Sunteți pe pagina 1din 87

Transformer

Professor Mohamed A. El-Sharkawi


Why do we need transformers?
• Increase voltage of generator’s output
– Transmit high power at low current
– Reduce cost of transmission system
• Adjust voltage to a usable level
• Create electrical isolation
• Match load impedance
• Filters
El-Sharkawi@University of Washing 2
ton
220kV-750kV

Distribution
Transformer

15 kV- 25kV Transmission


Transformer

Service 208V- 416V


Transformer

El-Sharkawi@University of Washing 3
ton
Transmission Transformer

El-Sharkawi@University of Washing 4
ton
Distribution Transformer

El-Sharkawi@University of Washing 5
ton
Distribution Transformer

El-Sharkawi@University of Washing 6
ton
Service Transformer

El-Sharkawi@University of Washing 7
ton
Service Transformer bank

El-Sharkawi@University of Washing 8
ton
Service Transformer bank

El-Sharkawi@University of Washing 9
ton
Service Transformer

El-Sharkawi@University of Washing 10
ton
Service Transformer

El-Sharkawi@University of Washing 11
ton
Service Transformer

El-Sharkawi@University of Washing 12
ton
Service Transformer

El-Sharkawi@University of Washing 13
ton
Service Transformer

El-Sharkawi@University of Washing 14
ton
Low power Transformer

El-Sharkawi@University of Washing 15
ton
Basic Components

Iron Core Insulated Copper Wire

El-Sharkawi@University of Washing 16
ton
Basic Components
Laminated
iron core

Insulated
copper wire

El-Sharkawi@University of Washing 17
ton
El-Sharkawi@University of Washing 18
ton
El-Sharkawi@University of Washing 19
ton
El-Sharkawi@University of Washing 20
ton
d d
e1  N1
dt e2  N 2
1
dt
 
N1  e1 dt
i1 i2

e1 N1 N2 e2

Primary Secondary

El-Sharkawi@University of Washing 21
ton
Basic Analysis:Voltage
d i1 i2
N1
e1  t  dt N1 + +
  e1 N1 N2 e2
e2  t  N d N 2 _ _
2
dt
  
E1 N1 E1 E2
  
E2 N 2 N1 N 2
• Volts/turn is constant
• Voltages are in phase (no phase shift)
• Voltage magnitudes vary with turns ratio.
El-Sharkawi@University of Washing 22
ton
Basic Analysis: Power and current
i1 i2
S1  S 2
+ + e2
e1 _
N1 N2
_
EI E I
1 1
* *
2 2

*
I E2 N 2 I1 N 2
1

*
  N1 I 1  N 2 I 2
I2 E1 N1 I 2 N1
• Currents are in phase.
• Current ratio is opposite to the voltage ratio
El-Sharkawi@University of Washing 23
ton
Basic Analysis: Reflected impedance
Flux

I2 Load
I1
Source
E1 N1 N2 E2 Zload

Primary Secondary

E2
Z load 
El-Sharkawi@University of Washing I2 24
ton
Basic Analysis: Reflected impedance
I1
E1
Source
' Z '

E1 Z load
load
I1
2
Primary Z '
E1 I 2  N1 

load
  
Z load E2 I1  N 2 
2
 N1 
Z '
load  Z load  
 N2 
El-Sharkawi@University of Washing 25
ton
Single-Phase, Ideal Transformer Ratings
I1 I2
Apparent Power
+ +
V1 N1 N2 V2
2 KVA, 120/240 V - -

Primary Voltage Secondary Voltage

El-Sharkawi@University of Washing 26
ton
Rated Values
• Rated voltage: The device can
continuously operate at the rated voltage
without being damaged due to insulation
failure
• Rated current: The device can
continuously operate at the rated current
without being damaged due to thermal
destruction
El-Sharkawi@University of Washing 27
ton
Example I1 I2
Transformer rating:
2 KVA, 240/120 V
Compute the currents + +
V1 N1 N2 V2
- -
S  V1 I1  V2 I 2  2 KVA
S
2 KVA
I2    16.67 A
V2 120 V

S
2 KVA
I1    8.33 A
V1 240 V
El-Sharkawi@University of Washing 28
ton
Multi-Secondary Transformer

El-Sharkawi@University of Washing 29
ton
Multi-secondary windings

El-Sharkawi@University of Washing 30
ton
I3

I1 N3 E3

E1 N1 I2

N2 E2

Primary
E1 N1

E2 N 2
E1 N1

El-Sharkawi@University of Washing
E3 N 3 31
ton
Current ratio: superposition

N2
I12 I12  I2
N1
E1 N1 I2

N2 E2

Primary

El-Sharkawi@University of Washing 32
ton
Current ratio: superposition

I3

N3
I13  I 3
I13 N3 E3

E1 N1
N1

Primary

El-Sharkawi@University of Washing 33
ton
I3 Superposition
N3 E3
I1

E1 N1 I2

N2 E2

Primary

N2 N3
I1  I12  I13  I 2  I3
N1 N1
I 1 N1  I 2 N 2  I 3 N 3
El-Sharkawi@University of Washing 34
ton
I3 Superposition
N3 E3
I1

