We will cover Carriers recommendations for the configuration, setup, installation, start-up, and wiring for a BACnet MS/TP network that will provide the best network performance with i-Vu Open controllers 2 We will cover:
Planning & Working With BACnet MS/TP Networks BACnet MS/TP Networks 3 Some of the definitions you may know from the CCN world are somewhat different in the BACnet world. Also, certain MS/TP network terms have no CCN equivalent.
A CCN Network = an i-Vu Open System This defines the entire system of controls
A CCN Bus = a MS/TP Network A MS/TP Network is equivalent to a CCN Secondary Bus. The concept of the primary and secondary bus does not exist in MS/TP networking
A Node refers to an Addressable Controller
A Physical Segment of an MS/TP network is a contiguous length of medium to which BACnet addressable controllers (nodes) are attached
A Segment of an MS/TP network is one or more Physical Segments connected by repeaters
A note about BACnet network definitions BACnet MS/TP Networks 4 MS/TP Network Planning BACnet MS/TP Networks 5 i-Vu User Interfaces (i-Vu Open server, Field Assistant)
Network devices (i-Vu Open routers and links)
Zoning Controls (factory & field installed)
Application Specific Controllers
Programmable Controllers & Expanders
Ancillary 485 boards
6 Network Devices & Tools BACnet MS/TP Networks Maximum of 750 Controllers (nodes) for an entire i-Vu Open System
Maximum of 60 nodes per MS/TP Network
A <2000 foot network can have 32 nodes (no repeaters required)
A repeater (REP485) is required after every 31 devices, or after 2000 feet (a repeater does not count as node)
Each node on the MS/TP network must have unique MS/TP MAC address
7 i-Vu Open Network Controller Requirements BACnet MS/TP Networks
MS/TP is a token passing network, meaning each node on the MS/TP network can communicate only when it has the token. The time needed for the token to cycle through the MS/TP network is dependent on many factors. Follow the guidelines below to optimize MS/TP network performance. MS/TP Network Design Guidelines BACnet MS/TP Networks 8 Baud Rate Maximum number of controllers per MS/TP network 76.8 kbps 60 38.4 kbps 30 19.2kbps/ 9600 bps 15 Each physical segment must be no longer than 2000 feet
Each physical segment must start and end with an end of line resistor
Maximum segment length of 10,000 feet (5 physical segments of 2,000 feet, 4 repeaters)
A surge suppression device (PROT485) should be installed for surge protection at each place communications wire enters or exits the building or within 250 feet of each controller
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D. Color code Black/white Shielding
Aluminum/Mylar shield with 24 AWG (7x32) TC drain wire Jacket SmokeGard (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D. Halar (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D. DC resistance 5.2 Ohms/1000 feet (50 Ohms/km) nominal Capacitance 12.5 pF/ft (41 pF/meter) nominal conductor to conductor Characteristic impedance
100 Ohms nominal BACnet MS/TP Networks 12 The wires are connected correctly to the terminal blocks: White wire to NET+ (typically, terminal 1 on a controller) Black wire to NET- (typically, terminal 2 on a controller) Shield/ground wire to Shield (typically, terminal 3 on a controller)
NOTE : 1. Communication wire should not touch the cables foil shield, shield wire or metal surface other than the terminal block 2. Do not ground the shield to earth ground or to the controllers power ground.
Analog & Discrete Sensor Distances < 100 ft: Single twisted pair, CM, 22AWG, Plenum rated wire Distances > 100 ft-500 ft: Single twisted shielded pair, CM, 22AWG, Plenum rated wire.
15 Daisy Chain Network Topology BACnet MS/TP Networks 16 17 BACnet MS/TP Networks Sample MS/TP Network Segment Note: This example shows a network segment consisting of 3 physical segments joined by two repeaters
i-Vu Open Ancillary RS485 Network Hardware BACnet MS/TP Networks 19 Nodes The TERM485 is a 120 ohm, watt resistor that is attached to the controller at the beginning and the end of each physical segment to terminate the physical segment per the BACnet spec.
The TERM485 is installed across the NET+ and NET- terminals on the end controllers on each physical segment. What Is A TERM485 BACnet MS/TP Networks 20 Purpose: The BT485 is a device that you attach to the controller at the beginning and the end of each physical segment to add bias and to terminate the physical segment Push the BT485 onto the connector located near the BACnet port on the controller BT485 has no polarity associated with it Verify the LED turns on What Is A BT485? BACnet MS/TP Networks 21 What is Network Bias? Network biasing drives the NET+ and NET- signal wires to a reference voltage (>200mV) when no device is transmitting. Network biasing promotes reliable communication on the MS/TP RS485 network. There should be one biasing device attached at each end of a network segment.
