AIR CONDITIONING
(HVAC)
CONTENT
1.
DEFINITION
2.
3.
CLASSIFICATION OF AC SYSTEM
4.
5.
6.
7.
PRESSEURE CASCADES
8.
DUCTING
9.
HVAC VALIDATION
10.
DEFINITION
An Air Handling Unit (AHU), or Air Handler, is a central air conditioner station that
handles the air that, usually, will be supplied into the buildings by the ventilation
ductwork.
Handling the air means that the air will be delivered into the building spaces with
thermo-hygrometric and IAQ (Indoor Air Quality) treatment. The accuracy of the
treatment will depend from the specificity of each project (offices, schools, swimmingpools, laboratories, factories with industrial processes, etc). This means, the Air Handling
Unit treat the air by filtering, cooling and/or heating, humidifying and/or dehumidifying.
There are several types of Air Handling Units: Compact, Modular, Residential, DX
integrated, Low Profile (ceiling), Packaged, Rooftop mounted (typically on the roofs of
buildings, with special weather protection), etc.
1 TR is amount of heat to be extracted from the atmosphere for melting 1 metric ton of
ice in 24 hrs.
1 TR = 12000 BTU/Hr. or 3025 kcal/Hr.
WORKING PRINCIPLE
CLASSIFICATION OF AC SYSTEM
II) DEPENDING ON SPACE AVAILABILITY FOR AHU , THE AHUs ARE CLASSIFIED
AS UNDER:a) HORIZONTAL TYPE FLOOR MOUNTED UNIT
b) VERTICAL TYPE FLOOR MOUNTED UNIT
c) CEILING SUSPENDED UNIT.
III) TYPE OF AHU DEPENDING UPON LOCATION OF FAN:a) DRAW THROUGH TYPE:- FAN IS LOCATED AFTER COOLING COIL
b) BLOW THROUGH TYPE:- FAN IS LOCATED BEFORE COOLING COIL
Overview components
Silencer Flow rate controller
Fan
Filter
Control damper
+
Prefilter
Humidifier
Cooling coil
with droplet
separator
Heating
coil
Terminal filter
Production Room
COMPONENTS OF AHU
Fans (Plug Fans, Double Inlet, Single Inlet, Axial, Centrifugal flows etc)
Filters (Plate Filters, Bag Filters, Compact Filters, HEPA Filters, ULPA Filters,
Carbon Filters)
Heat recovery systems (cross flow plate heat exchangers, heat wheel/rotating
heat exchangers, run around coils and heat pipes, etc)
Sound attenuators
Mist/Droplet eliminators
FUNCTIONS OF AHU
Cooling unit /dehumidifier : To cool the air to the required temperature or
to remove
control)
FILTER CLASSES
Dust filters
Standard
Aerosol
Coarse
Fine
Dp > 10 m
10 m > Dp > 1 m
G1 - G4
F5 - F9
EN 779 Standard
HEPA
ULPA
Dp < 1 m
H 11 - 13
U 14- 17
EN 1822 Standard
FILTERS
Secondary filter
DEHUMIDIFIER AND
HUMIDIFICATION
Adsorber wheel
Regeneration air
Air heater
Air flow
patterns
Uni-directional / laminar
displacement of dirty air
0,30 m/s
AHU
Main filter
Turbulent
Uni-directional
Turbulent
Production Room
HEPA Filter
Production Room
PRESSEURE CASCADES
Regulation of Room Pressure Pressure Differentials Concept
Room pressure
gauges
PRESSEURE CASCADES
Pressure cascade injectable
Protection from microorganisms and particles
Room 1
Room 2
30 Pa
60 Pa
Room 3
Room 1
45 Pa
Room 2
Room 3
15 Pa
15 Pa
15 Pa
LF
D
A ir L o c k
45 Pa
A ir L o c k
B
C
A ir L o c k
A ir L o c k
15 Pa
30 Pa
Passage
N o te : D i r e c ti o n o f d o o r o p e n i n g r e l a ti v e to r o o m p r e s s u r e
A ir
Lock
A ir
0 Pa
30 Pa
Passage
N o te : D i r e c ti o n o f d o o r o p e n i n g r e l a ti v e to r o o m p r e s s u r e
Lock
15 Pa
0 Pa
DUCTING
A Duct can be described as a device used to provide an isolation path to carry a
medium from one place to other place without bringing the product in contact with
the atmosphere before the delivery point.
DUCTING
Dont
No Bracing and width of the duct is more than
750mm.
Dos
Bracing should be done all around the duct from
outside when width of the duct is more than 750mm
to provide strength to the duct.
MS Bracing
8 Feet
4 Feet
T
B
W id t h o f t h e D u c t ( m m )
4 Feet
A (m m )
B (m m )
T (m m )
F ro m 7 0 0 to 1 2 0 0
25
25
A b ove 1 20 0
40
40
No Breathing Noise
DUCTING
COMPONENTS OF DUCTING
HVAC VALIDATION
Air balancing
Pressure balancing
Particle count
Recovery test
Fumigation
Documents handover
Instrument used for air balancing : Supply diffusers.
Instrument used velocity measurement: Digital anemometer
Instrument used for pressure balancing: magnehulic gauge.
Instrument used for particle count: particle counter
Instrument used for Air flow pattern: Fogger m/c , Video
Instrument used for PAO test : Aerosol photometer.
REQD. QTY.
UOM
UNIT COST
TOTAL COST
COST/ YEAR
(LAKHS)
TUBULER HEATERS
20
Set
10000.00
2.00
2.00
THERMOSTAT
10
NO.
2000.00
0.20
0.10
COOLING COIL
NO.
30000.00
1.20
NO.
15000.00
0.30
PRESSURE GUAGES
NO.
1500.00
0.09
MAGNELIC GUAGES
NO.
6000.00
0.24
TEMP. GUAGES
NO.
1500.00
0.09
AHU HARDWARE
Set
20000.00
0.20
CONTACTORS
NO.
1500.00
0.09
NO.
1000.00
0.06
15
NO.
50.00
0.01
12 MOTOR
NO.
25000.00
1.00
13 MPCB
NO.
3500.00
0.21
200
Ltr.
150.00
0.30
NO.
25000.00
0.50
11 PUSH BOTTONS
0.20
0.30