Sunteți pe pagina 1din 48

the performing arts cover forms of music (orchestral, choral, pop/rock

and jazz), opera,musicals, dance and drama.


It is acknowledged that the performing
arts also cover music-theatre, musicals, comedies,
music-hall, variety, vaudeville, puppet shows, revues,
mime, cabaret, folk music, live art, and street performers,

Design Requirement
A proscenium stage type auditorium of 1500 capacity of persons.
An open air theatre with 500 persons capacity seating.
Multi-cuisine food court with a capacity of 100.
Small shopping display arcade (six shops of varying sizes)
Conference rooms for press releases
Exhibition lobby space of 300 sq.m.
Four organisations office space of 50 sq. m. each.
Three dormitories of capacity 20 persons each.
PARKING


AREA PER SEAT WITH CIRCULATION= .5SQM
NO. OF SEATS= 1500
TOTAL AREA REQUIRED FOR SEATING= 1500* .5= 750SQM

C. Room/dormitory facilities
The standards of the rooms or dormitory facilities are important to allow workers to rest properly and to maintain
good standards of hygiene. Overcrowding should be avoided particularly. This also has an impact on workers
productivity and reduces work-related accidents. It is generally acknowledged that rooms/dormitories should be
kept clean and in a good condition. Exposure to noise and odour should be minimised. In addition,
room/dormitory design and equipment should strive to offer workers a maximum of privacy. Resorting to
dormitories should be minimised and single or double rooms are preferred. Dormitories and rooms must be
single-sex.
Benchmarks
1. Rooms/dormitories are kept in good condition.
2. Rooms/dormitories are aired and cleaned at regular intervals.
3. Rooms/dormitories are built with easily cleanable flooring material.
4. Sanitary facilities are located within the same buildings and provided separately for men and women.
5. Density standards are expressed either in terms of minimal volume per resident or of minimal floor space.
Usual standards range from 10 to 12.5 cubic metres (volume) or 4 to 5.5 square metres (surface).
6. A minimum ceiling height of 2.10 metres is provided.
7. In collective rooms, which are minimised, in order to provide workers with some privacy, only a reasonable
number of workers are allowed to share the same room. Standards range from 2 to 8 workers.
8. All doors and windows should be lockable, and provided with mosquito screens where conditions warrant.
9. There should be mobile partitions or curtains to ensure privacy.
10. Every resident is provided with adequate furniture such as a table, a chair, a mirror and a bedside light.
11. Separate sleeping areas are provided for men and women, except in family accommodation
Conference Center Design
4. Dedicated conference rooms are separated from living and leisure areas.5. Conference center has at least
one dedicated main conference room that contains a minimum of 93 square metres or 1,000 square feet and
can accommodate flexible seating arrangements. In addition, conference center has at least three other
dedicated conference rooms with no moveable walls.
6. Conferees that have multi-day meetings can safely store materials and equipment overnight in dedicated
conference rooms.
7. Conference center has sufficient inventory so that no less than 60% of all meeting space can be set up
using ergonomically designed chairs.
(The North American Chapter also requires that chairs have arms, that they swivel and tilt synchronously and
allow height adjustment. Chairs have a rounded or waterfall edge on the front of the seat pan. Chair seats
have a minimum width of .46 metre or 18 inches, a minimum depth of .4 metre or 16 inches and seat height
adjustable within at least 7.5 centimetres or 3 inches of the range between .38 and .53 metre (15 - 21 inches).
The seat and inside back of the chair are fully upholstered or constructed of Pellicle or like material. The
arms and outside back of the chair are fully upholstered or constructed of ABS molded plastic or of Pellicle or
like material. The base of the chair has five-prong design with casters.)
8. Conference center has sufficient inventory so that no less than 60% of all meeting space can be set up
using tables that are at least .6 metre or 24 inches wide and that have a non-reflective, hard writing surface
with a high-pressure laminate or hardwood veneer finish. Tables have sufficient length to allow at least .76
metre or 30 inches of space per occupant. Draped, skirted banquet tables are not acceptable.
(The North American Chapter also requires that the edge of the table is comprised of a high-pressure laminate
finish or a decorative edge banding material that is constructed of vinyl or wood products. Tables have a
reverse T style leg mechanism or its equivalent with offset legs that are permanently affixed or that fold, and
that do not impinge upon the tables occupants.)
9. Wherever meeting rooms have windows, the conference center has built-in manually or electrically operated
curtains that substantially eliminate light from outside the room.
10. All meeting rooms have lighting with in-room controls that produce maximum illumination levels between
500 and 700 lux or 50 and 70 foot candles at tabletop.
11. Dedicated conference rooms larger than 93 square metres or 1,000 square feet have zoned lighting and
controls that permit dimming across the spectrum from full-power to off.
12. All meeting rooms larger than 160 square metres or 1,750 square feet have fixtures that can illuminate a
targeted area and can be controlled separately from other zones and/or task lighting.
13. Dedicated conference rooms have individual climate controls.
Planning and anticipation audience members
must:
have knowledge of a performance: awareness by
advertising, reviews, word of mouth
organize friends and relations
have time available for attendance, including
travel
assess cost of attendance, including tickets,
refreshments, travel
have an accessible method of purchasing tickets
2 Travel to facility audience members need to
decide upon:
travel time and method (walking, car, bus, coach,
train), which will be affected by
ease of parking or convenience of public transport
3 Experience of facility impressions will be
formed of:
sequence of activities to and from seating: quality
of entrance, foyer, cloakroom, toilets, auditorium
quality of the performance: ability to see and hear;
content of play, show or concert; ability of performers,
and directors/choreographer/conductor
associated activities such as eating, drinking
and visits to art gallery, exhibitions and shops staff response to public: box office, access to seats,
directions
4 Travel from facility in addition to travelling
before a performance, post-performance factors
include:
travel time and method
convenience of public transport (if appropriate)
with services running after a performance a critical
issue
5 Recollection after the event audience members
will:
evaluate the quality of the experience. This phase
may commence the cycle again for another visit
to the facility
Auditorium design:
aural and visual limitations
levels in the auditorium
auditorium acoustics
sound insulation and noise control
seating layout
means of escape
circulation within auditorium

