Documente Academic
Documente Profesional
Documente Cultură
AIRSOURCEHEATPUMPS
UNIT43
AIRSOURCEHEATPUMPS
UNITOBJECTIVES
Afterstudyingthisunit,thereadershouldbeableto
Describetheoperationofreversecyclerefrigeration(heatpumps)
Explainthefunctionandoperationofheatpumpsystemcomponents
Listheatsourcescommonlyusedinheatpumpsystems
Discusshowheatpumpefficiencyisdetermined
Explaintheconceptsofcoefficientofperformanceandauxiliaryheat
Describethecontrolsequenceofanairtoairheatpumpsystem
Explainhowheatpumpefficiencycanbeincreased
Discusspreventivemaintenanceonaheatpumpsystem
REVERSECYCLEREFRIGERATION
Airconditioningequipmentcanonlypump
heatinonedirection
Heatpumpscanpumpheattwoways
Heatpumpshaveafourwayreversingvalve
Fourwayreversingvalvescontrolthedirection
offlowoftheheatladenvaporbetweenthe
lowandhighpressuresidesofthesystem
Functionsastheevaporator
intheheatingmode
Functionsasthecondenserin
theheatingmode
Functionsasthecondenserin
thecoolingmode
Functionsastheevaporator
inthecoolingmode
HEATSOURCESFORWINTER
Airconditionerspumpheatfromlowtemperatureinside
thestructuretoahighertemperatureoutsidethehouse
Thereisheatinasubstanceuntilitiscooledto460F
At0Foutsideairtemperature,thereisstill85%usable
heatintheair
Heatpumpshavetheabilitytoabsorbheatfromthe
structureinthesummertimeanddischargeittotheoutside
Heatpumpsareabletoabsorbheatfromtheoutsideair
anddischargeittotheinsideofthestructure
THEFOURWAYVALVE
Allowstheheatpumptopumpheatintwodirections
Divertsthedischargegastoeitherheatorcoolthe
conditionedspace
Refrigerantisdirectedfromthecompressortotheindoor
coilintheheatingmode
Refrigerantisdirectedfromthecompressortothe
outdoorunitinthecoolingmode
Controlledbythespacetemperaturethermostat
Pilotoperatedvalve
Fourpipingconnectionsonthevalve
Directacting
reversingvalveis
controlleddirectly
byasolenoidcoil
Hotgasfromcompressor
Moveableslide
insidevalve
Connectedto
outdoorcoil
Connectedto
indoorcoil
Suctiongasto
compressor
Pilotoperated
reversingvalveis
controlledbythe
systempressures
Hotgasfromcompressor
COOLING
Systemhigh
pressurepushes
theslidetothe
right
Connectedto
outdoorcoil
Connectedto
indoorcoil
Suctiongas
tocompressor
Pilotoperated
reversingvalveis
controlledbythe
systempressures
Connectedto
outdoorcoil
Hotgasfromcompressor
HEATING
Connectedto
indoorcoil
Suctiongas
tocompressor
TYPESOFHEATPUMPS
Airisnottheonlysourcefromwhichaheat
pumpbanabsorbheat,butitisthemostpopular
Otherheatsourcesforheatpumpsincludewater
andEarth
Atypicalwatertoairheatpumpuses3gallons
ofwaterperminuteintheheatingcycleand1.5
gallonsofwaterperminuteinthecoolingmode
pertonofrefrigeration
SOLARASSISTEDHEATPUMPS
Thesepumpscaptureheatfromthesun
Theheatisthenbroughttousablelevelsfor
heatinghomes
Somesystemsarespeciallydesignedto
operateinconjunctionwithsolarheat
THEAIRTOAIRHEATPUMP
Mostpopulartype
Basicsealedsystemcomponentsofaheat
pumparethesameasanairconditioner,but
theterminologychanges
Inaheatpump,thetermsindoorcoiland
outdoorcoilareused
Thefunctionofeachcoilchangesasthe
operatingmodeoftheheatpumpchanges
THEAIRTOAIRHEATPUMP
Functionofcoilsinthecoolingmode
Indoorcoilabsorbsheatbyboilingrefrigerantatlow
