platinum

- -

- - -

- -

- - - - - - - - - - - -

(c)2005 Penrose

Semi-Conductors
+

Dielectrics 4 Valence Electrons Polarize with Some Electron Flow due to Electrical Fields

(c)2005 Penrose

Insulators
No Free Electrons No Current Flow with Field
+

(c)2005 Penrose

Basic Electricity: Current, Voltage and Resistance

(c)2005 Penrose

Current (Amperage - I)
Current is the flow of electricity, much like the flow of water in a pipe. It is measured in Amperage as opposed to gallons per minute of water.

(c)2005 Penrose

Current

Electron!

Electron!

1 Amp = 6.28 x 1018 electrons per second 1 Amp = 1 Coulomb per second Electron charge = 1.60219 x 10-19 Coulombs Flows Negative Charge to Positive Charge
(c)2005 Penrose

Voltage (Volts - V or E)
Voltage is the electrical pressure in the system, much like water pressure. Electrical pressure is measured in Volts as opposed to Pounds per Square Inch. (ie: 110V like water from a tap, 4160 like a fire hose)
(c)2005 Penrose

Resistance (Ohms - R or )
Resistance is simply the restriction of current flow in a circuit. Smaller wire (conductors) and poor conductors have higher resistance.

(c)2005 Penrose

Resistance

e
e e e e

e e

e e

e e

Fewer Collisions = Less Heat! Many Collisions = Heat!

(c)2005 Penrose

Ohms Law
Current, Voltage, and Resistance relate as follow:

I=E/R

(c)2005 Penrose

Electrical and Magnetic Fields

(c)2005 Penrose

Magnetics
Magnetic Flux

South

Magnet

North

(c)2005 Penrose

Current Flow in Conductor

Current Flowing in a Conductor

(c)2005 Penrose

Generated Field Around Conductor

(c)2005 Penrose

Magnetic Field With Coil


North Magnetic Pole + +

South Magnetic Pole

(c)2005 Penrose

Interaction with Medium


Magnetic Flux

S Metal N

South

Magnet

North

(c)2005 Penrose

Alternating Current Electricity

(c)2005 Penrose

Electrical Properties
Frequency Inductance (L)
Mutual Inductive Reactance (XL)

Capacitance (C)
Capacitive Reactance (XC)

Phase Angle/Power Factor Impedance (Z)


(c)2005 Penrose

Frequency

90

180
(c)2005 Penrose

270

360

Inductance
Stores electromagnetic energy in its magnetic field mH di

I lags V

V L

dt
1 2 W Li 2

1 t i v( )d i(0) L 0
(c)2005 Penrose

Mutual Inductance
When 2 coils in close proximity, a changing current in one coil will induce a voltage in a second coil
N2 = 5 Turns 100 Volts

N1 = 5 Turns 100 Volts

90

180

270

360
(c)2005 Penrose

Inductive Reactance XL
Inductive Reactance is the AC Resistance of a coil Presented as a resistance in Ohms Frequency and Inductance Dependant

X L 2fL

(c)2005 Penrose

Capacitance
Stores energy in an electric field Dielectric between 2 plates The charged condition is maintained until a discharge path is present Causes current to lead voltage
(c)2005 Penrose

Capacitive Reactance XC

1 XC 2fC
(c)2005 Penrose

Phase Angle / Power Factor


In a coil or motor, current lags behind voltage This is represented as an angle or a fraction of unity Adding C can improve PF

V I

90

180

270

360

(c)2005 Penrose

Impedance Z

Z R (X L XC )
2
Complex AC Resistance

DC Resistance

X L 2fL X 1 C

2fC

(c)2005 Penrose

Summary
Atomic Structure and Electron Movement Conductors, Semi-Conductors, Insulators Basic Electricity: Current, Voltage and Resistance Electrical and Magnetic Fields Alternating Current Electricity: L, C, XL, XC, Z

(c)2005 Penrose

AC Induction Motor Theory


Howard W Penrose, Ph.D. Instructor

(c)2005 Penrose

Basic Motor Circuit


Resistance Inductance Capacitance Phase Angle Inductive Reactance XL Capacitive Reactance XC Impedance 2

