Documente Academic
Documente Profesional
Documente Cultură
ELECTRONICS
MAFAZ AHSAN
2K12-ELE-258
PAGES 342-355 CHAPTER 6
16.5
ON-OFF CONTROL
In some types of process applications, the
controlled variable changes very slowly, as
the temperature of the temperature of the
large mass is difficult to raise as compared
to the temperature of the smaller mass.
Due to delays the time lags are
unavoidable and thus they are tolerated.
The type of control mode often used for
slow acting operations is the one that
provides on-off actions.
FULLY-ON, FULLY-OFF
This kind of action controls a final
control element that has fully-on and
fully-off conditions.
One example is of the refrigerator unit.
As the Temperature increases above the
set point the compressor turns fully-on,
as the temperature lowers below the set
point, the compressor turns of.
DEAD BAND
A drawback to this system is that the
rate at which the final control element
switches on and off can be very high.
Excessive wear can occur to the
component. To reduce the switching rate
an on-off differential or hysteresis is
programmed into the controller also
referred as the DEADBAND , this allows
the controller to produce its on and off at
different values around the set point.
FIG-16.5
For example
Deadband
Temperature setting
Furnace turns-on
Furnace turns-off
=
=
=
=
4 degree
70 degree
68 degrees
72 degrees
DRAWBACK
The drawback is that controlled
variable will deviate from a set point
by a larger amount than the system
that does not use this system.
Graphical Representation
GENERAL EXAMPLE
One example is the alarm system
that stops a boiler from exploding by
not allowing the temperature to rise
from a certain level.
The alarm remains at rest until the
controller is manually at rest.
The controller is programmed to
close the fuel valve and active an
alarm if high limit temperature is
reached.
It is the
Its
limitation
least
is that it
expensive
cannot
system
vary
the
and
controlled
easiest to
variable
design
control action is with
to switch
thats Its
why
when extreme situations
exist
precision
it is used
causing the final element to
only turn fully on or fully off
CASE STUDY-1
To produce the product, raw materials are
made one batch at a time. Bulk materials
and liquids are combined in a large tank
shown in Figure 16-7.
Fig 16.8a
A heat jacket that
surrounds the tank is fed
with steam because, for
proper blending to occur.
the temperature of the
ingredients
must
be
maintained at 85 degrees If
for
some
reason
the
temperature should rise
above 85 degrees one of
the
ingredients
would
become overactive and the
product would be out of
tolerance. On the other
hand, if the batch is
allowed to cool below 75
degrees, blending will be
Fig-16.8b
The desired operating temperature. or setpoint
adjustment establishes the temperature at which the
controller causes the steam valve to open or close.
The set point of 80 degrees is adjusted by a knob
and the selling is displayed by the green indicator on
the left. The actual temperature is measured by a
sensor and is displayed by the red indicator on the
right. At start up, ingredients in the batch are at the
cool temperature. This condition causes the
controller to open the steam valve as shown in fig
16.8-b .
Fig 16.8c
Fig 16.9
Before the batch cools, its temperature rises slightly
above 80 degrees due to steam trapped within the jacket.
When the batch cools the indicator moves downwards
until the controller opens the valve. The heating cycle is
then repeated. A continuous record of temperature is
shown by a graph in fig 16.9. note that the variations are
well within the limits of plus or minus five degrees.
16.6
CONTINUOUS CONTROL
On-off control is suited to situations where it is
only necessary to keep a process variable
between two limits. For continuous processes
where the variable is required to be kept at a
particular setpoint level it becomes impractical.
The controlled variable can be maintained only if
the final control element is varied continuously
over the entire range of its output. Systems that
provide this function use anyone or a combination
of proportional, Integral, and derivative control
actions.
PROPORTIONAL MODE
A proportional controller produces an output signal with
a magnitude that is proportional to the size of the error
signal (E) it is correcting. The error signal is the
difference between the measured variable and the set
point (desired value). A small error will cause the output
to change by a small amount. Conversely a larger error
will cause a larger output change.
The output of the proportional controller moves the final
control element to a definite position to attain a desired
value of the controlled variable.