temperatureandpressure(evaporator)
Outdoorcoilrejectsheatbycondensingahigh
temperatureandpressurevaportoahigh
temperatureandpressurevapor(condenser)
Refrigerantfromthecompressorisfirstpumpedto
theoutdoorcoil
Hotgasfromcompressor
Connectedto
outdoorcoil
Connectedto
indoorcoil
Suctiongasto
compressor
THEAIRTOAIRHEATPUMP
Functionofcoilsintheheatingmode
Outdoorcoilabsorbsheatbyboilingrefrigerantat
lowtemperatureandpressure(evaporator)
Indoorcoilrejectsheatbycondensingahigh
temperatureandpressurevaportoahightemperature
andpressurevapor(condenser)
Hotgasfromthecompressorisfirstpumpedtothe
indoorcoil
Hotgasfromcompressor
Connectedto
outdoorcoil
Connectedto
indoorcoil
Suctiongasto
compressor
THEAIRTOAIRHEATPUMP
Modeofoperationisdeterminedbywhich
waythehotgasfromthecompressoris
flowing
Modeofoperationcanbedeterminedby
touchingthegaslinetotheindoorcoil
Inthecoolingmode,thegaslinewillfeelcool
Intheheatingmode,thegaslinewillfeelhot
REFRIGERANTLINEIDENTIFICATION
Thelargediameterlineiscalledthegaslinebecause
onlyrefrigerantvaporflowsthroughit
Thegaslineisacoldgaslineinthesummerandahot
gaslineinthewinter
Thesmallerdiameterlineiscalledtheliquidline
becauseonlyliquidrefrigeranttravelsthroughit
Duringthecoolingmode,theliquidtravelstothe
indoorcoil
Duringtheheatingmode,theliquidtravelstothe
outdoorcoil
HEATPUMPOPERATINGINTHEHEATINGMODE
IndoorUnit
OutdoorUnit
Hotgasfrom
compressor
Highpressureliquid
tometeringdevice
andevaporator
HEATPUMPOPERATINGINTHECOOLINGMODE
IndoorUnit
OutdoorUnit
Coolsuctiongasto
compressor
Highpressureliquid
tometeringdevice
andevaporator
METERINGDEVICES
Speciallydesignedforheatpumpapplications
Theremustbeameteringdeviceattheoutdoor
unitintheheatingmode
Theremustbeameteringdeviceattheindoor
coilinthecoolingmode
THERMOSTATICEXPANSION
VALVES(TEV,TXV)
MaintainsDesiredsuperheatintheevaporator
CheckvalvesarepipedparalleltotheTXVtoallow
refrigeranttobypassthecontrolwhenneeded
Heatingmode
TherefrigerantflowsthroughtheTXVattheoutdoorcoil
TherefrigerantbypassestheTXVattheindoorcoil
Coolingmode
TherefrigerantflowsthroughtheTXVattheindoorcoil
TherefrigerantbypassestheTXVattheoutdoorcoil
THECAPILLARYTUBE
Commonlyusedonheatpumps
Willallowrefrigeranttoflowinbothdirections
Sometimestwocapillarytubesareusedwith
checkvalves
Theremustbeadrier/strainerattheinletofthe
capillarytubetoensurethatthetubedoesnot
getclogged
BalltypeCheckValve
COMBINATIONSOFMETERING
DEVICES
Usesthecapillarytubeattheindoorcoil
Usedinthecoolingmode
Loadisrelativelyconstantinthewarmermonths
Usesathermostaticexpansionvalveatthe
outdoorcoil
Usedintheheatingmode
Allowssystemtoreachmaximumefficiencyquickly
ELECTRONICEXPANSION
DEVICES
Canmeterrefrigerantinbothdirections
Ifindoorandoutdoorcoilsareclosetogether,
onedevicecanbeused
Thecorrectsuperheatwillbemaintainedinboth
heatingandcoolingmodes
ORIFICEMETERINGDEVICES
Usedinconjunctionwithcheckvalves
Onedeviceislocatedateachcoil
Theboreattheindoorcoilislargerthanthe
boreattheoutdoorcoil
Normallyusedwithabiflowfilterdrier
LIQUIDLINEACCESSORIES
Twostandardfilterdrierscanbeusedon
systemswithcheckvalves
Onlyonedrierwillbeintherefrigerationcircuit
atatime