broadcasting requirements
latecomers
attendants
adaptation
sightlines
promenade performance
ventilation
lighting
sound equipment
fire protection
structure
ceiling zone
seating capacity
VARIOUS SHAPES IN RELATION WITH ORCHESTRA AND AUDIENCE
Opera, dance and musicals.
(a) Proscenium formats.
(b)Open stage formats.
Drama. (a) Proscenium formats. (b) Open
stage formats.
In order to discern facial expression essential
with drama the maximum distance from the
point of command on the stage should not exceed20 M.
The point of command is the geometric centre of an
open stage or the setting line of a proscenium stage.
In order to discern facial expression essential
with drama the maximum distance from the
point of command on the stage should not exceed
20 M. The point of command is the geometric
centre of an open stage or the setting line of a
proscenium stage.
For dance, the audience needs to appreciate the body
and feet of the dancers, and also to discern facial
expressions: the maximum distance from the point
of command on the stage should not exceed 20M
The greater the encirclement of the audience of the
platform/stage, then the greater the number of people
who can be accommodated within the aural and visual
limitations, up to an encirclement which places the
audience on three sides of the platform/stage. With
theatre-in-the-round the aural and visual limitations
restrict the distance from the stage, with drama, to not
more than six rows.

Seating layout
The seating layout in an auditorium depends mainly on the selection of format the
relationship between audience and performance and the visual and aural
limitations associated with a particular type of production as well as the number of levels and
sightlines. Other aspects which influence the layout, and
thereby condition seating capacity
Auditorium seating falls into three broad categories:
benches (with and without backs), fixed seats and
tip-up seats. Each of these can be with or without arms
Seatway
The seatway is the unobstructed distance between
two rows of seats, with the seat in its closed position
if
a tip-up type.
The minimum back-to-back dimension
between rows of seats with backs is
760mm. A good practice minimum is
between 850mm900mm.
The minimum width of seats with arms is
500mm centre of arm to centre of arm.
A good practice minimum is between
525mm550mm.
The minimum width of seats without arms
(individual seats or benches) is 450mm. A
good practice minimum is 500mm.
The unobstructed vertical space between
rows (seatway or clearway) should be a
minimum of 300mm. However, see detailed
table in Figure 4.4.1.
Distance from seat to gangway is now more
normally associated with number of seats
in a row (i.e. assuming typical seat width in
the order of 500mm550mm). See Figure
4.4.1, as number of seats in row dictates
seatway
EH: average eye height
A theoretical working height of 1120mm is normally
assumed. The final eye position ultimately depends on
the seat design.
TH: top of head
Distance taken from the centre line of eye to the top of
the head normally 100mm for the basis of the sightline
calculation. Enhanced allowances can be made up to
125mm. However, it is normally argued that an angled,
between-heads view combined with 100mm provides
a good basis.
Seating geometry
Seating geometry (c) Curved rows: rows focused towards platform/stage.
(d) Angular rows: straight sections to each row, angled
and focused towards the platform/stage. (e) Angular rows as (d) with
curve at change of direction. (f) Distinct blocks of seating focused towards
platform/stage. (g) Straight rows angled and focused towards
platform/stage with blocks of seats and gangways located at change of
direction. (h) Setting out
point for seating rows same as centre of performance area: this
coincidence of seating out points tends to be a characteristic of open
stage layouts. (i) Setting
out point for seating rows distinct from geometry of performance area and
extreme side sightlines: this arrangement tends to be a characteristic of
proscenium
formats.
Seating geometry. (a) Straight rows. (b)
Straight rows, with
side blocks of seats angled and focused
towards the platform/stage:
blocks of seating defined by gangways.
Exit widths
The exit widths are laid down by regulations. The
base calculation is 45 persons per minute per unit
width of 520530 mm. The minimum total exit
widths required are outlined
Travel distance
. For traditional seating the travel distance is
18 M measured from the gangway: for continental
seating, 15 M from any seat. The aim is to evacuate
the audience of each level within 2.5 minutes.
Circulation within auditorium
Audience entry points into the auditorium from the
foyer can be at the rear or sides of the seating, or
within the banks of seating, and should be related to
the gangway positions Gangways for use by wheelchair users
require to
be flat or ramped: the pitch should not exceed 1.15
for a ramp with a maximum distance of 10 M. beyond
10 M, the regulations require a flat platform, which
in a large auditorium may be inconvenient as it may
break the line of the seating banks. Permission will
be necessary to have a continuous ramp. For a wheelchair
user moving from a ramped gangway to a flat
platform will require an intermediate ramp.
Gangway widths are established through the regulations
covering fire escape from auditoria. The minimum
width though is taken as 1100 mm unless used
by wheelchair users where the width increases to
1200mm.


Handrails will be required to a stepped gangway
adjacent to an enclosing wall; to a stepped gangway if
a drop at the side; at landings, rear of rostra and where
there is a drop of more than 600 mm; where the rake
is above 25 to a gangway the ends of the rows served
by the gangway may require a loop rail (Figure 12.23).
Rails are usually 900 mm above the pitch line and
1200 mm above landings, with panels either solid or
sub-divisions which may require a 100mm maximum
gap.
EXIT WIDTH REQUIRED= 6.4M
Number of seats in a row
With traditional seating the maximum
number is 22 if there are
gangways at both ends of the row, and 11
for gangway at one end.
Thus in all but the smallest auditorium the
gangways divide the
seating into blocks.
Exit numbers
. The number of exits per level are two
for each level within
an auditorium with the seating capacity
up to 500: an
additional exit is required for every
further 250 seats as
defined by legislation.
REQUIRED= 4 MIN
Exit route
The exits from the auditorium must lead directly to a
place of safety. Staircases within the
route are subject to the following conditions: the
maximum number of steps, 16: the minimum number,
2; tread/riser to be 275 180, as a recommended
ratio, and consistent.
Ramps should be at a pitch of 1.15, in lengths of
10 m maximum with intermediate platforms.

