GROUNDING
AND BONDING
Introduction
Why Electrical Grounding and Bonding?
The most controversial and misunderstood
concepts in the Code.
The most neglected subject by electrical
practitioners.
When improperly installed, it may results to
physical injuries, costly damage to electrical
facilities or even death to individual.
Each utility (power, telephone, cable TV)
has
its own grounding electrodes.
Electrical Grounding and Bonding circuit
follows the basic laws of electricity.
a
conductor
used
to
connect
equipment or the grounded circuit
of a wiring system to a grounding
electrode conductor.
From PEC 2009
Grounded Conductor
208Y/120
V, ThreePhase
480Y/277V, ThreePhase
Phase A
Black
Black
Brown
Phase B
Red
Red
Orange
Blue
Yellow
Phase C
Neutral
Conductor
White
Gray
Equipment
Grounding
Conductor
Green
Green
Green
Service Equipment
The necessary equipment, usually
consisting of a circuit breaker(s) or
switch(es)
and
fuse(s)
and
their
accessories, connected to the load end of
the of service conductors to a building or
other
structure,
or
an
otherwise
designated area, and intended to
constitute the main control and cut off of
the supply.
Service
Service
Existing Practice???
Panel board Located in the Kitchen Is this
readily accessible?
Service Equipment-Disconnecting
Means
Accessible, Readily
3) Concrete-Encased
Electrode. An electrode
encased by at least 50 mm of
concrete, located within and near
the bottom of a concrete
foundation or footing that is in
direct contact with the earth,
consisting
of at least 6 000 mm of one or
more bare or zinc galvanized or
other
electrically conductive coated steel
reinforcing bars or rods of not less
than 13 mm in diameter, or
consisting of at least 6 000 mm of
bare copper conductor not smaller
than 22 mm2. Reinforcing bars
shall be permitted to be bonded
together by the usual steel tie
wires or other effective means.
6) Plate Electrodes.
less
than 0.186 m2 (2 ft2) of surface to exterior soil. Electrodes of iron or
steel plates shall be at least 6 mm in thickness. Electrodes of
nonferrous metal shall be at least 1.5 mm in thickness.
2 500
4. Where more than one of the electrodes of are used, each electrode of
one grounding system (including that used for air terminals) shall not be
less than 1 800 mm from any other electrode of another grounding
system. CORRECT
5. Two or more grounding electrodes that are effectively bonded together
shall not be considered a single grounding electrode system. WRONG
2.80.2 Installation
2.80.2.1 Location. Surge arresters shall be
permitted to be located indoors or outdoors. Surge
arresters shall be made inaccessible to unqualified
persons, unless listed for installation in accessible
locations.
2.80.2.2 Routing of Surge Arrester
Connections. The conductor used to connect the
surge arrester to line or bus and to ground shall not
be any longer than necessary and shall avoid
unnecessary bends.
2.85.2 Installation
2.85.2.1 Location. TVSSs shall be permitted to be
located indoors or outdoors and shall be made
inaccessible to unqualified persons, unless
listed for installation in accessible locations.
2.85.2.2 Routing of Connections. The conductors
used to connect the TVSS to the line or bus and to
ground shall not be any longer than necessary and
shall avoid unnecessary bends.