R ( X L X C )2
(c)2005 Penrose

The Polyphase Induction Motor


Stator Windings Fan Stator Laminations Rotor Bearing

(c)2005 Penrose

Interaction of Rotor Field and Stator Field


Interaction of Two Magnetic Fields Electrical Energy to Mechanical Torque
Stator Field S
(c)2005 Penrose

Rotor Field

Rotating Fields

(c)2005 Penrose

Rotating Field and Rotor Cage

(c)2005 Penrose

Rotor Cage

(c)2005 Penrose

Output Torque

(c)2005 Penrose

Operating Motor

(c)2005 Penrose

Insulation System Considerations for MCA and Motor Connections


Quantum Mechanics and Motor Diagnostics

(C)2004, Howard W Penrose, Ph.D., All rights reserved

STATOR LAMINATIONS

(c)2005 Penrose

Stator Failure Modes


Turn to Turn Coil to Coil Open Circuit Phase to Phase Coil to Ground

(c)2005 Penrose

Insulation Diagram of Motor


Phase A Ground

Phase B Phase C

Circuit Capacitance Changes due to charge Effects of atoms in Insulation medium. Dipoles are created As electric field crosses Atoms. As they align Capacitance increases.
(c)2005 Penrose

The Dipole

Neg Potential

Pos Potential

(c)2005 Penrose

Dipolar Motion in Operation


Capacitance Wire High Low GRND High

MegOhms Wire High

Ground Insulation

Low High Voltage

(c)2005 Penrose

Dipolar Motion in DC Tests


Capacitance Neg High

GRND Pos

Low

MegOhms Neg High

Meg Ohms
(c)2005 Penrose

Low

Time

Dipolar Motion in Surge Test

Conductor 1

Conductor 2

Overcomes Dipolar Spin and Circuit Capacitance Requires Higher Voltage as a Result In order to cross air gap (Paschen) Potentially Destructive!!! Voltage

Impulse

(c)2005 Penrose

Time

Accelerated Insulation Degradation

Arc during fault detection using surge test. The separated insulation is the result of the arc (burned). The grey area on the copper is carbonized insulation.

(c)2005 Penrose

Dipolar Motion in MCA - 1


wire wire wire

wire

wire

wire

Good Phase Phase Angle: 77 degrees Current/Frequency: -44%


(c)2005 Penrose

Dipolar Motion in MCA - 2


wire wire wire

Capacitive Defect

wire

wire

wire

Bad Phase Phase Angle: 73 degrees Current/Frequency: -40%


(c)2005 Penrose

Before and After Defect


1-2 Resistance Impedance Inductance Phase Angle I/F Ins Resist 0.6821 21 8 77 -47 1-3 0.6798 21 8 76 -45 >99 2-3 0.6865 39 7 76 -47 Resistance Impedance Inductance Phase Angle I/F Ins Resist 1-2 0.6786 21 8 77 -47 1-3 0.6797 21 8 77 -43 >99 2-3 0.6819 39 7 76 -47

MCA Result on 20 hp with contamination and slight phase to phase defect. Still running.

MCA test results following surge test from previous example. Trips on start.

(c)2005 Penrose

Time to Failure Estimation Techniques


Howard W Penrose, Ph.D. T-Solutions, Inc.

(c)2005 Penrose

Concept of TTFE
Setting test frequencies such that faults can be detected in advance Setting alarms at a point where fault detection is effective Knowing that failures are random Know that the resistance to failure decreases following detection of a CBM alarm
(c)2005 Penrose

Condition-Directed Example
100%

A (New Motor Installed)

Resistance to failure

B (Insulation begins to degrade between turns)

P (Interturn insulation degradation detection)

0%

Inspection Interval
DT

F (Winding fails)

(F-P)

Operating age (time T)

Source: reliability-centered maintenance, Nowlan and Heap


(c)2005 Penrose

Example of TTFE in MCA

(c)2005 Penrose

This Presentation
Stages of Winding Failure Causes and Effects Trending Time to Failure Discussion
< 600 Vac Standard, integral, three phase motors, operating an average of 4000 hours 50% load, balanced voltage, good power quality, constant load
(c)2005 Penrose

Insulation Breakdown
Contamination
Moisture and electric field expansion Gasses, vapors, dust, etc.

