Simple overcurrent and earth fault relay will not provide adequate protection for winding earth faults. Degree of earth fault protection is very much improved by the application of unit differential or Restricted Earth Fault systems. Both windings of the transformer can thus be protected separately with restricted earth fault.
Simple overcurrent and earth fault relay will not provide adequate protection for winding earth faults. Degree of earth fault protection is very much improved by the application of unit differential or Restricted Earth Fault systems. Both windings of the transformer can thus be protected separately with restricted earth fault.
Simple overcurrent and earth fault relay will not provide adequate protection for winding earth faults. Degree of earth fault protection is very much improved by the application of unit differential or Restricted Earth Fault systems. Both windings of the transformer can thus be protected separately with restricted earth fault.
in Transformers A simple overcurrent and earth fault relay will not provide adequate protection for winding earth faults. Need some earth fault protection. Degree of earth fault protection is very much improved by the application of unit differential or restricted earth fault systems.
Restricted Earth Fault
Protection
Restricted Earth Fault - How it
Works On the HV side, the residual current of the 3 line CTs is balanced against the output current of the CT in the neutral conductor. For the LV side, earth faults occurring on the delta winding may also result in a level of fault current of less than full load. HV overcurrent relays will not provide adequate protection. A relay connected to monitor residual current will provide restricted earth fault protection since the delta winding cannot
Restricted Earth Fault - How it
Works .. 2 Both windings of the transformer can thus be protected separately with restricted earth fault. Provide high speed protection against earth faults over the whole of the transformer windings. Relay used is an instantaneous high impedance type.
High Impedance Differential
Scheme
High Impedance Scheme - How it
Works The CTs generate currents that create a high voltage across the relay (which has a high burden).
CTs must generate 2 times the trip voltage to
work on an internal fault If one only CT saturates for through fault, not enough voltage is generated to trip relay.
High Impedance Scheme Requirements
CTs must have identical turns ratios, knee-point voltages 2 times relay operating voltage, high accuracy, low reactance (PX class) High internal faults can generate high voltage across relay - some form of voltage dependent resistor (metrosil) is required to avoid this.