Documente Academic
Documente Profesional
Documente Cultură
Autotransformer
An
autotransformer
(sometimes
called
autostep down transformer)[1] is an electrical
transformer with only one winding. The "auto"
(Greek for "self") prefix refers to the single coil
acting on itself and not to any kind of
automatic mechanism.
Autotransformers have the advantages of often
being smaller, lighter, and cheaper than typical
dual-winding transformers, but the disadvantage
of not providing electrical isolation.
Other advantages of autotransformers include
lower leakage reactance, lower losses, lower
excitation current, and increased KVA rating.[2]
Autotransformer
Autotransformer
Sin V1 I1
Sout V2 I 2
Problem
The primary and secondary voltages
of an autotransformer are 500 V and
400 V respectively. Show with the
aid of a diagram, the current
distribution in the winding when the
secondary current is 100 A. Calculate
the output power for unity power
factor.
V1 N1
a
V2 N 2
I1 1
I2 a
Auto-Transformer
Turns link the
same flux
V1 N1
a
V2 N 2
I1 1
I2 a
Variable-voltage autotransformers
Three-Phase Transformers
Three Phase
1. Constructing Transformers
a three-phase transformer on a common
magnetic structure
Three Phase
Transformers
V P
VLP
3
VLS 3V S
The overall voltage ratio is
3V P
VLP
a
VLS
3V S
Wye-wye connection
When transformers are connected in wye-wye, special
precautions have to be taken to prevent severe distortion of
the line-to-neutral voltages.
(1) connect the neutral of the primary to the neutral of
the source, usually by way of the ground
Fig.6 Wye-wye connection with neutral of the primary connected to the neutral of the source.
Wye-wye connection ()
(2) provide each transformer with a third winding,
called tertiary winding.
Wye-wye connection
V P
VLP
3
VLS V S
The overall voltage ratio is
3V P
VLP
3a
VLS
V S
V P VLP
The secondary phase voltage is
VLS 3V S
The overall voltage ratio is
V P
VLP
a
VLS
3V S
3
advantages and the same
phase shift as the Y-
connection.
V P VLP
The secondary phase voltage is
VLS V S
The overall voltage ratio is
VLP V P
a
VLS V S
Open-delta connection
It is possible to transform the voltage of a 3-phase
system by using only 2 transformers, connected in opendelta.
The open-delta arrangement is identical to a delta-delta
connection, except that one transformer is absent.
The open-delta connection is seldom used because the
load capacity of the transformer bank is only 86.6 percent
of the installed transformer capacity.
Open-delta connection ()
The open-delta connection is mainly used in emergency
situations. Thus, if three transformers are connected in
delta-delta and one of them becomes defective and has to
be removed, it is possible to feed the load on a temporary
basis with the two remaining transformers.
Three-Phase Transformers
One-line Diagram
One-line diagrams are simplified
schematics used to show the main
power distribution systems for
commercial or industrial settings.
Three-Phase Transformers
Delta-delta connection
Example 1
Delta-delta connection
Delta-delta connection
Delta-delta connection
Delta-wye connection
Delta-wye connection
Example 2
Delta-wye connection
Fig.5
Delta-wye connection