E1 N1 I2

N2 E2

Primary

S1  S 3  S 3
EI E I EI
1 1
* *
2 2
*
3 3

El-Sharkawi@University of Washing 35
ton
Example
• The transformer consists of one primary winding and two secondary
windings. The number of turns is each winding is
N1  4000; N 2 1000; N 3  500
A voltage source of 120V is applied to the primary winding, and
purely resistive loads are connected across the secondary windings. A
wattmeter placed in the primary circuit measures 300W. Another
wattmeter placed in the secondary winding N2 measures 90W.
Compute the following:

• The voltages of the secondary windings


• The currents in N3
• The power consumed by the load connected across N3

El-Sharkawi@University of Washing 36
ton
Solution
N2 1000
E 2  E1 120  30
N1 4000
N3 500
E3  E1 120  15
N1 4000
P1 300
I1    2.5
E1 cos1 120
P2 90
I2   3
E 2 cos 2 30

El-Sharkawi@University of Washing 37
ton
Solution
I1 N1  I 2 N 2  I 3 N 3
2.5 * 4000  1000 * 3  500 I 3
I 3  14

E1 I1  E 2 I 2  E3 I 3
120 * 2.5  30 * 3 15 I 3

I 3  14
El-Sharkawi@University of Washing 38
ton
Solution

P1  P2  P3
300  90  P3

P3  210

El-Sharkawi@University of Washing 39
ton
Autotransformer

El-Sharkawi@University of Washing 40
ton
I1 I2
A1 B1

E1 E2
V1 N1 N2 V2
A2
B2

El-Sharkawi@University of Washing 41
ton
Autotransformer: Voltage and current
Is
I load  I1  I 2 N1
A1

E1 I1

A2
Iload
V1
V1  E1  E2 N2
B1

E2 I2 V2

B2

El-Sharkawi@University of Washing 42
ton
I1 I2 Autotransformer
+ + Is
E1 N1 N2 E2 A1
N1
E1 I1
- -
A2 Iload
V1 B1
N2
S A  E1 I1  E2 I 2 E2 I2 V2

B2

S B  V1 I s  V2 I load
El-Sharkawi@University of Washing 43
ton
Autotransformer: Power

S B  V1 I s  ( E1  E2 ) I1  E1 I1  E2 I1
S B  S A  E 2 I1

SB  S A
El-Sharkawi@University of Washing 44
ton
Example
Ratings of regular transformer: 10 kVA, 400/200 V
New voltage ratio: 600/200 V
Is
Compute the new ratings A 1
N1
Solution E1 I1
10 Iload
I2   50 A A2
0.2 V1 B1
10 N2
I1   25 A E2 I2 V2
0.4
S B  V1 I1  600  25  15 kVA B2

El-Sharkawi@University of Washing 45
ton
VARIC: Variable Auto-Transformer
Z

N3
Is
Y

Sliding
I1 terminal
N1
V1 Iload

N2 I2 V2

El-Sharkawi@University of Washing 46
ton
Output Voltage
N2
Vload  Vs Z

N1  N 2 Is N3

Y
Sliding
I1 terminal

At Y N1
Iload
N1  N 2 V1
Vload  Vs  Vs
N1  N 2 N2 I2 V2

At Z
N1  N 2  N 3
Vload  Vs
N1  N 2
El-Sharkawi@University of Washing 47
ton
Three-Phase Transformer

El-Sharkawi@University of Washing 48
ton
3-phase transformer

El-Sharkawi@University of Washing 49
ton
3-phase transformer Y-Y connection.
Also known as star-star connection
a A
Ratio of Phase Voltage

Ratio of Line Voltage


N1 N2
n N

c b C B

Van N1 Vac 3 Van N1


  
VAN N2 VAC 3 VAN N2
El-Sharkawi@University of Washing 50
ton
Ratio of Phase Voltage and line voltage
3-phase transformer ( -)
A
a

N1 N2
B
c b
C
Vac N1

VAC N2
El-Sharkawi@University of Washing 51
ton
3-phase transformer (Y-)
Also known as star-delta connection
a A
Ratio of Phase Voltage

Ratio of Line Voltage


N1
n
N2 B

c b C
Van N1 Vac 3 Van 3 N1
  
VAC N2 VAC VAC N2
El-Sharkawi@University of Washing 52
ton
3-phase transformer bank (Y-)
a A
V AB N2 Vab Van N1 N2
 VAB
Van N1
b B
V AB V AB N2 N1 N2
 
