Documente Academic
Documente Profesional
Documente Cultură
Chapter 14
Page 425
1
Objectives
Describe how detectors are listed by
Underwriters Laboratories (UL)
Explain why detectors are not permitted to
be positioned too close to the corners of a
room where the ceiling meets the wall
Determine the spacing of detectors in a
room with a smooth flat ceiling
Determine locations of detectors in a room
with unusually configured walls
2
Objectives
Space detectors in a corridor
Discuss rules for placement of detectors
on sloped ceilings
Determine the locations of detectors on
ceilings with solid joists or beams
Explain why detectors are not permitted to
be located too close to supply air ducts
3
Objectives
Describe the effect of floor-mounted
partitions on a ceiling jet
Determine the optimum locations for beam
detectors, flame detectors, gas detectors,
and duct detectors
10
11
12
13
Figure 14-8. Sectional view of a peaked ceiling; a detector must be placed within 3
feet (900 mm) of the roof peak,
15
and spacing is measured along the floor, not along the slope
17
18
20
21
25
26
Gas-Sensing Detector
Placement
May sense a potentially hazardous
condition in advance of ignition, or may
sense gaseous combustion by products
Spaced in accordance with NFPA 72
(2007) and their listing
NFPA 72 has replaced detailed spacing
requirements on gas-sensing fire detectors
29
An Engineering Approach To
Heat Detector Placement
Best way to ensure detection in a building
Conduct fire testing in numerous areas
Determine best detector
Determine best detector locations
Summary
The placement of detectors must consider
Type of fire
Dynamics of the ceiling jet
Attributes of the detector
Properties of the ceiling or surface onto which
the detectors are mounted
Summary
Designers must analyze the anticipated
fire and the space requiring detection
Annex B of NFPA 72 provides engineered
approach to positioning detectors
Specific requirements for
Heat detectors
Smoke detectors
Beam detectors
Gas detectors
32