Theyareinstalledwiththearrowspointinginthe
samedirectionasthecheckvalves
Biflowfilterdriers
Twodriersinone
Designedforheatpumpapplications
COOLINGMODE
Refrigeranttoindoorcoil
Checkvalve
closed
Refrigerantfromoutdoorcoil
HEATINGMODE
Checkvalve
closed
Refrigerantfromindoorcoil
Refrigeranttooutdoorcoil
APPLICATIONOFTHEAIRTOAIRHEATPUMP
Usuallyinstalledinmilderclimates(temperaturesaslow
as10)
Inthewinter,theoutdoorcoilabsorbsheat
Differencebetweenoutdoorandevaporatortemperature
isabout25
Ifoutsidetemperatureis10,therefrigerantboilsat
approximately15
Thecompressorandthesystemloseefficiencyasthe
evaporatortemperaturegoesdown
Thesystemlosescapacityastheoutsidetemperature
drops
AUXILIARYHEAT
Requiredwhentheheatpumpcannotprovide
alltheheatastructureneeds
Theheatpumpistheprimaryheatsource
Auxiliaryheatcouldbeelectric,oilorgas
Electricheatisthemostcommonauxiliaryheat
used
Astheoutsidetemperaturedrops,thestructure
requiresmoreheat
BALANCEPOINT
Balancepointoccurswhentheheatpumpcan
pumpinexactlyasmuchheatasthestructureis
leakingout
Abovethebalancepoint,theheatpumpwillcycle
onandoff
Belowthebalancepoint,theheatpumpwillrun
continuouslyandsecondstage(auxiliary)heat
willbeenergized
COEFFICIENTOFPERFORMANCE
Onewattofusableheatissuppliedforeach
wattofenergypurchased
Usingelectricresistanceheat
Thisiscalled100%efficient
Coefficientofperformance(COP)of1:1
Theoutputisthesameastheinput
AirtoairheatpumpscanhaveaCOPof3.5:1
When1wattofelectricalenergyisusedbythe
compressor,itcanfurnish3.5wattsofusableheat
(COPis3.5:1)
COEFFICIENTOFPERFORMANCE
HighCOPonlyoccursduringhigheroutdoorwinter
temperatures
AheatpumpsCOPfallsastheoutdoortemperaturefalls
AtypicalairtoairheatpumphasaCOPof1.5:1at0F
Somemanufacturershavecontrolstoshutoffthe
compressorattemperaturesof0to10F
Watertoairheatpumpsmightnotneedauxiliaryheat
sincetheheatsource(water)temperatureisconstant
WatertoairheatpumpshaveaCOPratingashighas4:1
SPLITSYSTEMAIRTOAIR
HEATPUMPS
Airtoairsystemscanbesplitorpackagetype
Bothheatpumpsandstraightcoolingunitslook
identical
Splitsystemsrequiretheinstallationofthegas
andliquidrefrigerantlinestoconnecttheindoor
andoutdoorunits
Fieldinstalled
refrigerantlines
Functionsastheevaporator
intheheatingmode
Functionsasthecondenserin
theheatingmode
THEINDOORUNIT
Thepartofthesystemthatcirculatestheair
withinthestructure
Itcontainsthefanandcoilandoftentheelectric
stripheaters
Therefrigerantcoilmustbelocatedinthe
airstreambeforetheauxiliaryheatingcoil
Theindoorunitmaybeagasoroilfiredfurnace
THEINDOORUNIT
Ifgasoroilfurnaceistheindoorunit,thecoil
mustbelocatedintheoutletairstreamofthe
furnace
Ifagasoroilfurnaceisused,theheatpump
willnotoperatewhentheyareoperating
Heatpumpsaddedtoelectricfurnacesshould
havethecoillocatedaftertheheatstrips
AIRTEMPERATUREOFTHE
CONDITIONEDAIR
Airtemperaturesofaheatpumparenotashot
aswithfossilfuelequipment
Maximumheatpumpairsupplytemperatures
arearound100F
Mostheatpumpsrequireaminimumof400
cfmpertonofrefrigeration
Supplyairtemperaturewillfallwhenoutside
airtemperaturesdrop
Returnairfromthe
occupiedspace(75F)
Heatedair
(100F)
Supplyduct
Airhandler(condenserinwinter)
THEOUTDOORUNITINSTALLATION