The proportional action can be accomplished in two
different ways, by the time proportioning method
and by the amplitude proportional method.
TIME PROPORTIONING
Time proportioning is a method in which the
output al the controller is continually
switched fully on and fully off.
The average voltage produced is varied by
changing the ratio of signal-on to signal-off.
The ratio produced by the controller is
determined by how much the measured
variable differs from the setpoint.
If the measured variable equal the set point
, the output on-off ratio is 1:1
EXAMPLE
For example, assume the output dc voltage of
the controller is 10 volts when the controller is
set for 100 percent; the output is on all of the
time and the average produced is 10volts. If
the controller is set for 60 percent the output
is switched on to 60 percent of the time and
the average voltage is 6 volts.
(10volts X 0.6= 6volts)
When the controller is set for 0%,the output
voltage is not on at all and the average
voltage is 0volts.
AMPLITUDE PROPORTIONAL
The amplitude proportional method is the most
common technique used to produce a proportional
signal.
The magnitude of the signal is proportional to the
size of the error signal. The analog signal produced
by a controller is either variable voltage or a
variable current. The controller has the capability of
amplifying the amount at which the output changes
in proportional to the change applied to its input.
There are two ways to refer to the amplification of a
proportional controller, proportional gain and
proportional band.
PROPORTIONAL GAIN
Is the ratio of change in output to the
change in input as described
mathematically
GAIN
=
PECENTAGE OUTPUT
CHANGE
PERCENTAGE INPUT
CHANGE
GAIN
50% OUTPUT
CHNAGE
25% INPUT CHANGE
PROPORTIONAL BAND
Amplification is also expressed as
proportional band. Proportional band
is defined as the percentage change
in the controlled variable that causes
the final control element to go
through 100 percent of its range. The
proportional band can be determined
mathematically
by
using
the
following formula
Proportional action only occurs above and below the set point
within the proportional band. The set point is located at the
midpoint of the range of values in the proportional band.
Outside the proportional band, the controller functions as if it
is in the on-off mode. When the controlled variable is below
the proportional band the final control element is fully-on.
When the controlled variable is above the proportional band
the final control element is fully-off. Within the proportional
band however, the final control element is turned on at an
amount that is proportional to the difference between the
measured variable and the set point. Gain and proportional
band are two different ways by which an adjustable
amplification setting is made to the controller. Both values
determine the amount at which the output changes in
response to an input change. A larger gain, or smaller PB,
causes a greater output response to an input change than a
smaller gain or larger PB.
SENSITIVITY
A common term used 10 describe a controller's ability to
respond to input changes is sensitivity. The larger the gain or
the narrower the PB. the more sensitive a controller is 10
input changes. The proportional controller can be too
sensitive. If the float in Figure 1612 is moved closer to the
pivot point. The valve position will change too much in
response 10 a small change in level. If the level drops below
set point the valve will open fully and allow an inrush of
liquid. causing the level to rise 100 high. This situation makes
the valve fully close, and results in the liquid dropping below
set point again. Since the system (and the controlled
variable) constantly oscillates above and below set point. Its
operation is similar to on-off control. Proportional control is
adequate when the inertia of the process is relatively large.
The process reaction rate is relatively slow, and the process
lag and dead time are relatively small. All of these
characteristics permit the use of high gain (narrow PB) and
provide fast corrective action for small-to-moderate load
CASE STUDY 2:
PROPOTIONAL CONTROL
As the sales of the company product grow, blending tanks are
added to increase production. Eventually there is no space left in
the plant for additional tanks and no surrounding property on
which to increase the size of the building. The plant's maximum
output peaks at 10.000 bottles a day. One day a reliable customer
offers a long- term contract which will generate an order for
20.000 items per day. Instead of building a completely new plant
at another location. the chemical company decides to remodel the
existing building and installs a continuous process machine to
increase production .With the new machine raw materials at a
precise now rate will be fed into an in-line mixer as shown on
Figure 16- 13. An auger will provide rough blending. but the final
blending will be performed,,?, being heated 10 degrees as the
ingredients flow through a heat exchanger. The blended end
product Will then flow through pipeline to two automatic bottling
machines. To control the temperature the engineers install an onoff controller. When the installation is complete and the process
starts they observe that the metering of the raw material and the
machines mixings operation is highly successful. However, as the
The steam valve the temperature in the heat exchanger cycles first to 90
degrees. And then decreases to 70 degrees. The reason why the
temperature in the heat exchanger fluctuates too much is because the
rate Of heating is too rapid. This condition develops because the mass of
liquid in the heat exchanger is too small to absorb the energy change from
the steam as it varies in temperature. The engineers determine that if the
valve is slowly adjusted until just the right amount of steam is admitted to
the heat exchange, the temperature can be held within the desired range.
