Substation Automation Products Training

Control IED
REC 670
Measurements

ABB Power Technologies AB, 2005

Contents

2006-03-30
2

Substation Automation Products Training

Hardware

Measuring Function Blocks

Application Configuration

Signal Matrix

Monitoring and supervision

Signal Monitoring

Local HMI

Exercise

ABB Power Technologies AB, 2005

Hardware - IED670 IEDs

2006-03-30
3

Substation Automation Products Training

Hardware Structure - IED670 IEDs

2006-03-30
4

Substation Automation Products Training

PSM

AD1
NUM
GSM
BIM
BIM
BOM
IOM
MIM

ABB Power Technologies AB, 2005

TRM1

19 rack, 6U high

Transformer Input Module


6I + 6U, 9I+3U, 6I or 12I TRM1
(TRM2)

Analog Digital Conversion


module ADM1 (ADM2)

Central Processing Unit NUM

GPS time synchronization


module GSM (option)

Binary Input / Output modules


BIM, BOM, IOM and MIM

Power supply module PSM

Transformer input module (TRM)

Isolation barrier preventing


disturbances to enter into
IED670

Adapt measured values to


static circuitry

Up to 12 analog inputs can be


connected

ABB Power Technologies AB, 2005

2006-03-30
5

Substation Automation Products Training

0 - 6 U, 110-220V rated
range 50/60 Hz

6 -12 I, 1A or 5A rated current

Max 2 TRM in each IED

Analog / Digital conversion Module (ADM)

Analog inputs (from TRM)

ABB Power Technologies AB, 2005

Mounting position for OEM


module (only on AD1)

2006-03-30
6

Substation Automation Products Training

ABB Power Technologies AB, 2005

mA input module (MIM)

2006-03-30
7

Substation Automation Products Training

6 independent input channels

Software selected input ranges

0-5, 0-10, 0-20, mA

1-5, 2-10, 4-20, mA

5, 10, 20 mA

Resolution: 16 bit

Accuracy: 0,1%

Independent settable digital


filters

Measuring Function blocks

ABB Power Technologies AB, 2005

2006-03-30
8

Power system measurement (in primary values)

Apparent, active and reactive power

Voltage and current

Frequency

Power factor

Phase currents

Phase-phase voltages

Sequence quantities (in primary values)

Positive, negative and zero sequence voltages

Positive, negative and zero sequence currents

DC measurement
Substation Automation Products Training

Measuring Function blocks General

Measured information via

ABB Power Technologies AB, 2005

Service values

Single one-line diagram

Monitoring tool within PCM600 (local or remote)

IEC 61850-8-1 (direct or via MVGGIO)

IEC 60870-103 (via special 103 function blocks)

LON (via Event function blocks (EVxx))

Disturbance function block (DRA4)

Zero point clamping

Input: Group signals (voltage or current)

Measurement supervision

2006-03-30
9

Local HMI

Three Reporting modes

Level supervision output (4 levels)

Substation Automation Products Training

Measuring Function blocks Service Values (SVRx)

Logical Node: CVMMXU

Max 3 instances

9 measuring modes

ABB Power Technologies AB, 2005

2006-03-30
10

Substation Automation Products Training

use one, two or three voltages,

use pos. seq. voltage

etc

Calibration of analog inputs

Amplitude and angle compensation

Three points (5, 30 and 100 %)

Class 0.5 accuracy

Low pass filtering

Compensation facility

Level supervision (xRANG)

ABB Power Technologies AB, 2005

Measuring Function blocks Service Values (SVRx)

2006-03-30
11

Substation Automation Products Training

ABB Power Technologies AB, 2005

Measuring Function blocks Voltage and Current (VPx, CPx)

2006-03-30
14

Substation Automation Products Training

Logical Node: VMMXU

Max 3 instances

Output: Phase to phase voltages

Calibration of analog inputs

Amplitude and angle compensation

Three points (5, 30 and 100 %)

Class 0.5 accuracy

Level supervision (ULxRANG)

Logical Node: CMMXU

Max 10 instances

Output: Phase currents

Calibration of analog inputs

Level supervision (ILxRANG)

ABB Power Technologies AB, 2005

Measuring Function blocks Sequence (VSQx and CSQx)

2006-03-30
15

Substation Automation Products Training

Logical Node: VMSQI

Max 3 instances

Output: Positive, negative and zero


sequence voltages

Level supervision (UxRANG)

Logical Node: CMSQI

Max 3 instances

Output: Positive, negative and zero


sequence currents

Level supervision (IxRANG)

Measuring Function blocks DC measurement (MVxx)

Logical Node: MVGGIO

Max 16 instances

Input:

ABB Power Technologies AB, 2005

2006-03-30
16

Substation Automation Products Training

SMMI function block (mA currents)

etc

Level supervision (RANGE)