Vab 3 Van 3 N1
C
c
N1 N2

El-Sharkawi@University of Washing 53
ton
El-Sharkawi@University of Washing 54
ton
Ratings of Ideal 3-phase
Transformer
Apparent Power (3-phase)

100 MVA, 13.8/138 KV

Primary Voltage Secondary Voltage


line-to-line line-to-line
El-Sharkawi@University of Washing 55
ton
Example
• Three single-phase transformers are used to form a three-
phase transformer bank. Each single-phase transformer is
rated at 10 kVA, 13.8 KV/240 V. One side of the
transformer bank is connected to a three-phase, 13.8 kV
transmission line. The other side of the transformer is
connected to a three-phase residential load of 415.7V,
9kVA at 0.8 power factor lagging. Determine the
connection of the transformer bank, the voltage ratio of the
transformer bank, and the line current of the bank at the
13.8 kV side

El-Sharkawi@University of Washing 56
ton
Solution
• Secondary voltage (Low voltage side) should be in
Y to provide the needed residential voltage
415.7
 240 V
3
• The high voltage side must be Delta-connection
– The line-to-line voltage of the supply is 13.8 kV. Same
as the transformer rating of the primary.
– If the primary is connected in Y, the voltage of the load
would be lower than 240 V.

El-Sharkawi@University of Washing 57
ton
Solution Van= 240 V
A a
VAB= 13.8 kV N1 N2 Van Vab

B
b
N1 N2

C
c

El-Sharkawi@University of Washing 58
ton
VAB VAB 13,800
Solution Van= 240 V

  A a
Vab 3 Van 3 240 VAB= 13.8 kV Van V
N1 N2 ab

Phase current of the load B b


9000 N1 N2
I2  3  12.5 A C
240 c
Phase current of the Transformer primary

N2 240 Line Current in primary


I1  I 2  12.5  0.2174 A
N1 13,800 I A  3 I1  0.377 A
El-Sharkawi@University of Washing 59
ton
Actual Transformer
• Windings: i1 i2
– Resistance
+ + e2
– Inductance e1 _
N1 N2
_
• Core:
– Eddy Current
– Hysteresis

El-Sharkawi@University of Washing 60
ton
Windings Impedance
R1 X1 R2 X2

N1 N2

Ideal Transformer
El-Sharkawi@University of Washing 61
ton
Core Hysteresis
i B
+
e N
_

B f   e dt 
H  f i El-Sharkawi@University of Washing 62
ton
e

El-Sharkawi@University of Washing 63
ton
Core Model i

Let
e R
e  Emax sin t
e
Emax
 e dt    cos t
e Emax
i  sin t i
R R

El-Sharkawi@University of Washing 64
ton
Core Model i

Let
e Xl
e  Emax sin t
Emax e
 e dt    cos t
di
eL
dt
i
1 Emax
i   e dt   cos t
L L
El-Sharkawi@University of Washing 65
ton
i

e R Xl

e
e

i
i

El-Sharkawi@University of Washing 66
ton
Equivalent Circuit
'
R1 X1 I 2 R2 X2
N1 N2
Io
I1 I2

load
V1 E1 E2 V2
Ro Xo

E1 N1 V1 '
I2 N2 I1
   
E2 N 2 V2 I2 N1 I2
El-Sharkawi@University of Washing 67
ton
Referred impedance
'
R1 X1 I 2 R2 X2
N1 N2
Io
I1 I2
V1 E1 E2 V2
Ro Xo

E1 
N1
N2
E2 
N1
N2
 I 2  R2  jX 2   V2 

El-Sharkawi@University of Washing 68
ton
Referred impedance
'
R1 X1 I 2 R2 X2
N1 N2
Io
I1 I2
V1 E1 E2 V2
Ro Xo

N1 N 1  ' N1 
E1  E2  I2  R2  jX 2   V2 
N2 N2  N2 
El-Sharkawi@University of Washing 69
ton
N1 N 1  ' N1 
E1  E2  I 2  R2  jX 2   V2 
N2 N2  N2 
2
 N1  N1
Define: E1  I  '
2
  R2  jX 2   V2
 N2  N2
2
 N1 
R'2    R2
 N2 
2
 N1  Then:
X '2 
  X 2
 N2 
' N1
V2  V2
 
E1  I 2' R2'  jX 2'  V2'
N2 El-Sharkawi@University of Washing 70
ton
Equivalent Circuit Referred to
Source Side