Muchlikearegularairconditioninginstallation
Musthavegoodaircirculationaroundit
Prevailingwindsaffectperformance
Inthewintertime,theoutdoorcoilwillcollectmoisture
andthemoisturewillfreezeonthecoil
Outdoorcoilshouldbeinstalledsoitisraisedabovethe
groundpadtoallowdefrostwatertoruntotheground
Adefrostsystemisprovidedtodefrosttheicefromthe
outdoorcoil
PACKAGEAIRTOAIRHEATPUMPS
Hasallthesealedsystemandelectrical
componentsinonehousing
Worksmuchthesamewayasapackagedair
conditioningunit
Onlyonepowersupplyrequired
Supplyandreturnductworkmustbefield
installed
Supplyandreturnducts
arefieldinstalled
Packageheatpumpsystem
CONTROLSFORAIRTOAIRHEATPUMPS
Controlsaredifferentthanotherheating/cooling
equipment
Inaheatpump,therearetwoheatingsystemsandone
coolingsystem
Auxiliaryheatingsystemmustbeoperatedasasystem
byitselfincasetheheatpumpfails
Auxiliaryheatisreferredtoasemergencyheatwhen
usedbecauseofheatpumpfailure
Thespacethermostatisthekeytocontrollingthe
system
Normally,atwostageheatingandtwostagecooling
thermostatisused
CONTROLSFORAIRTOAIRHEATPUMPS
Automaticchangeoverthermostatchangesautomatically
betweenheatingandcoolingmodes
Coolingcyclecontrols
Thermostatcontactscontroltheoperationofthecompressor,
outdoorfanmotor,andreversingvalvecoil
Whenthethermostatissatisfied,thecompressor,outdoorfan
motor,andindoorfanmotoraredeenergized
Thereversingvalvesolenoidcoilremainsenergized
FIRSTSTAGECOOLING(SIMPLIFIED)
Outdoorunit
H(Y)
Heat
Cool
1ST
1(W)
1ST
2ND
2ND
C(Y)
4wayreversingvalve
coilenergized
SECONDSTAGECOOLING(SIMPLIFIED)
Outdoorunit
H(Y)
Heat
Cool
1ST
1(W)
1ST
2ND
2ND
C(Y)
4wayreversingvalve
coilenergized
Compressorcontactor
coilenergized
CONTROLSFORAIRTOAIR
HEATPUMPS
Spaceheatingcontrol
Thermostatcontrolscompressor,outdoorfan
motor,andindoorfanmotoroperation
Excessivelycoldtemperaturesenergizesecond
stageheat
Secondstageheatcyclesonandofftoassist
theheatpump
FIRSTSTAGEHEATING(SIMPLIFIED)
Outdoorunit
H(Y)
Heat
1(W)
Cool
1ST
1ST
2ND
2ND
C(Y)
Compressorcontactor
coilenergized
SECONDSTAGEHEATING(SIMPLIFIED)
Outdoorunit
H(Y)
Heat
1(W)
Cool
1ST
1ST
2ND
2ND
C(Y)
Compressorcontactor
coilenergized
SECONDSTAGEHEATINGWITHOUTDOORTHERMOSTATS
(SIMPLIFIED)
Outdoorunit
H(Y)
Heat
1(W)
Cool
1ST
1ST
2ND
2ND
C(Y)
Compressorcontactor
coilenergized
Outdoorthermostatsforelectricheaters
CONTROLSFORAIRTOAIR
HEATPUMPS
Balancepoint
Pointatwhichtheheatpumpcansatisfytheloadwithout
shuttingdown
Maybemultiplebalancepoints
Electricheatersareenergizedatdifferenttemperatures
Onlytheminimumnumberofheatersisenergizedatatime
Conservesenergy
Auxiliaryheatoperationindicatedbysignallighton
thermostat
CONTROLSFORAIRTOAIRHEATPUMPS
Emergencyheatmode
Usedintheeventofheatpumpfailure
Allheatingelementsareenergized
Signallightonthermostat
Heatanticipators
Foundonheatpumpthermostatsandconventional
thermostats
Mostheatpumpthermostatsareequippedwithtwo
EMERGENCYHEATING(SIMPLIFIED)
H(Y)
1(W)
Heat
Cool
1ST
1ST
2ND
2ND
C(Y)
Emergencyheatrelay
contacts
THEDEFROSTCYCLE
Defrostsicefromoutsidecoilduringwinteroperation
Outdoorcoiloperatesbelowfreezinganytimetheoutsideair
isbelow45F
Outdoorcoiloperates20to25Fbelowtheoutsideair
