New F-Generation
Flow Sensor
Increase reactor spec. 10A 25mH -> 14A 10.5mH 3A 15mH -> 6A 35mH
Pressure Sensor
Expansion Vessel Tank
Add Alternative CIMM (Italy) or HengXiang (China)
Water Pump
Heater Assy
DC Fan Motor
Compressor Size Up
5JD420 -> 5JD650
Reduce length by increase heater density Add alternative JuNichi (China) or Vitar (Malaysia)
Water Pump
Heater Assy
Reduce length by increase heater density Add alternative JuNichi (China) or Vitar (Malaysia)
AFTER
H16C0613
Additional water outlet sensor 2 (new) New PCB - Pump circuit for Erp compliance - Additional water outlet sensor Omit relay (PCB built in)
Magnet relay
ELCB
Omit Single phase ELCB -P.S. Cord Holder - Screw - Grounding terminal
New PCB for pump circuit Omit 1 pcs ELCB and magnet relay for simplify strcuture ( Back up & tank heater share usage - with only 1 heater ON at one time)
BEFORE
AFTER
B601008
B621128
Minimum flow rate: 10 l/min (ON/OFF signal) Minimun flowrate: 17 l/min Operation diagram Operation diagram
Change supplier to SIKA - reduce flow rate to improve market installation (without extra pump) for replacement market.
A50C3164
Detect heat exchanger unit water outlet temperature for new deice control judgment (prevent WHE cracked)
NOT AVAILABLE
AFTER
Speed setup from RC Step 1 : Press Service button Step 2 : Display SR 02 Step 3 : Change speed (7 speeds selection & default at 4)
B621092
B62C1195
Allocate at bottom base pan and turn anti clock wise to open
Manually twist to release water Pressure greater 3 bar will push the paddle and reliese water
Pressure greater 3 bar will push the paddle and release water
Level up to reliese water Change supplier to Matsui
Amount of refrigerant
Old type had 3,1 kg, now we are below 3 kg, so that the endcustomer doesnt need to do a leak test once per year
outdoor
Tank
outdoor
Tank
indoor
indoor
ELB1
ELB2
ELB3
ELB
ELB2
Adoption Sep-2013 shipmentFrom 16kW T-CAP2Model Later, plan to install this method in next 2 fan types models. (Same time as Class A pump) Advantage It can significantly reduce activation point of backup heater during normal operation.
Water inlet temperature
Free Heater ON
25 20
23 18 10
12
Heater ON HP OFF
Heater ON HP OFF
Actual operation
OD Heat Ex
4-way valve
Main exp valve COMP 2-way valve bypass bypass exp valve Sub-cooler
4-way valve
COMP
New Remote Controller No compatible with old bi-block models 2012 current 2013 new
kpa
L/mni
30
40
50
60
70
Min
W
Speed 7 Speed 6 Speed 5 Speed 4 Speed 3
Speed 2
Speed 1 Max
30 L/min 40
50
60
70
Min
HP stops if water outlet temp. = 37C water inlet temp. = 32C ( with nominal water flow )
HP starts if water inlet temp. 29C = 32C 3 K
18C
< 14C
HP starts < 1K
HP stops 3K
52C < tank temperature < 48C Tank mode stops 2K Tank set temp. = 50 C < tank temperature < Tank mode starts 2K
50C < tank temperature < 48C Tank mode stops 0K Tank set temp. = 50C < tank temperature < Tank mode starts 2K
HP stops if water outlet temp. = 57C water inlet temp. = 52C ( with nominal water flow )
HP starts if water inlet temp. 49C = 52C 3 K
H20
During new deice cycle, when water pump turned off, if flow SW was continuously detect ON for 10 sec
F30
1) Open circuit : Less than -50C for 5 sec continuously detection 2) Short circuit : 127C or more for 5 sec continuously detection