Environmental maintenance & other related problems 36% ELECTRICAL PROTECTION Overload protection
Earth fault protection
Locked rotor protection
Start/Stall protection
Number of starts limitation
Protection In Stage-III Mill PA FD Inverse time over load relay Y Y Y Instantaneous Over Current Y N Y Definite Time Overload N N N Earth Fault N N N Sensitive Earth Fault Y Y Y Locked rotor protection N N Y Differential relay N Y N
50 R
Y
B TO DDCMIS SPAR E 51I 1 51i 1 51i 2 50L R 50 A 50N 2 T R Y B SURGE ARREST ER VACCUM CIRCUIT BREAKER
When a motor is started, it draws a current well in excess of full load rating throughout the period that the motor takes to run-up to speed. While the motor starting current reduces somewhat as motor speed increases.
When ever a motor stall whilst running, or fail to start, due to excessive loading, the motor will draw a current equal to its locked rotor current. It is not therefore possible to distinguish between a stall condition and a healthy start solely on the basis of the current drawn. Discrimination between the two conditions must be made based on the duration of the current drawn. LOCKED ROTOR PROTECTION STALL PROTECTION
Start time => safe stall time: since the time delay required is longer than the maximum time that the motor can be allowed to carry starting current safely. An additional means of detection of rotor movement, indicating a safe start, is required. A speed-sensing switch usually provides this function. SENSITIVE/ INSTANTANEOUS EARTH FAULT RELAY
Here we calculate fault between one phase and ground
Fault Impedance =11.2ohm
Fault current = 3E/(X1+X2+X0+3Xf)= 3(6.6K)/(8.6+8.6+3(11.2)) = 390A
If = 300 app
Since earth fault current must be less than 300A
CT secondary = 300/150 = 2A
INSTANTANEOUS E/F RELAY SENSITIVE E/F RELAY INVERSE TIME OVER CURRENT RELAY Alarm at 105%
And tripping at 110%
Rated current = 126.5A
Trip at = 126.5*110% =139.15A
CT primary = 139.15A
CT secondary = 139.15/150 =0.92A
Current setting = 92% INSTANTANEOUS O/C RELAY
Short circuit current = 40KA app. CT secondary = 40KA/150 = 267A Normal current = 126.5A
Current setting =126.5*700% = 885A
CT secondary = 885/150 = 5.9A
Current setting = 600% but it is set for 800%
NUMBER OF STARTS LIMITATION Any motor has a restriction on the number of starts that are allowed in a defined period.
Starting should be blocked if the permitted number of starts is exceeded.
The situation is complicated by the fact the number of permitted hot starts in a given period is less than the number of cold starts, due to the differing initial temperatures of the motor.
To allow the motor to cool down between starts, a time delay may be specified between consecutive starts DIFFERENTIAL PROTECTION