temperature
Theneedfordefrostvariesdependingonoutsideair
temperaturesandconditions
Themoremoistureintheair,themorefrostthatformson
theoutdoorcoil
Defrostaffectstheefficiencyofthesystems
HEATINGSEASONAL
PERFORMANCEFACTOR(HSPF)
Seasonalperformanceforparticularpieceofequipment
Breaksthecountryintosixzones
Usedtocalculateoperationcosts
Considersaveragenumberandlengthofdefrostcycles
peryear
Considerswhetherauxiliaryheatersareenergizedduring
defrost
SEERandHSPFareresultsoffederalenergypolicies
HEATPUMPDEFROST
Airtoairheatpumpsaccomplishdefrostbystopping
theoutdoorfanandcyclingunitintocoolingmode
Duringdefrost,onestageofstripheatisturnedon
Thesystemiscoolingandheatingatthesametime
duringdefrost
Demanddefrostmeansdefrostingonlywhenneeded
Combinationsoftime,temperature,andpressuredrop
acrosstheoutdoorcoilarealsousedinsomesystems
todeterminewhendefrostisneeded
INITIATINGTHEDEFROSTCYCLE
Manufacturersdesignthesystemstostartdefrostwhen
frostaffectsperformance
Someusetimeandtemperatureinitiateddefrostsystems
Bothconditionsmustbemetbeforedefrostwillbe
activated
Coiltemperaturesensingdeviceswillclosearound
outdoorcoiltemperatureof25
Typically,thetimerwillrunanytimethecompressor
runs
L1
TIMEANDTEMPERATUREINITIATEDDEFROST
Defrostrelay
Timermotor
4wayreversing
valvecoil
Outdoorfan
Outdoorcoilthermostat
L2
INITIATINGTHEDEFROSTCYCLE
Somesystemswillalsoincludeapressure
switchalongwiththetemperatureandtimer
function
Wheniceformsonthecoil,thepressureswitch
closes
Time,temperature,andpressuredefrostsystems
ensurethatthereisicebuildupontheoutdoor
coil
TIME,TEMPERATUREANDPRESSUREINITIATEDDEFROST
L2
L1
Defrostrelay
4wayreversing
valvecoil
Timermotor
Pressure
Outdoorfan
Outdoorcoilstat
TERMINATINGTHEDEFROSTCYLE
Stoppingthedefrostisasimportantasstartingthe
defrost
Time,temperature,andpressurecanallbeusedto
terminatethedefrostcycle
Temperaturesensorsusedforthedefrosting
functionwillopenat50F
10minutesisthenormalmaximumtimeallowed
fordefrostcycle
L1
TIMEORTEMPERATURETERMINATEDDEFROST
Defrostrelay
Timermotor
4wayreversing
valvecoil
Outdoorfan
Outdoorcoilthermostat
L2
ELECTRONICCONTROLOF
DEFROST
Electronictimersandthermistorsusedto
controldefrost
Moreaccuratecontrolthannonelectronic
methods
Canincorporatetimeandtemperature
featuresintoasingleunit
INDOORFANMOTORCONTROL
Inaheatpump,thefanmustbestartedatthe
beginningofeachmodeofoperation
Theindoorfanisstartedwiththethermostat
FanswitchterminalfunctionisnormallytheG
terminalonthethermostat
Theindoorfanmotoroftenoperatesduringdefrost
Circulatesairtopreventcoilfreezing
Airistemperedtopreventcoldairfrombeing
introducedtotheoccupiedspace
AUXILIARYHEAT
Usuallyaccomplishedwithelectricheat
Requiredtoassisttheheatpumpwhenit
cannotprovidealltheheatthestructureneeds
Alsousedasemergencyheatwhentheheat
pumpneedsservice
Heatersalsoenergizedduringdefrost
SERVICINGTHEAIRTOAIRHEATPUMP
Muchlikeservicingarefrigerationsystem
Duringthecoolingmode,systemisoperatingasahigh
temperaturerefrigerationsystem
Duringtheheatingmode,systemisoperatingasalow
temperaturerefrigerationsystem
Servicingofthesystemisdividedintoelectricaland
mechanical
Theheatpumpmayrunfordaysandnotstopwhen