E1  I 2' R2'  jX 2'  V2' 
'
R1 X1 I 2 R2 X2
N1 N2
Io
I1 I2
V1 E1 E2 V2
Ro Xo

R1 X1 R'2 X '2

Io
I1 I 2'
V1 E1 V2'
Ro Xo

El-Sharkawi@University of Washing 71
ton
Practical Considerations
R1 X1 R'2 X '2

Io '
I1 I 2
V1 E1 V2'
Ro Xo

'
R1  Ro  R2 ' I1  I 2  I o
'
X 1  X o  X 2' I 2  I o  I1
El-Sharkawi@University of Washing 72
ton
R1
X1 R'2 X '2

Io
I1 I '
2
V1 V2'
Ro Xo

X1 X '2 I 2'
R1 R'2

Io
I1 V2'
V1
Ro Xo

El-Sharkawi@University of Washing 73
ton
X1 X '2
R1 R'2

I 1  I '2
V1 V2'

'
Req  R1  R2
Define:
'
X eq  X 1  X 2

El-Sharkawi@University of Washing 74
ton
Analysis of Transformer
Req X eq

I 1  I '2
V1 V2' Z

'
V1  V2  '
I2  Req  jX eq 
El-Sharkawi@University of Washing 75
ton
Terminologies
V2 Load Voltage

Load Voltage referred to Source side


N1
V  2
'
V2
N2 Impedance referred to Source side

2
 N1 
I2 Load Current R  
'
2
 R2
 N2 
2
Load current referred to Source side  N1 
X  
'
2
 X 2
N2  N2 
I 
'
2 I2
N1 El-Sharkawi@University of Washing 76
ton
Analysis of Transformer
Req X eq

I 1  I '2
V1 V2' Z’

'
V1  V2  '
I2  Req  jX eq 
El-Sharkawi@University of Washing 77
ton
Req X eq

I 1  I '2
V1 V2' Z’

'
I2 X eq
'
I2
'
I2 Req
El-Sharkawi@University of Washing 78
ton
Req X eq

'
I1  I 2
V1 V2' Z

V1  V2'  I 2' Req  j I 2' X eq V1


I '2 Z eq
 I '2 X eq
 V2' I '2 Req
'
I2
El-Sharkawi@University of Washing 79
ton
Ratings of Actual 3-phase
Transformer
Apparent Power (3-phase)

100 MVA, 13.8/138 KV


'
V 2 V2
line-to-line line-to-line

El-Sharkawi@University of Washing 80
ton
Example
A transformer has the following parameters:
N1
10 Z l  0.530  o
N2

Req  R1  R2' 1; X eq  X 1  X 2' 10; Ro 1000; X 0  5000

The rated voltage of the primary winding is 1000V.


Compute the load voltage.

El-Sharkawi@University of Washing 81
ton
Req X eq
Solution

'
 N1 
2
I1  I 2
Z  Z L 
'
L
  50  V1 V2' Z’
 N2 

V 1000  0 0
I 2'  1
  17. 7   38.31o
A
 Req  j X eq   Z L 1 j 10  50 30
' o

V  I Z  17.7   38.31
2
' '
2
'
L
o
 50 30   885   8.31
o 0
V
N2 1
V2  V  885  88.5 V
'
2
N1 10
El-Sharkawi@University of Washing 82
ton
Voltage Regulation VR
Req X eq

'
I1  I 2

Load
V1 V2'

Vno load  V full load


VR 
V full load
V1  V2'
VR 
Measured at the load side V2'
El-Sharkawi@University of Washing 83
ton
Example
Calculate the voltage regulation of the transformer in the
previous problem.

Solution:
'
V1  V2
VR 
'
V2
7209.5  7200
VR   100  0.14 %
7200

El-Sharkawi@University of Washing 84
ton
Efficiency  Req Xeq

Io
I1 '
V1 I 2 V2'
Ro Xo

 
Output Power Pout
Input Power

Pin
Pcu   
' 2
I2 Req
V12
Pin  Pout  Losses Piron 
Ro
Plosses  Pcu  Piron ' '
Pout  V2 I 2 cos 
El-Sharkawi@University of Washing 85
ton
Example
A 10 kVA, 2300/230 V, single phase distribution transformer
has the following parameters:
R1  5.8  ; X 1  X '2  12  ; R'2  6.05 
Ro  75.6 k ; X o  69.4 k
At full load and 0.8 power factor lagging, compute the efficiency
of the transformer.

El-Sharkawi@University of Washing 86
ton
Solution
Pout  V2' I '2 cos   S cos   10  0.8  8 kW

' S 10 ,000
I2    4.35 A
' 2300
V2

Pcu   
' 2
I2 Req  ( 4.35 )2   5.8  6.05   224.23 W

Piron 
V 1
2

V

 
 2300
2
' 2
 70 W
2

Ro Ro 75,600
Pout 8000
    100  96.45 %
Pin 8000  224.23  70
El-Sharkawi@University of Washing 87
ton

S-ar putea să vă placă și