BACnet MS/TP Networks 22 What is the difference between a BT485 and a Terminating Resistor? The BT485 provides network bias and termination, the terminating resistor only provides network termination What is Network Termination? Network Termination adds a fixed resistance across the network, improving communications reliability by suppressing signal reflections and reducing signal distortion. BACnet MS/TP Networks 23 BT485 and Line Terminators Application Notes
A MS/TP network segment should have either of the following in order or priority:
1. A BT485 at each end (unless the segment is less than 10 feet [3 meters] long) to add bias and prevent signal distortions.
2. A 1/2 watt, 120 Ohm terminating resistor (Part# TERM485) at each end to prevent signal distortions
NOTES
A network should always be installed with some kind of termination.
The USB Cable used with the i-Vu Open server does not support the BT485. It would therefore require a 120 ohm terminating resistor if the server is at one end of the network.
If the network segment contains a third-party device that applies bias to the network, you must do one of the following: Set the third-party device so that it does not apply bias Replace BT485's with 120 Ohm terminators
If a third-party device has its own termination resistance and is located at one end of the network segment, do not install a BT485 or 120 Ohm terminator at that end of the network segment.
To attach a 120 Ohm terminator to an i-Vu Open controller, remove the MS/TP bus connector then attach the terminator across NET+ and NET terminals. Reconnect MS/TP bus to controller. REP485 i-Vu Open Router Application of a BT485 Terminator BACnet MS/TP Networks 24 Purpose: It is a surge suppressor, and guards against large electrical surges on the communications network. It does not count as a network node The PROT485 has two replaceable .5 A fuses What Is A PROT485? BACnet MS/TP Networks 25 Purpose: Protects against large electrical surges on the communications network Mount at each place where communication bus enters or exits the building Install at least one PROT485 within 250 feet of every controller Use the same polarity throughout the network segment PROT485 Installation and Wiring BACnet MS/TP Networks 26 Use 12 AWG grounding wire, no more that 6 feet long. If controller is within 6 feet of the PROT485 (as shown above), connect one ground wire to the power ground of the controller and another ground wire to earth ground. Connect grounding wires to the PROT485 Earth Ground spade lugs with spade connectors 6 feet long 6 feet long Female spade connector: 3M Corporation P/N FD114-250C or equivalent Grounding the PROT485 Controller within 6 feet BACnet MS/TP Networks 27 Chassis Ground Use 12 AWG grounding wire (no more that 6 feet long. Connect single grounding wire to the PROT485 Earth Ground connectors with female spade connector
6 feet long Grounding the PROT485 No controller within 6 feet of PROT485 BACnet MS/TP Networks 28 It is recommended to mount a PROT485 at each place where communication wire enters or exits the building, and to install at least one PROT485 within 250 feet of every controller Sample PROT485 Network BACnet MS/TP Networks 29
It is a physical layer repeater that can be used to extend the capacity and/or length of an RS485 MS/TP network It has two bi-directional isolated ports that can communicate at baud rates from 1200bps to 156kbps A network of <2000 feet can have 32 nodes (no repeater required) The REP485 is not addressable
What Is A REP485? BACnet MS/TP Networks 30
On a network longer than 2,000 feet, place a REP485 after 2,000 feet regardless of the number of controllers (Segment A) Each REP485 counts against the 32 nodes/segment rule (Segment B) On a network with more than 32 controllers, place a REP485 after 32 nodes regardless of the length of the network (Segment C)
Using A REP485 (cont)? BACnet MS/TP Networks 31 Nodes 1200 ft 1 2000 ft 600 ft
2
3
4
5
6
7
8
9
1 2 3 29 30
28
1
2
3
30
31 Segment A Segment B Segment C LEDs 1. Power 2. Network A blink when receiving data 3. Network B blink when receiving data Female spade connector 3M Corporation P/N FD114-250C or equivalent Connect Earth Ground terminal with a piece of 12 AWG ( no longer 2 feet ) Power: 24Vac 6VA) BT485 BT485 Network A Network B Power Jumper REP485 Hardware Detail BACnet MS/TP Networks 32 Connect Earth Ground terminal with a piece of 12 AWG (2 feet maximum). Use spade connector: 3M Corporation P/N FD114-250C or equivalent REP485 Wiring Terminations BACnet MS/TP Networks 33 Power: 24Vac 6VA) Place the power jumper in the OFF position Remove the screw connector from the 24V supply terminals on the REP485 Connect 24 Volts to the screw terminal connector Measure the voltage at the power input terminals to verify that the voltage is within the operation range of 21.6 26.4 Vac. Connect the