This control action can be performed by using the proportional mode of the
controller. By sending an output signal to open or close to the valve to a
position proportional to the temperature the steam valve, the temperature
in the heat exchanger cycles first to 90 degrees and then decreases to the
70 degrees. The reason why the temperature in the heat exchanger
fluctuates too much is because the rate of heating is too rapid. This
condition develops because the mass of liquid in the heat exchanger is too
small to absorb the energy change from the steam as it varies in
temperature. The engineers determine that if the valve is slowly adjusted
until just the right amount of steam is admitted to heat exchange the
temperature can be held within the desired range. This control action can
be performed using the proportional mode of the controller. By sending an
output signal to open or close the valve to a position proportional to the
temperature. The controller can maintain the heat at a more constant level
.
Figures
INTEGRAL MODE
When the set point valve position
in Figure 16-15 is exactly 50 percent
of its full flow rate capacity.
Suppose a load change occurs from
an increase of the outflow through
the drain pipe. As the level drops,
the float mechanism causes the
opening of the inflow valve to
increase. When the inflow equals
the new outflow value, the system
stabilizes. However, the level is
below set point. as shown by the
diagram. This error, a constant
difference between set point (SP)
and the controlled variable (CV), is
called offset.
When the system stabilizes after a load change, the new level is
lower than the desired height of 50 percent. By manually moving the
float toward the pivot point. an action that simulates an increase in
controller gain, the valve opens farther and causes the inflow to
become greater than the outflow. Eventually. the liquid rises and
returns to its desired level, causing the offset to become zero. At this
time the float should be moved back to a position that causes the
inflow and outflow to equal. Moving the float and increasing the gain
while there is an offset represents the integral action. Moving the
float away from the pivot point when the level returns to the setpoint
illustrates how the integral function expires when there is no longer
an offset. Controllers perform the integral action automatically by
using electronic circuitry or microprocessor-based devices. Integral is
also referred to as reset. The term reset is derived from the way in
which the integral action periodically adds the controllers output by
repeating the previous proportional action.
CASE STUDY 3
As the ingredients flow through the exchanger at a rate required to fill
one bottling machine the proportional controller is able to keep its
temperature within the required range. When a second machine is
started the flow through the heat exchanger is doubled. However, the
valve is positioned at that moment to only emit enough steam to heat
one machine. Therefore, the product temperature drops when the
second machine is added. The proportional controller senses the
change and gradually increases the opening of the valve. When the
temperature levels off it is below the desired set point and an offset
condition exists. To open the valve beyond that which is dictated by
proportional action, it is necessary to add the integral mode function to
the controller. As long as the error signal is present, the integral action
causes the output of the controller to slowly increase. Eventually the
valve opening becomes large enough to pass the correct amount of
steam which allows the temperature to return to set point. Once that
happens the error signal becomes zero and the integral action stops.
DERIVATIVE MODE
If the Setpoint or load changes suddenly, the
controlled variable (CV) will deviate from the set
point (SP) and create an error signal. The faster the
initial rate of change the farther the controlled
variable is apt to move away from the set point. In
some
process
applications
this
situation
is
undesirable. If the proportional gain is increased to
minimize this condition, the controlled variable will
likely overshoot and oscillate. This situation may not
be acceptable because a product could be ruined if
the tolerance of its condition is exceeded during the
overshoot or peak of each oscillation. Instead of
increasing the proportional gain to reduce the error
signal the derivative mode of the controller is used.
The derivative function produces a response as soon
as it senses that the CV is changing relative to SP.