Performers access through the
auditorium
Performers may have access to the stage
through the
auditorium during a performance by way of:
access along the gangways, with stepped
access
onto the stage if raised;
access through vomitories exclusively for
performers.
Details of a performers vomitory are shown
in
Figure 12.24. The performers vomitory can
be filled
to accommodate auditorium seating if not in
use.
Stairs
Staircase flights should have at least two risers and not more
than
16. All treads should be 275 mm and risers 180 mm.
Ramps
Wheelchair users should be provided with flat or ramped
escape
routes which may be separate from other routes. Ramps should
not
be longer than 4.5 m or steeper than 8.5%.
3.13 Circulation
While gangway lengths and widths are calculated as part of the
fire
escape route, they also provide the circulation through the
auditorium, with possible additional gangways from the
audience
entry points to individual rows and seats.
3.14 Entry points
The audience can enter the auditorium from the foyer at the
rear,
at the sides of the seating or from vomitories within the seating
banks,
Gangways
The widths of gangways within seating layouts at
each level within an auditorium are determined by
their role as escape routes and the number of seats
served. The minimum width is 1100 mm. Gangways
can be ramped up to a ratio of 1.10 and 1.12 if used by
persons in wheelchairs.
Broadcasting requirements
Television cameras
Television camera position, with operative. The area required
for each position is 1.5 1 M minimum.
3.17 Latecomers
A waiting area at the rear of the auditorium
either within the
auditorium or in a separate enclosed space
with viewing panel
and tannoyed sound, or elsewhere with a
closed-circuit television
facility.
Sightlines: seated audience
For the whole of the audience to have an uninterrupted
view of the performance and its setting over the
heads in front and clear of overhangs, the section and
plan of the auditorium needs to conform to certain
limitations set by vertical and horizontal sightlines