outdoortemperaturesarebelowthebalancepoint
TROUBLESHOOTING
MECHANICALPROBLEMS
Canbehardtoidentifyinaheatpump,
particularlyinwinteroperation
Summeroperationofaheatpumpissimilar
toanairconditioningunit
Mechanicalproblemsaresolvedwithgage
manifolds,wetbulbanddrybulb
thermometers,andairmeasuringinstruments
TROUBLESHOOTINGTHE
FOURWAYVALVE
Commonproblems:stuckvalve,defectioncoil
andinternalleaks
Checktoseeifcoilisenergized
Awarmcoilindicatespowerisbeingsuppliedto
thecoil
Placeascrewdriveronthesurfaceofthecoilto
sensemagneticfield
Checkforvoltagesuppliedtothecoil
Defectivecoilscanbereplacedwithoutchanging
theentirevalve
TROUBLESHOOTINGTHE
FOURWAYVALVE
Fourwayvalvesleakingthroughcanbeconfusedwitha
compressorthatisnotpumpingtocapacity
Capacityofthesystemwillnotbenormalinsummeror
wintercycles
Checkthetemperatureofthelowsideline,thesuction
linefromtheevaporator,andthepermanentsuctionline
betweenthefourwayvalveandthecompressor
Inthischeck,thetemperaturedifferenceshouldnotbe
morethanabout3F
Leakingreversing
valveinthecooling
mode
Hotgasfromcompressor
50F
Connectedto
outdoorcoil
Connectedto
indoorcoil
60F
Suctiongasto
compressor
Leakingreversing
valveintheheating
mode
Hotgasfromcompressor
Connectedto
outdoorcoil
40F
Connectedto
indoorcoil
30F
Suctiongasto
compressor
CHECKINGTHECHARGE
Mostheatpumpshaveacriticalrefrigerantcharge
Ifsystemsarelowoncharge,techniciansmust
locateandrepairleaks
Cautionshouldbetakenwhenchargingsystems
withsuctionaccumulators
Suctionaccumulatorsstorepartofthechargein
thewintermodeandwillboiloutlater
CHECKINGTHECHARGE
Sweatingsuctionlineaccumulator
Whencheckingorchargingasystem,heatthe
accumulatorbyrunningwateroverittodrivethe
refrigerantoutofit
Oftentheaccumulatorwillfrostorsweatata
particularlevelifliquidrefrigerantiscontainedinit
SPECIALAPPLICATIONFOR
HEATPUMPS
Useofoilorgasfurnacesforauxiliaryheat
Moreefficientapplicationsthanauxiliaryelectricheat
Theheatpumpcoilmustbeinstalleddownstreamofthe
oilorgasheatexchanger
Theairmustflowthroughthefurnaceheatexchanger
beforetheheatpumpcoil
Theoilorgasfurnacemustnotoperateatthesametime
thattheheatpumpisoperating
HEATPUMPSUSINGSCROLL
COMPRESSORS
Ideallysuitedforheatpumpapplicationbecause
ofitspumpingcharacteristics
Scrollsdonotloseasmuchcapacityas
reciprocatingcompressors
Scrollcompressorpressuresareaboutthesame
asreciprocatingcompressors
Scrollcompressorsaredischargegascooled,
HEATPUMPSUSINGSCROLL
COMPRESSORS
Scrollcompressorshaveacheckvalveinthe
dischargeleavingthecompressortoprevent
pressuresfromequalizingthroughthe
compressorduringtheoffcycle
Scrollcompressorsnormallydonotrequirea
suctionlineaccumulatorbecausetheyarenotas
sensitivetoliquidfloodback
HEATPUMPSYSTEMSWITH
VARIABLESPEEDMOTORS
Useofvariablespeedmotorsforthecompressorand
bothfanmotorsisthemethodusedtoimprovesystem
efficiencyinheatpumpsystems
Sizedclosertotheheatingrequirementsofthestructure
atfullloadandwillrunatpartloadandreducedpower
inwarmermonths
Lessauxiliaryheatisrequiredforthesesystems
Variablespeedisaccomplishedwithelectronically
controlledmotors
SUMMARY1
Heatpumpscanpumpheattwowaystoprovideboth
heatingandcooling