Arc Tracking
High Current Between Conductors

Thermal Aging (10oC)


Partially Assembled 125 horsepower Motor in repair shop

(c)2005 Penrose

Insulation Breakdown
VFD Applications
Partial Discharge

Mechanical Faults
Stress cracking Parts Faults
Stators awaiting assembly after rewind

(c)2005 Penrose

Stages of Winding Failure


Time to Failure
Severity of the Fault Potential Between Conductors Type and Amount of Insulation Cause of the Fault Cycling and Load

Contamination, Thermal, Moisture Incursion, Corona, Transients, Overloads, etc. may initiate fault.
(c)2005 Penrose

Stage 1
Insulation between conductors stressed Changes to R and C between conductors High temps and reactive faults Carbonization begins to occur MCA values of Fi and I/F begin to change

(c)2005 Penrose

Stage 2
Fault becomes more Resistive Mutual Inductance between good and bad I2R losses increase at point of fault Motor may start tripping although may run after short cooling period (ins res increases as insulation cools)
(c)2005 Penrose

Stage 3
Insulation breaks down Possible explosive rupture Vaporization of windings Inductance and sometimes resistance may change
Stage 3 winding failure

(c)2005 Penrose

Review
MCA Requirement:
Resistance Loose connections, Broken Wires (~5%) Impedance and Inductance Rotor position or contaminated windings. Also, used for rotor test in assembled equipment. (Parallel good, Unparallel bad) I/F and Fi Early winding shorts (I/F: +/-2; Fi: +/-1) Insulation Resistance Ground Faults (5 MOhm/100 MOhm)

Combination used for troubleshooting or trending Comparative tests: Assumes that phases do not fail at same rate

(c)2005 Penrose

How Trended
AC Motors
% unbalance: R, Z and L Phase Diff: I/F and Fi Reading: Insulation Resistance

Induction Rotors: Need numerical method (Rotor Grading System RGS)

MCA Being used to confirm the Winding voltage connection in a submersible Pump.

(c)2005 Penrose

AC Rotating Machine Testing


Reading R, Z, L R, Z, L Change from Baseline < 3% >3 and <5% Severity Green Yellow

R, Z, L
Fi, I/F

>5%
<1 pt

Red
Green

Fi, I/F
Fi, I/F

>1 and <3


>3
(c)2005 Penrose

Yellow
Red

Trended Reading

(c)2005 Penrose

AC Motor 2

(c)2005 Penrose

PdM Testing Frequency


Motor Type 3-Phase Non-Critical 3-Phase Production 3-Phase Critical DC Motors Transformer Clean/Dry Environment Moderate Environment Dirty/Wet Environment

12 Mo 6 Mo 3 Mo 6 Mo 12 Mo
(c)2005 Penrose

9 Mo 6 Mo 2 Mo 6 Mo 9 Mo

6 Mo 3 Mo 1 Mo 3 Mo 6 Mo

Estimating Time To Failure!

What To Do Once A Fault Is Detected

Motor ready for test in motor repair shop


(c)2005 Penrose

What Makes Fault Detection Difficult?


Time To Failure
Application Type of Fault Severity of Fault

Based upon Stages of Failure, Insulation fails over time

(c)2005 Penrose

Winding Contamination
7
Time to Action (Months)

6 5 4 3 2 1 0 Annual 9Months
(c)2005 Penrose

Semi Test Frequency

Quarterly

Monthly

Turn to Turn Shorts


Time to Action (Months)

10 8 1pt 6 4 2 0 Annual 9 Months Semi Quarterly Monthly Test Frequency 2pt 3pt >3

(c)2005 Penrose

Phase to Phase or Coil to Coil 7 6 5 4 3 2 1 0 -1 Annual 9 Months Semi Quarterly Monthly Test Frequency (c)2005 Penrose 1pt 2pt 3pt >3

Time to Action (Months)

TTFE Software

(c)2005 Penrose

Final Comments
When is TTFE effective?
Technology can detect developing faults (Condition-Based) Optimized testing frequency or continuous monitoring A history exists or can be obtained Multiple-Technology approach to confirm condition and stage of failure Understanding that the functional failure is not instantaneous and some forcing function drives the failure Action is taken on findings: Risk-based decision
(c)2005 Penrose

SUCCESS by DESIGN