Application configuration (CAP531) Pre-processor blocks

SMAI Function Block


(Virtual Analog Input Block)
for VOLTAGE measurements

#1

ABB Power Technologies AB, 2005

2006-03-30
17

Substation Automation Products Training

Application configuration (CAP531) Pre-processor blocks

ABB Power Technologies AB, 2005

SMAI Function Block


(Virtual Analog Input Block)
for CURRENT measurements

#2
I
2006-03-30
18

Substation Automation Products Training

Group signals

Sum3Ph Function Block


for SUMMATION

Application configuration (CAP531) Pre-processor blocks

ABB Power Technologies AB, 2005

SMMI Function Block


(Virtual Analog Input Block)
for mA measurements

2006-03-30
19

Substation Automation Products Training

Configuration of Analog Inputs in CAP531

ABB Power Technologies AB, 2005

Function blocks using


analog signals is configured in
CAP531
- Group signals
- Sampled signals

2006-03-30
20

Substation Automation Products Training

ABB Power Technologies AB, 2005

PCM600, Signal Matrix Tool and Application configuration

Inputs/Outputs in CAP531 are hardware independent


2006-03-30
21

Substation Automation Products Training

PCM600 and Signal Matrix Tool (SMT)

ABB Power Technologies AB, 2005

SMT is the tool to define relationship


between VIRTUAL INPUT/OUTPUT signals
(Analog and or Digital) and REAL
INPUT/OUTPUT signals (Analog or Digital).

2006-03-30
22

Substation Automation Products Training

SMT: Virtual and Real Analog Inputs

Hardware:
TRM

ABB Power Technologies AB, 2005

CAP531 view:
Virtual analog input

2006-03-30
23

Substation Automation Products Training

SMT: Virtual and Real mAmpere Inputs

Hardware:
MIM

ABB Power Technologies AB, 2005

CAP531 view :
Virtual mA input

2006-03-30
24

Substation Automation Products Training

Monitoring
Measurement supervision applies to different measuring
function blocks

Service values

S, P, Q, U, I, ILx and ULxy-ULyz

Sequence Components

xMSQI

Positive, Negative and Zero sequence quantities

Generic measured values

xMMXU

MVGGIO

For instance mA-input signals

Reporting modes:

ABB Power Technologies AB, 2005

2006-03-30
25

Cyclic reporting
Amplitude dead-band supervision
Integrated dead-band supervision

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Cyclic reporting

2006-03-30
26

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Amplitude dead-band supervision

2006-03-30
27

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Integrating dead-band supervision

2006-03-30
28

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Reporting, Settings

2006-03-30
29

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Supervision levels

2006-03-30
30

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Supervision levels AC-signals, Settings

2006-03-30
31

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Supervision levels mA-signals, Settings

2006-03-30
32

Substation Automation Products Training

ABB Power Technologies AB, 2005

Monitoring Expander block (XPxx)

2006-03-30
33

Substation Automation Products Training

Logical Node: --

Max 66 instances

Input: xRANGE, Integer

Output: Binary signal

ABB Power Technologies AB, 2005

PCM600 and Signal Monitoring

2006-03-30
34

Substation Automation Products Training

Signal Monitoring

Service Values

xMMXU

Sequence components

xMSQI

(Binary I/O

BIM, BOM and IOM)

Online monitoring Automatic or Manual refresh

ABB Power Technologies AB, 2005

Presentation in primary values of


measured/calculated quantities delivered by
Measuring Function blocks

2006-03-30
35

Substation Automation Products Training

Signal Monitoring
Phase values
IL1 3, UL12 31
Service Values
S, P, Q, I, U, Pf and f

ABB Power Technologies AB, 2005

Sequential values
I1, I2, 3I0, U1, U2 and 3U0

2006-03-30
36

Substation Automation Products Training

Local HMI
Co n t r o l

Measured values may be presented:

on the Single Line Diagram


(Control Screen) on medium
sized LCD
in the HMI-tree sub menu

Measurement
Monitoring
Service Values

ABB Power Technologies AB, 2005

Current Phasors

Voltage Phasors
Current Sequence Components
Voltage Sequence Components
2006-03-30
37

Substation Automation Products Training

Sc r een
BB 1 4 2 1 k V
BB 2
0 kV
QB 1

QB 2

QC1
QA 1

QC2
0A
0 kV
QB 9
QC9
So u t h Po i n t

4 0 0 k V OHL

Do you want to
close QC1?

Las t D i s t u r bance
Re c # 0 6 0
2004 - 12 - 16
F a u l t l o c a t i o n : 2 4 0 . 5 km
of
0 1 1 TOC1 - TR I P
0 1 2 TR I P - TR I P
of
0 2 5 ZM1 - S T L 1
of
2004 - 12 - 17 08 : 37
No r

12 : 43 : 57 . 349
f
f
f
t

- >on
- >on
- >on
h Co n n e c t i o n

Measurements engineering

Exercise

time

ABB Power Technologies AB, 2005