EARTH GRND terminal with 12 AWG wire (2 feet or less ) Insert screw terminal connector into REP485 device. Place the power jumper in the ON position. Verify the POWER LED lights is on. Note: i-Vu Open controllers can share a power supply as long as you maintain the same polarity and use the power supply only for i-Vu Open controllers REP485 - Power Wiring BACnet MS/TP Networks 34 Connect the communications wiring to the REP485s Network A and Network B connectors. Add BT485 to each side of the repeater Verify communication with the network by viewing module status reports (modstat) in i-Vu or Field Assistant for controllers beyond the REP485. REP485 - Communication Wiring BACnet MS/TP Networks 35 Hybrid Network Topology BACnet MS/TP Networks 36 Star Network Topology BACnet MS/TP Networks 37 1 4 5 6 3 Physical Segment Physical Segment Note 1: This example shows a network segment consisting of 6 physical segments. #1, 2, and 3 form the main branch, and #4, 5, and 6 are connected in a Star topology, using repeaters to establish the branches of the Star. Note 2: There are no nodes on physical segment #2. 2 P h y s i c a l
S e g m e n t
2 1 5 6 7 4 8 Star Network Topology BACnet MS/TP Networks 38 Note: This example shows a network segment consisting of 8 physical segments connected in a Hybrid topology, using 4 repeaters to establish the branches of the Star, and 3 repeaters to establish the main branch. The top, side, and bottom physical segments (#1 through 4) are part of the main network segment. The three center physical segments (#5, 6, 7), and the physical segment on the bottom (#8) are the branches of the Star. Physical Segment Physical Segment Physical Segment P h y s i c a l
S e g m e n t
Physical Segment 3
A message from one controller to another controller may not pass through more than 4 repeaters (same as in a daisy chain)
A branch in a Star network may not have more than 4 physical segments joined by three repeaters, thus a maximum of 8,000 feet
A physical segment in a Star network must begin with a repeater
A physical segment in a Star network must be terminated at both ends
An MS/TP network using Star network topology is limited to no more than 60 nodes (same as a daisy chain MS/TP network)
Rules Governing Hybrid Network Layouts BACnet MS/TP Networks 39 Made up of various MS/TP networks back-boned by an IP network
Each i-Vu Open server USB based MS/TP Network can have a maximum of 60 nodes.
Each MS/TP network is made up of segments. Maximum length of one segment is 2000 feet with 32 devices max per segment.
An i-Vu Open router will increase the capacity of the system, allowing up to 60 more MS/TP nodes per router to be connected to the network.
On any given MS/TP network, a message from any controller cannot pass through more than 4 repeaters in order to reach its destination.
1-31 controllers 32 - 60 controllers Summary BACnet MS/TP Networks 40 Use proper cable and the following principles when connecting a node to an MS/TP network.
Connect the shields of the cables together at each node.
End-of-line termination- each MS/TP network physical segment requires end-of-line termination for proper operation of the network. 41 MS/TP Best Networking Practices BACnet MS/TP Networks Avoid running communications wiring or sensor input wiring next to AC power wires or relay wires.
MS/TP networking cable is comprised of a single twisted pair of wires (NET+ and NET-) and a shield (Alternatives are listed in the installation guide)
1. Is EOL termination (BT485 or TERM485) installed at BOTH ends of the physical segment? 2. Are repeaters installed as required? 3. If sharing power, is polarity maintained amongst all the controllers? 4. Is the shield grounded at one or both ends instead of being terminated at the controller? 5. If sharing the MS/TP network with 3 rd party BACnet controllers, make sure that these controllers do not have EOL termination or biasing enabled unnecessarily (check literature or rep of 3 rd party equipment).
44 BACnet MS/TP Networks Optimizing Performance
1. Follow the max controllers per segment based upon the selected baud rate. 2. Controllers should follow contiguous addressing starting at 1. 3. Configure the Max Master and Max Info Frames to suit the system (set within driver properties of controller) a. Max Master the highest addressed controller would have this set to his address b. Max Info Frames specifies how many requests a controller can make while he has the token. Defaults for i-Vu Open devices: a. Routers are set to 50 b. Controllers are set to 10
45 BACnet MS/TP Networks
Additional BACnet Reference Information 46 MS/TP Networking/Wiring BACnet Installation Guide
The MS/TP Networking/Wiring BACnet Installation Guide can be found on HVACPartners
ASHRAE BACnet Specification
The BACnet specification is available from ASHRAE at www.ashrae.org BACnet MS/TP Networks