Fourwayreversingvalvescontrolthedirectionofflow
oftheheatladenvaporbetweenthelowandhigh
pressuresidesofthesystem
Inthecoolingmode,theoutdoorcoilfunctionsasthe
condenserandtheindoorcoilfunctionsastheevaporator
Intheheatingmode,theoutdoorcoilfunctionsasthe
evaporatorandtheindoorcoilfunctionsasthecondenser
SUMMARY2
Meteringdevicesarelocatedattheinletofboththeindoor
andoutdoorcoils
Checkvalvesareusedtobypassthemeteringdevicethat
shouldnotbeintheactiverefrigerantcircuit
Bidirectionalorbiflowfilterdriersaretwodriersina
singleshellandaredesignedforheatpumpapplications
Intheheatingmode,heatpumpsloseefficiencyasthe
outsideambienttemperaturedrops
Auxiliaryheatisrequiredwhentheheatpumpcannot
providealltheheatastructureneeds
SUMMARY3
Balancepointoccurswhentheheatpumpcanpumpin
exactlyasmuchheatasthestructureisleakingout
Coefficientofperformanceistheratioofusableheat(in
watts)producedfromeachwattofenergypurchased
Inwinteroperation,theCOPincreasesastheoutside
ambienttemperatureincreases
Splitheatpumpsystemsrequiretheinstallationofgas
andliquidlinestoconnecttheindoorandoutdoorunits
Theindoorunitcontainsthefanandcoilandoftenthe
electricstripheaters
SUMMARY4
Maximumairsupplytemperaturesarearound100F
Outdoorcoilshouldbeinstalledsoitisraisedabovethe
groundpadtoallowdefrostwatertoruntotheground
Adefrostsystemisprovidedtodefrosttheicefromthe
outdoorcoil
Packageheatpumpsystemshaveallsystemandelectrical
componentsinonehousing
Therearetwoheatingsystemsandonecoolingsystem
Auxiliaryheatingsystemmustbeoperatedasasystemby
itselfincasetheheatpumpfails
SUMMARY5
Automaticchangeoverthermostatchangesautomatically
betweenheatingandcoolingmodes
Emergencyheatmodeisusedintheeventofheatpump
failure
Theneedfordefrostvariesdependingonoutsideair
temperaturesandconditions
Themoremoistureintheair,themorefrostthatforms
ontheoutdoorcoil
Defrostaffectstheefficiencyofthesystems
Airtoairheatpumpsaccomplishdefrostbystoppingthe
outdoorfanandcyclingunitintocoolingmode
SUMMARY6
Combinationsoftime,temperature,andpressure
dropacrosstheoutdoorcoilarealsousedinsome
systemstodeterminewhendefrostisneededand
whendefrostisterminated
Defrostcanalsobecontrolledelectronically
Inaheatpump,thefanmustbestartedatthe
beginningofeachmodeofoperation
Theindoorfanmotoroftenoperatesduringdefrost
Duringthecoolingmode,systemisoperatingasa
hightemperaturerefrigerationsystem
SUMMARY7
Duringtheheatingmode,systemisoperatingasalow
temperaturerefrigerationsystem
Commonreversingvalveproblemsinclude:stuck
valve,defectioncoilandinternalleaks
Temperaturereadingsofthereversingvalve
connectionscanbetakentoevaluatethevalve
Mostheatpumpsarecriticallychargedsystems
Ifthesystemoperatedcorrectlyinatleastonemode,
therefrigerantchargeiscorrect
SUMMARY8
Oilorgasfurnacescanbeusedforauxiliaryheat
Theheatpumpcoilmustbeinstalleddownstreamofthe
oilorgasheatexchanger
Scrollcompressorisideallysuitedforheatpump
applicationsbecauseofitspumpingcharacteristics
Scrollcompressorsnormallydonotrequireasuctionline
accumulatorbecausetheyarenotassensitivetoliquid
floodback
Useofvariablespeedmotorsforthecompressorandboth
fanmotorsisthemethodusedtoimprovesystem
efficiencyinheatpumpsystems