P = The platform/stage height, when raised, can
range
from 600 to 1100 mm above the lowest level of
the auditorium
HD HORIZONTAL DISTANCE= can vary from
760 to
1150 mm and more.
EH Average eye height at 1120 mm above the theoretical
floor level:
E= For assurance that there is a clear view over the
heads of those in the row in front, this dimension
should be at least 125mm.
D =Distance to front row, as previously described.
Also the maximum rake is 35 and the highest seat in
the auditorium should be on a sightline which is not
more than 30 to the horizontal from point P.
Cabaret layout
Cabaret layout may consist of
loose tables and chairs:
there must be a provision for clear
gangways through
the area covered by this layout.
Allow a minimum of
1.1M2 per person of a seated
audience, excluding general
circulation
Horizontal sightlines
Horizontal sightlines are to be considered only with a
proscenium stage and possibly end stage and platforms
for classical and choral music. the audience should be contained
within a 130 angle peripheral spread of vision
from the performer at the point of command on the
performance area for opera, dance, musicals and
drama
Public address
Loudspeakers may be required within the auditorium
for announcements to the audience as a separate
system.
Platform/stage design
The size and shape of the platform or stage are determined
by the type of production, the relationship
between the audience and the performance and the
scale of the selected production.
Raised stage
The height of the stage can be between 600 mm and 1100 mm with
a straight, angled or curved front edge. The floor to the
performance area, in part or total, may be a series of traps, that is
modular sections usually 1200mm square which can be removed
selectively.
Side and rear stages
Sizes should relate to the size of the performance area. These areas
may need to hold sets as on the performance area, with circulation
all round. The clear height required to be the highest scenery plus
1 m.
Stage basement
The space under the stage should be fully accessible with a
minimum headroom of 4.5 m.
4.12 Spaces associated with the audience area
Lighting control room
A room centrally at the rear of the auditorium fully enclosed and
sound-proofed with an observation window and space for the
lighting control console and for the operator who needs to sit by the
console and view the performance through the observation window
which has an unrestricted view of the stage, 20.60. There should also
be space for an assistant, a worktop for plans and scripts. A
minimum size would be 3 m wide 4.5 m deep and 4.4 m high.
Dimmer rooms
Space is required for the dimmer racks which are the direct means
of control for all of the stage lighting instruments. The racks also
contain the individual fusing for each stage lighting circuit. Mains
cabling runs from the dimmer room to all outlets of the stage
lighting installation, and also to the house lights, but the
connection between the dimmer racks and the lighting control
itself is not a mains voltage line.
The dimmer room should be placed so that quick access may be
achieved either from the lighting control position or from the stage area.
The dimmer room will also normally contain the mains
isolation for the stage lighting system. In large installations which
have a three-phase supply, each single-phase installation should be
physically separated
Sound control room
An open enclosure in a representative position within the
auditorium. The operator requires an interrupted view of the
performance area as well as being able to hear the performance.
The room contains a control desk, equipment racks, monitor
loudspeakers and worktop for scripts. The minimum size is 3 m
wide, 4.4 m deep and 4.4 m high.
Auditorium sound-mixing position
For the mixing of amplified sound from the stage by an operator
who requires to hear the same sound as the audience. The area
requires to be flat, set within the seating area: minimum area of 2 m
2 m, with mixer pad sound control desk and protective barrier.
TV, radio and recording control room
This is a separate soundproof control room, with observation
window and clear view of the stage. It will accommodate
announcers, and staff for balancing and directing transmissions and
recording. A minimum area of 2 m 2 m, but should be larger.
Observation room
Those associated with production may need to check activities on
the stage from a room at the rear of the auditorium, with a clear
view of the stage through an observation window, minimum area,
2 m 2 m
4.14 Spaces for actors, singers and dancers
Dressing rooms
Arrangements are illustrated in 20.61 to 20.69,
covering single
shared and communal occupancy rooms.
Green room with kitchen and servery: 3.4m2 per
occupant.
Laundry for repair and maintenance of costumes,
20m2
minimum.
Costume store, including skips and rails
Costume delivery.
Specialist make-up room: 10 m2 minimum per
person.
Pre-pelformance practice room(s) (singers): 15 m2
minimum.
Pre-performance dance studio (dancers): 1000 m2
minimum.
Physiotherapy room (dancers): 15 m2 minimum.
Wig store and hairdressers room: 510m4.
Waiting area for visitors and dressers.
Offices: childrens supervisor, company manager,
touring manager,
etc. 10m2 minimum per office.
Toilets.
Performers assembly areas: at points of entry to
stage.
CONFERENCE HALLS
The plan shape of the conference hall can be:
Rectangular
Fan-shapde, with angles of 135, 90 or
60. The last is best for
screening
Hexagonal
Circular
Oval, or
Coffin
Parking
Parking provision is essential and covers the following:
Public car parking close to the public entrance, with the number of car park spaces
as 25 per
cent ofthe seating capacity in the auditorium: buildings in city centres, which are
served by
good adjacentpublic transport, can have less provision, while in rural areas the
number of
spaces should beincreased to 40 per cent minimum. It is normally
NO OF SEATS= 2000
PARKING REQUIRED= 500
ECS FOR CAR PARKING
OPEN PARKING= 25SQM
STILT = 30SQM
BASEMENT= 35SQM
Office spaces

Four organisations office space of 50 sq.
m. each
Shops

SMALL SHOPS

These are shops having a sales area less than 280 m2
and not more
than three stores, one of which may be a basement.
Shops
employing fewer than 20 people or 10 above the
ground floor do
not normally require a fire certificate.
Cafeteria

Cafeterias are self-service establishments,
commonly run on a non-commercial basis as a
service to staff and others such as students.
They are characterised by:
Scale of operation: usually fairly large, giving
certain economies of scale
Concentration of demand: a short service
period demands a high rate of service. Above
600 meals a day, free-flow and multi-counter
service is practical.
Menus: balanced to meet nutritional standards.
Degree of choice will determine counter layout
and/or length.
Operation: also used in high-demand
commercial services (airports, stores, service
stations)
Space: counters add 0.20.3m2 to area per
seat in the dining room.`
Separate rooms adjoining the main
kitchen
Low walls, approx 1200 mm high
between these areas and main Kitchen.

toilets

S-ar putea să vă placă și